Professional Documents
Culture Documents
• However, if the wall or roof is a single homogeneous slab, the governing differential equation is:
𝜕𝑡 𝑘 𝜕2𝑡
=
𝜕𝜃 𝜌𝑐𝑝 𝜕𝑥 2
• 𝑞"𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑖𝑜𝑛,𝑒𝑥𝑡,𝑗,𝜃 is not equal to 𝑞"𝑐𝑜𝑛𝑑𝑢𝑐𝑡𝑖𝑜𝑛𝑖𝑛,𝑗,𝜃 unless steady-state heat transfer conditions prevail
Likewise, the interior surface heat balance on the jth surface at time θ may be represented conceptually as:
𝑁𝑦 𝑁𝑥 𝑁𝑞
𝑁𝑧 𝑁𝑦 𝑁𝑞
𝑁𝑧 𝑁𝑦 𝑁𝑞
0.5mph<Vs<9mph
0.2m/s<Vs<4m/s
Exterior Radiation
Exterior Surfaces:
• Surrounding Ground
• Vegetation
• Parking Lots
• Sidewalks
• Other Buildings
• The Sky
Exterior Radiation-Assumptions
1. Surfaces opaque, diffuse, isothermal and uniform
2. Surfaces gray with single values of absorptivity and emissivity
3. Radiation to sky: heat transfer to a surface with an effective sky
temperature
4. Other buildings: flat, featureless, plane vertical wall has a view
factor of 0.5 with the ground and 0.5 between the wall and the sky
5. Tground ≈ tair
Exterior Radiation-Assumptions
With these Assumptions:
Exterior Radiation-Assumptions
View factors:
Then:
BLAST Program
Effective sky temperature = outdoor dry bulb temperature - 10.8 R(6K)
For non horizontal surfaces:
Exterior Surface Heat Balance Formulation
• Energy balance:
• Replacing terms of solar radiation, exterior convection and exterior radiation and
solving for 𝑇𝑒𝑠,𝑗,𝜃 :
• Wind velocity and direction usually change from winter to summer, making an appreciable difference in the
computed infiltration rates for heating and cooling
• The direction of the prevailing winds usually changes from winter to summer
• This should be considered in making infiltration estimates because the load will be imposed mainly in the
space where the air enters
• During the summer, infiltration will enter the upper floors of high-rise buildings instead of the lower floors
Zone Air Heat Balance
4- System Heat Transfer:
• The system heat transfer is the rate that heat is transferred to the space by the
heating/cooling system
• Although, the zone air heat balance can be formulated to solve for system heat
transfer when the zone air temperature is fixed, it is convenient to be able to
represent the system and determine the zone air temperature and heat extraction
rate simultaneously
• It is convenient to make a simple, piecewise linear representation of the system
known as a control profile
• This usually takes the form:
- a and b are coefficients that apply over a certain range of zone air temperatures
- ti is the zone air temperature
• Note that 𝒒ሶ 𝒔𝒚𝒔𝒕𝒆𝒎,𝜽 is positive when heating is provided to the space and
negative when cooling is provided
• When the zone air temperature is fixed, it is equal in magnitude but opposite in
sign to the zone cooling load
Example 8-8
• A small, variable air-volume system with electric reheat has the following operating parameters and control strategy that
apply to a particular zone:
• Both the flow rates and minimum fraction are determined upstream of the reheat coil (i.e., the density may be
determined from the supply air temperature and an assumed pressure of one atmosphere). It is controlled with the
following strategy:
• Assuming linear modulation of the terminal unit and the reheat coil, determine the amount of heating or cooling
provided by the system for the following zone temperatures: 50, 67, 70, 72, 76, 80 F. Then, calculate the coefficients a
and b for the piecewise linear function:
• For purposes of determining thermodynamic properties, assume the air exiting the cooling coil is approximately saturated
Zone Air Heat Balance Formulations
• The simplest formulation of the zone air heat balance is to determine the
cooling load (i.e., for a fixed zone air temperature, determine the required
system heat transfer)
Example 8-9
• Find the sensible cooling load for the zone from the preceding examples.
The convective portion of the internal heat gains is 1500 Btu/hr. The
infiltration rate is 1 air change per hour and the outdoor air is at 85 F, and
has a specific volume of 13.9 ft3/lbm. The surface areas, temperatures, and
convection coefficients are summarized in the table below:
Zone Air Heat Balance Formulations
• Likewise, the zone air heat balance can be formulated to determine the
instantaneous zone temperature when there is no system heat transfer.
Setting the system heat transfer rate equal to zero and solving for the zone air
temperature gives:
Example 8-10
• Find the zone air temperature for the zone from Example 8-9 if there is no
system heat transfer. All other details (surface temperatures, infiltration rate,
internal heat gains) are the same.
Zone Air Heat Balance Formulations
• Finally, the zone air heat balance can be formulated to determine the zone
temperature when there is system heat transfer. Substituting the piecewise
linear expression for system capacity into the zone air heat balance and
solving for the zone air temperature gives:
Example 8-11
• Find the zone air temperature for the zone from Example 8-9, if the system
described in Example 8-8 is operating. All other details (surface
temperatures, infiltration rate, internal heat gains) are the same.