Professional Documents
Culture Documents
• Thermal comfort
• Indoor & Outdoor Design Conditions & Criteria
• Cooling Load Principles & Estimation
1- Conventional method “Maximum load”
2-CLTD/SCL/CLF method for Nonresidential
building.
3- CLTD/GLF for residential building.
• Heating Load calculation
Thermal comfort
Thermal comfort : Is that condition of mind which expresses satisfaction
with the thermal environment.
50 % RH
Recommended inside design condition
96
Design Conditions in Beirut
The outdoor and the indoor conditions considered in our project are
the following: ( Lat= 33.8 Deg. , Elevation 29 m)
Summer Conditions Winter Conditions
(August –Beirut ) (January - Beirut )
100
The heat storage effect for different types of
construction
The relation between heat gain and cooling load and the effect of the mass
of the structure ( light, medium & heavy ) is shown below. From the figure
it is evident that, there is a delay in the peak heat, especially for heavy
construction.
101
Conversion of heat gain into cooling load
There are four distinct but related heat flow rates used in the design of Air
conditioning system: 1-Space heat gain, 2- Space cooling load, 2- Space heat
extracted rate ; 4- Cooling load.
Conversion of heat gain into cooling load
1-Space heat gain instantaneous rate of heat gain, is the rate at which
heat enters a space, or heat generated within a space during a time
interval.
2-Space cooling load is the rate at which heat is removed from the
conditioned space to maintain a constant space air temperature. Previous
figure shows the difference between the space heat gain and the space
cooling load. The difference between the space heat gain and the space
cooling load is due to the heat storage of a portion of radiant heat in the
structure.
3- Space heat extracted rate is the rate at which heat is removed from
the conditioned space.
4-Cooling coil load :is rate at which energy is removed at the cooling coil
that serves one or more conditioned spaces in any central air conditioning
systems.
Sudden increases
Sudden decrease
in temp and
in temp and
gradual increases
relative humidity
in relative
humidity
Significant rise in
temp and lower
relative humidity
Summary of Cooling Load
Calculation Methods
•Conventional method ( peak load )
Evaluate max. load to size/select equipment
• CLTD/GLF Method
For residential buildings single & multifamily buildings
• CLTD/CLF Method
Hand Calculation Method
For non-residential buildings office building ,industrial ,etc..
Simplified Factors based on TFM (above)
•Radiant Time Series (RTS) Method
Based on Heat Balance Method (exact solution)
Requires Computer-Based Solution Techniques
•TETD/TA Method
Equivalent cooling load temperature difference .
Originally Developed by Willis Carrier
Widely used but sources not well-documented
•Transfer Function Method (TFM)
Rigorous & Complex
Requires Computer
• Rules of thumb & floor areas “Cooling Load
Check figures”
1. The Heat Balance Method (ASHRAE)
Fundamental Method, most reliable
Application of the first law of thermodynamics
Real application and requires fewer assumptions
Advantages:
1. Using a complete heat balance would give better results than simplified
methods
2. Additional information about the component performance could be
determined and not only cooling load
Disadvantages:
1. A complete description of the input data should be provided by this
method
2. Iterative procedure is included because all of the heat balance equations
must be solved simultaneously, and therefore, a computer program should
be used
The Radiant Time Series (ASHRAE)
2- Coefficients to convert radiant heat gain components to cooling
load
Advantages:
1. Is a simplification of the heat balance method and can be
performed step by step, thus it does not require iterations
2. Can be implemented in a computerized sheet
Disadvantages:
1. Sol-Air temperatures have to be found for each hour of the 24
2. Periodic response factor has to be found for each wall, roof …
according to its layer section
3. It is not suitable for manual calculations because the periodic
response factors and the radiant time factors has to be found
using a software
The Radiant Time Series (cont’.)
• Wall and window conduction 63%, 37%
• Roof conduction 84%, 16%
• People 70%, 30%
• Lighting 67%, 33%
• Equipment, 20%, 80%
• Transmitted solar heat gain 100%, 0%
• Absorbed solar heat gain, 63%, 37%
• Infiltration 0%, 100%
3. The Admittance Method (CIBSE)
Uses the heat balance equations to find the load
Internal temperature is not assumed constant
Demonstrate the role of internal mass in modifying room
temperature
Advantages:
1. Simple
2. No iteration is needed
3. Allows the calculation in two modes: overheating calculation
(floating temperature), and a peak cooling load calculation
Disadvantages:
1. It was lately shown that the environmental model contains several
flaws
2. Tends to underpredict lighter weight zones cooling loads and
overpredict loads for heavyweight zones (because of radiant
factors)
Cooling Load estimation
C . L. QT Q S Q L Qo Qe QV
Where :
QT Is the heat transm itted through structures
Qs Is the heat gained from Sun.
