Professional Documents
Culture Documents
With Testing
Fernando Calero
Schweitzer Engineering Laboratories, Inc.
AbstractUnderstanding and testing distance elements Distance elements are used in line protection schemes for
require linking the theory related to their design to the fault their definite reach. Simple overcurrent protection lacks this
voltages and currents used during tests. This paper discusses the property, and its reach is highly dependent on the source
theory, deriving the characteristics of phase and ground distance
elements with a focus on three in particular. The derivation will
impedance. A definite reach is highly desired in distance
introduce certain concepts, including the impedance plane, elements.
source impedance, forward fault impedance, reverse fault In general, protective relaying elements are implemented
impedance, fault resistance, and load flow behavior. The discus- by comparing thresholds to measured and/or combined power
sion is based on the use of symmetrical components to under- system quantities. While early electromechanical distance
stand the design, behavior, and characteristics of distance relays used actual magnitude comparisons of the voltage-
elements. This paper also reviews some testing procedural errors.
A confident understanding of the theory allows for an easier
produced restraining torque to the current-produced operating
understanding of the testing results obtained. torque [4], distance elements have been preferably imple-
mented by comparing the phase relationship of two vectors.
I. INTRODUCTION The comparison is done with a phase comparator, which can
be implemented with an electromechanical unit (a two-phase
Distance units are the main protection algorithms imple-
motor, for example), a solid-state coincidence timer (measur-
mented in most line protection schemes. Even with line dif-
ing a quarter-cycle coincidence between square waves), or
ferential schemes, distance schemes are used as backup,
numerical comparator [2][3][5]. Regardless of the technology,
keeping these elements in the protective relaying inventory.
the threshold condition of a phase comparator is described by
While different distance elements have been proposed
(1).
according to the requirements and preferences of manufactur-
ers, there are concepts that should be linked from the aca- S1
arg = 90 (1)
demic analysis to the practical testing of these elements. S2
Knowing the theory that derives the characteristics of the
The quantities S1 and S2 are phasor quantities, inputs to
element makes it easier to understand the behavior while test-
the phase comparator. S1 is normally called the operating
ing the element or comprehending its operation in the field.
quantity, and S2 is the polarizing quantity or reference. For
Distance units have been traditionally categorized in phase
distance elements, S1 will normally be the assumed voltage
and ground units. They have been designed to detect power
drop (V Zc I) across the elements replica impedance Zc.
system faults that do not involve the ground return (3I0) for
Voltage V is the restraining voltage, and (Zc I) is the operating
phase faults and those that involve the ground return for
quantity that overcomes the restraining voltage. To compare
ground faults. Phase-to-phase-to-ground faults are a design
whether (Zc I) is larger than V with a phase comparator, a
choice for manufacturers; generally, these faults will be asso-
reference quantity is required (S2).
ciated with phase fault detection.
S2 is the reference and must be a stable quantity (no
With ten fault types possible, determining the impedance to
significant phase change) during normal and faulted power
the fault is not a simple measurement of voltage and current
system conditions. The choice of S2 may differ from manu-
[1][2][3]. In traditional line protection schemes, six impedance
facturer to manufacturer, and benefits and drawbacks have
units are used, usually identified as AG, BG, CG, AB, BC,
been described in literature [2].
and CA elements. These six elements constitute a protection
zone and should detect all of the ten fault types possible.
2
F2 F3
Z1
F1 Fault S1
S2
(IA+k0 3I0) Zc
No Op VA
Trip F2 Fault Fig. 2. Circle Defined by Arbitrary a and b Vectors on the Z Plane
S2
(a) Fig. 2 illustrates a circle and the graphical proof of (2).
VA
One-half of the circle satisfies the +90 requirement; the other
No Op
(IA+k0 3I0) Zc half satisfies the 90 requirement. The circle is split by the
Trip line connecting the tips of a and b.
S1
F3 Fault An academic and important fact to constantly remember is
S2 (b) that the plot in Fig. 2 represents the circle on the Z plane.
