Professional Documents
Culture Documents
Power System Eng Part1
Power System Eng Part1
Syllabus
References
1
Structure of electrical power systems
The structure of electric power systems consists of the following
main parts :
1- Generating stations ( power station ) : Bulk electric power is
produced by special plants known as generating stations or
power plants . This part divided in two section :
a- Mechanical section It is sources of mechanical energy as
( Boiler, Turbine.) .
b- Electrical section as ( Alternators, transformers,
protection apparatus, controls system, and measuring
instruments.. ) .
2- Transmission lines: are the connecting links between the
power stations and the distribution system and lead to other
power systems over interconnections .There are two types:
a- Overhead transmission line .
b- Under ground cables .
3- Distribution systems: It connects all the individual loads to
the transmission line.
ELECTRICAL POWER GENERATION
Energy Resources
The resources of electrical energy ( primary fuels ) may be
divided into :
a - Thermal : as Coal, Oil, Natural gas, Nuclear, and Solar
b- Non Thermal : as Hydropower , Wind , and direct solar
conversion .
2
While considering primary fuels in meeting the worlds
energy requirements we may therefore include the
following :
3
Location of power station
The best geographical location of the generating plants would be
close to the electrical load centers , i.e, the regions where the
major energy demand exists . However, the locations of the
primary fuel conventional energy sources do not necessarily
coincide with load centers.
We are therefore faced with following choice ;
1- Build the power plants close to the energy sources and then
transport the electrical energy to the load centers
2- Build the power plants close to load centers and transport the
fuel from the source locality.
The electrical power grid makes the first alternative
technically feasible . However, in reality , the actual choice will
be based upon a combination of technical , economical and
environmental factors.
5
Main parts of power station are :
Boilers : It is a device meant for production steam under
pressure.
There are two type of boiler:
a) Fire tube boiler ; b ) Water tube boiler
For electrical power stations , generally water tube boiler
are used.
Turbine : It is the main part of the mechanical system of the
power station from which the mechanical energy
can be obtained.
Alternator ( Synchronous generator and exciter) : It is the main
part of electrical system from which the electrical
energy can be obtained.
2-pole ; 3000 r.p.m ( 50 HZ )
; 3600 r.p.m ( 60 HZ )
Power 1000 MW ; 11-33 KV ; 3-phase ; stare
connection
Air cooling up to 40 MW , above 40 MW using
hydrogen for cooling
Main exciters are compound d.c generators of 115 V or
230 V .
Generally , power factor is 0.8 lagging .
6
Selection of site :
The water supply should be available .
The site should be easily accessible.
Stability of foundation.
Land should be available at a reasonable price and further
extension should be possible
Restrictions of surrounding.
7
* Kinetic energy of water is its energy in motion ( flow of
water ) and is a function of mass and velocity .
* Potential energy is a function of the difference in level of
water between two points ( head ) .
Choice of site :
1- The station should be situated where a sufficient flow and
head of water are available .
2- The site should be easily a accessible
There are three different methods of classification hydro-
electric plants :
According to quality of water available , according to this
classification the plants may be divided into :
a) Run-off river plant without pond age.
b) Run-off river plant with pond age.
c) Reservoir plants.
According to available head , according to this
classification the plants may be divided into :
a) High head H > 300 m
b) medium head 30 < H < 300 m
c) Low head H < 30 m
According to nature of load. , according to this classification
the plants may be divided into :
8
a) Base load.
b) Peak load.
c) Pumped storage plants for peak load.
Main parts of hydro-electric plants:
1- Reservoir : Its purpose is to store water .
2- Dam : The function of dam is to provide a head of water to
be utilized in the water turbine.
3- Penstocks : These are pipes of large diameter, taking water
from the intake works to the power house (
turbine )
4- Prime mover : It is converted kinetic energy of ( turbine )
water into mechanical energy .
5- Power house : It consists of two main parts :
* Turbine
* Electric equipment ( generator ).
9
10
Choice of site :
1- As in the case of steam power station the water should be
available .
2- It should be situated a way from the populated area from the
safety point of view.
3- The site should be easily accessible.
4- There should be sufficient space to get rid of radio active
waste.
5- It should be situated as near to the load center as possible to
avoid losses in transmission
Fuels:
Fuels generally used in reactor are natural Uranium ( U ) , 235
92
available .
Natural uranium occurs in three isotopes (U , 0.7%) , (U ,
235
92
238
92
11
of steam power station is replaced by the nuclear reactor and heat
exchanger.
