You are on page 1of 21

Distance Elements: Linking Theory

With Testing

Fernando Calero
Schweitzer Engineering Laboratories, Inc.

Revised edition released August 2009

Previously presented at the


62nd Annual Conference for Protective Relay Engineers, March 2009

Previous revised editions released December 2008 and October 2008

Originally presented at the


35th Annual Western Protective Relay Conference, October 2008
1

Distance Elements: Linking Theory With Testing


Fernando Calero, Schweitzer Engineering Laboratories, Inc.

AbstractUnderstanding and testing distance elements Distance elements are used in line protection schemes for
require linking the theory related to their design to the fault their definite reach. Simple overcurrent protection lacks this
voltages and currents used during tests. This paper discusses the property, and its reach is highly dependent on the source
theory, deriving the characteristics of phase and ground distance
elements with a focus on three in particular. The derivation will
impedance. A definite reach is highly desired in distance
introduce certain concepts, including the impedance plane, elements.
source impedance, forward fault impedance, reverse fault In general, protective relaying elements are implemented
impedance, fault resistance, and load flow behavior. The discus- by comparing thresholds to measured and/or combined power
sion is based on the use of symmetrical components to under- system quantities. While early electromechanical distance
stand the design, behavior, and characteristics of distance relays used actual magnitude comparisons of the voltage-
elements. This paper also reviews some testing procedural errors.
A confident understanding of the theory allows for an easier
produced restraining torque to the current-produced operating
understanding of the testing results obtained. torque [4], distance elements have been preferably imple-
mented by comparing the phase relationship of two vectors.
I. INTRODUCTION The comparison is done with a phase comparator, which can
be implemented with an electromechanical unit (a two-phase
Distance units are the main protection algorithms imple-
motor, for example), a solid-state coincidence timer (measur-
mented in most line protection schemes. Even with line dif-
ing a quarter-cycle coincidence between square waves), or
ferential schemes, distance schemes are used as backup,
numerical comparator [2][3][5]. Regardless of the technology,
keeping these elements in the protective relaying inventory.
the threshold condition of a phase comparator is described by
While different distance elements have been proposed
(1).
according to the requirements and preferences of manufactur-
ers, there are concepts that should be linked from the aca- S1
arg = 90 (1)
demic analysis to the practical testing of these elements. S2
Knowing the theory that derives the characteristics of the
The quantities S1 and S2 are phasor quantities, inputs to
element makes it easier to understand the behavior while test-
the phase comparator. S1 is normally called the operating
ing the element or comprehending its operation in the field.
quantity, and S2 is the polarizing quantity or reference. For
Distance units have been traditionally categorized in phase
distance elements, S1 will normally be the assumed voltage
and ground units. They have been designed to detect power
drop (V Zc I) across the elements replica impedance Zc.
system faults that do not involve the ground return (3I0) for
Voltage V is the restraining voltage, and (Zc I) is the operating
phase faults and those that involve the ground return for
quantity that overcomes the restraining voltage. To compare
ground faults. Phase-to-phase-to-ground faults are a design
whether (Zc I) is larger than V with a phase comparator, a
choice for manufacturers; generally, these faults will be asso-
reference quantity is required (S2).
ciated with phase fault detection.
S2 is the reference and must be a stable quantity (no
With ten fault types possible, determining the impedance to
significant phase change) during normal and faulted power
the fault is not a simple measurement of voltage and current
system conditions. The choice of S2 may differ from manu-
[1][2][3]. In traditional line protection schemes, six impedance
facturer to manufacturer, and benefits and drawbacks have
units are used, usually identified as AG, BG, CG, AB, BC,
been described in literature [2].
and CA elements. These six elements constitute a protection
zone and should detect all of the ten fault types possible.
2

Fig. 1 shows the theoretical operation of S1 and S2 for


faults in the reverse direction (Fig. 1a), in zone (Fig. 1b), and
out of zone (Fig. 1c) for a distance unit. S2 should be a solid
reference that should not change drastically during fault
conditions.
F1 Z1

F2 F3

Z1

F1 Fault S1

S2
(IA+k0 3I0) Zc

No Op VA

Trip F2 Fault Fig. 2. Circle Defined by Arbitrary a and b Vectors on the Z Plane
S2
(a) Fig. 2 illustrates a circle and the graphical proof of (2).
VA
One-half of the circle satisfies the +90 requirement; the other
No Op
(IA+k0 3I0) Zc half satisfies the 90 requirement. The circle is split by the
Trip line connecting the tips of a and b.
S1
F3 Fault An academic and important fact to constantly remember is
S2 (b) that the plot in Fig. 2 represents the circle on the Z plane.
Keeping this concept in mind avoids mixing other or similar
(IA+k0 3I0) Zc
S1 results that are based on different planes.
No Op
VA A simple and generic example of a distance element is used
Trip to demonstrate (2). This element is a self-polarized distance
unit, where:
(c)
S1 = V Zc I (3)
Fig. 1. Distance Relay Operation
S2 = V (4)
Protective relaying theory is heavily based on the theory of This distance unit is called self-polarized because the
symmetrical components. The derivation of distance-unit polarizing quantity (S2) is the same as the restraining voltage.
characteristics is no exception. In fact, it is the theory that uses Substituting the S1 and S2 values of (3) and (4) into (2)
symmetrical components in the most elegant and ingenious yields:
way.
S1 V Zc I
arg = arg = 90
II. DESCRIBING A CIRCLE S2 V
(5)
Mho distance elements are circles on an impedance plane. V Zc Z Zc
An equation describing a circle should lead to the description
arg I = arg = 90

V
I Z
of these distance units. Equation (2) is a vector equation of a
circle [3]. In (5), the a and b vectors can be easily recognized as:
JG a = Zc (6)
S1 Za
arg = arg JG = 90 (2)
S2 Z b b=0 (7)

Equation (2), which is an extension of (1), can be readily
visualized in Fig. 2 for an arbitrary set of a and b vectors.
3

The plot of this characteristic is shown in Fig. 3.