Keeping this concept in mind avoids mixing other or similar
(IA+k0 3I0) Zc
S1 results that are based on different planes.
No Op
VA A simple and generic example of a distance element is used
Trip to demonstrate (2). This element is a self-polarized distance
unit, where:
(c)
S1 = V Zc I (3)
Fig. 1. Distance Relay Operation
S2 = V (4)
Protective relaying theory is heavily based on the theory of This distance unit is called self-polarized because the
symmetrical components. The derivation of distance-unit polarizing quantity (S2) is the same as the restraining voltage.
characteristics is no exception. In fact, it is the theory that uses Substituting the S1 and S2 values of (3) and (4) into (2)
symmetrical components in the most elegant and ingenious yields:
way.
S1 V Zc I
arg = arg = 90
II. DESCRIBING A CIRCLE S2 V
(5)
Mho distance elements are circles on an impedance plane. V Zc Z Zc
An equation describing a circle should lead to the description
arg I = arg = 90
V
I Z
of these distance units. Equation (2) is a vector equation of a
circle [3]. In (5), the a and b vectors can be easily recognized as:
JG a = Zc (6)
S1 Za
arg = arg JG = 90 (2)
S2 Z b b=0 (7)
Equation (2), which is an extension of (1), can be readily
visualized in Fig. 2 for an arbitrary set of a and b vectors.
3
Equation (16) is important in the analysis and is expressed Fig. 5 illustrates a very important conceptthe fact that
in terms of ZL1, which is the impedance on which plane the these impedances are all in the forward direction, as derived
characteristic will be derived. from the symmetrical component network interconnection in
Returning to (9), simplify to find a more useful expression Fig. 4. A negative impedance (ZL1 = jX), for example, does
for S2: not mean the fault is in the reverse direction; it means that
ZL1 is a capacitor in the forward direction.
S2 = ( VR1 VF1) + VF1
To contrast the forward fault characteristics of distance
= ( VR1 VF1) VF2 VF0 elements, the reverse fault characteristics can be derived.
(17)
= ( VR1 VF1) + ( Zs1 + ZL1) IR2 B. Positive-Sequence Polarized AG Ground Distance Unit
+ ( Zs0 + ZL0 ) IR0 (Reverse Characteristics)
The symmetrical component network connection shown in
Using (13) and (14), (17) simplifies to:
Fig. 6 is the network used to derive the reverse fault charac-
S2 ZL0 Zs0 teristics for the AG element described by S1 and S2 in (8) and
= ZL1 2 + + Zs11 + Zs1 (18)
IR1 ZL1 (9). The impedance ZL is of interest, and the reverse fault
characteristics of this distance unit will be plotted on the ZL1
The results in (16) and (18) can be used in (2) to find the a
plane. Notice again the directions of the distance-unit current
and b vectors:
measurements are denoted by the current orientations.
Zc0
2 + Zc1 ZL1' Zs1
a = Zc1 (19)
ZL0
2 + ZL1
IR1
Zs0
1 + Zs1
VF1 VR1
Vs
b = Zs1 (20)
ZL0
2 + ZL1
ZL1' Zs1
The impedance ratio of Zc1 and Zc0, via kc0 in (10),
should equate the line impedance ratio of ZL1 and ZL0,
because these are the replica impedances. Therefore, (19) is
IR2
further simplified to:
a = Zc1 (21) VF2 VR2
VF0 VR0
( )
S1 = a 2 a ( VR1 VR2 ) Zc1( IR1 IR2 )
(33)
= j 3 ( VR1 VF1) VR2 Zc1( 2IR1) + VF1
S1
= j 3 ( 2ZL1 1Zc1) (34)
IR1
and for S2:
( )
S2 = a 2 a ( VR1 VF1 + VF1)
(35)
= j 3 ( VR1 VF1) + IR1( Zs1 + ZL1)
S2
= j 3 ( 2 ZL1 Zs1) (36) Fig. 10. Symmetrical Component Network for a Reverse BC Fault
IR1
Using the results in (34) and (36), the resulting a and b Returning to (31), simplify to find a more useful expression
vectors are: for S1, based on the network shown in Fig. 10:
a = Zc1 (37) S1 = (a 2 a) [ (VR1 VR2) Zc1 (IR1 IR2)]
Zs1 = j 3 ( VR1 VF1) VR2 Zc1( 2IR1) + VF1
b= (38)
2 (39)
The positive-sequence polarized phase distance unit has a = j 3[( VR1 VF1) VR2 Zc1( 2IR1)
definite reach, given by Vector a. Fig. 9 illustrates the + VR2 ZL ' IR1
threshold locus on the ZL1 plane.