The heat energy thus released is utilized in raising steam at high
temperature and pressure . the steam runs the steam turbine which
converts steam energy into mechanical energy .
Moderator : It is used to moderate or reduce the neutron speeds
to value that increase the probability of fission occurring . made
from Graphite heavy water or beryllium.
Shielding : the purpose of shielding is to give protection from
the deadly radiation.
Control rod : by this rod can be controlled chain reaction . The
materials of rod are Cadmium , Boron .
Coolant : A coolant transfer heat production in side the reactor
to a heat exchanger . The coolants commonly used are gas ( air ,
Hydrogen , helium ) , water , heavy water , liquid metals
( sodium ) .
12
Advantages
1- The design and layout of the plant are quite simple.
2- It occupies less space , and it can be located at any place .
3- It can be started quickly and can pick up load in a short time .
4- There are no standby losses , and it requires less quantity of
water for cooling and less operating staff .
5- The overall cost is much less than that of steam power station
of the same capacity .
6- The thermal efficiency of the plant is higher than that of a
steam power station ( 35% )
13
Disadvantages
1- The plan has high running charges as the fuel ( i.e diesel )
used is costly .
2- The plant does not work satisfactory under overload
conditions for a longer period .
3- The plant can only generate small power .
4- The cost of lubrication and maintenance charges are
generally high .
14
Advantages
1- It is simple in design , and much smaller in size as compared
to steam power station of the same capacity since no boiler
and their auxiliaries such as feed water arrangement are
required .
2- The initial and operation costs are much lower than that of
equivalent steam power station .
3- It requires comparatively less water as no condenser is used .
4- The maintenance charge are quite small because it is simple
in construction and operation as compared to steam turbine .
5- It can be started quickly from cold conditions .
15
6- There are no standby losses .These losses occur in a steam
power station because boiler is kept in operation even when
the steam turbine is supplying no load .
Disadvantages
1- There is problem for starting the unit. It is because before the
starting the turbine , the compressor required power from
some external source .
2- The overall efficiency of such plants is low ( about 20 % )
because the exhaust gases from the turbine contain sufficient
heat , and a greater part of power developed by the turbine is
used in driving the compressor .
3- The temperature of combustion chamber is quite high
(3000 F) so that its life is comparatively reduced .
Load Curves and Factors
In choosing the type of generation ( thermal , hydro-electric and
nuclear) ,and to select the size and number of generating units , a
number of points have to be considered . Some of these are :
The kind of fuel available and its cost, availability of suitable
sites for a hydro station , and the nature of load to be supplied.
The load which a power system has to supply is never constant
because of variable demands at different time of the day .The
variations can be see from the predication load curve.
load curve :
It is a graphic record showing the demand of the power for every
instant during the hour , the day , the month or the year .
The figure below , represent the daily load curve
16
Important terms and factors
17
3. Maximum demand : It is the greatest demand of load on the
power station during a given period .
Max. demand is very important to
determine the installed capacity of the
station . The station must be capable
meeting the max. demand .
Max. demand
4. Demand factor = Connected load
18
Also :
Average demand
6- Load factor (L.F.) = Max demand (load ) during a certain
period
19
1
L.F < 1 ; L.F Max. demand
y1 y 2 y 3
D .F
Y
3y 300
= Y = 300
= 1 ( Very bad D.F )
300
Fig ( b ) D.F 3 ( Very good D.F )
100
20
KW KW
y1
y2 Y
y1 y2 y3 Y y3
0 8 16 24 hours 0 14 16 hours
Fig. b Fig. a
1
D.F 1 ; D.F Max. demand
1
Cost of plant D.F
21
Average load ( demand ) T
= Max . demand T
Average demand
= Plant Capacity
( 6.5 10 6 ) 10 3
plant use factor = ( 20 10 6 ) 2100 = 0.154
= 15.4 %
22
Load Duration Curve
When the load elements of a load curve are arranged in the order
of descending magnitudes , the curve thus obtained is called a
load duration curve . It gives the data in more presentable form.
Figures below represent i) daily load curve , ii) daily load
duration curve
Area under daily load curve = Area under daily load duration
curve .
= Total energy generated ( KWh ) on
the day
23
Load curves and selection of the number and sizes of
the generation units
24
The important points in the selection of generator
units are:
25
The load curve can be fit very accurately if large number and
small capacity of units are selected , this is one side , in other
side , the investment cost per KW of capacity increases as the
size of the units decreases .