Q L Is the light heat gained .
Qo Is the heat of Occupants.
Qe Is the heat of equipem ent, m otors
QV Is the heat of Ventilation or
QI Is the heat of Infiltration.
C.L. QT QS QL Qo Qe QV
Heat transmission through
structures .
The heat gained through structures is estimated from the
following equation:
Qt [ U A (To Ti)]
where Q is the heat gained per second ( W ) ,
U is the overall heat transmission coefficient (W/m2 .K )
A Area .
To Design Outside temperature (33.9 35 C ) [in Beirut ]
Ti Inside temperature (24 25 C )
Sun Heat gain SHG.
(Walls & windows)
Maximum (peak )
Sun heat gain Factor on Windows
SHGF (W/m2 )
Windows
SHGF W/m2.
SW SE
Beirut
Remark ! Sun heat gain
•If two or more walls are exposed to sun ray, the wall
having the higher sun effect value will be selected for
cooling load calculation, assuming that TS is based on
the peak load.
• However, we could add them all if it is required to
calculate the cooling load at a particular time of the day
(let say @ 5 o'clock). In this case, TS will be based on
the actual load at the particular time.
Simultaneously at the same time of the day ( for example south & East
walls are exposed )
Q S [(U A ΔTS ) North A (W/m ) North Sc]
2
115
Sun Heat gain ( Roof )
117
Shade Coefficient SC for glass
Shade Coefficient SC for windows
Heat of Occupants
Qo n Q / person D.F .
Where :
n Num ber of occupants
Q Heat produced / person
Q (Q s Q L ) / person
D .F . Diversity factor
Diversity of the cooling
Another design consideration is the diversity of the cooling
load. "diversity of cooling load results from the probable
non-occurrence of part of the cooling load on a design day.
Diversity factors are applied to the refrigeration capacity
in large air-conditioning systems. These factors vary with
location, type and size of the application, and are based
entirely on the judgment of the engineer."
The diversity factor, as a ratio of actual load/design load,
can be applied to people and lighting loads in large
multistory office, Hotel or apartment buildings. For
example, in an office building, the diversity factor for the
refrigeration capacity due to people may be from 0.75 to
0.90 and, due to the lighting, from 0.70 to 0.85. In
addition, the design engineer must consider the storage
load factors for heat gain due to lighting and solar gains
44
by glass.
Diversity factor
Carrier
Example:
100 persons seating in theater @ night. Calculate the
heat From occupants:
Qo n Q / person
Qs 100 70 7000 W
QL 100 35 3500 W
Qo 100 (105) 0.8 8400 W
Assuming D.F . 0.8
121
Light Heat gain.
Q L (I n 1.25 F) in watt
Where :
I n heat radiation from lamps
in watt. ( From Electrical Drawing)
F heat radiation From Fluorescent
Or using Specific table ;
Q L Area ( W/m 2 ) DF.
Diversity Factor DF tak ing into consideration
the possibilty of not using all lighting connections at
the sametime. For Exam ple 65% of the light is ON
DF 0.65
Light Heat gain
Example
W / m2 Type of Building
For 150 m2 area flat,
estimate the heat gained 60 Office
from lighting:
45 Factory
150 x 20 x0.65 =
40 School, University
=1950 W.
Assuming DF = 0.65. 20 Flat, theater, hotel,
17 Restaurant
15 Hospital, Library,
Museum
123
Heat of equipment & Motors
Qe Sum ( E (1 ))
Where :
E Power in watt.
Efficiency of the m otor.
Heat of equipment & Motors
Example:
Motor Power Efficiency
A computer room,
having 10 computers
Less than 200 Watts. 0.6
128
Heat gained by Ventilation (fresh air )
[sensible + latent]
QV= Qsensible + QLatent .