S1
= j 3 ( 2 ZL1 + 2 Zc1) (40)
X
a = Zc1 ( IR1)
Returning to (32), simplify to find a more useful expression
for S2:
S2 = (a 2 a) [ (VR1 VF1) + VF1]
(41)
= j 3 ( VR1 VF1) IR1( Zs1 + ZL1)
S2
= j 3 ( 2 ZL1 Zs2 ) (42)
( IR1)
R
Using the results in (40) and (42), the resulting a and b
Zs1
b= vectors are:
2
a = Zc1 (43)
Zs1
b= (44)
bmem = Zs1 2
X
Equation (58) is the same as (8) and can also be simplified Zs1 ZL1
to the expression in (16).
The polarizing quantity S2 is different. To simplify S2, a
relatively nonacademic mathematical trick can be used. IR1
Vs
S2 = 0 (VR1 VF1) + j IR1 e jT (60) VR1 VF1
S2 0 j e jT
= ZL1 + (61)
IR1 0 0
Zs1 ZL1
The end result is:
Zc0
2 Zc1
ZL1 Zc1 IR2
2 ZL0 VR2 VF2
S1 ZL1
= jT
(62) 3Rf
S2 j e
ZL1 +
ZL0
02
ZL1 Zs0 ZL0
{
Im VRA ZL1(IRA + kc0 3I0)* = } (65)
{
Im (If Rf ) ZL1(IRA + kc0 3I0)* }
and:
Rf =
{
Im VRA Zc1(IRA + kc0 3I0)* } (66)
Im { If (Zc1(IRA + kc0 3I0) }
*
j 90 T + 2 +
Zc0
In one design choice [2], the If value was chosen to be:
Zc1
b = e
(IR0 + IR2)
If = 3 (67)
2
Fig. 14. Reactive Line Component of a Ground Quadrilateral Unit Equation (66) yields the fault resistance value (Rf), which
B. Resistance Element for a radial system adds to the line impedance. This result is a
The resistive check for a quadrilateral element could be straight calculation of Rf and cannot be plotted on an imped-
implemented with equations similar to (58) and (59), using ance plane. In fact, the directional element that keeps the
S2 = IR2 and Zc = R [3]. Another approach is to actually reactance unit from detecting reverse faults cannot be plotted
calculate the resistive component of the fault [1][2]. on the plane. The quadrilateral element is a combination of the
Consider the symmetrical component representation of a reactance line, the resistive check, and a directional element.
ground fault with resistance, as shown in Fig. 15. The follow-
ing is true: V. TESTING OF DISTANCE ELEMENTS
VF1 + VF2 + VF0 = If Rf Relay engineers are curious. Most of them want to have a
(64) deep understanding of the devices that are connected to their
VRA ZL1(IRA + kc0 3I0) = If Rf power system. When the device fundamentals are understood,
analysis and testing are simple. There are three types of testing
that satisfy different functions of a numerical protective relay:
acceptance, commissioning, and maintenance [7].
