LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 2 of 49
1.0 PURPOSE
a) Lightning protection requirement for Old wadi Cement plant,Power plant and
Colony Area.
b) To estimate the number of Lightning electrodes required at the above area.
c) To prove that the maximum value of resistance of the earthing system shall not be
more than 3 ohms as per 12.3.1 of IS 2309:1989 .
Depending upon the characteristic features of above factors, various weighting factors are given
in Table 1A to 1E of IS:2309. The probability of the structure being struck by lightning in one
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 3 of 49
year is the product of lightning flash density and the effective collection area of the
structure to be protected.
P = Ac * Ng * 10 6
3.2.3 If the value of risk index is less than 10 -5, then in the absence of other Overriding
consideration, protection shall not be necessary.
3.2.4 If the risk index is more than 10 -5 then sound reasons shall be necessary to
Support the decision of not providing the lightning protection.
4. Earth Terminations
Air Terminations: The vertical and horizontal conductors or combination of both, installed over
or near the structure to attract the lightning stroke to themselves are called air terminations.
3.4.2 Protective Zone : The space around the air terminations in which there is almost no
probability
Direct lightning discharge is called the protective zone of air termination. Protective zones of
various arrangements shall be as given in IS: 2309 - 1989 etc. for correctness.
3.4.3 The angle between vertical line passing through the conductor and side of protective zone is
called protective angle.
3.4.4 Horizontal air terminations: Arranged along the contours such as parapets, ridges and edges of
the roof and wherever necessary, over the flat surfaces, horizontal air termination network
form basic protection arrangement, if roof of the building has large horizontal dimensions.
3.4.5 Protective angle of horizontal air termination is 45 for normal protection and upto 30 if
higher protection is needed.
3.4.6 Protective angle for two horizontal air terminations, spaced at a distance not greater than twice
the height, shall be used within the space between conductors and 45 and 30 respectively if
higher protection is needed.
3.4.7 The spacing, between adjacent horizontal air terminations shall not be more than 10 metres
and no part of the roof shall be more than 5 metres away from the nearest horizontal
conductor.
3.4.10 Where a structure has two elevations, out of which lower is projecting outside the higher
elevation such that the network in higher elevation does not protect the lower elevation, both
networks shall be interconnected by connecting the higher elevation down conductors to the
lower network.
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 5 of 49
3.4.11 If a particular small portion in the structure is projecting above the level of horizontal
conductors by more than 1000 mm, a separate network shall be formed for the same.
3.4.12 All the metal piping, railing, etc. on the roof shall be bonded to the protective network
with a bolted connection.
3.5.1 Size and material of the down conductors shall be given under clause 3.3.
3.5.2 Number
a) As per IS.2039, a structure having a base area less than 100 sq. mtr shall be provided with
only one down conductor. Chimneys, whose over all width at the top or diameter is less than
1.5 metres shall be provided with only one down conductor.
b) For buildings having base area more than 100 m 2 , the number of down conductors shall be
smaller
the number obtained by the following two criteria
i) one down conductor for first 100 m 2 area plus one for every additional 300 m 2 area or part
thereof
ii) one down conductor for every 30 metres of periphery
Non-conducting chimneys whose overall width at the top or diameter is more than 1.5 metres shall
be provided two down conductors. Structures on rocky terrain where testing and inspection is
difficult shall be provided with minimum two down conductors.
As per BS: 6651 1999 at least one down conductor should be provided for each 20 mtr or part
thereof of the perimeter at roof level. Structures greater than 20-mtr height, shall have a down
conductor per 10 mtr or part thereof.
a) Unless aesthetic and architectural considerations prohibit, down conductors shall be uniformly
distributed around the outside walls of the structure.
b) The path between the air terminations and earth terminations shall be as direct as possible and
shall avoid sharp bends upturns and kinks.
c) No deep re-entrant loop, in which length of the conductor forming the loop is more than 8 times
the width of open side of the loop, shall be recommended. This is shown in Figure-1 and is
avoided to prevent large inductive voltage drop across the open side of the loop.
d) In a building cantilevered from first storey onwards, the down conductors shall not follow the
contour of the building as shown in Figure-2.
f) When suitable external route for down conductors is not possible or advisable, the conductors
may run in air space provided by non-metallic, non-combustible ducts not smaller than 75 x 15 mm
or in any vertical, service duct running through the height of the building, provided it does not
contain any unarmoured, non-metal sheath cable.
g) Down conductors may be embedded in the wall of the structure. In such case, reinforcing bars
shall be bonded to the down conductor.
h) In case metallic object such as pipes, structures etc. exists in the vicinity of down conductors,
there is a risk of side flash over between the down conductor and these objects. In such
cases, the object shall be bonded to or installed on the basis of the recommendations given
under
Clause3.7.1.