Ventilation:
Qsensible= 1 .23 x n x (L/S/Person) x (to - ti) watt
Qlatent = 3010x n x (L/S/Person) x (Wo - Wi) watt
Qtotal = 1.2x n x (L/S/Person) x (ho – hi) watt
Where:
Q = L/s/person from ASHRAE standard tables, ventilation or infiltration.
to, ti = outside, inside air temp., o C.
Wo, Wi = outside, inside air humidity ratio, kg(water)/kg(dry air).
ho, hi = outside, inside air enthalpy, kJ/kg (dry air).
n = number of occupants 129
ho
O
outside
hx
hI
Qlatent = 3010x n x (L/S/P
X
I Room
131
Heat of Infiltration
The heat loss by infiltration (Leakage from Windows
openings) is determined from the following formula:
3 1
Q I Sum L ( L / s / m ).10 ( ho hi ).10 3 . (W )
o
ν o Specif volume (from psych. Chart )
h o Enthalpy @ the Outside temperature
h i Enthalpy @ the inside temperature.
Sum of L Perimeter.
L/ S / m 0.82 ( from table )
(for Glass window , Aluminum.Frame )
L/ S /m 5 (for Wooden door )
(Leakage from Windows ) L/s/m
133
(Leakage due to door opening) L/s/m
Practical
Infiltration Loss
(Air change method)
C
Qv ACH V (t i t o )
3600
Qv 0.333 ACH V (t i t o )
Review
Supplied Air for cooling
(Volume flow rate mS)
In order to determine the required air supply for cooling
a specific room, we should have the following information
and data:
1- Does the system require forced fresh air from
outside door, mixing box , etc. or is it just a split unit?
2- What is the total cooling load ? & the Sensible room
load ?
3- What is the RSHF ?
4- Locate the point S in the psychometric chart & find
supply temperature Ts. Approximately Ts is about (14-16
C)
Location of point S , ( Ts)
Calculated
C.L.
ms ( Kg / s )
(hR hS ) 103
141
Approximation
0.37 Pt
T fan
fan m
QS = q (tot) x 1.05
Approximate values for Cooling Load
“Residential Building” Check
up only
As a rule of thumb
· For Bed Room 1 m2 650 BTH/hr.
· For Salon or Dining 1 m2 850-950 BTH/hr.
· For Roof 1 m2 800- 900 BTH/hr. (rooms)
For Roof 1 m2 950- 1000 BTH/hr. (Salon)
For heating 1 m2 90 Kcal/hr. (Beirut)
No forced
fresh air.
Only heat
gain from
infiltration is
included in
the C.L.
calculation
No plenum box
2
4&6
5
3&1
forced fresh
air (ventilation)
+ infiltration
are included in
the C.L.
calculation
5
3&4
1& 6
Part 2 72
forced fresh
air (ventilation)
is not included
in the
calculation of
C.L.
No Mixing
Heating Load Estimation
Qt U A (Ti To)
where Q is the heat loss per second ( W ) ,
U is the overall heat transmission coefficient (W/m2.C)
A Area .
To Outside temperature (6 8 C ) [in Beirut ]
Ti Inside temperature (21 C )
Ventilation loss (Fresh air )
3 1
Qv n ( L / s / person)10 (hi ho ) 103. (W ) Or
o
3 1
Qv n ( L / s / person)10 Cp (Ti To ) 103. (W )
o
o Specif volume ( from psych. Chart )
To Outside temperature
Ti inside temperature.
n Number of Persons.
Cp 1.005 Kj / Kg .C
Infiltration Loss (leakage)
3 1
Q I Sum L ( L / s / m ).10 ( hi ho) 10 3 . (W )
o
Or sim lpy
3 1
Q I Sum L ( L / s / m ).10 Cp (Ti To ) 10 3 . (W)
νo
ν o Specif volume (from psych. Chart )
To Outside temperature
Ti inside temperature.
Sum of L Perimeter.
L/S/M 0.82 , Cp 1.005 Kj/Kg.