10
Acceptance testing involves the study of the protective 1) Apparent Impedance for a Ground Fault
device and its characteristics. Some users qualify protective The network in Fig. 4 is also used to derive the expression
devices over a period of time, studying and testing the for the apparent impedance. Therefore, for the AG fault in
characteristics provided by the device. This test is performed Fig. 4:
in a quiet environment, usually the companys protection VF1 + VF2 + VF0 = 0
laboratory, with ample time to verify the published character-
(VR1 ZL1 IR1)
istics. During this type of testing, the users have an oppor- (68)
tunity to obtain an understanding of the relay principles. + (VR2 ZL1 IR2) + (VR0 ZL0 IR0) = 0
Commissioning testing involves the actual installation of VRA + ZL1 [ IRA + kL0 (3I0) ] = 0
the protective device and the testing of the connections to it
Equation (68) simplifies to:
(e.g., polarities and phasing) and of the programmable logic.
Some distance-unit reaches may be verified on the distance VRA
ZL1 = (69)
elements. The commissioning testing is by no means as IRA + kc0 (3I0)
involved as the acceptance testing, due to the timing and most
where kc0 is defined in (10) as a relay setting. It should be
likely the pressure to get the devices installed.
equal to kL0:
Maintenance testing involves a periodic and simple func-
tional evaluation of the protective device. The testing takes ZL0 ZL1
kL0 = (70)
advantage of the self-check algorithms in numerical protective 3ZL1
relays and also the nature of the hardware design. Since the
2) Apparent Impedance for a Phase-to-Phase Fault
firmware is a software program, it is not expected that the
The following is true for the network in Fig. 8:
features tested in the acceptance testing and the commission-
ing testing have changed. A visual inspection of the enable VF1 VF2 = 0
light, confirmation that the metering matches known levels, (VR1 ZL1 IR1) (VR2 ZL1 IR2) = 0 (71)
and testing of auxiliary contacts or devices should suffice. The (VR1 VR2) ZL1(IR1 IR2) = 0
maintenance testing interval is dependent on the data collected
from the device. If the metering and oscillographic reports are Equation (71) simplifies to:
accessed constantly, the maintenance interval may be longer VRB VRC
ZL1 = (72)
than for a device that is totally isolated and not reporting any IRB IRA
events.
B. Confirming the Distance Unit Characteristic
It is hoped that the information in this section helps in
understanding the actual operation of distance elements and Symmetrical components are used to derive the distance
acceptance testing. The implementation of the distance units element characteristics on the ZL1 plane. Assuming a radial
has been tested and verified by the manufacturer and users system, this is how the impedance characteristics on the ZL1
several times, especially if the device is mature in the market- plane are derived. The effect of load flow and fault resistance
place. is neglected; their influence is easier to visualize on the appar-
ent impedance plane when the operation of the unit is studied.
A. Apparent Impedance Symmetrical component theory is fundamental for relay engi-
The term apparent impedance is largely used in protective neers. It makes three-phase power system analysis simple and
relaying literature when discussing distance elements. It is a understandable.
calculation of the impedance in terms of the measured volt- When testing a memory polarized distance unit, the way
ages and currents. For a simple radial system with no load the prefault and faulted voltages are managed affects the test
flow, the apparent impedance can be readily used to verify the results. The memory effect will not be noticeable when the
plots of Fig. 5 and Fig. 9 on the ZL1 plane. For load flow and calculated fault voltages are maintained and the calculated
fault resistance in a two-source network, the term is not a fault current is increased until the unit trips. But if the prefault
physical impedance. It is a measurement that implies apparent voltages are healthy and then fault quantities are applied, the
impedance, and it only represents an impedance (ZL1 in our memory effect will be noticeable.
discussion) if the system is radial. When fault resistance and
load flow are considered, the apparent impedance is just a
measurement.
