Professional Documents
Culture Documents
Abstract: A new approach to CT saturation assessment is presented situations described is given in section IV. It is shown that
in the paper. Detailed algorithms for decaying DC component due to the reasons mentioned relay maloperation (over-
measurement and CT saturation prediction are proposed and their tripping) could occur. Thus application of the adaptivity idea
accuracy is discussed. The information on CT saturation period is
further used for adaptation of the generator / transformer differential
is indispensable to assure proper operation of the protection
protection. Improved stabilization for external faults is achieved by for external faults with small through currents accompanied
appropriate temporal adjustment of the differential curve for the with CT saturation due to DC component.
time period of CT saturation. The protection developed was tested In the following chapters the general idea of adaptive
with both EMTP-generated and real world registered current protection together with the detailed information on the
signals.
algorithms of current parameter estimation, CT operation
Index Terms: CT saturation, differential protection, digital signal prediction and determination of the necessary adaptation
processing, measurement of decaying DC parameters, synchronous degree are described. The main attention is paid to the
machine, transformer. procedures of CT saturation assessment, which bring key
information for further protection adaptation.
I. INTRODUCTION
a) 15
10
malfunction. Contradictory requirements of high sensitivity
and selectivity can not reconcile in cases of faults with small
through currents which may evoke over-tripping if the CTs 5
I2
(Fig. 1b) that the negative half of the signal wave is also 15
falsely transformed to the CT secondary side.
In Fig. 2 sample waveforms of DC components from CT 10
cycles from the beginning of fault. Fig. 1. Primary, secondary and magnetizing currents of a CT during: a) high
An illustration of the differential protection operation (in amplitude faults, b) generator-close fault with small through current.
traditional, non-adaptive as well as adaptive versions) for the
a) amplitude as well as the level of decaying DC is to be
10
evaluated. The following subsections unfold the problems of
Primary and secondary DC currents (A)
1,2
the DC component based on the assumption of a detailed
1
deterministic signal model and modified half- or full-cycle
filters (Fourier or Walsh functions) [8, 9, 10].
0,8
Below three algorithms belonging to the last group of
0,6
estimators are described and their accuracy and dynamics are
0,4
analyzed.
0,2
The algorithm described in [8] is based on signal filtering
0
0 0,02 0,04 0,06 0,08 0,1 0,12 0,14 0,16 0,18 0,2 with half-cycle Fourier filters (HCDFT). The equations for
Time (s)
determination of decaying DC component parameters are as
Fig. 2. Currents and flux density components of a CT under fault conditions: a) follows:
DC components of primary and secondary currents, b) components of the CT
magnetizing current, c) components of flux density in the CT core; I1=2In1, Tp
IDC=I1, TN=300ms. T N = qT p = (1)
ln( Q)
II. CT SATURATION ASSESSMENT and
The evaluation of CT saturation period is necessary if the N [ic ( N / 2) i c ( N / 2 + 1)]
I DC = , (2)
adaptivity concept is to be implemented in practice to get 4 cos( 2 / N )Q(1 + Q N / 2 )
required improvement of the differential protection operation. where
It is to be emphasized that a kind of CT saturation prediction
procedure has to be developed since the traditional saturation Q = e 1 / q =
[ic ( N / 2 + 2) ic ( N / 2 + 2)]cos( 2 / N ) , (3)
detection methods (e.g. as described in [1, 2]) are not able to [ic ( N / 2 + 1) ic ( N / 2)] cos( 4 / N )
recognize the situation until it appears. Furthermore, before
ic current signal after filtering, Tp sampling rate and N
suitable formulae for calculation of time to saturation and its
number of samples in one cycle of fundamental frequency.
end can be fired, the fundamental frequency component
The algorithm described in [9] is based on full-cycle signals from fault recorders installed in a real network. The
filtering with first order Walsh function (W1), which in results of DC parameters measurement with the algorithms
recursive form is given by the formula mentioned for three chosen fault cases are gathered in Table I
(description of the cases under the Table). It is seen that all
iw1(k ) =iw1(k 1) + wal1(k)[i(k) +i(k N / 2)] . (4) the algorithms are almost perfect for the signals that are not
contaminated by any additional components. For real cases,
The sought time constant TN is then calculated from however, when some harmonics or other noise is present in
current signal their accuracy is lower. Ranking positions
Tp
TN = , (5) assigned according to the level of measurement errors clearly
ln[r (k )] indicate that the best performance is expected when the full-
cycle averaging algorithm (W0) is used.