Fig. 3. Self-Polarized Distance Element on the Z Plane

III. ANALYSIS OF TWO MHO DISTANCE ELEMENTS


To support this discussion, two examples of mho distance
Fig. 4. Symmetrical Component Network for a Forward AG Fault
elements are used: a ground distance unit and a phase distance
unit. Both units polarized with positive-sequence voltage The impedance plane for which the analysis will be per-
illustrate the proper development of distance element charac- formed is the positive-sequence impedance in the forward
teristics. The technique is also applicable to other elements direction. The analysis will find the ZL1 impedances for
found in the industry [3]. The analysis will review the AG and which the unit will operate. Interestingly, the following iden-
BC distance units, which are traditionally the most illustrative tity will allow for an easier analysis:
because they use Phase A symmetrical components. The other VR1 VF1
units are derived in a similar way and are an extension of these ZL1 = (11)
IR1
distance units.
Returning to (8), simplify to find a more useful expression
A. Positive-Sequence Polarized AG Ground Distance Unit for S1:
(Forward Characteristics)
S1 = ( VR1 + VR2 + VR0 )
This ground distance unit is designed with:
Zc1 ( IR1 + IR2 + IR0 + kc0 3IR0 )
S1 = VRA Zc1 ( IRA + kc0 3IR0 ) (8) (12)
= ( VR1 VF1) + VF1 + VR2 + VR0
S2 = VA1 (9)
( Zc1IR1 + Zc1IR2 + Zc0 IR0 )
where:
Zc0 Zc1 using:
kc0 = (10) VF1 = VF2 VF0
3Zc1
(13)
Zc1 and Zc0 are the relay settings. Zc1 is the reach of the = ( VR2 ZL1IR2 ) ( VR0 ZL0 IR0 )
ground distance element, and Zc0 is implicitly defined in the and:
relay settings when kc0 is adjusted for the particular applica-
IR1 = IR2 = IR0 (14)
tion. These constants are to be visualized as the replica imped-
ances of the line to be protected. Next, simplify (12):
Fig. 4 illustrates the symmetrical component network inter- S1 = ( VR1 VF1) + ZL1IR1 + ZL0IR1
connection of a source (with its own positive- and zero- (15)
sequence impedance) and an impedance located in the forward Zc0
Zc1IR1 2 +
direction to the distance element location. The distance Zc1
element measurements are denoted by R; these are the vol- S1 ZL0 Zc0
tages and currents that the unit is measuring. The direction of = ZL1 2 + Zc1 2 + Zc1 (16)
IR1 ZL1
the measurement is clearly shown with the current orienta-
tions.
4

Equation (16) is important in the analysis and is expressed Fig. 5 illustrates a very important conceptthe fact that
in terms of ZL1, which is the impedance on which plane the these impedances are all in the forward direction, as derived
characteristic will be derived. from the symmetrical component network interconnection in
Returning to (9), simplify to find a more useful expression Fig. 4. A negative impedance (ZL1 = jX), for example, does
for S2: not mean the fault is in the reverse direction; it means that
ZL1 is a capacitor in the forward direction.
S2 = ( VR1 VF1) + VF1
To contrast the forward fault characteristics of distance
= ( VR1 VF1) VF2 VF0 elements, the reverse fault characteristics can be derived.
(17)
= ( VR1 VF1) + ( Zs1 + ZL1) IR2 B. Positive-Sequence Polarized AG Ground Distance Unit
+ ( Zs0 + ZL0 ) IR0 (Reverse Characteristics)
The symmetrical component network connection shown in
Using (13) and (14), (17) simplifies to:
Fig. 6 is the network used to derive the reverse fault charac-
S2 ZL0 Zs0 teristics for the AG element described by S1 and S2 in (8) and
= ZL1 2 + + Zs11 + Zs1 (18)
IR1 ZL1 (9). The impedance ZL is of interest, and the reverse fault
characteristics of this distance unit will be plotted on the ZL1
The results in (16) and (18) can be used in (2) to find the a
plane. Notice again the directions of the distance-unit current
and b vectors:
measurements are denoted by the current orientations.
Zc0
2 + Zc1 ZL1' Zs1
a = Zc1 (19)
ZL0
2 + ZL1
IR1
Zs0
1 + Zs1
VF1 VR1
Vs
b = Zs1 (20)
ZL0
2 + ZL1

ZL1' Zs1
The impedance ratio of Zc1 and Zc0, via kc0 in (10),
should equate the line impedance ratio of ZL1 and ZL0,
because these are the replica impedances. Therefore, (19) is
IR2
further simplified to:
a = Zc1 (21) VF2 VR2

Fig. 5 illustrates the derived characteristic on the ZL1


plane. Any ZL1 impedance (with a characteristic ZL0/ZL1
impedance ratio) inside the circle indicates an operating ZL0' Zs0
condition.
X
a = Zc1
IR0

VF0 VR0

Fig. 6. Symmetrical Component Network for a Reverse AG Fault

Returning to (8), simplify to find a more useful expression


R for S1:
S1 = ( VR1 + VR2 + VR0 )
Zc1( IR1 + IR2 + IR0 kc03IR0 )
(22)

= ( VR1 VF1) + VF1 + VR2 + VR0
Zs0 Zs0
1 + 2 +
b = Zs1
Zs1
bmem = Zs1
Zs1 ( Zc1IR1 + Zc1IR2 + Zc0 IR0 )
ZL0 ZL0
2 + 2 +
ZL1 ZL1 using:
VF1 = VF2 VF0
Fig. 5. Forward Fault Characteristic on the ZL1 Plane (23)
= ( VR2 + ZL1'IR1) ( VR0 + ZL0'IR0 )
5

Equation (22) can be simplified to: X

S1 = ( VR1 VF1) ZL1'IR1 ZL0'IR1 Zc0


1 +
Zc0 (24) a = Zc1
Zc1
Zc1IR1 2 + ZL0 '
Zc1 2 +


ZL1'
R
using:
VR1 VF1 Zs0
Zl1' = (25) 1+
( IR1) Zs1
b = Zs1
ZL0 '
2 +
ZL1'
S1 ZL0' Zc0
= ZL1' 2 + + Zc1 2 + (26)
( IR1) ZL1' Zc1
Returning to (9), simplify to find a more useful expression
for S2:
Fig. 7. Reverse Fault Characteristic on the ZL1 Plane
S2 = ( VR1 VF1) + VF1
C. Positive-Sequence Polarized BC Phase Distance Unit
= ( VR1 VF1) VF2 VF0 (Forward Characteristics)
(27)
= ( VR1 VF1) ( Zs1 + ZL1) IR1 The symmetrical component network connection shown in
( Zs0 + ZL0 ) IR1 Fig. 8 is the network used to derive the forward fault charac-
teristic for the BC element described in (31) and (32).
S2 ZL0 Zs0 This phase distance unit is defined by:
= ZL1' 2 + + Zs11 + Zs1 (28)
IR1 ZL1 S1 = ( VRB VRC ) Zc1( IRB IRC ) (31)
The results in (26) and (28) can be used in (2) to find the a
S2 = VB1 VC1 (32)
and b vectors:
Zc0
2 + Zc1
a = Zc1 (29)
ZL0'
2 + ZL1'

Zs0
1 + Zs1
b = Zs1 (30)
ZL0'
2 + ZL1'

The ground element is mostly directional for all reactive
impedances and may encounter problems if capacitances are
located in the reverse direction. Fig. 7 illustrates that there are
impedances on the ZL1 plane (mainly capacitive and with
negative resistance values) for which the element will operate.
This is a desirable distance element characteristic. For security Fig. 8. Symmetrical Component Network for a Forward BC Fault
purposes, most manufacturers will opt to supervise the opera-
tion of distance elements with directional elements to avoid
unwanted operations if the fault impedances in the reverse
direction fall inside the characteristic, as shown in Fig. 7.
6

Following a similar procedure for S1 as that described in


Section III, Subsection A:

( )
S1 = a 2 a ( VR1 VR2 ) Zc1( IR1 IR2 )
(33)
= j 3 ( VR1 VF1) VR2 Zc1( 2IR1) + VF1

S1
= j 3 ( 2ZL1 1Zc1) (34)
IR1
and for S2:

( )
S2 = a 2 a ( VR1 VF1 + VF1)
(35)
= j 3 ( VR1 VF1) + IR1( Zs1 + ZL1)