11
Fig. 16 shows the corresponding mho circle derived from Va = 73.670, Vb = 82.7287.86,
p7
Vc = 58.88155.35 21.07
the parameters in Table I. Ten random points were chosen 2.1320
Ia = 20.8626.80, Ib = 0, Ic = 0
from the plot, and their impedances were calculated. For each
point, the symmetrical component analysis yielded the corre- p8
Va = 62.690, Vb = 66.17146.27,
sponding test voltages and currents, as shown in Table II. By Vc = 79.30101.14 13.96
2.71170
fixing the voltages and slowly increasing the current, the trip Ia = 13.92164.43, Ib = 0, Ic = 0
point is found when the distance unit trips. The fault magni- Va = 62.720, Vb = 69.42130.35,
p9
tude listed in Table II corresponds, within the margins of the Vc = 74.06114.33 6.48
5.85140
test equipment error, to the theoretical value, also shown in Ia = 6.45133.88, Ib = 0, Ic = 0
Table II. Va = 63.230, Vb = 70.83124.37,
p10
Vc = 72.05119.53 4.36
X 8.80110
a = 1080
Ia = 4.32104.03, Ib = 0, Ic = 0
p1
p10 This example illustrates the link between theoretical values
p2
and proper testing. The values in Table II come from the
symmetrical component analysis of the fault.
p9 The source impedance magnitude was not sufficient to
make the memory effect noticeable; a larger source impedance
p3 should be chosen.
p8 p4
R
p5
p6
380
1 + p7
185
b = (185 )
3070
2 +
1080
Fig. 16. Points on the Ground Distance Characteristic for the Example in
Table I
12
p3 Va = 700, Vb = 72.86167.64,
p7
Vc = 15.6485.70 5.23
p8 p4 6.8220
Ia = 0, Ib = 5.77167.64, Ic = 5.7743.78
R
p5 Va = 700, Vb = 21.87113.73,
p8
p6 Vc = 64.39161.89 4.83
6.82170
Ia = 0, Ib = 4.83152.17, Ic = 4.8327.84
p7
1085
b= Va = 700, Vb = 29.67122.89,
2 p9
Vc = 59.37155.19 3.88
7.74150
Ia = 0, Ib = 4.04157.12, Ic = 4.0422.88
bmem = 1085
Va = 700, Vb = 35.73129.06,
p10
Fig. 17. Phase Distance-Unit Points on the Impedance Plane Vc = 54.99149.71 3.53
8.65130
Ia = 0, Ib = 3.52164.21, Ic = 3.5215.79
Table IV shows the test voltages and currents used to
confirm the no-memory characteristic. The test voltages are The outer characteristic is related to the memory effect on
constant, while the current is increased until the phase distance S2. It is impractical to test this characteristic. The memory
element trips. The fault current magnitudes correspond to the algorithms in protective relays are constantly updated; the
expected values, within the margins of error of the test equip- filtering behavior of the relays will make the memory value
ment and the device under test. (S2) change almost instantly. Therefore, any values calculated
with the outer-circle impedances will not yield any practical
results.
13
Table VI represents seven points on the reactance line. 3) Use Symmetrical Components When Testing
These impedances lie on the threshold of operation. The The distance element theory is based on symmetrical com-
recorded current in the right-hand column is within the margin ponents. More than any other aspect of power systems,
of error in the test equipment and the protective relay. symmetrical components are the foundation of power system
TABLE VI
protective relaying and, in particular, distance elements. The
TEST VOLTAGES AND CURRENTS FOR FIG. 19 faulted voltages and currents presented earlier were obtained
from symmetrical component analysis of the faults.
Point/
Voltages and Currents I A traditional way to estimate faulted voltages and currents
ZL1 for an AG ground fault, for example, is by using a phasor
p1
Va = 64.150, Vb = 70.34140.11, diagram, as illustrated in Fig. 20. The faulted voltage is
Vc = 7.200138.07 3.75 decreased, and the faulted current is modified according to the
10.38108.33
Ia = 3.72102.33, Ib = 0, Ic = 0 impedance magnitude and angle requirement. While this
Va = 63.710, Vb = 70.72123.03, methodology provides a quick and dirty way to make an
p2
Vc = 71.83120.44 3.87 estimate, it is not based on any theory. The unfaulted voltages
9.9899.21 remain with their healthy values, and the angles between volt-
Ia = 3.8593.21, Ib = 0, Ic = 0
ages remain constant. This is not what happens in a real power
Va = 63.530, Vb = 71.10122.06,
p3 system.
