Measurements and Recording P34x/EN MR/B76
CONTENTS
(MR) 8-
MR
Measurements and Recording P34x/EN MR/B76
1.1 Introduction
The P34x is equipped with integral measurements, event, fault and disturbance recording
facilities suitable for analysis of complex system disturbances.
The relay is flexible enough to allow for the programming of these facilities to specific user
application requirements and are discussed below.
Setting range
Menu text Default setting Step size
Min. Max.
VIEW RECORDS
Select Event 0 0 249
MR
Setting range from 0 to 511. This selects the required event record from the possible 512
that may be stored. A value of 0 corresponds to the latest event and so on.
Latched alarm active, Latched alarm
inactive, Self reset alarm active, Self reset
alarm inactive, Relay contact event, Opto-
Menu Cell Ref (From record)
isolated input event, Protection event,
General event, Fault record event,
Maintenance record event
Indicates the type of event.
Time and Date Data
Time & Date Stamp for the event given by the internal Real Time Clock.
Event text Data.
Up to 32 Character description of the Event. See event sheet in Menu Database chapter,
P34x/EN/MD or Measurements and Recording chapter, P34x/EN MR for details.
Event Value Data.
32 bit binary string indicating ON or OFF (1 or 0) status of relay contact or opto input or
alarm or protection event depending on event type. Unsigned integer is used for
maintenance records. See event sheet in Menu Database chapter, P34x/EN/MD or
Measurements and Recording chapter, P34x/EN MR for details.
Select Fault 0 0 4 1
Setting range from 0 to 4. This selects the required fault record from the possible 5 that
may be stored. A value of 0 corresponds to the latest fault and so on.
P34x/EN MR/B76 Measurements and Recording
Setting range
Menu text Default setting Step size
Min. Max.
Faulted Phase 00000000
Displays the faulted phase as a binary string, bits 0 8 = Start A/B/C/N Trip A/B/C/N.
Start elements 1 00000000000000000000000000000000
32 bit binary string gives status of first 32 start signals. See Data Type G84 in Menu
Database chapter, P34x/EN/MD for details.
Start elements 2 00000000000000000000000000000000
32 bit binary string gives status of second 32 start signals. See Data Type G107 in Menu
Database chapter, P34x/EN/MD for details.
Start elements 3 00000000000000000000000000000000
32 bit binary string gives status of third 32 start signals. See Data Type G129 in Menu
Database chapter, P34x/EN/MD for details.
Trip elements 1 00000000000000000000000000000000
32 bit binary string gives status of first 32 trip signals. See Data Type G85 in Menu
Database chapter, P34x/EN/MD for details.
Trip elements 2 00000000000000000000000000000000
32 bit binary string gives status of second 32 trip signals. See Data Type G86 in Menu
Database chapter, P34x/EN/MD for details.
Trip elements 3 00000000000000000000000000000000
32 bit binary string gives status of third 32 trip signals. See Data Type G130 in Menu
Database chapter, P34x/EN/MD for details.
MR Fault Alarms 0000001000000000
32 bit binary string gives status of fault alarm signals. See Data Type G87 in Menu
Database chapter, P34x/EN/MD for details.
Fault Time Data.
Fault time and date.
Active Group Data.
Active setting group 1-4.
System Frequency Data
System frequency.
Fault Duration
Fault duration. Time from the start or trip until the undercurrent elements indicate the CB is
open.
CB Operate Time Data.
CB operating time. Time from protection trip to undercurrent elements indicating the CB is
open.
Relay Trip Time Data.
Relay trip time. Time from protection start to protection trip.
Measurements and Recording P34x/EN MR/B76
Setting range
Menu text Default setting Step size
Min. Max.
The following cells provide measurement information of the fault : IA-1, IB-1, IC-1, VAB,
VBC, VCA, VAN, VBN, VCN, IA-2, IB-2, IC-2, IA Differential, IB Differential, IC Differential,
VN1 Measured, VN2 Measured, VN Derived, IN Measured, I Sensitive, IREF Diff, IREF
Bias, I2, V2, 3 Phase Watts, 3 Phase VARs, 3Ph Power Factor, RTD 1-10, CLIO Input 1-4,
64S V Magnitude, 64S I Magnitude, 64S Rprimary.