26
Solution :
(KW)
2400
2000 2000
1600
1200 1400
800 1000
400 300
6 14 18 24 hours
27
Sum of indiviual max . demands
2- Diversity factor = max . demand on power station
28
Solution :
16600
= 0 .49
1400 24
E1 E1
L.F 1 ; 0.416
24 M 1 24 M 1
10 M1 = E1 .. (1)
29
E2
0 .458
24 M 2
11 M2 = E2 (2)
M1 M 2
1 . 142
1400
1600 = M1 + M2 .(3)
Energy generated from power station = E1 + E1
16600 = E1 + E2 .(4)
Put (3) and (4) in (2)
11 ( 1600 M1 ) = 16600 E1
17600 16600 11 M1 + E1 = 0 .(5)
Put (1) in (5)
1000 11 M1 + 10 M1 = 0
M1 = 1000 KW
From (3) M2 = 1600 1000 = 600 KW
From (1) E1 = 10 x 1000 = 10000 KWh
From (2) E2 = 11x 600 = 6600 KWh
30
Discussion Questions
1- Draw the important components of a steam power station .
2- What factors are taken into account to select the site of steam power station .
3- State the main parts of a thermal power station , and discuss the function of
each part .
5- What factors are taken into account to select the site of Hydro-Electric power
station .
7- What factors are taken into account to select the site of nuclear power station .
8- What do you understand from the load curve and what information are
converged by a load curve.
9- Discuss the important points to be taken into consideration while selecting the
size and number of units generation .
10- Explain the terms , connected load , load factor , plant use factor , diversity
factor .
Tutorial Problems
Q1 A power station is to supply three loads. The daily cycle of loads are given below:
Time in hours 0 - 10 10 - 20 20 - 24
Loads B in MW 0 15 0
31
Q2 A power station is to supply two loads . The daily load curves of two loads are
shown in figures below :
MW MW
25 25
20 20
15 15
10 10
4 12 16 20 24 hours 12 16 24 hours
Q3 A Power station is to supply two loads . The daily of loads are given below.
Draw the load and duration curves of power station, and find:
1- Load factor of each load.
2- Load factor of the power station.
3- Diversity factor of the power station.
4 - The capacity factor when the station is having reserve set 20% of the
max. Demand.
32
Prediction of load and Energy Requirements
The nature of load to be supplied affects the choice of plant to a considerable extent. The load
which a power system has to supply is never constant because of variable demands at different
time of the day . The variations can be seen from the predicated LOAD CURVE.
The minimum capacity of generating station must be such as to meet the maximum demand At
the same time it is essential for the power system to maintain reliability and continuity of power
supply at all time.
Therefore to determine the prediction of load and energy requirement must be draw the load
curve of demand. There are some methods for this purpose ,are:
1- Load survey
2- Methods of extrapolation
3- Mathematical methods
In choosing the type of generation ( thermal, hydro-electric and nuclear ) , and to select the size
and number of generating units, a number of points have to be considered. Some of these are:
The kind of fuel available and its cost, abundant quantity of cooling water should be available (
for thermal station ), availability of suitable sites ( for hydro station ), and the nature of load to be
supplied.
33
The selection of units should be approximately fit the annual ( yearly) load curve of the
station.
The capacity of the plant should be made 15 to 20% more than the maximum demand.
By using identical units ( having the same capacity ) ensure saving in cost of station .
34
Power Transmission
P1 phase VI cos ( 1 )
IF cos constant
loss ,
P 1 phase V I { C.S . A of conductor cost
Voltage regulation (V . R )
cost of transformers , towers,
insulators , and switch gears
Ptr2 Qtr2
Ploss Rl 2
watt
Vtr
Ptr2 Qtr2
Qloss X l 2
var .( 2 )
Vtr
transmission
costs
total costs
fixed costs
economical voltage
transmission voltage level
3P
V 5 .5 0 . 62 l ..( 3 )
150
Standard voltage levels
Conductor material
Characteristics of material ;
1- High electrical conductivity .
2- High tensile strength .
3- Low cost .
Better materials :
1- Copper (Cu):
Conductivity and tensile strength of copper
are high , but cost of material also high .
2- Aluminum (AL) :
a- conductivity of AL is 60% of that of Cu .
b- Coefficient of expansion is high .
c- Weak (low) tensile strength .
d- Lower cost and lighter weight of an AL
conductor compared with a Cu .
e- For the same resistance , AL conductor has
a large diameter than an Cu conductor , i.e
low effect of corona .