Vc = 71.56121.54 3.91
8.6520
Ia = 3.8983.59, Ib = 0, Ic = 0 Moreover, as illustrated in Fig. 20, increasing the faulted
current angle results in the faulted current and the faulted volt-
Va = 63.670, Vb = 71.42121.00, age being in phase. This condition will not occur in a trans-
p4
Vc = 71.21122.56 3.86
1080 mission network. Directional elements will not declare the
Ia = 3.8374.00, Ib = 0, Ic = 0
fault to be in the forward direction because, for ground faults,
p5
Va = 64.080, Vb = 71.65120.01, it is assumed that the source is reactive and not resistive, as
Vc = 70.84123.38 3.73 equal angles will suggest.
10.4270.94
Ia = 3.7064.93, Ib = 0, Ic = 0
Va = 64.660, Vb = 71.78119.19,
p6
Vc = 70.50123.92 3.54
11.07662.76
Ia = 3.5156.76, Ib = 0, Ic = 0
Va = 65.300, Vb = 71.83118.59,
p7
Vc = 70.21124.20 3.32
6.8220
Ia = 3.2949.62, Ib = 0, Ic = 0
For ground faults, the plane is defined by (69). For phase Zs0 mZL0 (1 m)ZL0 Zr0
faults, the plane is defined by (72). In the appendix of this
paper, the impedance circles are derived for both the ground
and phase distance elements. IR0
VR0 VF0
It is mathematically very difficult to find the impedance
locus on any plane to describe the distance element
characteristics because the distribution of currents is different
Fig. 22. Two-Source Symmetrical Component Representation of a Ground
depending on the faulted impedance and load flow. With the
Fault
use of the equations derived in the appendix, it is simpler to
visualize the location of the apparent impedance measured Solving for m = 1 and Rf = 0, only the load flow effect is
with respect to the distance-unit characteristics. illustrated in Fig. 23. The figure shows a computer-generated
Another important point is that all the information is avail- graph based on the equations derived in the appendix. As
able from the local measurements to calculate the apparent reported in other literature, mho circles adjust appropriately to
impedance. prevent overreach due to the direction of the load flow [3].
To illustrate the plotting on the apparent impedance plane, The pivot point is the units reach.
the system in Fig. 21 is used. The end characteristic on the
left-hand side is plotted, and a large source impedance is
selected to illustrate the mho circle behavior compared to the
radial characteristics discussed before.
Zs1 = 1085 ZL1 = 1080 Zr1 = 285
Zs0 = 2075 ZL0 = 3070 Zr0 = 280
Vr = 700 Vr = 70 20
Fig. 21. Sample Power System Used to Illustrate the Impedance Plot With
Rf and Load Flow
For the same point (m = 1) and the same load flow but with TABLE VII
TEST VOLTAGES AND CURRENTS FOR APPARENT IMPEDANCES IN
fault resistance (Rf = 0.5 ohms), Fig. 24 illustrates the plot of FIG. 23, FIG. 24, AND FIG. 25
the apparent impedance and the distance-unit characteristics.