Each down conductor shall be provided with testing point as discussed in Clause 3.7.2 (f)
j)Holes in cornice and parapet walls shall be used for the passage of down conductors,
wherever possible.
3.6Earth Terminations
3.6.1 Earthing conductors embedded in the soil and designed for the safe discharge of lightning
currents into the soil are called earth terminals.
3.6.2 Down conductor shall be provided an earth electrode and all earth electrodes shall be
interconnected.
3.6.3 Earthing resistance of earth terminations shall be such that the combined resistance is not more
than 3 ohms. In case, the earthing resistance is not within limits, the earth electrodes shall be
located in treated earth pit.
3.6.4 Disconnecting facility shall be provided in some of the earth electrodes so that it is possible to
measure the earthing resistance.
3.6.5 Lightning protective earthing system may be interconnected with operational and safety
earthing system.
3.6.6 Earthing conductors shall not be more than 1.5 to 2.0 metres away from the structure except
when high temperatures are likely to be encountered in subsoil or when sufficient space near
the structure is not available.
3.6.7 Metal pipes and other structures buried in earth shall be bonded to or isolated from the
earthing conductors on the basis of the recommendation given under clause 3.7.1.
a) The use of rod/pipe/plate electrodes is permissible. their choice will depend upon the site
conditions, soil resistivity and economic considerations. In general, the use of pipe electrodes is
recommended.
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 7 of 49
b) The material of earth electrodes shall be either galvanised steel or copper. The choice will
depend upon the material of the air termination, down conductors and soil resistivity. It is
preferable to use the same material throughout the system.
For complex structure it can be calculated based on the guidelines given in item 4.2 of
IEC 61024-1-1 standard.
The risk factor P is multiplied by the product of the weighting factors( Table 1A-1E of IS
2309:1989).
If the overall risk factor is greater than 10-5 protection is required for the structure.
Calculation for the overall risk factor is done below for each building in the Old Wadi Cement
plant, Colony and Power plant.
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 8 of 49
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (49.5) 2
: 7693.785 m2
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (29.8) 2
: 2788.45 m2
Weighing Factors
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 10 of 49
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
: 1290105.505 m2
Length (L) : 34 M
Width ( W) : 36 M
Height (H) : 11.5 M
Length (L) : 22 M
Width ( W) : 36 M
Height (H) : 16.5 M
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 4088.86 m2
Length (L) : 34 M
Width ( W) : 36 M
Height (H) : 16.5 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
LIGHTNING CALCULATION
CLIENT : ACC LIMITED REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTINING CALCULATION SHEET : Page 12 of 49
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 4388.86 m2
Length (L) : 16 M
Width ( W) : 7.5 M
Height (H) : 11.5 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 552.32 m2
PACKING PLANT:
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 4890.132 m2
CEMENT SILO:
Diameter(D) : 12 M
Height (H) : 34.5+2.5=37 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (37) 2
: 4298.66 m2
PACKING PLANT:
Length (L) : 14 M
Width ( W) : 16 M
Height (H) : 30 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 2024 m2
Length (L) : 11 M
Width ( W) : 24 M
Height (H) : 69.36 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
: 20225.142 m2
Weighing Factors
A : 1.0
B : 1.0
C : 0.8
D : 1.0
E : 0.3
: 11275.132 m2
COAL MILL :
Length (L) : 46 M
Width ( W) : 33 M
Height (H) : 44 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
