LIGHTNING RISK ASSESSMENT CALCULATIONS SUMMARY

BUILDING/INSTALLATION = Dining Hall & Surau

LOCATION/AREA = SK. Balambangan Bangi, Kudat, Sabah

NUMBER OF THUNDERSTORM DAYS PER YEAR Td = 75

LIGHTNING DENSITY Ng = 9

STRUCTURE
Length , L (m) L = 42.00

Width, w (m) W = 10.80

Height, H (m) H = 6.00

2
Collection Area (m ) Ad = 3372.41

DANGER FOR PEOPLE h = No particular danger

OCCUPATION OF THE STRUCTURE Lf1 = Structure normally occupied

LIGHTNING CONDUCTOR Pd = None

ELECTRICAL LINE Ai = Underground

RELATIVE LOCATION OF THE STRUCTURE Cd = Structure surrounded by higher objects or trees

FIRE RISK rf = Ordinary

SERVICE Lf2 = No

SURGE ARRESTOR Pi = None

RESULT OF THE RISK ASSESSMENT

Risk of Human Loss, RT1 = ACCEPTABLE

Risk of Loss of Service, RT2 = ACCEPTABLE

Risk of Loss of Culture Heritage, RT3 = ACCEPTABLE