Select Maint 0 0 9 1
Setting range from 0 to 9. This selects the required maintenance report from the possible
10 that may be stored. A value of 0 corresponds to the latest report and so on.
Maint Text Data.
Up to 32 Character description of the occurrence. See Measurements and Recording
chapter, P34x/EN MR for details.
Maint Type Data.
Maintenance record fault type. This will be a number defining the fault type.
Maint Data 0 0 4 1
Error code associated with the failure found by the self monitoring. The Maint Type and
Data cells are numbers representative of the occurrence. They form a specific error code
which should be quoted in any related correspondence to Report Data.
Reset Indication No No, Yes N/A
Resets latched LEDs and latched relay contacts provided the relevant protection element
has reset.
For extraction from a remote source via communications, refer to the SCADA
Communications section (P34x/EN SC), where the procedure is fully explained.
MR
Note that a full list of all the event types and the meaning of their values is given in document
P34x/EN MD.
The Event Value is an 8, 12, 16, 24 or 32-bit word showing the status of the opto inputs,
where the least significant bit (extreme right) corresponds to opto input 1 etc. The same
information is present if the event is extracted and viewed via PC.
P34x/EN MR/B76 Measurements and Recording
The Event Value is a 7, 11, 14, 15, 16, 22, 24 or 32 bit word showing the status of the output
contacts, where the least significant bit (extreme right) corresponds to output contact 1 etc.
The same information is present if the event is extracted and viewed via PC.
Resulting event
Alarm condition
Event text Event value
Alarm Status 1 (Alarms 1 - 32) (32 bits)
Bit position 2 in 32 bit
Setting Group Via Opto Invalid Setting Grp Invalid ON/OFF
field
Bit position 3 in 32 bit
Protection Disabled Protn Disabled ON/OFF
field
Bit position 13 in 32 bit
MR Frequency Out of Range Freq out of Range ON/OFF
field
Bit position 4 in 32 bit
VTS Alarm VT Fail Alarm ON/OFF
field
Bit position 6 in 32 bit
CB Trip Fail Protection CB Fail ON/OFF
field
Alarm Status 2 (Alarms 1 - 32) (32 bits)
SR User Alarm 1 - 4 SR User Alarm 1 - 4 Bit position 17 - 31 in 32
(Self Reset) ON/OFF bit field
MR User Alarm 5 - 16 MR User Alarm 5 - 16 Bit position 16 - 27 in 32
(Manual Reset) ON/OFF bit field
Alarm Status 3 (Alarms 1 - 32) (32 bits)
Bit position 0 in 32 bit
Battery Fail Battery Fail ON/OFF
field
Bit position 1 in 32 bit
Field Voltage Fail Field V Fail ON/OFF
field
The previous table shows the abbreviated description that is given to the various alarm
conditions and also a corresponding value between 0 and 31. This value is appended to
each alarm event in a similar way as for the input and output events previously described. It
is used by the event extraction software, such as MiCOM S1 Studio, to identify the alarm and
is therefore invisible if the event is viewed on the LCD. Either ON or OFF is shown after the
description to signify whether the particular condition has become operated or has reset.
The User Alarms can be operated from an opto input or a control input using the PSL. They
can thus be useful to give an alarm led and message on the LCD display and an alarm
indication via the communications of an external condition, for example trip circuit
supervision alarm, rotor earth fault alarm. The menu text editor in MiCOM S1 Studio can be
used to edit the user alarm text to give a more meaningful description on the LCD display.
Measurements and Recording P34x/EN MR/B76
A complete list of the General Events is given in the Relay Menu Database, P34x/EN MD),
which is a separate document, available for downloaded from our website.
Where # = 1 to 4
RECORD CONTROL
Clear Events No No or Yes
Selecting Yes will cause the existing event log to be cleared and an event will be
generated indicating that the events have been erased.
Clear Faults No No or Yes
MR Selecting Yes will cause the existing fault records to be erased from the relay.
Clear Maint. No No or Yes
Selecting Yes will cause the existing maintenance records to be erased from the relay.
Alarm Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for all alarms.
Relay O/P Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any change in relay output
contact state.
Opto Input Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any change in logic input
state.