: 14549.04 m2
DG SET BUILDING:
Length (L) : 52 M
Width ( W) : 20 M
Height (H) : 15 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.4
C : 1.0
D : 1.0
E : 0.3
: 2346.5 m2
3 NOS. OF 1 X 25 MW TG BUILDING :
Weighing Factors
A : 1.0
B : 0.4
C : 1.0
D : 1.0
E : 0.3
: 5382.67 m2
: 16146 m2
CHIMNEY -1
Diameter(D) :4 M
Height (H) : 113 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
-Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.4
C : 1.0
D : 2.0
E : 0.3
Collection Area AC : H2
: (113) 2
: 40094.66 m2
CHIMNEY -2
Diameter(D) :4 M
Height (H) : 106.8 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
-Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.4
C : 1.0
D : 2.0
E : 0.3
Collection Area AC : H2
: (106.8) 2
: 35815.59 m2
COLONY AREA
Diameter(D) :13.90 M
Height (H) : 23.40 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
-Rating factor for Wadi
Weighing Factors
A : 0.7
B : 0.4
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (23.4) 2
: 1719.338 m2
Diameter(D) :9.4 M
Height (H) : 24.55 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
-Rating factor for Wadi
Weighing Factors
A : 0.7
B : 0.4
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (24.55) 2
: 1892.485 m2
Length (L) : 40 M
Width ( W) : 15 M
Height (H) : 10 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.2
B : 0.4
C : 1.7
D : 0.4
E : 0.3
: 2014 m2
Length (L) : 17 M
Width ( W) : M
Height (H) : 10 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.2
B : 0.4
C : 1.7
D : 0.4
E : 0.3
: 2014 m2
V. P BUNGALOW:
Weighing Factors
A : 1.2
B : 0.4
C : 1.7
D : 0.4
E : 0.3
: 861.53 m2
SPORTS CLUB:
Length (L) : 55 M
Width ( W) : 20M
Height (H) : 18 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.3
B : 0.4
C : 1.7
D : 1.0
E : 0.3
QUARY CRUSHER:
Length (L) : 24 M
Width ( W) : 12M
Height (H) : 15 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
- Rating factor for Wadi
Weighing Factors
A : 1.0
B : 0.8
C : 0.8
D : 1.0
E : 0.3
: 2074.9 m2
Diameter(D) :4 M
Height (H) : 12 M
Lightning Flashes/Sq.Km / year(Ng) : 3.284
-Rating factor for Wadi
Weighing Factors
A : 0.7
B : 0.4
C : 0.8
D : 1.0
E : 0.3
Collection Area AC : H2
: (12) 2
: 452.16 m2
Re = 100 x loge 4 x l
2xxl d
= 41.36 .
2 L wt
2
Rs = 100 x 312 Log e 2 x 12500 = 2.38
2x3.14x12500 60x5
Re = Re /3 = 41.36 / 3 = 13.78
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 33 of 48
Re + Rs 13.78+2.38
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 14640 = 2.0
2x3.14x14640 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Rt = Re x Rs = 20.68 X 2 = 1.8
Re + Rs 20.68+2.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 30160 = 1.1172
2x3.14x30160 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Re + Rs 20.68+1.1172.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 20405.6 = 1.568
2x3.14x20405.6 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Re + Rs 20.68+1.568.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 35 of 48
2 L wt
2
Rs = 100 x 312 Log e 2 x 20405.6 = 1.568
2x3.14x20405.6 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Re + Rs 20.68+1.568.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 10394.8 = 2.799
2x3.14x10394.8 60x5
Re = Re /1 = 41.36 / 1 = 41.36
Re + Rs 41.36+2.799.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 17730 = 1.77
2x3.14x17730 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Re + Rs 20.68+1.77.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 37 of 48
2 L wt
2
Rs = 100 x 312 Log e 2 x 32033 = 1.07
2x3.14x32033 60x5
Re = Re /2 = 41.36 / 2 = 20.68
Re + Rs 20.68+1.07.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 25672 = 1.285
2x3.14x25672 60x5
Re = Re /1 = 41.36 / 1 = 41.36
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 38 of 48
Rt = Re x Rs = 41.36X1.285 = 1.240
Re + Rs 41.36+1.285.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 56730 = 0.64