Steel strands
Aluminum strands
Stranded conductors are easier to manufacture , since
larger conductor size can be obtained by simply
adding successive layers of strands , and also easier
to handle and more flexible than solid conductors .
No.of layers 1 2 3 4 5
(n)
Ns, including 6+1=7 18+1=19 36+1=37 60+1=61 90+1=91
the Single
center strand
First layer
Second layer
Stranded conductors usually have central wire (core)
around which are successive layers of ( 6 , 12 , 18 ,
24 ) wires as shown in above fig.
19 1 3 n ( n 1 )
18 3n 2 3n
n2 n 6 0
( n 3)( n 2) 0
n2
D (1 2 n ) d
(1 2 2 ) 2 . 9 14 . 5 mm
Parameters of overhead transmission lines
The same current flows through the upper and lower
part of each section the resistance and inductance of
both can be combined and the equivalent circuit of
below fig. is obtained . Thus :
R1 r1 r1 , L1 l1 l1 etc.
Section of
unit length
Reaistance
2- Temperature :
R2 T t2
..( 7 )
R1 T t1
Inductance :
L henrys ( 8 )
I
Where - is flux linkage ( Weber-turns )
I - is current ( amperes )
d dLi di
e L ( 9 )
dt dt dt
Where e is induced voltage ( volt ) .
L is constant of proportionality , inductance
( henrys ) .
di
dt - is rate of changes of current
( amps/second ) .
dx
A dx . 1
mmf N I
mmf H l
mmf NI AT
H ( )
l l m
Where H field intensity .
l - length of path of flux .
l 2 x
N No. of turns of conductor { for our analysis N=1
(one conductor )}
Hl I
Or 2 x H x I x
Ix x2 x
Hx I I AT / m
2 x r . 2 x
2
2 r 2
We know : B H
And , B r 0 H
2 r 2
Also , we know : B
A
B A ; d Bx .dA
xI xI
d dA dx.1 Wb / m
2 r 2
2 r 2
therefore , 0 4 10 7
0 I 4 10 7 1
int . I 10 7 Wb.T / m
8 8 2
int . 10 7
Lint . henrys / meter (11)
I 2
conductor carried D1 P1
current = I
x dx
D2
P2
mmf N I H l
l 2 x ; N 1
N No. of turn
2 x H x I x I
I
Hx AT / m
2 x
B H
A
I
Bx Wb / m 2
2 x
B A ; d Bx .dA
The flux links with current I in the thickness dx :
I
d dx Wb / m
2 x
The flux linkage per meter :
D2
I I D2
12
D1
2 x
dx
2
ln
D1
Wb.T / m
therefore , 0 4 10 7
D2
12 2 10 I ln
7
Wb.T / m
D1
12 D
L12 2 10 7 ln 2 henrys / m
I D1
..(12)
Inductance L12 , this only for flux linkage of an
isolated conductor which lie between the points
P1 and P2 distant D1 and D2 respectively from the
center of the conductor as shown in fig.
conductor
radius r2
conductor
radius r1
D
L1ext 2 10 7 ln henrys / m
r1
For internal flux only ( eq. 11 )
10 7
L 1int . henrys / meter
2
Therefore , total inductance of the circuit due to
current in conductor 1 only is :
L1 L int L ext
1 D
L1 10 7 2 10 7 ln
2 r1
1 D D
2 10 7 ln 2 10 7 ln e 1 / 4 ln
4 r1 r1
D D
2 10 7 ln e 1 / 4 2 10 7 ln 1 / 4
r
1 e r1
1 / 4
But , e 0 .7788
D
L1 2 10 7 ln
0.7788 r1
D
L1 2 10 7
ln henrys / m
r1 ( 13 )
Where , r1 0.7788
r1 is called Geometric mean radius ( G.M.R )
r1 = 0.7788 times the radius of conductor .