S2
= j 3 ( 2 ZL1 Zs1) (36) Fig. 10. Symmetrical Component Network for a Reverse BC Fault
IR1
Using the results in (34) and (36), the resulting a and b Returning to (31), simplify to find a more useful expression
vectors are: for S1, based on the network shown in Fig. 10:
a = Zc1 (37) S1 = (a 2 a) [ (VR1 VR2) Zc1 (IR1 IR2)]
Zs1 = j 3 ( VR1 VF1) VR2 Zc1( 2IR1) + VF1
b= (38)
2 (39)
The positive-sequence polarized phase distance unit has a = j 3[( VR1 VF1) VR2 Zc1( 2IR1)
definite reach, given by Vector a. Fig. 9 illustrates the + VR2 ZL ' IR1
threshold locus on the ZL1 plane.
S1
= j 3 ( 2 ZL1 + 2 Zc1) (40)
X
a = Zc1 ( IR1)
Returning to (32), simplify to find a more useful expression
for S2:
S2 = (a 2 a) [ (VR1 VF1) + VF1]
(41)
= j 3 ( VR1 VF1) IR1( Zs1 + ZL1)
S2
= j 3 ( 2 ZL1 Zs2 ) (42)
( IR1)
R
Using the results in (40) and (42), the resulting a and b
Zs1
b= vectors are:
2
a = Zc1 (43)
Zs1
b= (44)
bmem = Zs1 2
X

Fig. 9. Forward Fault Characteristic on the ZL1 Plane

D. Positive-Sequence Polarized BC Phase Distance Unit R


(Reverse Characteristics)
a = Zc1
In this section, we will follow a similar procedure as Zs1
b=
described in Section III, Subsection B. Fig. 10 is the network 2
used to derive the reverse fault characteristic for the BC phase
distance element.

Fig. 11. Reverse Fault Characteristic on the ZL1 Plane


7

E. Phase-to-Phase-to-Ground Faults Using:


An interesting design choice is the detection of phase-to- Zs0 + ZL0
phase-to-ground faults. These can be considered either as IR2 = IR1 (46)
Zs0 + ZL0 + Zs1 + ZL1
ground faults (due to the involvement of the ground return) or
(45) yields:
phase faults (due to their multiphase nature). The choice is a
design choice of the manufacturer. Zs0 + ZL0
When single-pole trip, line distance protection schemes are ZL1 1 + Zs0 + ZL0 + Zs1 + ZL1
S1
designed, phase-to-phase-to-ground faults are to trip the three = j 3 (47)
IR1 Zs0 + ZL0
poles of the breaker. Only phase-to-ground faults, when Zc11 +
detected, imply the opening of a single pole of the breaker. Zs0 + ZL0 + Zs1 + ZL1
This argument, by itself, justifies detecting phase-to-phase-to Returning to (32), derive a more useful expression for S2:
ground faults with the phase elements. Other arguments
S2 = j 3[(VR1 VF1) + VF1] (48)
include the operation of the phase selectors in the overall
scheme. using (46):
The positive-sequence polarized phase distance unit Zs0 + ZL0
described by (31) and (32) readily detects phase-to-phase-to- ZL1 1 + Zs0 + ZL0 + Zs1 + ZL1
S2
ground faults. Fig. 12 is the network used to derive the = j 3 (49)
forward fault characteristic for the BCG phase distance IR1 Zs0 + ZL0
+ Zs1
element. Zs0 + ZL0 + Zs1 + ZL1
Zs1 ZL1 Next, use (47) and (49) to find the a and b vectors:
a = Zc1 (50)
Zs0 + ZL0
IR1 b = Zs1
Vs Zs1 + ZL1 + 2Zs0 + 2ZL0 (51)
VR1 VF1 = f (ZL1)
While Vector a is well-defined with a very definite and
desired reach, Vector b is a function of ZL1 but in the nega-
Zs1 ZL1 tive direction. The result indicates that to find the shape
requires an iterative process, because b is not in the same
position for two different values of ZL1. However, what really
IR2 matters is (50) because the element has a definite reach.

VR2 VF2 F. Three-Phase Faults and Memory in S2


For both the ground distance elements and the phase
distance element, three-phase faults can be shown to present
the same characteristic on the ZL1 plane. The a and b vectors
Zs0 ZL0 can be shown to be the ones found for the self-polarized
distance unit, described in (6) and (7).
The characteristic plotted in Fig. 3 shows that the circle
IR0 boundary passes through at the distance element location.
VR0 VF0
Neither the ground nor the phase element can detect the fault
due to the lack of any voltage to calculate the positive-
sequence polarizing quantity (S2). The distance unit should be
Fig. 12. Symmetrical Component Network for a Forward BCG Fault able to detect these faults.
Returning to (31), derive a more useful expression for S1 In general, memory action is provided, and S2 remem-
based on the network shown in Fig. 12: bers the proper polarizing quantity after the fault when all
voltages are zero. In most implementations of modern relays,
S1 = j 3[(VR1 VF1) + VF1 VF2) S2 is implemented with memory for all phase and ground
(45)
Zc1 (IR1 IR2)] distance elements [6]. Besides the benefit associated with
detecting three-phase faults right at the location of the distance
unit, providing memory action enhances the ability of distance
protection schemes to be applied in lines with series capacitors
and increases fault detection ability.
8

For the positive-sequence polarized phase distance unit, a


modified S2 polarizing vector is:
S2 = VB1mem VC1mem (52)
This translates to:
S2 = j 3(Vs1)
(53)
= j 3(VR1 + Zs1 IR1)
For a three-phase fault:
S2
= j 3(ZL1 + Zs1) (54)
IR1
Using (54) together with (37), the memory effect expands
the circle with:
bmem = Zs1 (55) Fig. 13. Response of All Three Ground Distance Elements to an AG Fault
In fact, it can be shown that polarizing the ground and on the ZL1 Plane
phase distance elements with memory modifies Vector b, Interestingly, the responses of the elements do not over-
resulting in the following values. reach. Therefore, as a protective scheme design choice, the
For the ground distance unit: distance elements can detect all types of faults. The other
Zs0 choice could be to use a phase selector to enable only the type
2 + Zs1 of distance unit appropriate for the type of fault. That way,
bmem = Zs1 (56) only the AG element detects AG faults, since the fault detector
2 + ZL0 has determined the type of fault.
ZL1
For the phase distance unit: H. Fault Resistance and Load Flow
bmem = Zs1 (57) Fault resistance and load flow are not considered when
describing the characteristics of distance elements. The plots
These results are shown in Fig. 5 and Fig. 9. In the opera-
in Fig. 5 and Fig. 9 are provided and assume a radial system.
tion of these distance elements, the memory has a time
The appendix of this paper provides the complete deriva-
constant, which varies with the design and purpose [6]. In
tions of the impedance plots on the apparent impedance plane,
traditional phase distance relay applications, the time constant
considering these two factors.
should be enough to detect the zero-voltage, three-phase fault.
Fault resistance and load flow are more important in the
Series capacitor applications require a longer time constant
analysis of the operation of distance units. During the testing
and associated logic that changes short and long memory
of the characteristics distance units, these two factors are
constants.
generally not considered.
When picturing the operation of these units, the b vector
starts at b = bmem, and after a few time constants, its value
IV. ANALYSIS OF A QUADRILATERAL GROUND
approaches that of the no-memory mho circle. DISTANCE UNIT
G. Response to Other Fault Types and Phase Selector Quadrilateral distance units are provided in protection
Criteria systems to cover ground faults. While their advantages over
Although not part of this paper, it has been shown else- traditional mho ground distance units and ground overcurrent
where that all distance elements have a response to other types protection are a matter of discussion, these units are present in
of faults [3]. However, with the methodology described protective relays and merit consideration.
previously, these characteristics can be derived. Implementing a quadrilateral element requires a reactance
Fig. 13 is an example of the composite response for an AG element, a resistance element, and a directional element.
fault of all the ground distance elements. There are areas of
A. Reactance Element
the ZL1 plane where two or three of these elements will oper-
ate. The same is true for phase distance elements and their The reactance element for a ground directional element is
responses to other fault types. defined by the following equations [2][3]:
S1 = VRA Zc(IRA + kc0 3I0) (58)
jT
S2 = j IR2 e (59)
The polarizing quantity S2 is a current; T is the
nonhomogeous correction angle to be described later. It can
be shown that I2 is the better choice when load is considered.
However, I0 and (IA+K0 I0) are other possibilities for
obtaining a reactance line.
9

