Diagrammatic only
SYSTEM DATA
-1-
CABLE DATA
Cable dimensions
Thermal Specific
Diameter
resistivity Heat
mm K.m/W J / m3 K
CONDUCTOR 44,3 3450000
NON METALLIC SCREEN 47,7
INSULATION 95,8 3,5 2400000
NON METALLIC SCREEN 98,6
METALLIC SCREEN 101,6 3450000
BEDDING 103,2 6 2000000
METALLIC SCREEN 109,2 1450000
SERVING 119 3,5 2400000
Metallic components
Conductor:
D.C. resistance at 20 C 0,0151 Ohm/km
Maximum operating temperature 90 C
D.C. resistance at max. operating temperature 0,0193 Ohm/km
A.C. resistance at max. operating temperature 0,0218 Ohm/km
Ks 0,8
Kp 0,5
Skin effect ys 0,128
Proximity effect yp 0,00238
Electrical resistivity at 20 C 1,72E-8 m
Temperature coefficient at 20 C 0,00393 K-1
Screen / sheath:
Resistance at 20 C 0,0769 Ohm/km
Operating temperature 80,15 C
A.C. resistance at operating temperature 0,0951 Ohm/km
Electrical resistivity at 20 C 1,72E-8 m
Temperature coefficient at 20 C 0,00393 K-1
Sheath loss factor 0,018
S.L.F. caused by circulating currents 0
S.L.F. caused by eddy currents 0,018
Capacitance:
Relative permittivity 2,3
Loss factor of insulation 0,0008
Core capacitance 0,183 F/Km
Capacitive current (per core) 7,31 A/km
CABLE INSTALLATION
-2-
Ambient temperature 29,4 C
THERMAL RESISTANCES
LOSSES
Losses splitting:
Current dependent losses:
Conductor (for each phase) 21,73 W/m
Screen (average for each phase) 0,392 W/m
Voltage dependent losses:
Dielectric (for each phase) 0,743 W/m
Total (for the three phases) 68,02 W/m