ANGUS

WATER CURTAIN NOZZLE /


OPEN WINDOW DRENCHER

Bore K - Factor Weight


A (mm) (Brass)
8.0 23 215g
10.5 39 206g
13.0 53 185g
16.3 78 165g

Materials:
Naval Brass Cu/Zn35Sn1
St.Steel AISI 316
Titanium Grade 2
Connection: NPT (option BSPT) Finish:
Natural or ENP
Approx. 4 metre

120

Water Curtain Nozzles with K-Factor 23, 39, 53 & 78 are tested in the vertical or upwards position, but
can be used in the pendent or downward position.
Test range 4 10 bar.
Extract from LPC drencher rules:
Drenchers must be fixed so that stream forms a water curtain contacting the window 610mm from the top.
Horizontal spacing of drenchers not to exceed 2400mm.

The right is reserved to vary or modify any specifications without prior notice.

ANGUS FIRE - SPRINKLER DIVISION Data Sheet: Water Curtain Nozzle


Thame Park Road, Thame, Oxfordshire, OX9 3RT. UK
TEL: 44 (0) 1844 265000 FAX: +44 (0) 1844 265159
Email: sprinkler@angusuk.co.uk Page: 1 of 3
Date: 6 / 12 - 2010
DATA SHEET No: WS030 1001 B
ANGUS
WATER CURTAIN NOZZLE /
OPEN WINDOW DRENCHER

4
1.75 bar

3
0.85 bar
200

0.35 bar

2
610 Max.

Window

1
striking window.
Line of spray

METRES
0
1800

1
2
3
4

ANGUS FIRE - SPRINKLER DIVISION Data Sheet: Water Curtain Nozzle


Thame Park Road, Thame, Oxfordshire, OX9 3RT. UK
TEL: 44 (0) 1844 265000 FAX: +44 (0) 1844 265159
Email: sprinkler@angusuk.co.uk Page: 2 of 3
Date: 6 / 12 - 2010
DATA SHEET No: WS030 1001 B
ANGUS
WATER CURTAIN NOZZLE /
OPEN WINDOW DRENCHER

Pressure/Flow Graph

11.0
K23 K39 K53 K78
10.0
9.0
8.0
7.0
Pressure (bar)

6.0

5.0
4.0
3.0
2.0
1.0
0.0
0
15
30
45
60
75
90
105
120
135
150
165
180
195
210
225
240
255
270
Flow Q (lpm)

ANGUS FIRE - SPRINKLER DIVISION Data Sheet: Water Curtain Nozzle


Thame Park Road, Thame, Oxfordshire, OX9 3RT. UK
TEL: 44 (0) 1844 265000 FAX: +44 (0) 1844 265159
Email: sprinkler@angusuk.co.uk Page: 3 of 3
Date: 6 / 12 - 2010
DATA SHEET No: WS030 1001 B

You might also like