Equation (58) is the same as (8) and can also be simplified Zs1 ZL1
to the expression in (16).
The polarizing quantity S2 is different. To simplify S2, a
relatively nonacademic mathematical trick can be used. IR1
Vs
S2 = 0 (VR1 VF1) + j IR1 e jT (60) VR1 VF1

S2 0 j e jT
= ZL1 + (61)
IR1 0 0
Zs1 ZL1
The end result is:
Zc0
2 Zc1
ZL1 Zc1 IR2
2 ZL0 VR2 VF2
S1 ZL1
= jT
(62) 3Rf
S2 j e
ZL1 +
ZL0
02
ZL1 Zs0 ZL0

Equation (62) is not rigorously correct, but it allows for a


criterion to obtain the expression for Vector b.
IR0
Zc0
j 90 T + ang 2 +
Zc1 VR0 VF0
b=e
(63)
Vector a is expressed in (19). Fig. 14 illustrates the graphi-
cal result. Vector b is a very large and infinite vector but with Fig. 15. Symmetrical Component Representation of an AG Fault With Fault
Resistance (Rf)
an angle. The reactance line is a circle with infinite radius.
If the protective relay is doing a DFT (discrete Fourier
transform) or cosine filter calculation, the real and imaginary
parts of the vectors are available. It follows that:

{
Im VRA ZL1(IRA + kc0 3I0)* = } (65)
{
Im (If Rf ) ZL1(IRA + kc0 3I0)* }
and:

Rf =
{
Im VRA Zc1(IRA + kc0 3I0)* } (66)
Im { If (Zc1(IRA + kc0 3I0) }
*


j 90 T + 2 +
Zc0

In one design choice [2], the If value was chosen to be:
Zc1
b = e
(IR0 + IR2)
If = 3 (67)
2
Fig. 14. Reactive Line Component of a Ground Quadrilateral Unit Equation (66) yields the fault resistance value (Rf), which
B. Resistance Element for a radial system adds to the line impedance. This result is a
The resistive check for a quadrilateral element could be straight calculation of Rf and cannot be plotted on an imped-
implemented with equations similar to (58) and (59), using ance plane. In fact, the directional element that keeps the
S2 = IR2 and Zc = R [3]. Another approach is to actually reactance unit from detecting reverse faults cannot be plotted
calculate the resistive component of the fault [1][2]. on the plane. The quadrilateral element is a combination of the
Consider the symmetrical component representation of a reactance line, the resistive check, and a directional element.
ground fault with resistance, as shown in Fig. 15. The follow-
ing is true: V. TESTING OF DISTANCE ELEMENTS
VF1 + VF2 + VF0 = If Rf Relay engineers are curious. Most of them want to have a
(64) deep understanding of the devices that are connected to their
VRA ZL1(IRA + kc0 3I0) = If Rf power system. When the device fundamentals are understood,
analysis and testing are simple. There are three types of testing
that satisfy different functions of a numerical protective relay:
acceptance, commissioning, and maintenance [7].
10

Acceptance testing involves the study of the protective 1) Apparent Impedance for a Ground Fault
device and its characteristics. Some users qualify protective The network in Fig. 4 is also used to derive the expression
devices over a period of time, studying and testing the for the apparent impedance. Therefore, for the AG fault in
characteristics provided by the device. This test is performed Fig. 4:
in a quiet environment, usually the companys protection VF1 + VF2 + VF0 = 0
laboratory, with ample time to verify the published character-
(VR1 ZL1 IR1)
istics. During this type of testing, the users have an oppor- (68)
tunity to obtain an understanding of the relay principles. + (VR2 ZL1 IR2) + (VR0 ZL0 IR0) = 0
Commissioning testing involves the actual installation of VRA + ZL1 [ IRA + kL0 (3I0) ] = 0
the protective device and the testing of the connections to it
Equation (68) simplifies to:
(e.g., polarities and phasing) and of the programmable logic.
Some distance-unit reaches may be verified on the distance VRA
ZL1 = (69)
elements. The commissioning testing is by no means as IRA + kc0 (3I0)
involved as the acceptance testing, due to the timing and most
where kc0 is defined in (10) as a relay setting. It should be
likely the pressure to get the devices installed.
equal to kL0:
Maintenance testing involves a periodic and simple func-
tional evaluation of the protective device. The testing takes ZL0 ZL1
kL0 = (70)
advantage of the self-check algorithms in numerical protective 3ZL1
relays and also the nature of the hardware design. Since the
2) Apparent Impedance for a Phase-to-Phase Fault
firmware is a software program, it is not expected that the
The following is true for the network in Fig. 8:
features tested in the acceptance testing and the commission-
ing testing have changed. A visual inspection of the enable VF1 VF2 = 0
light, confirmation that the metering matches known levels, (VR1 ZL1 IR1) (VR2 ZL1 IR2) = 0 (71)
and testing of auxiliary contacts or devices should suffice. The (VR1 VR2) ZL1(IR1 IR2) = 0
maintenance testing interval is dependent on the data collected
from the device. If the metering and oscillographic reports are Equation (71) simplifies to:
accessed constantly, the maintenance interval may be longer VRB VRC
ZL1 = (72)
than for a device that is totally isolated and not reporting any IRB IRA
events.
B. Confirming the Distance Unit Characteristic
It is hoped that the information in this section helps in
understanding the actual operation of distance elements and Symmetrical components are used to derive the distance
acceptance testing. The implementation of the distance units element characteristics on the ZL1 plane. Assuming a radial
has been tested and verified by the manufacturer and users system, this is how the impedance characteristics on the ZL1
several times, especially if the device is mature in the market- plane are derived. The effect of load flow and fault resistance
place. is neglected; their influence is easier to visualize on the appar-
ent impedance plane when the operation of the unit is studied.
A. Apparent Impedance Symmetrical component theory is fundamental for relay engi-
The term apparent impedance is largely used in protective neers. It makes three-phase power system analysis simple and
relaying literature when discussing distance elements. It is a understandable.
calculation of the impedance in terms of the measured volt- When testing a memory polarized distance unit, the way
ages and currents. For a simple radial system with no load the prefault and faulted voltages are managed affects the test
flow, the apparent impedance can be readily used to verify the results. The memory effect will not be noticeable when the
plots of Fig. 5 and Fig. 9 on the ZL1 plane. For load flow and calculated fault voltages are maintained and the calculated
fault resistance in a two-source network, the term is not a fault current is increased until the unit trips. But if the prefault
physical impedance. It is a measurement that implies apparent voltages are healthy and then fault quantities are applied, the
impedance, and it only represents an impedance (ZL1 in our memory effect will be noticeable.
discussion) if the system is radial. When fault resistance and
load flow are considered, the apparent impedance is just a
measurement.
11