D
L 4 10 7 ln henrys / m ( H / m)
r
And ,
D
L 0.4 ln mH / Km
r
...........( 14 )
I 1 I 2 I 3 ....... I n 0
If 1 p1 denotes all the flux linkages of conductor 1
due to its own current I1 , internal and external , upto
point P . By using eq. (11) and (12) :
I1 D1 P
1 p1 2 I 1 ln 10 7
2 r1
DP
2 10 7 I 1 ln 1 Wb .T / m
r1
where r1 = 0.7788 r1
D12
Similarly for 1 p 3 , ........ 1 pn
The flux linkages 1 p with conductor 1 due to
I 1 , I 2 , I 3 ,... I n , but excluding flux beyond point P is:
D1 p D2 p D3 p Dnp
1 p 2 10 I1 ln
7
I2 ln I3 ln .... In ln
r1 D12 D13 D1n
1 1 1 1
I ln I ln I ln .... I ln
7 1
2 10 r1
2
D12
3
D13
n
D 1n
I ln D I ln D I ln D ..... I ln D
1 1p 2 2p 3 3p n np
But , I n I 1 I 2 I 3 ....... I n 1
1 1 1 1
1
I ln I ln I ln .... I ln
r1
2 3 n
D12 D13 D1n
1 p 2 107 I1 ln D1 p I 2 ln D2 p I3 ln D3 p ..... (I1
I 2 I3 ...... I n1) ln Dnp
1 1 1 1
I1 ln I 2 ln I3 ln .... I n ln
7
r1 D12 D13 D1n
1 p 2 10
D D D
I1 ln 1 p I 2 ln 2 p ...... I n1 ln (n1) p
Dnp Dnp Dnp
1 1 1 1
1 2 107 I1 ln I 2 ln I3 ln .... I n ln
r1 D12 D13 D1n
Wb.T / m
1 1 1 1
1 2 107 I1 ln I 2 ln I3 ln .... I n ln
D11 D12 D13 D1n
Wb.T / m .(15)
conductor A conductor B
carried current I carried current - I
Applying eq. (15) to segment (filament ) (a) of
conductor A , we obtain for flux linkage of filament (a)
I 1 I 1 I 1
a 2 10 ln
7
ln ..... ln
P Daa P Dab P Dap
I 1 I 1 I 1
2 10 7 ln ln ..... ln
q D q D q Daq
aa ab
1 1 / p 1
1/ p
1
1/ p
ln
ln ..... ln
7
2 10 I Daa
Dab Dap
lnDaa lnDab ..... lnDaq
1/ q 1/ q 1/ q
1 / q
1 1
ln ln ln D 1/ q
Where D
aa
D aa 1 / q aa
(16)
La - Inductance of filament (a) .
In similar manner we may write :
Where :
ln ( x y z ) ln x ln y ln z
ln ( y / x ) ln y ln x
ln ( x ) y y ln x
The average inductance of the filaments of conductor A
is :
L L L ..... Lp
L average a b c
p
Conductor A is composed of (p) filaments electrically
in parallel ;
1- If , L a Lb Lc Lp Laverage
L
LA a
p
Where LA , inductance of conductor A .
2 - If L a Lb Lc Lp
Laverage La Lb Lc ......Lp
LA
P P2
The numerator is called Geometric mean distance
( G.M.D ) between conductors A and B , and denoted
Dm , but denominator is called Geometric mean radius
( G.M.R ) and denoted DS .
Dm
LA 2 107 ln henrys/ meter ..(18)
DSA
D
LB 2 107 ln m henrys/ meter
DSB
Dm
L LA LB 4 107 ln H /m
DS
Dm .(19)
0.4 107 ln mH / Km
DS
Inductance of three-phase lines :
A) Equilateral spacing :
Ia Ib Ic 0
By using eq.(15)
1 1 1
a 2 107 I a ln Ib ln Ic ln Wb.T / m
r D D
Ia (Ib Ic )
D
a 2 107 I a ln Wb.T / m
r
D
La 2 107 ln H /m .(20)
r
r 0.7788 r
L a - Inductance per phase of 3-phase line .
IF conductor is stranded , r DS , therefore :
D
La 2 107 ln H /m .........(21)
DS
B) Unsymmetrical spacing :
1- Transposed conductor with unsymmetrical spacing:
1 1 1
a3 2 107 I a ln Ib ln Ic ln
r D31 D23
a1 a 2 a 3
a
3
1 1 1 1 1
a 2 107 I a ln Ib ln Ic ln
r 3 D12D23D31 3 D12D23D31
7
1 1 1
2 10 I a ln Ib ln Ic ln
r 3 D D D 3 D D D
12 23 31 12 23 31
But , I a ( I b I c )
3 D D D
a 2 10 I a ln 12 23 31
7
Wb.T / m
r
a 3 D12 D23 D31
7
La 2 10 ln H /m
Ia r
7
Deq
L a 2 10 ln H /m
Ds (22)
3La
La
3
7
Deq
2 10 ln H /m
Ds
2- Untransposed conductors with unsymmetrical
spacing :
a
L
And inductance of phase (a) , a
Ia
1 I 1 Ic 1
La 2 107 ln b ln ln
r I a D12 I a D31
Ia Ib Ic 0
If I a is taken as a reference phasor :
I a I a 0 ; I b I a 240 ; I c I a 120
And ,
Ib
1240 cos 240 j sin 240
Ia
1 3
j
2 2
Ic
1120 cos120 j sin 120
Ia
1 3
j
2 2
Thus summarizing :
D12D31 D12
7
L a 2 10 ln j 3 ln H /m
r D31
D23 D12 D23
7
L b 2 10 ln j 3 ln H /m
r D12
D31D23 D
L c 2 10 ln
7
j 3 ln 31 H /m
r D23
...........(23)
d - bundle spacing .