General Event Enabled Enabled or Disabled
Disabling this setting means that no General Events will be generated. See event record
sheet in the menu database chapter, P34x/EN MD for list of general events.
Fault Rec Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any fault that produces a
fault record.
Maint. Rec Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any maintenance records.
Protection Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any operation of the
protection elements.
Measurements and Recording P34x/EN MR/B76
DDB 31 - 0 11111111111111111111111111111111
32 bit setting to enable or disable the event recording for DDBs 0-31. For each bit 1 =
event recording Enabled, 0 = event recording Disabled.
DDB 1407 - 1376 11111111111111111111111111111111
32 bit setting to enable or disable the event recording for DDBs 1407 1376. For each bit
1 = event recording Enabled, 0 = event recording Disabled. There are similar cells
showing 32 bit binary strings for all DDBs from 0 1407. The first and last 32 bit binary
strings only are shown here.
Note that some occurrences will result in more than one type of event, e.g. a battery failure
will produce an alarm event and a maintenance record event.
If the Protection Event setting is Enabled a further set of settings is revealed which allow the
event generation by individual DDB signals to be enabled or disabled.
For further information regarding events and their specific meaning, refer to relay menu
database document P34x/EN MD.
Setting range
Menu text Default setting Step size
Min. Max.
DISTURB RECORDER
Duration 1.5s 0.1s 10.5s 0.01s
Overall recording time setting.
Trigger Position 33.3% 0 100% 0.1%
Trigger point setting as a percentage of the duration. For example, the default settings
show that the overall recording time is set to 1.5s with the trigger point being at 33.3% of
this, giving 0.5s pre-fault and 1s post fault recording times.
Trigger Mode Single Single or Extended
If set to single mode, if a further trigger occurs whilst a recording is taking place, the
recorder will ignore the trigger. However, if this has been set to "Extended", the post
trigger timer will be reset to zero, thereby extending the recording time.
P34x/EN MR/B76 Measurements and Recording
Setting range
Menu text Default setting Step size
Min. Max.
Unused, VA, VB, VC, VN1, A-1, B-1, C-
1, N, Sensitive, A-2, B-2, C-2, VN2,
Analog. Channel 1 VA V64S, I64S, Frequency, 64R CL Input Raw
(unfiltered), 64R R Fault Raw (unfiltered),
64R R Fault (filtered).
Selects any available analog input to be assigned to this channel.
Analog. Channel 2 VB As above
Analog. Channel 3 VC As above
Analog. Channel 4 VN1 As above
Analog. Channel 5 A-1 As above
The pre and post fault recording times are set by a combination of the "Duration" and
"Trigger Position" cells. "Duration" sets the overall recording time and the "Trigger Position"
sets the trigger point as a percentage of the duration. For example, the default settings
show that the overall recording time is set to 1.5s with the trigger point being at 33.3% of
this, giving 0.5s pre-fault and 1s post fault recording times.
If a further trigger occurs whilst a recording is taking place, the recorder will ignore the trigger
if the "Trigger Mode" has been set to "Single". However, if this has been set to "Extended",
the post trigger timer will be reset to zero, thereby extending the recording time.
As can be seen from the menu, each of the analog channels is selectable from the available
analog inputs to the relay. The digital channels may be mapped to any of the opto isolated
inputs or output contacts, in addition to a number of internal relay digital signals, such as
protection starts, LEDs etc. The complete list of these signals may be found by viewing the
available settings in the relay menu or via a setting file in MiCOM S1 Studio. Any of the
digital channels may be selected to trigger the disturbance recorder on either a low to high or
a high to low transition, via the "Input Trigger" cell. The default trigger settings are that any
dedicated trip output contacts (e.g. relay 3) will trigger the recorder.
Measurements and Recording P34x/EN MR/B76
It is not possible to view the disturbance records locally via the LCD; they must be extracted
using suitable software such as MiCOM S1 Studio. This process is fully explained in the
SCADA Communications document, P34x/EN SC.
1.4 Measurements
The relay produces a variety of both directly measured and calculated power system
quantities. These measurement values are updated on a per second basis and can be
viewed in the Measurements columns (up to three) of the relay or via MiCOM S1 Studio
Measurement viewer. The P34x relay is able to measure and display the following quantities
as summarized.