Memory algorithms may vary among different manufactur- TABLE II


TEST VOLTAGES AND CURRENTS
ers, but the decay of the polarizing memory voltage (S2) is,
for most practical purposes, too fast to obtain the memory Point/
Voltages and Currents I
voltage characteristic. Moreover, the filtering of the voltages ZL1
and currents may take some time, and the memory voltage
Va = 63.680, Vb = 71.76120.70,
may have already changed its value. However, by choosing an p1
Vc = 70.81122.78 3.86
impedance point in between the no-memory and with- 10.0080
Ia = 3.8474.15, Ib = 0, Ic = 0
memory polarization, the behavior can be checked. This will
be illustrated with the phase distance element. Va = 64.240, Vb = 72.91117.11,
p2
Vc = 69.58126.03 4.35
8.9550
1) Testing the Ground Distance Unit Ia = 4.3244.31, Ib = 0, Ic = 0
For illustration, the parameters in Table I were chosen for
Va = 65.360, Vb = 74.34111.39,
the model. p3
Vc = 67.59131.34 6.58
6.0420
TABLE I Ia = 6.5114.07, Ib = 0, Ic = 0
GROUND DISTANCE-UNIT MODEL PARAMETERS
Va = 66.150, Vb = 75.33108.2,
p4
Parameter Value Description Vc = 66.43134.44 8.23
4.8710
Zc1 10 80 Positive-sequence reach Ia = 8.1514.07, Ib = 0, Ic = 0

Derived from the setting kc0 (10) that Va = 67.410, Vb = 76.79103.58,


Zc0 3070 p5
is normally a setting Vc = 64.80138.85 10.73
3.810
Ia = 10.676.04, Ib = 0, Ic = 0
kc0 0.67414.93 The actual kc0
Va = 69.690, Vb = 79.1396.90,
Zs1 185 Positive-sequence source impedance p6
Vc = 62.34145.61 14.87
2.8510
Zs0 380 Zero-sequence source impedance Ia = 14.7416.42, Ib = 0, Ic = 0

Fig. 16 shows the corresponding mho circle derived from Va = 73.670, Vb = 82.7287.86,
p7
Vc = 58.88155.35 21.07
the parameters in Table I. Ten random points were chosen 2.1320
Ia = 20.8626.80, Ib = 0, Ic = 0
from the plot, and their impedances were calculated. For each
point, the symmetrical component analysis yielded the corre- p8
Va = 62.690, Vb = 66.17146.27,
sponding test voltages and currents, as shown in Table II. By Vc = 79.30101.14 13.96
2.71170
fixing the voltages and slowly increasing the current, the trip Ia = 13.92164.43, Ib = 0, Ic = 0
point is found when the distance unit trips. The fault magni- Va = 62.720, Vb = 69.42130.35,
p9
tude listed in Table II corresponds, within the margins of the Vc = 74.06114.33 6.48
5.85140
test equipment error, to the theoretical value, also shown in Ia = 6.45133.88, Ib = 0, Ic = 0
Table II. Va = 63.230, Vb = 70.83124.37,
p10
Vc = 72.05119.53 4.36
X 8.80110
a = 1080
Ia = 4.32104.03, Ib = 0, Ic = 0
p1
p10 This example illustrates the link between theoretical values
p2
and proper testing. The values in Table II come from the
symmetrical component analysis of the fault.
p9 The source impedance magnitude was not sufficient to
make the memory effect noticeable; a larger source impedance
p3 should be chosen.
p8 p4
R
p5
p6
380
1 + p7
185
b = (185 )
3070
2 +
1080

Fig. 16. Points on the Ground Distance Characteristic for the Example in
Table I
12

2) Testing the Phase Distance Element TABLE IV


TEST VOLTAGES AND CURRENTS WITH NO MEMORY
To illustrate the phase distance-unit testing, the parameters
from Table III were chosen. Point/
Voltages and Currents I
TABLE III ZL1
PHASE DISTANCE-UNIT MODEL PARAMETERS
Va = 700, Vb = 47.26140.11,
p1
Parameter Value Description Vc = 45.36138.07 3.05
10.0080
Ia = 0, Ib = 3.03172.63, Ic = 3.037.38
Zc1 1080 Positive-sequence reach
Va = 700, Vb = 53.57146.19,
Zs1 1085 Positive-sequence source impedance p2
Vc = 39.22130.53 3.24
9.7050
In this example, the source impedance is larger and will Ia = 0, Ib = 3.23157.84, Ic = 3.2322.16
allow testing of the memory effect on the distance character- Va = 700, Vb = 60.63153.32,
p3
istics. Vc = 31.49120.18 3.87
8.6520
Fig. 17 illustrates the plot of the phase distance element Ia = 0, Ib = 3.85145.14, Ic = 3.8534.86
based on the parameters in Table III. The inner circle, as dis- Va = 700, Vb = 63.12155.97,
p4
cussed in a previous section, is the characteristic with no- Vc = 28.51115.67 4.18
memory effect on the polarizing vector (S2). 8.2310
Ia = 0, Ib = 4.16142.04, Ic = 4.1637.97

X a = 1080 Va = 700, Vb = 66.20159.41,


p5
Vc = 24.63109.02 4.61
p1 7.740
Ia = 0, Ib = 4.60139.55, Ic = 4.6040.85
p2
p10
Va = 700, Vb = 69.46163.27,
p6
Vc = 20.3099.86 5.17
7.2610
p9 Ia = 0, Ib = 5.14137.19, Ic = 5.1442.81

p3 Va = 700, Vb = 72.86167.64,
p7
Vc = 15.6485.70 5.23
p8 p4 6.8220
Ia = 0, Ib = 5.77167.64, Ic = 5.7743.78
R
p5 Va = 700, Vb = 21.87113.73,
p8
p6 Vc = 64.39161.89 4.83
6.82170
Ia = 0, Ib = 4.83152.17, Ic = 4.8327.84
p7
1085
b= Va = 700, Vb = 29.67122.89,
2 p9
Vc = 59.37155.19 3.88
7.74150
Ia = 0, Ib = 4.04157.12, Ic = 4.0422.88
bmem = 1085
Va = 700, Vb = 35.73129.06,
p10
Fig. 17. Phase Distance-Unit Points on the Impedance Plane Vc = 54.99149.71 3.53
8.65130
Ia = 0, Ib = 3.52164.21, Ic = 3.5215.79
Table IV shows the test voltages and currents used to
confirm the no-memory characteristic. The test voltages are The outer characteristic is related to the memory effect on
constant, while the current is increased until the phase distance S2. It is impractical to test this characteristic. The memory
element trips. The fault current magnitudes correspond to the algorithms in protective relays are constantly updated; the
expected values, within the margins of error of the test equip- filtering behavior of the relays will make the memory value
ment and the device under test. (S2) change almost instantly. Therefore, any values calculated
with the outer-circle impedances will not yield any practical
results.
13