2x3.14x56730 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.68X0.64 = 0.62
Re + Rs 20.68+0.64.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 52000 = 0.64
2x3.14x52000 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.68X0.64 = 0.62
Re + Rs 20.68+0.64.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
5.2.1 DG Set
2 L wt
2
Rs = 100 x 312 Log e 2 x 63800 = 0.578
2x3.14x63800 60x5
Re = Re /3 = 41.36 / 3= 13.78
Rt = Re x Rs = 13.78X0.578 = 0.55
Re + Rs 13.78+0.578
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 81802.2 = 0.588
2x3.14x81802.2 60x5
Re = Re /4 = 41.36 / 4= 10.34
Rt = Re x Rs = 10.34X0.588 = 0.5532
Re + Rs 10.34+0.588
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
5.2.3 Chimney-1
2 L wt
2
Rs = 100 x 312 Log e 2 x 23659 = 1.379
2x3.14x23659 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.68X1.379 = 1.285
Re + Rs 20.68+1.379.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
5.2.4 Chimney-2
2 L wt
2
Rs = 100 x 312 Log e 2 x 24899 = 1.379
2x3.14x24899 60x5
Re = Re /2 = 41.36 / 2= 20.68
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 42 of 48
Rt = Re x Rs = 20.68X1.379 = 1.285
Re + Rs 20.68+1.379.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
5.3 Colony
2 L wt
2
Rs = 100 x 312 Log e 2 x 15875.2 = 1.94
2x3.14x15875.2 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.68X1.94 = 1.764
Re + Rs 20.68+1.94.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 43 of 48
2 L wt
2
Rs = 100 x 312 Log e 2 x 13329.2 = 2.26
2x3.14x13329.2 60x5
There are 2 Nos of earth pits are used, therefore
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.36X2.26 = 2.0
Re + Rs 20.36+2.26.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 22100 = 1.46
2x3.14x22100 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.36X1.46 = 1.35
Re + Rs 20.36+1.46.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 14194 = 2.14
2x3.14x14194 60x5
Re = Re /2 = 41.36 / 2= 20.68
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 45 of 48
Rt = Re x Rs = 20.36X2.14 = 1.925
Re + Rs 20.36+2.14.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
2 L wt
2
Rs = 100 x 312 Log e 2 x 33200 = 1.027
2x3.14x33200 60x5
Re = Re /2 = 41.36 / 2= 20.68
Rt = Re x Rs = 20.36X1.027 = 0.97
Re + Rs 20.36+1.027.
50x6 G.I Flat strip is selected for vertical down conductor and horizondal earth
conductor.
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 46 of 48
6.0 RESULTS
a) 38 mm ID,3 M long pipe suggested for earth pit refer drg. No. E-ECB-
A565-LTNG-001(Sheet 2 of 4).
b) 50 x 6 G.I flat strip suggested for down conductors and burried conductor.
c) The No.of Lightning conductors and earth pits required are as shown in the
drawing.
d) The Lightning conductor shall be placed at the topmost height of every
Building.
e) The Location of Earthpits shall be fixed as per the site conditions.
f) The Earthing Resistance shall be maintained below 3 ohms.
g) The down conductors shall be insulated from the metal structures inorder
to reduce the leakage current.
h) All the down conductors shall have a test Link arrangement between the
arrestor and Earthpit.
structure.
Colony Area
Note: The Horizotal Air terminations to be Placed as marked in the drawing for
Water Tanks and Gust houses.
need to provide.
Note: The Horizotal Air terminations to be Placed as marked in the drawing for
D.G set building & T.G building.
As the Chimneys are provided with the 2 nos of 25x3 GI Flat as down
conductor, the same shall be retained as it is and the required earth value
of less than 3 ohms should be confirmed.
a) There are three Tank in this area ,in each Tank one Arrester shall be
placed.
LIGHTNING CALCULATION
CLIENT : ACC -WADI REV/DATE : 0 /24.06.05
PROJECT : LIGHTNING ARRESTOR REQUIREMENT CALCULATION PRE/CHKD : LB/ MK
TITLE : LIGHTNING CALCULATION SHEET : Page 49 of 48
c) In quary crusher area one Arrestor and Two nos. of earth pits shall be placed as
marked in the drawing.