In the apparent impedance plane, the Rf component is not a Point/
Voltages and Currents I
straight line, and moreover, the apparent Rf component is ZApp
magnified several times due to the strong remote source. Va = 37.330, Vb = 67.94124.33,
p1 Vc = 69.02113.01
15 2.89
Fault Location X 10.0080 Ia = 2.8871.83, Ib = 0.53143.88,
Apparent Impedance Ic = 1.67106.12
Va = 39.570, Vb = 67.77112.93,
p2 Vc = 69.51124.88 No
10.4753.82 Ia = 2.9746.46, Ib = 0.69137.72, trip
Ic = 1.67123.59
Va = 40.940, Vb = 75.50105.75,
R p3 Vc = 72.96146.88
0 3.20
8.6330.02 Ia = 3.1918.63, Ib = 1.1293.09,
Ic = 1.08145.79
R
0
Fig. 26. Impedance Trajectory for a Ground Fault at m = 0.25 and Rf = 0.5
17
B. Phase Distance Unit the units reach (Zc) with a negative angle for loads in the
The symmetrical component network interconnection for a forward direction (export) and a positive angle for loads in the
phase-to-phase fault is shown in Fig. 27. The system parame- reverse direction (import), as illustrated in Fig. 29.
ters are the ones shown in Fig. 21. The appropriate a and b X
Reverse Load Effect
vectors for the fault resistance and load flow are derived in the
appendix. This unit also exhibits a beneficial tilt due to load
flow. Zc
Zc = 1080
Va = 48.420, Vb = 68.83140.44,
p4 Vc = 68.2197.40 IR1 IF1 IR1
2.12
16.63125.50 Ia = 2.13115.07, Ib = 0.51123.08, VR1 VF1
Vs Vr
Ic = 1.4481.23
IF2
VII. FINAL DISCUSSION
Zs1 ZL1 Zr1
This paper presented a general technique to derive distance 3 Rf
elements, as well as deriving the characteristics of three dis-
tance units. Knowing the distance element theory allows for IR2 IF1 IR1
the understanding of the units, which in turn facilitates the VR2 VF2
acceptance testing sequence.
The distance-unit characteristics are plotted on an imped-
ance plane. The positive-sequence impedance plane represents IF0
the behavior of the units, and a radial system with no fault Zs0 ZL0 Zr0
resistance or load flow is assumed.
The characteristics imply faults in the forward direction.
IR0 IF0 IR0
Distance units also have characteristic plots for the reverse
VR0 VF0
direction.
When considering fault resistance and load flow, the
apparent impedance plane describes the measurement with
respect to the impedance characteristic. Fig. 31. AG Fault Symmetrical Component Network Interconnection
Mho distance elements are directional with a desirable
Returning to (8), simplify to find a more useful expression
response in the forward and reverse fault impedance character-
for S1:
istics. Memory action on these units allows for an expansion
larger than the normal expansion due to the source impedance. S1 = VRA Zc [ IRA + kc0 (3IR0) ] (75)
When the fault voltages are fixed and the fault current is
Equation (75) can be simplified to:
increased until the distance element trips, testing will show the
steady-state (no-memory) characteristics. Using two states S1 VA
= Zc1 (76)
during the testing, with the prefault state considering only [ IA + kc0 (3I0)] [ IA + kc0 (3I0)]
healthy voltages, the influence of the memory effect in dis-
tance units can be observed when the fault state is applied.
Quadrilateral distance units are composed of a reactance
unit, a resistance check unit, and a directional element. The
reactance unit presented is a circle of infinite radius. The
directional element and the resistance check of a particular
design cannot be plotted on the apparent impedance plane.
The impedance trajectories can be plotted on the apparent
impedance planes for both the ground and phase distance
units. These plots represent a measurement and not an actual
impedance.