with the coefficient r(k) defined as
TABLE I. ERRORS OF DC PARAMETERS MEASUREMENT
iw1(k) iw1(k 1)
r(k) = . (6) Case Measurement errors
Algorithm used
iw1(k 1) iw1(k 2) HCDFT W1 (N/2) for IDCW0 (N)
(2) (7) (10)
With this method correct estimation results of TN are 1 absolute [A] 0,0 0,05 0,1
relative [%] 0,0 1,7 0,3
expected after k=N/2+1 sampling periods counted from the 2 absolute [A] 0,9 0,4 0,1
fault inception moment, at the earliest. The coefficient r is relative [%] 40,9 18,2 4,5
often additionally limited upwards to the level of 1.0 and, 3 absolute [A] 0,14 0,04 0,02
relative [%] 8,2 2,3 1,1
downwards, with a lowest reasonable time constant TN=4ms. Ranking 3 2 1
The initial value of DC component is here determined from 1) Current defined in MATLAB: TN=300ms, IDC=3A, I1=5A, f=50Hz
2) Fault current (EMTP-Simulation): TN=20ms, IDC=2,2A, I1=3,9A, f=50Hz
r(k) kT p 3) Current at the generator terminals (real fault case): TN=120ms,
I DC = e (7)
2 IDC=1,7A, I1=3,8A, f=60Hz
6
with the exponential term in (7) introduced to compensate for HCDFT W1 W0
the time going by. 4.5
The algorithm based on full-cycle signal averaging (which
Current and its DC component (A)
solvable for the time ts1 e.g. with the least error squares LW L0 + Ls + Lb
method. Herein are: magnetic permeability of the iron TW = = . (18)
RW R2 + Rs + Rb
core, w2 number of turns of the secondary winding, l
middle length of magnetic force lines in the CT iron core,
Needless to say, the application of the above-presented
I2 amplitude of the secondary current (fundamental
formulae is possible in dependence on the availability of the
frequency component), TW CT time constant, TN time
CT and network parameters.
constant of the network seen from the fault point
(equivalent to time constant of DC component in fault 0.4
current).
0.35
b) Simplified version of (11), with CT time constant TW
assumed as infinite (significantly higher as the network 0.3
measured
Time to saturation ts1 (s)
eq. (12)
B S q 0.2
t s1 =T N ln1 ,
(12)
T N R 2 I 2 0.15
0.1
c) Formula proposed in IEEE Standard C37.110-1996 [13]:
0.05
( X / R ) K s 1 K 1 eq. (13)
t s1 = ln1 =TN ln1 s , (13) 0
2 f ( X / R ) TN
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Relative level of DC component IDC/I1
tance and resistance of the network at the fault spot, To evaluate the quality of the formulae for ts1 and ts2
R2 resistance of the CT secondary winding, Rs calculation a number of simulation tests have been conducted.
resistan-ce of the leads, Zb apparent impedance of the A variety of simulation cases with diverse combinations of
CT burden. fundamental frequency and decaying DC components
amplitudes and time constants were prepared. Introductory
From the magnetic flow law
analyses and simulative investigations have shown that the
values obtainable with formula (12) are very close to those
B s = w2 i s ' , (14)
l resulting from simulation of CT operation and real-world
recordings. The outcomes of equation (13) are usually
by is = I DC e ts 2 /TN (neglect of ampere turns due to fundamental underestimated, i.e. smaller than in reality (Fig. 4). That
frequency current), one can derive a formula for the CT means the IEEE standard formula delivers rather conservative
saturation end time (ts2) in the form values of ts1, being (in our case) situated on the right side in
the sense of eventual adaptation being realized somewhat The fault occurred close to generator terminals and was
earlier than really required. On the other hand, the formula accompanied with DC induced CT saturation.
(13) is the only one that may be applied in the cases when In Fig. 6 the current signals from both sides of the
precise data on required CT parameters is not available. protected generator (secondary signals, phase L1) are shown
with additionally superimposed DC component. One can see
III. ADAPTIVE DIFFERENTIAL PROTECTION that the DC parameters (calculated according to (5) and (10))
The adaptive approach to the differential protection are found quite correctly, since the DC curve follows closely
developed is summarized in Fig. 5. The procedure of adaptive the maxima of current waveforms, especially for the time
adjusting of the differential characteristic consists of the period before CT saturation for which the values were
following steps: determined. Higher values from those calculated for currents
Calculation of the initial value (amplitude) IDC and time 6
a)
constant TN of the decaying DC component as well as the IDC +I1
[A]
0
fault case (shifting up of the differential curve or slope
changing of the stabilizing section), -1.5
procedure
Id/In
0.5
Calculation of Yes
t=0.081s
I1DC , T1 N IS <3I1n ?
I2 DC , T2 N 0.25
ts1=0.062s Out
(with
No ad. b)
CT Determination of
Stop 0
data Calculation of adaptation 0 0.05 0.1 0.15 0.2 0.25
t1s1, t1s2 , t2s1, t2s2 degree Time [s]
I dmax , Id /IS c) 0.5
Ratio of differential to nominal Id/In currents (pu)
m1'=0.41
Fig. 5. Block scheme of the adaptive protection.
0.4
It is worth to notice that the calculation of mentioned
above values is performed for the signals from CTs at both ad. b)
0.3
sides of the protected plant (big indexes 1, 2 Fig. 5). The
adaptation is carried into effect at or slightly before the
0.2
predicted time instant of CT saturation (lower from both m0=0.15
calculated values is accepted for this purpose). The detailed m1=0.25
0.1
equations for the expected values of Idmax and ratio Id/Is, in
dependence on CT saturation beginning ts1 or saturation
duration ts2-ts1, may be found in [14]. 0
0 0.2 0.4 0.6 0.8 1 1.2 1.4
Ratio of stabilizing to nominal Is/In currents (pu)