Slip Frequency
In addition to the measured power quantities the relay calculates the power factor on a
phase by phase basis in addition to a three-phase power factor.
These power values are also used to increment the total real and reactive energy
measurements. Separate energy measurements are maintained for the total exported and
imported energy. The energy measurements are incremented up to maximum values of
1000GWhr or 1000GVARhr at which point they will reset to zero, it is also possible to reset
these values using the menu or remote interfaces using the reset demand cell.
MR Rms. phase voltage and current values are calculated by the relay using the sum of the
samples squared over a cycle of sampled data.
1.4.7 Settings
The following settings under the heading measurement set-up can be used to configure the
relay measurement function.
MEASURET SETUP
Description/Plant Reference/
Frequency/Access Level/3Ph + N
Default Display Description
Current/3Ph Voltage/Power/Date
and Time
This setting can be used to select the default display from a range of options, note that it is
also possible to view the other default displays whilst at the default level using the and
keys. However once the 15 minute timeout elapses the default display will revert to that
selected by this setting.
Local Values Primary Primary/Secondary
This setting controls whether measured values via the front panel user interface and the
front courier port are displayed as primary or secondary quantities.
Remote Values Primary Primary/Secondary
This setting controls whether measured values via the rear communication port are
displayed as primary or secondary quantities.
Measurement Ref. VA VA/VB/VC/A/B/C
Using this setting the phase reference for all angular measurements by the relay can be
selected.
Measurement Mode 0 0 to 3 step 1
This setting is used to control the signing of the real and reactive power quantities; the
MR
signing convention used is defined in the Measurements and Recording section
(P34x/EN MR)
Fix Dem Period 30 minutes 1 to 99 minutes step 1 minute
This setting defines the length of the fixed demand window.
Roll Sub Period 30 minutes 1 to 99 minutes step 1 minute
The rolling demand uses a sliding/rolling window. The rolling demand window consists of a
number of smaller sub periods (Num Sub Periods). The resolution of the rolling window is
the sub period length (Roll Sub Period) with the displayed values being updated at the end
of each sub period.
Num Sub Periods 1 1 to 15 step 1
This setting is used to set the number of rolling demand sub periods.
Remote 2 Values Primary Primary/Secondary
nd
This setting controls whether measured values via the 2 rear communication port are
displayed as primary or secondary quantities.
P34x/EN MR/B76 Measurements and Recording
1.4.8.1 Measurements 1
Setting range
Menu text Default setting Step size
Min. Max.
MEASUREMENTS 1
IA / IA-1 Magnitude Data. IA. P342/ IA-1. P343,4,5
IA / IA-1 Phase Angle Data. IA. P342/ IA-1. P343,4,5
IB / IB-1 Magnitude Data. IA. P342/ IA-1. P343,4,5
IC / IB-1 Phase Angle Data. IA. P342/ IA-1. P343,4,5
IC / IC-1 Magnitude Data. IA. P342/ IA-1. P343,4,5
IC / IC-1 Phase Angle Data. IA. P342/ IA-1. P343,4,5
IN Measured Mag Data.
IN Measured Angle Data.
IN / IN-1 Derived Mag Data. IN = IA+IB+IC. P342/ IN-1 = IA-1+IB-1+IC-1. P343,4,5.
IN Derived Angle Data.
I Sen Magnitude Data.
I Sen Angle Data.
MR I1 Magnitude Data. Positive sequence current.
I2 magnitude Data. Negative sequence current.
I0 Magnitude Data. Zero sequence current.
IA RMS Data.
IB RMS Data.
IC RMS Data.
IN-2 Derived Mag Data. IN-2 = IA-2+IB-2+IC-2. P343,4,5.
VAB Magnitude Data.
VAB Phase Angle Data.
VBC Magnitude Data.
VBC Phase Angle Data.
VCA Magnitude Data.
VCA Phase Angle Data.
VAN Magnitude Data.
VAN Phase Angle Data.
VBN Magnitude Data.
VBN Phase Angle Data.
VCN Magnitude Data.
VCN Phase Angle Data.
VN / VN1 Measured
Data. VN.P342/ VNI. P343,4,5
Mag
Measurements and Recording P34x/EN MR/B76
Setting range
Menu text Default setting Step size
Min. Max.