Visually, note that the memory polarizing voltage is


changing to the new faulted value and the circle starts from
the outer boundary and decays finally to the inner, no-memory
boundary.
To test this behavior, impedances in between the outer and
inner circle can be chosen. The midpoint impedances shown in
Fig. 17 are good choices. These values are the average of the
two impedances at the same angle from the outer and inner
circles.
Moreover, to test the memory behavior, apply the fault
after healthy voltages have been present for a while. Both fault
voltages and currents should correspond to the calculated
values.
Table V describes the midpoint impedances and the fault Fig. 18. Typical Fault Sequence Verifying the Voltages and Currents in
Table V
voltages and currents used to verify the memory polarization
of the phase distance element. Healthy prefault voltages and 3) Testing the Ground Reactance Distance Unit
currents start the fault sequence. To illustrate the testing of the ground reactance distance
unit, the parameters in Table I will be used. The setting T
TABLE V
TEST VOLTAGES AND CURRENTS WITH MEMORY compensates for any effect associated with the tilt on the
reactance line.
Point/ The reactance setting T (58) will be set to:
Voltages and Currents
ZL1
Zc0
T = arg 2 + = 6.00 (73)
Zc1
p3 Va = 700, Vb = 61.69151.70, Vc = 33.17118.19

9.5120 Ia = 0, Ib = 3.69143.373, Ic = 3.6936.627
This value makes the reactance line horizontal, as seen in
p4 Va = 700, Vb = 64.71153.75, Vc = 31.01112.684
Fig. 19.
9.3210 Ia = 0, Ib = 3.95139.25, Ic = 3.9540.75
p5 Va = 700, Vb = 68.56156.25, Vc = 24.63104.70 Zc = 1080

9.080 Ia = 0, Ib = 4.31134.94, Ic = 4.3145.06

p6 Va = 700, Vb = 72.77158.86, Vc = 26.32994.64


8.8410 Ia = 0, Ib = 4.76131.29, Ic = 4.7648.71
p7 Va = 700, Vb = 78.08161.92, Vc = 24.6080.10
8.6120 Ia = 0, Ib = 5.35127.85, Ic = 5.3552.152

p8 Va = 700, Vb = 25.95107.19, Vc = 67.08158.31


8.19170 Ia = 0, Ib = 4.51147.66, Ic = 4.5132.34
p9 Va = 700, Vb = 31.52120.11, Vc = 60.66153.29
8.66150 Ia = 0, Ib = 3.85155.09, Ic = 3.8524.91

p10 Va = 700, Vb = 36.45127.95, Vc = 55.59148.86


9.15130 Ia = 0, Ib = 3.43163.46, Ic = 3.4316.54

Fig. 18 illustrates the operation of the distance element and


the fault sequence. Note the effects of the memory action. The
memory voltage is decaying much slower than the actual Fig. 19. Points on the Reactance Ground Distance Characteristic
positive-sequence voltage. As the polarizing voltage decays,
there will be a point in the decay where there is not enough
polarizing voltage to operate the distance unit. The element
eventually drops out, visualized as the circle dropping from
the full-memory characteristic to the steady-state character-
istic, which is polarized by V1. The memory action, however,
has allowed an expansion of the element.
14

Table VI represents seven points on the reactance line. 3) Use Symmetrical Components When Testing
These impedances lie on the threshold of operation. The The distance element theory is based on symmetrical com-
recorded current in the right-hand column is within the margin ponents. More than any other aspect of power systems,
of error in the test equipment and the protective relay. symmetrical components are the foundation of power system
TABLE VI
protective relaying and, in particular, distance elements. The
TEST VOLTAGES AND CURRENTS FOR FIG. 19 faulted voltages and currents presented earlier were obtained
from symmetrical component analysis of the faults.
Point/
Voltages and Currents I A traditional way to estimate faulted voltages and currents
ZL1 for an AG ground fault, for example, is by using a phasor
p1
Va = 64.150, Vb = 70.34140.11, diagram, as illustrated in Fig. 20. The faulted voltage is
Vc = 7.200138.07 3.75 decreased, and the faulted current is modified according to the
10.38108.33
Ia = 3.72102.33, Ib = 0, Ic = 0 impedance magnitude and angle requirement. While this
Va = 63.710, Vb = 70.72123.03, methodology provides a quick and dirty way to make an
p2
Vc = 71.83120.44 3.87 estimate, it is not based on any theory. The unfaulted voltages
9.9899.21 remain with their healthy values, and the angles between volt-
Ia = 3.8593.21, Ib = 0, Ic = 0
ages remain constant. This is not what happens in a real power
Va = 63.530, Vb = 71.10122.06,
p3 system.
Vc = 71.56121.54 3.91
8.6520
Ia = 3.8983.59, Ib = 0, Ic = 0 Moreover, as illustrated in Fig. 20, increasing the faulted
current angle results in the faulted current and the faulted volt-
Va = 63.670, Vb = 71.42121.00, age being in phase. This condition will not occur in a trans-
p4
Vc = 71.21122.56 3.86
1080 mission network. Directional elements will not declare the
Ia = 3.8374.00, Ib = 0, Ic = 0
fault to be in the forward direction because, for ground faults,
p5
Va = 64.080, Vb = 71.65120.01, it is assumed that the source is reactive and not resistive, as
Vc = 70.84123.38 3.73 equal angles will suggest.
10.4270.94
Ia = 3.7064.93, Ib = 0, Ic = 0

Va = 64.660, Vb = 71.78119.19,
p6
Vc = 70.50123.92 3.54
11.07662.76
Ia = 3.5156.76, Ib = 0, Ic = 0

Va = 65.300, Vb = 71.83118.59,
p7
Vc = 70.21124.20 3.32
6.8220
Ia = 3.2949.62, Ib = 0, Ic = 0

C. Comments on the Impedance Testing Results


The results obtained, the description of the testing, and the
theory described in the previous sections allow for discussing
a few interesting issues.
1) The Plot Is on the ZL1 Plane Fig. 20. Fixing Voltages and Changing the Fault Current Does Not
The impedance plots correspond to the ZL1 plane. The Accurately Represent Faults in a Power System
characteristics represent actual impedances in a radial network
4) Directional Elements Supervise Distance Units
for which the distance unit will operate. For purposes of test-
If symmetrical components are used to calculate faulted
ing the units characteristic, a radial network is assumed.
voltages and currents, the directional units supervising the
Plots that correspond to other planes should not be con-
distance elements will be transparent to the testing procedure.
fused or used together with the distance element characteristic
Directional unit theory is based on symmetrical compo-
plots. For example, the impedance-based ground directional
nents as well. For example, for ground directional elements,
element plots its characteristics on a V2/I2 or V0/I0 plane.
the source impedance determines that the direction to the fault
2) The Plot Is for Faults in the Forward Direction is in the forward direction (the measurement is Zs for a
Fig. 7 and Fig. 11 illustrate the characteristics of distance forward fault).
units for faults in the reverse direction. They represent the The use of symmetrical components and a known source
impedance values on the reverse impedance plane (ZL1) for impedance ensures that directional elements will not block the
which the element will operate and are a totally different plane operation of distance units.
than the forward fault impedance plane (ZL1) shown in Fig. 5
and Fig. 9.
Reverse fault characteristics are not possible to test in
practice because distance elements are generally supervised by
directional elements that keep distance units operating in the
forward direction only.
15