(for Glass window , Aluminum.Frame)
Questions:
C
Qv N V (ti to )
3600
Qv 0.333 N V (ti to )
Number of air change Winter ASHRAE 97
A27.4
ASHRAE 72
Q A C P n
Pwind C p 2
V wind
2
P0 h 1 1
Ps C d g
Pressure coefficient Ra To Ti
2 P0 h 1 1
P C p Vwind C d g Ppressurization
2 Ra To Ti
Pressure coefficient Cp
Wall
Roof
Stack effect
The stack effect occurs when the air density differs between the inside
and outside of a building. On winter days, the lower outdoor temperature
causes a higher pressure I at ground level on the outside and consequent
infiltration. Buoyancy of the warm
inside air leads to upward flow, a higher inside pressure at the top of the
building, and exfiltration of air. In the summer, the process reverses with
infiltration in the upper portion of the building and exfiltration in the
lower part.
Considering only the stack effect, there is a level in the building where no
pressure difference exists. This is defined as the neutral pressure level.
Theoretically, the neutral pressure level will be at the mid-height of the
building if the cracks and other
openings are distributed uniformly in the vertical direction. When larger
openings predominate in the lower portion of the building, the neutral
pressure level will be lowered .Similarly; the neutral pressure level will be
raised by larger openings in the upper portion of the building. Normally the
larger openings will occur in the lower part of the building because of doors.
The theoretical pressure difference with no internal
separations is given by:
P0 h 1 1
Pstack g
Ra To Ti
Po = outside pressure, Pa
h = vertical distance from neutral pressure level, m
To = outside temperature, K
Ti = inside temperature, K
Ra = gas constant for air, J/(kg-K)
HEAT LOSS THROUGH BASEMENT WALLS & FLOORS BELOW THE GROUND LEVEL
The loss through the floor is normally small and relatively constant
because the ground temperature under the floor varies only a little
throughout the year. The ground is a very good heat sink and can absorb or
lose a large amount of heat without an appreciable change in temperature
at about the 8 ft (2.4 m) level . Above the 8 ft level, the ground
temperature varies with the outdoor temperature, with the greatest
variation at the surface and a decreasing variation down to the 8 ft depth.
The heat loss thru a basement wall may be appreciable and it is difficult to
calculate because the ground temperature varies with depth. Carrier -
tables 35 thru 37 have been empirically calculated to simplify the
evaluation of heat loss thru basement walls and floors. The heat loss thru a
slab floor is large around the perimeter and small in the center. This is
because the ground temperature around the perimeter varies with the
outdoor temperature, whereas the ground temperature in the middle
remains relatively constant, as with basement floors.
Part 2 92
Use of Tables 35 thru 37 carrier
Heat Loss thru Masonry Floors and Walls in Ground
The transmission coefficients listed in Table 35 may be used for any thickness of
un-insulated masonry floors where there is good contact between the floor and the
ground.
The perimeter factors listed in Table 36 are used for estimating heat loss thru
basement walls and the outside strip of basement floors. This factor can be used
only when the space is heated continuously. If there is only occasional heating,
calculate the heat loss using the wall or floor transmission coefficients as listed in
Tables 21 thru 33 (ref 3 ) and the temperature difference between the basement
and outdoor air or ground as listed in Table 37.
The heat loss in a basement is determined by adding the heat transferred thru the
floor, the walls and the outside strip of the floor and the portion of the wall above
the ground level.
Part 2 93
Part 2 94
Part 2 95
Example 5 Ref carrier
T0 = 0 F
Tb = 65 F 9 ftt
6 ft
Basement floor
Tg = 55 F
100 ft
40 ft width
Part 2 96
Where U = Heat transmission coefficient of wall above ground (Table 5.1 text
book ) and floor (Table 35 Carrier) in Btu/(hr) (sq ft) (deg F)
A 1 = Area of wall above ground, sq ft= 2(100+40)x(9-6)
A 2 = Entire floor area, sq ft= (100x 40)
Lp = Perimeter of wall, ft = 2(100+40)
q = Perimeter factor (Table 36) = 1.05 Btu/(hr) (sq ft) (deg F)
Tb = Basement dry-bulb temp, = 65 F
Tg = Ground temp, F, (Table 37) = 55 F
Ta = Outdoor design dry-bulb temp, = 0 F
Solution:
Heat loss above ground
Q1 = U X A1 X (Tb – Ta ) = 0.18 X [2(100 + 40)] X 3 X (65 - 0) = 9828 Btu/hr
2. Heat loss thru walls and outside strip of floor below ground.
Q2 = Lp X q X (Tb – Ta ) = {2(100 + 40)} X 1.05 X (65 - 0)= 19100 Btu/hr
3. Heat loss thru floor
Q3 = U‟ X A2 (Tb – Tg ) = 0.05 X (100 X 40) X (65 - 55)= 2000 Btu/hr
Part 2 97
Total Heat Loss = 30,928 Btu/hr
Class exercise
99
Manual and Computer method
Derived from Heat Balance method
Depends on tabulated data
calculated using the TF method
Assumption made:
Zone Air temperature is assumed
constant
Sol-Air temperature is assumed for
outside
One dimensional heat flow through
structure
Cooling Load Temperature Difference (CLTD) combines
the temperature difference between indoor and outdoor
and solar radiation and considers thermal capacity of the
enclosure.
CLTD method is a simplified version of the Transfer
function method, which can be used with certain types of
buildings for which application data are available. This one
step procedure uses cooling load temperature differences
(CLTD), solar cooling load factors (SCL), and internal
cooling load factors (CLF), to calculate the cooling loads
.Therefore, cooling load temperature differential data for
conduction heat gain through sunlit walls, cooling load
factors for solar and internal loads, and solar cooling load
factors are developed in the form of tables to produce a
direct one-step calculation for each process.
Part 2 101
CLTD & CLF
Cooling load temperature difference & cooling load factor
are used to convert the space sensible heat gain to space
cooling load .
The CLTD values are found from tables (A 28-32) & (A 28-
34), which are designed for fixed conditions of outdoor /
indoor temperatures, latitudes , etc.. Corrections and
adjustments are made if the conditions are different.
Sensible coolingLoad Qs
CLF
Sensible heat gain Qes
104
Conventional method
Q U A (To Ti)
Fixed value
Lead to Maximum Load
CLTD/CLF method
Q U A CLTD
Function of:
An adjustment must be subjected to the CLTD values; since the values in the
following table are for indoor temperature 25.5˚C, outdoor temperature 35˚C
and daily range 11.6˚C , July at 40 ˚ North latitude
106
Adjust the CLTD values to fit your data .
QWall U A CLTDWall
Typical Steps to calculate the Wall load as follows:
1-Determine wall construction and overall heat transfer
coefficient (U) (Chapter 24 ASHRAE 1997, Table A24-4,
A29-5)
2-Select wall from ASHRAE Table 33 which is closest to
matching actual wall construction.
3- Select wall CLTD for time of interest, typically on an
hourly basis (Chapter 28 ASHRAE Table A28-32, A28-34)
4-Correction
5-Calculate wall area (A) from architectural drawing
Code Number SI
Wall Number
1997 ASHRAE Handbook, Fundamentals, Chapter 28
Wall CLTD
SOLAR LOAD THROUGH GLASS
Table 34 Table 36
Solar load thru glass window by conduction
Q=Aglass x U x CLTD
A= Glass area m2
U= Overall heat transition coefficient for glass
(W/m2K ) , table 5
CLTD = cooling load temp. difference W/m2 (Table
A28-34)
Conduction, thru glass
Q=Aglass x U x CLTD
Conventional method
Solar radiation
CLTD/CLF method
Table 34 Table 36
Case of conventional method :The heat loss thru window by conduction is calculated previously with the structure heat gain
Solar Radiation
A=glass area m2
Sc = Shading Coefficient table 5
SCL = Solar cooling load factor (Table A28-36 Pp51)
For example
A room in a single story building, having one or two expose walls ,concrete
block partitions, carpet over concrete ,no external or internal shading.
From Table 35 B . Glass solar will be zone type B , People & equipment
type C , light type C.
Solar Radiation thru glass SC L
Example 7 from A28 Pp49.
Cooling load from south and west glass. Determine the cooling
load caused by glass on the south and west walls of a building at
1200, 1400, and 1600 h in July. The building is located at 40°N latitude
with outside design conditions of 35°C dry-bulb temperature and a 11°C
daily range. The inside design dry bulb temperature is 25°C.
Assume the glass zone is C category
The south glass has a U values is (3.63 W/m2K) with an area of 10 m2 and
Sc=0.82 . The west glass U values is (4.6 W/m2K) an area of 10 m2 and
Sc=0.53.
Conduction heat gain thru Glass , CLTD correction
From Table 34 we get:
CLTD12:00 = 5 , CLTD 14:00 = 7, and CLTD 16:00 = 8.