To calculate inductance of bundle conductor , DS in
eq.( 21 , 22 , 23 ) replaced by the GMR of the bundle ,
b
which is denoted by DSL .
b
2 ( DS d ) 2 4 ( DS d ) 2 ( DS d )
2
DSL
b
3 ( DS d d )3 9 ( DS d 2 )3 3 DS d 2
2
DSL
Inductance of parallel circuit three phase lines
with symmetrical spacing :
a a a C
b b b b
c C c a
D D
3D 2D 3D
D 30 30 D
1 1 1 1
a r
I ln ln
b I ln ln
2D D 3D
a 2 107
1 1
Ic ln ln
3D D
1 1 1
a 2 10 I a ln
7
I b ln I c ln
2
2 D r 3D 2
3D
1 1
a 2 107 I a ln I b I c ln
2
2 D r 3D
But , I a I b I c 0
7 1 1
a 2 10 I a ln I a ln
2
2Dr 3D
3D2 3D
a 2 10 I a ln
7
7
2 10 I a ln
2 D r 2 r
Inductance of phase (a) :
a 3D
La 2 10 ln
7
H /m
Ia 2 r (24)
EX.1 A 3-phase , 50Hz , 132 KV overhead transmission
lines has conductor diameter of 4 cm each , are
arranged in a horizontal plane as shown in fig .
supplies a balanced load , assume the line is
completely transposed . Find the inductance per
Km per phase .
4m 4m
Solution :
D m Deq 3 D AB D BC DCA
3 4 4 8 5.04 m
DS r 0.7788 r
4
0.7788 1.5576 cm
2
7 Dm 7 5.04
L 2 10 ln 2 10 ln
Ds 1.5576 10 2
11 .53 10 7 H / m
1.153 mH / Km
EX.2 A 3-phase , 50Hz , 400 KV overhead transmission
lines are arranged in a horizontal plane , each phase
has two strand bundle conductors , the diameter
of each strand is 25mm , as shown in the fig.
below. Find the inductance per Km per phase .
0.3m 25mm
6m 6m
Phase A Phase B Phase C
Solution :
D m Deq 3 D AB D BC DCA
3 6 6 12 7.56 m
DS r 0.7788 r
25
0.7788 9.735 mm
2
b
DSL DS d
9.735 10 3 0.3 0.054 m
7 Dm 7 7.56
L 2 10 ln 2 10 ln
Ds 0.054
9.88 10 7 H / m 0.988 mH / Km
Discussion Questions
1 The resistance of a transmission line is effected by some factors .
Explain these factors .
2 What is the effect of skin effect in the resistance of transmission
line conductors .
3 Show that the inductance of a conductor due to internal flux is
given by :
1
L 10 7 H /m
2
4 What is the effect of temperature in the resistance of transmission
line conductors .
5 Derive in expression for the inductance per phase for a 3- phase
overhead transmission line when conductors are of equilateral
spacing .
6 What is the effect of unsymmetrical spacing of conductors in a
3-phase transmission line .
7 State the advantage of bundle conductor lines over single
conductor lines .
Tutorial Problems
Q1. A 3-phase , 50 Hz , 110 KV , overhead transmission line consists
of three solid conductors of 3 cm diameter positioned on the
corners of triangle with sides of 2 m , 2.5 m , 3.125 m .
If the conductor of each phase of this line is replaced by three-
strand bundle conductor has the same equivalent area of one solid
conductor , and the space between the strands of bundle is 0.2 m .
Find the inductance for two conditions . Assume the internal
magnetic flux of conductor is neglected and the line is transposed.
Q2. A 3-phase , 132 KV , 50 Hz , 100 Km , single circuit bundle
conductor transmission line as shown in the figure below . If the
diameter of each strand is 1 cm , and the conductors are
regularly transposed . Determine , the inductance per phase per
Km .
6m
5m
0.18 m