VI. APPARENT IMPEDANCE, LOAD FLOW, IF1


AND FAULT RESISTANCE Zs1 mZL1 (1 m)ZL1 Zr1

The theory and testing covered in the previous sections


illustrate a radial network and the graphical view of all the
IR1
impedances that would make the distance unit operate. Load VR1 VF1
Vs Vr
flow and fault resistance are factors that are present in all line
IF2
distance protection schemes.
The ZL1 plane is not the proper plane to visualize the Zs1 mZL1 (1 m)ZL1 Zr1
operation of the distance units when there is load flow and 3 Rf

fault resistance. The fault resistance is not part of any of the


IR2
three symmetrical component networks (positive, negative, VR2 VF2
and zero sequence).
The proper plane to use is the apparent impedance plane. IF0

For ground faults, the plane is defined by (69). For phase Zs0 mZL0 (1 m)ZL0 Zr0
faults, the plane is defined by (72). In the appendix of this
paper, the impedance circles are derived for both the ground
and phase distance elements. IR0
VR0 VF0
It is mathematically very difficult to find the impedance
locus on any plane to describe the distance element
characteristics because the distribution of currents is different
Fig. 22. Two-Source Symmetrical Component Representation of a Ground
depending on the faulted impedance and load flow. With the
Fault
use of the equations derived in the appendix, it is simpler to
visualize the location of the apparent impedance measured Solving for m = 1 and Rf = 0, only the load flow effect is
with respect to the distance-unit characteristics. illustrated in Fig. 23. The figure shows a computer-generated
Another important point is that all the information is avail- graph based on the equations derived in the appendix. As
able from the local measurements to calculate the apparent reported in other literature, mho circles adjust appropriately to
impedance. prevent overreach due to the direction of the load flow [3].
To illustrate the plotting on the apparent impedance plane, The pivot point is the units reach.
the system in Fig. 21 is used. The end characteristic on the
left-hand side is plotted, and a large source impedance is
selected to illustrate the mho circle behavior compared to the
radial characteristics discussed before.
Zs1 = 1085 ZL1 = 1080 Zr1 = 285
Zs0 = 2075 ZL0 = 3070 Zr0 = 280

Vr = 700 Vr = 70 20

Fig. 21. Sample Power System Used to Illustrate the Impedance Plot With
Rf and Load Flow

A. Ground Distance Unit


Using the impedances in Fig. 21 and the network shown in
Fig. 22, circuit analysis techniques can solve for the network.
The distance-unit settings are the same as the ones shown in
Table I. Fig. 23. Load Flow Effect on the Apparent Impedance Characteristic
16

For the same point (m = 1) and the same load flow but with TABLE VII
TEST VOLTAGES AND CURRENTS FOR APPARENT IMPEDANCES IN
fault resistance (Rf = 0.5 ohms), Fig. 24 illustrates the plot of FIG. 23, FIG. 24, AND FIG. 25
the apparent impedance and the distance-unit characteristics.
In the apparent impedance plane, the Rf component is not a Point/
Voltages and Currents I
straight line, and moreover, the apparent Rf component is ZApp
magnified several times due to the strong remote source. Va = 37.330, Vb = 67.94124.33,
p1 Vc = 69.02113.01
15 2.89
Fault Location X 10.0080 Ia = 2.8871.83, Ib = 0.53143.88,
Apparent Impedance Ic = 1.67106.12

Va = 39.570, Vb = 67.77112.93,
p2 Vc = 69.51124.88 No
10.4753.82 Ia = 2.9746.46, Ib = 0.69137.72, trip
Ic = 1.67123.59

Va = 40.940, Vb = 75.50105.75,
R p3 Vc = 72.96146.88
0 3.20
8.6330.02 Ia = 3.1918.63, Ib = 1.1293.09,
Ic = 1.08145.79

Each point on the apparent impedance plane can be plotted


using the expressions in the appendix; examples are shown in
Fig. 23, Fig. 24, and Fig. 25. Distance units are monitoring the
Forward Load
Radial Effect
power system constantly. When there is a fault, the numerical
Characteristic algorithm calculates the phasor values of the voltages and cur-
15 rents. It therefore follows that the impedance trajectory on the
15 0 15
apparent impedance plane can be plotted over time.
Fig. 24. Load Flow and Fault Resistance Apparent Impedance Numerical distance units make calculations in discrete time
periods called processing intervals. It is therefore possible to
The advantage of using a computer program to calculate
evaluate the impedance trajectory to the fault over time. In
the voltages and currents of the network is that a point on the
Fig. 26, a plot of the impedance trajectory is shown. Note that
plot can be found. With this point, the voltages and currents
at each processing interval, the apparent impedance changes.
can be calculated.
The apparently random motion until the impedance stabilizes
to the actual fault apparent impedance is also due to the fil-
tering algorithm used.
15
X

R
0

Fig. 25. Boundary Fault at m = 0.5 and Rf = 4.0


15
15 0 15

Fig. 26. Impedance Trajectory for a Ground Fault at m = 0.25 and Rf = 0.5
17

B. Phase Distance Unit the units reach (Zc) with a negative angle for loads in the
The symmetrical component network interconnection for a forward direction (export) and a positive angle for loads in the
phase-to-phase fault is shown in Fig. 27. The system parame- reverse direction (import), as illustrated in Fig. 29.
ters are the ones shown in Fig. 21. The appropriate a and b X
Reverse Load Effect
vectors for the fault resistance and load flow are derived in the
appendix. This unit also exhibits a beneficial tilt due to load
flow. Zc

Forward Load Effect

Fig. 29. Adaptive Ground Reactance Unit Characteristic

Even with the adaptive characteristics described by the


equations derived in the appendix, there is a chance of over-
reaching. The setting T provides perfect adjustment due to
load flow and fault resistance and will adjust for the
Fig. 27. Two-Source Symmetrical Component Representation of a Phase-to- nonhomogeneity of the negative-sequence network imped-
Phase Fault
ances. The angle T should be the difference between negative-
Fig. 28 illustrates the impedance trajectory for a BC fault. sequence current at the fault (IF2) with respect to the negative-
The expressions (85) and (86), derived in the appendix, sequence current measured at the distance-unit location (used
accurately describe the apparent impedance trajectory. to polarize the reactance line) [7].
At the elements reach (usually Zone 1 is the most critical),
the expression for T is:
Zs1 + ZL1 + Zr1
T = arg (74)
Zr1
The network in Fig. 21 illustrates the adaptability of this
element. The solution of the currents and voltages is obtained
by solving the network in Fig. 22. The fault will be located at
the end of the line (the reach of the element is also set to this
length), and a few Rf values will be used. For the network in
Fig. 21, T = 2.273.
Fig. 30 illustrates selected points used to derive the test
voltages and currents in Table VIII.

