Professional Documents
Culture Documents
This is an attempt to understand the different methods described in IEC-62305 part-3 towards
protection against lightning.
IEC 62305/2010 part 1-4 are adapted as such by BIS without any change in the year 2016.
As per IEC 623051/2010, protection measures may be adopted in order to reduce the risk
according to the type of damage.
Surges may occur even if lightning does not strike in the immediate vicinity. In order to evaluate
whether or not lightning protection of a structure is needed, a risk assessment in accordance with
the procedures contained in IEC 62305-2 shall be made. The following risks shall be taken into
account;
Four LPLs are introduced. For each LPL, a set of maximum and minimum lightning current
parameters is fixed (LPL I to IV)
The maximum values of lightning current parameters are used to design lightning protection
components (Eg. Cross section of conductors, thickness of metal sheets, current capability of SPDs
and Separation distance against dangerous sparking).
The minimum values of lightning current amplitude for the different LPL are used to derive the
Rolling Sphere Radius in order to define the Lightning Protection Zone (LPZ0B) which cannot be
reached by direct strike.
LPL I II III IV
Maximum
200 150 100 100
Current (KA)
Minimum
3 5 10 16
Current (KA)
LIGHTNING CURRENT FOR EACH LPL BASED ON 10/350S WAVEFORM
The design of an LPS shall contain all the information necessary for correct and complete
installation.
EXTERNAL LPS
ISOLATED SYSTEM: An isolated external LPS should be considered when the thermal and explosive
effects at the point of strike may cause damage to the structure or to the contents. Typical
example includes structures with combustible covering, combustible walls and areas at risk of
explosion and fire.
NON-ISOLATED SYSTEM: A non-isolated system may be fitted where no such danger exists. In most
cases, the external LPS may be attached to the structure to be protected.
These individual elements of an LPS should be connected together using appropriate lightning
protection components. This will ensure that in the event of a lightning current discharge to the
structure, any potential damage to the structure protected will be minimized.
The role of an air termination system is to capture the lightning discharge current and dissipate it
harmlessly to earth via down conductor and earth termination system. Therefore, it is very
important to use a correctly designed Air-termination system.
Air termination systems can be composed of any combination of the following elements;
The individual air-termination rods should be connected together at roof level to ensure current
divisions.
5.2.2 POSITIONING
Air termination components installed on a structure shall be located at corners, exposed points
and edges in accordance with one or more of the following methods;
The value of the protection angle, rolling sphere radius and mesh size for each class of LPS are
given in table-2and fig-1. Detailed information on the positioning of the air-termination is given in
Annex A.
PROTECTION METHOD
Rolling Sphere radius
Class of LPS Mesh Size (m) Protection angle ()
(r) in meter
I - VERY HIGH RISK 20 5X5
II - HIGH RISK 30 10X10
See Fig-1 below
III - MODERATE RISK 45 15X15
IV - LOW RISK 60 20X20
(Table 2)
NB: The class of LPS shall be selected on the basis of a risk assessment (see IEC 62305-2)
Not applicable beyond the values marked with () only rolling sphere and mesh method
apply in these cases
h is the height of the air-termination above the reference plane of the area to be
protected.
The angle will not change for values of h below 2m
CONSTRUCTION
LPS not isolated from the structure to be protected may be installed as follows;
If the roof is made of non-combustible material, the air termination conductors may be
positioned on the surface of the roof.
(Annex-A)
For each non-isolated LPS, the number of down conductors shall be not less than two. A down
conductor should be installed at each exposed corner of the structure, where this is possible.
A2 POSITIONING OF THE AIR TERMINATION SYSTEM UTILIZING THE ROLLING SPHERE METHOD
(Suitable for all complex shaped building)
Applying this method, the positioning of the Air-Termination system is adequate if no point of the
structure to be protected comes into contact with a sphere with radius r depending on the class
of LPS (see table) rolling around on top of the structure in all possible directions. In this way, the
sphere only touches the air termination system (see figure)
There are different radii of the Rolling Sphere that corresponds to the relevant class of LPS.
A3 POSITIONING OF THE AIR TERMINATION SYSTEM UTILIZING THE MESH METHOD (Suitable
for all flat surface building)
For the purpose of protecting flat surfaces, a mesh is considered to protect the whole surface
dependent upon all of the following conditions being fulfilled.
(b) The mesh dimensions of the air termination network are not greater than the values given
in table-2
(c) The network of the air termination system is constructed in such a way that the lightning
current will always encounter at least two distinct metal routes to earth termination.
(d) No metal installation protrudes outside the volume protected by Air Termination System.
(e) The air termination conductors follow as far as possible, the shortest and most direct route.
For each non-isolated LPS, the number of down conductors shall be not less than two. A down
conductor should be installed at each exposed corner of the structure, where this is possible.
Table 4: Typical preferred value of the distance between each conductors according to class of LPS
For non-isolated LPS, down conductors are mounted directly onto the building (without separation
distance) if the wall is made of flame resistant or normally inflammable material, the down
conductors may be installed directly on or in the wall.
Metal frame work of a steel structure or the interconnected reinforcing steel of the structure can
be used as down conductor. Reinforcement of existing structure cannot be used as natural down
conductor unless the reinforcement is safely interconnected. Separate external down conductors
must be installed.
Such cables are used as down conductors where separation distance cannot be maintained in new
and existing building to prevent dangerous flashover between the parts of external LPS and
conductive parts of external LPS and conductive parts inside the structure (electrical/electronic
equipment, pipes, ventilation ducts) requires only for isolated LPS.
A lot of techno-commercial discussions has raged over past few years regarding the validity of the
claims made by the proponents of such systems. This topic was discussed extensively with in the
technical working groups that compiled IEC 62305. The result was to stick on with this standard.
Typically, Annex A(normative) which discusses the positioning of the air termination rods (finials)
states unequivocally that the volume or zone of protection afforded by the air termination system
shall be determined only by the real physical dimension of the air termination system. If the air
termination rod is 5m tall then the only claim for the zone of protection afforded by this air
termination would be based on 5m and the relevant class of LPS and not any enhanced
dimensions claimed by some non-conventional air termination rods.
There is no other standard being contemplated to run in parallel with this standard IEC 62305.
SAMPLE CALCULATION
MATERIALS REQUIRED:
___________________________________________________________________