2- Domestic water tank cooling / heat gain load calculations performed by Hatco.
- Cooling / heat gain calculation has been considered only the load coming from
the income hot water.
- Cooling / heat gain calculation did not consider the heat transfer which is coming
from outside ambient condition through the tank walls (tank cylinder body). This heat
transferred will be only reduced by tank thermal insulation however it will be still
valid.
- Cooling / heat gain calculation did not consider the heat transfer which is coming
for the sun solar energy. This will be caused more heating load through the tank
body and that will heat the water. Tank insulation will be reduced this load
but heating load will be also still valid.
Conclusion,
Based on the above analysis out conclusion as the following
- Provide and installed the water tank inside totally sealed room (wall and roof).
And does not exposed to outside ambient condition. This scenario will maintain the
cooling unit 4-5 Tons
- Revised the 4 Tons unit to 10-12 Tons and keep the tank location as shown on
current drawing.