19
Returning to (9), simplify to find a more useful expression Returning to (31), find a more useful expression for S1:
for S2: S1 = (VRB VRC) Zc (IRB IRC) (81)
S2 = VR1 + VR2 + VR0 VR2 VR0
Equation (81) yields:
= VRA VR2 VR0 (77)
S1 (VRB VRC)
= VRA + Zs1 IR2 + Zs0 IR0 = Zc (82)
(IRB IRC) (IRB IRC)
S2 VRa Returning to (32), find a more useful expression for S2:
=
IA + kc0 (3I0) IA + kc0 (3I0) S2 = VB1 VC1 + VB2 VB2 VC2 + VC2
IR2 IR0 Zs0 (83)
+ (78) = VB VC VB2 + VC2
+ Zs1 IR1 IR1 Zs1
1 + IR2 + Zc0 Zs0 1
IR1 Zc1 Zs1 S2 VB VC
= Zs1 (84)
The results in (76) and (78) can be used in (2) to find the a
IRB IRC IRB IRC 1 IA1
IA2
and b vectors:
Using (82) and (84), the resulting a and b vectors are:
a = Zc1 (79)
a = Zc1 (85)
IR2 IR0 Zs0
+
b = Zs1 IR1 IR1 Zs1 (80) 1
1 + IR2 + Zc0 Zs0 b = Zs1 (86)
IR1 Zc1 Zs1 1 IA1
IA2
B. Positive-Sequence Polarized Phase Distance Unit
(Apparent Impedance Plane Forward Characteristics) C. Ground Reactance Distance Unit (Apparent Impedance
Fig. 32 is the symmetrical component network intercon- Plane Forward Characteristics)
nection of a two-source power system for a BC fault used to The reactance element is defined by (57) and (58). Finding
analyze the positive-sequence polarized phase distance unit the S1 and S2 vectors on the apparent impedance plane
defined by (31) and (32). follows:
S1 VA
= Zc1 (87)
[ IA + kc0 (3I0)] [ IA + kc0 (3I0)]
S2 = 0 VA + j IR2 e jT (88)
With S2, a rigorous mathematical procedure is not prac-
tical, as shown in (89).
VA
IA + kc0 (3I0)
S2 0 [ ]
= (89)
[ IA + kc0 (3I0)] 0 + j IR2 e jT
0 [ IA + kc0 (3I0)]
The division by zero is infinity, and what matters is the
angle.
IA1 IA0 Zc0
j 90T + ang 1+ +
IA2 IA2 Zc1
b=e
(90)
IX. REFERENCES
[1] J. Roberts, A. Guzmn, and E. O. Schweitzer, III, Z=V/I Does Not
Make a Distance Relay, proceedings of the 20th Annual Western
Protective Relay Conference, Spokane, WA, October 1993. Available:
http://www.selinc.com/techpprs.htm.
[2] E. O. Schweitzer, III and J. Roberts, Distance Relay Element Design,
proceedings of the 46th Annual Conference for Protective Relay
Engineers, College Station, TX, April 1993. Available:
http://www.selinc.com/techpprs.htm.
[3] W. A. Elmore, Protective Relaying Theory and Applications, New York:
Marcel Dekker, Inc., 1994.
[4] Type HZM Distance Relay, Westinghouse Electric Corporation,
Instruction Manual, I.L. 41-412.1K, May 1954.
[5] F. Calero, Development of a Numerical Comparator for Protective
Relaying: Part I, IEEE Transactions on Power Delivery, Vol. 11, No. 3,
pp.12661273, July 1996.
[6] D. Hou, A. Guzmn, and J. Roberts, Innovative Solutions Improve
Transmission Line Protection, proceedings of the 24th Annual Western
Protective Relay Conference, Spokane, WA, October 1997. Available:
http://www.selinc.com/techpprs.htm.
[7] SEL-421 Reference Manual. Available: http://www.selinc.com/
instruction_manual.htm.
X. BIOGRAPHY
Fernando Calero received his BSEE in 1986 from the University of Kansas,
his MSEE in 1987 from the University of Illinois (Urbana-Champaign), and
his MSEPE in 1989 from the Rensselaer Polytechnic Institute. From 1990 to
1996, he worked in Coral Springs, Florida, for the ABB relay division in the
support, training, testing, and design of protective relays. Between 1997 and
2000, he worked for Itec Engineering, Florida Power and Light, and Siemens.
Since 2000, Mr. Calero has been an application engineer in international sales
and marketing for Schweitzer Engineering Laboratories, Inc., providing
training and technical assistance.