CLTDcorrected = CLTD + (25.5 - Ti) + (Tm - 29.4)
@ 12:00 CLTDcorec = 5 + (25.5 - 25) + (35 -11/2 - 29.4) = 5.6 oC
@ 14:00 CLTDcorec = 7 + (25.5 - 25) + (35 -11/2 - 29.4) = 7.6 oC
@ 16:00 CLTDcorec = 8 + (25.5 - 25) + (35 -11/2 - 29.4) = 8.6 oC
Qcond=Aglass x U x CLTD
Q=Aglass x U x CLTD
SCL for South & West glass windows
Qrad=Aglass x Sc x SCL
Aglass= 10 m2
Watt
Watt
CLF = Cooling load factor which is a function of: zone type, number of
hours after entry, and number of hours in space (Table A28-37)
133
People
Estimate the cooling load in a building at 12:00, 14:00, 16:00 from four moderately
active people occupying an office from 9:00 to 17:00 ( 8 hours in space)
The office temperature is 25°C, and the cooling system operates continuously. Assume
the conditions of the space as applied to table 33A; define it as type D.
The period of occupancy is 8 h.
137
After 6 hours in work
Lighting
138
Example 9 :A28-Pp53
Estimate the cooling load for a private office at 12:00 pm, 14:00 and
16:00 pm ,for fluorescent light (800Watt).
All the lights are turned on at 8 am, and turned off at 18:00 i.e. (remain
on for 10 hours).
Estimate the sensible heat gains from light.
Assuming zone type C
Motor & equipments such as fans, pumps, machine tools, elevators, escalators
and other machinery, which add significantly to the heat gain.
N.B. The motor location inside or outside the room will effect the 140
power load
Appliance , equipments
Fua= usage factor, See 1997 ASHRAE Fundamentals, Chapter 28, Table 6 and 7
Fra = radiation factor A28Tables 5-9
, qis =Sensible rated energy input from appliances –A28 Tables 5-9
Or use manufacturer‟s data .For computer ,monitors ,printers see 2001
ASHRAE Fundamentals, Chapter 29, Tables 8, 9, & 10.
142
Example 10:A28-Pp53 Appliance cooling load.
Determine the cooling load in a building at 12.00, 14.00, and 16.00 caused
by an electric coffee brewer with one brewer and one warmer. The brewer
operates continuously from 9.00 to 15.00 h and does not have an exhaust hood.
The cooling system runs 24 h/day, including weekends.
Room categorized as type D
Q Sens= qis x Fua x Fra x CLF (Sensible)
Solution:
From Table 8, qs and qt for an unhooded, two-burner coffee
brewer is 1100 sensible and 560 W latent , respectively , and for a coffee
heater (per warming burner) is and 67 sensible and 32 W latent , respectively.
The brewer is ON for 6 h, and @ 12.00 h is 3 h after the brewer is turned on.
@ 14.00 h is 5 h after the brewer is turned on. @ 16.00 h is 7 h after the
brewer is turned on. From Table 37 & type D we get CLFs
Where:
Q = L/s/person from ASHRAE standard tables, ventilation or infiltration.
to, ti = outside, inside air temp., o C.
Wo, Wi = outside, inside air humidity ratio, kg(water)/kg(dry air).
ho, hi = outside, inside air enthalpy, kJ/kg (dry air).
148
CLTD/GLF Method
Part 2 149
CLTD/GLF Method
(Calculation procedure)
15 Hospital, Library,
Museum Greater than 15 Kw. 0.88
Part 2 160
Heat Gain by Equipment:
The table below gives an example of heat
generated for different types of equipment
used in residential buildings
Heat gained from infiltration:
Q=1.2 q xT
q = 1000/3600 (ACH) Vroom
Q=0.333 (ACH ) Vroom x T
Table 8
A27-8
Effect of infiltration on Latent load factor
LF = 0.58 + 42 x w
Fenestration. Clear double glass, 3 mm thick, in and out. Assume closed, medium-
color venetian blinds. The window glass has a 600 mm overhang at the top.
Doors. Solid core flush with all-glass storm doors [U = 1.82 W/(m2·K)].
Q=Aglass x U x CLTD
A= Glass area m2
U= Overall heat transition coefficient for glass
(W/m2K ) , table 5
CLTD = cooling load temp. difference W/m2 (Table
A28-34)