VN / VN1 Measured
Data. VN.P342/ VNI. P343,4,5
Ang
VN Derived Mag Data. VN = VA+VB+VC.
V1 Magnitude Data. Positive sequence voltage.
V2 Magnitude Data. Negative sequence voltage.
V0 Magnitude Data. Zero sequence voltage.
VAN RMS Data.
VBN RMS Data.
VCN RMS Data.
Frequency Data.
I1 Magnitude Data. Positive sequence current.
I1 Phase Angle
I2 Magnitude Data. Negative sequence current
I2 Phase Angle Data.
I0 Magnitude Data. Zero sequence current.
I0 Phase Angle Data.
V1 Magnitude Data. Positive sequence voltage.
V1 Phase Angle
V2 Magnitude Data. Negative sequence voltage. MR
V2 Phase Angle Data.
V0 Magnitude Data. Zero sequence voltage.
V0 Phase Angle Data.
VN2 Measured Mag Data. P344,5.
VN2 Measured Ang Data. P344,5.
1.4.8.2 Measurements 2
Setting range
Menu text Default setting Step size
Min. Max.
MEASUREMENTS 2
A Phase Watts Data.
B Phase Watts Data.
C Phase Watts Data.
A Phase VARs Data.
B Phase VARs Data.
C Phase VARs Data.
A Phase VA Data.
B Phase VA Data.
C Phase VA Data.
3 Phase Watts Data.
3 Phase VARs Data.
P34x/EN MR/B76 Measurements and Recording
Setting range
Menu text Default setting Step size
Min. Max.
3 Phase VA Data.
NPS Power S2 Data. Negative sequence power, S2 =V2xI2
3Ph Power Factor Data.
APh Power Factor Data.
BPh Power Factor Data.
CPh Power Factor Data.
3Ph WHours Fwd Data.
3Ph WHours Rev Data.
3Ph VArHours Fwd Data.
3Ph VArHours Rev Data.
3Ph W Fix Demand Data.
3Ph VAr Fix Demand Data.
IA Fixed Demand Data.
IB Fixed Demand Data.
IC Fixed Demand Data.
3Ph W Roll Demand Data.
3Ph VAr Roll
Data.
Demand
1.4.8.3 Measurements 3
Setting range
Menu text Default setting Step size
Min. Max.
MEASUREMENTS 3
IA-2 Magnitude Data. P344,5
IA-2 Phase Angle Data. P344,5
IB-2 Magnitude Data. P344,5
IB-1 Phase Angle Data. P344,5
IC-2 Magnitude Data. P344,5
IC-2 Phase Angle Data. P344,5
IA Differential Data. P343,4,5.
IB Differential Data. P343,4,5.
IC Differential Data. P343,4,5.
IA Bias Data. P343,4,5.
IB Bias Data. P343,4,5.
IC Bias Data. P343,4,5.
IREF Diff Data.
IREF Bias Data.
Data. 3rd harmonic neutral voltage used by 100% stator earth fault.
VN 3rd harmonic
P343,4,5.
NPS Thermal Data. Negative phase sequence thermal state. MR
Reset NPS Thermal No No, Yes N/A
Reset negative phase sequence thermal state command. Resets NPS Thermal state to 0
RTD 1 Data.
RTD 2-10 Data.
RTD Open Cct 00000000
This menu cell displays the status of the eight RTDs as a binary string, 0 = No Open
Circuit, 1 = Open Circuit. The Open Cct alarms are latched.
RTD Short Cct 00000000
This menu cell displays the status of the eight RTDs as a binary string, 0 = No Short
Circuit, 1 = Short Circuit. The Short Cct alarms are latched.
RTD Data Error 00000000
This menu cell displays the status of the eight RTDs as a binary string, 0 = No Data Error,
1 = Data Error. The Data Error alarms are latched.
Reset RTD Flags No No, Yes N/A
Reset RTD alarms command. Resets latched RTD Open Cct, Short Cct, Data Error
alarms.
P34x/EN MR/B76 Measurements and Recording
Setting range
Menu text Default setting Step size
Min. Max.
APh Sen Watts Data.
APh Sen VArs Data.
APh Power Angle Data.