Zc = 1080

Fig. 28. Impedance Trajectory for a Phase-to-Phase Fault at m = 0.5 and


Rf = 0.5

C. Ground Reactance Element


The load and fault resistance characteristic equations are
derived in the appendix. The Vector b equation (90) deter-
mines the angle at which the reactance line tilts. The ground
reactance line defined by (57) and (58) is an adaptive reac-
tance line because it adjusts its tilt depending on the load flow. Fig. 30. Test Points on the Reactance Line With Different Fault Resistance
Quadrilateral distance units tend to overreach due to load flow Values
and fault resistance. The ground reactance element pivots on
18

TABLE VIII VIII. APPENDIX


TEST VOLTAGES AND CURRENTS FOR APPARENT IMPEDANCES IN FIG. 30
This section introduces how to find the distance element
Point/ characteristics on the apparent impedance plane. On this
Voltages and Currents I
ZApp plane, the graphical characteristics of the distance elements
Va = 44.940, Vb = 67.8117.44, can be observed, along with the influence of load and fault
p1 Vc = 69.83130.92 resistance. Only for radial networks, the ZL1 plane is equal to
2.91
12.3835.97 Ia = 2.9129.26, Ib = 0.83130.45, the apparent impedance plane.
Ic = 1.65134.07
A. Positive-Sequence Polarized Ground Distance Unit
Va = 39.570, Vb = 67.77112.93, (Apparent Impedance Plane Forward Characteristics)
p2 Vc = 69.51124.88
10.4753.82
2.99 Fig. 31 illustrates a simple two-source network and a
Ia = 2.9746.46, Ib = 0.69137.72,
Ic = 1.69123.59 Phase A-to-ground fault. The ground distance unit is
characterized by (8) and (9).
Va = 41.160, Vb = 68.35135.53,
p3 Vc = 68.53101.68
2.61 IF1
12.03106.78 Ia = 2.5797.61, Ib = 0.45136.83, Zs1 ZL1 Zr1
Ic = 1.5789.26

Va = 48.420, Vb = 68.83140.44,
p4 Vc = 68.2197.40 IR1 IF1 IR1
2.12
16.63125.50 Ia = 2.13115.07, Ib = 0.51123.08, VR1 VF1
Vs Vr
Ic = 1.4481.23

IF2
VII. FINAL DISCUSSION
Zs1 ZL1 Zr1
This paper presented a general technique to derive distance 3 Rf
elements, as well as deriving the characteristics of three dis-
tance units. Knowing the distance element theory allows for IR2 IF1 IR1
the understanding of the units, which in turn facilitates the VR2 VF2
acceptance testing sequence.
The distance-unit characteristics are plotted on an imped-
ance plane. The positive-sequence impedance plane represents IF0
the behavior of the units, and a radial system with no fault Zs0 ZL0 Zr0
resistance or load flow is assumed.
The characteristics imply faults in the forward direction.
IR0 IF0 IR0
Distance units also have characteristic plots for the reverse
VR0 VF0
direction.
When considering fault resistance and load flow, the
apparent impedance plane describes the measurement with
respect to the impedance characteristic. Fig. 31. AG Fault Symmetrical Component Network Interconnection
Mho distance elements are directional with a desirable
Returning to (8), simplify to find a more useful expression
response in the forward and reverse fault impedance character-
for S1:
istics. Memory action on these units allows for an expansion
larger than the normal expansion due to the source impedance. S1 = VRA Zc [ IRA + kc0 (3IR0) ] (75)
When the fault voltages are fixed and the fault current is
Equation (75) can be simplified to:
increased until the distance element trips, testing will show the
steady-state (no-memory) characteristics. Using two states S1 VA
= Zc1 (76)
during the testing, with the prefault state considering only [ IA + kc0 (3I0)] [ IA + kc0 (3I0)]
healthy voltages, the influence of the memory effect in dis-
tance units can be observed when the fault state is applied.
Quadrilateral distance units are composed of a reactance
unit, a resistance check unit, and a directional element. The
reactance unit presented is a circle of infinite radius. The
directional element and the resistance check of a particular
design cannot be plotted on the apparent impedance plane.
The impedance trajectories can be plotted on the apparent
impedance planes for both the ground and phase distance
units. These plots represent a measurement and not an actual
impedance.
19

Returning to (9), simplify to find a more useful expression Returning to (31), find a more useful expression for S1:
for S2: S1 = (VRB VRC) Zc (IRB IRC) (81)
S2 = VR1 + VR2 + VR0 VR2 VR0
Equation (81) yields:
= VRA VR2 VR0 (77)
S1 (VRB VRC)
= VRA + Zs1 IR2 + Zs0 IR0 = Zc (82)
(IRB IRC) (IRB IRC)
S2 VRa Returning to (32), find a more useful expression for S2:
=
IA + kc0 (3I0) IA + kc0 (3I0) S2 = VB1 VC1 + VB2 VB2 VC2 + VC2
IR2 IR0 Zs0 (83)
+ (78) = VB VC VB2 + VC2

+ Zs1 IR1 IR1 Zs1
1 + IR2 + Zc0 Zs0 1
IR1 Zc1 Zs1 S2 VB VC
= Zs1 (84)
The results in (76) and (78) can be used in (2) to find the a
IRB IRC IRB IRC 1 IA1
IA2
and b vectors:
Using (82) and (84), the resulting a and b vectors are:
a = Zc1 (79)
a = Zc1 (85)
IR2 IR0 Zs0
+
b = Zs1 IR1 IR1 Zs1 (80) 1
1 + IR2 + Zc0 Zs0 b = Zs1 (86)
IR1 Zc1 Zs1 1 IA1
IA2
B. Positive-Sequence Polarized Phase Distance Unit
(Apparent Impedance Plane Forward Characteristics) C. Ground Reactance Distance Unit (Apparent Impedance
Fig. 32 is the symmetrical component network intercon- Plane Forward Characteristics)
nection of a two-source power system for a BC fault used to The reactance element is defined by (57) and (58). Finding
analyze the positive-sequence polarized phase distance unit the S1 and S2 vectors on the apparent impedance plane
defined by (31) and (32). follows:
S1 VA
= Zc1 (87)
[ IA + kc0 (3I0)] [ IA + kc0 (3I0)]
S2 = 0 VA + j IR2 e jT (88)
With S2, a rigorous mathematical procedure is not prac-
tical, as shown in (89).
VA
IA + kc0 (3I0)
S2 0 [ ]
= (89)
[ IA + kc0 (3I0)] 0 + j IR2 e jT


0 [ IA + kc0 (3I0)]
The division by zero is infinity, and what matters is the
angle.
IA1 IA0 Zc0
j 90T + ang 1+ +
IA2 IA2 Zc1
b=e
(90)

Fig. 32. BC Fault Symmetrical Component Network Interconnection


20

IX. REFERENCES
[1] J. Roberts, A. Guzmn, and E. O. Schweitzer, III, Z=V/I Does Not
Make a Distance Relay, proceedings of the 20th Annual Western
Protective Relay Conference, Spokane, WA, October 1993. Available:
http://www.selinc.com/techpprs.htm.
[2] E. O. Schweitzer, III and J. Roberts, Distance Relay Element Design,
proceedings of the 46th Annual Conference for Protective Relay
Engineers, College Station, TX, April 1993. Available:
http://www.selinc.com/techpprs.htm.
[3] W. A. Elmore, Protective Relaying Theory and Applications, New York:
Marcel Dekker, Inc., 1994.
[4] Type HZM Distance Relay, Westinghouse Electric Corporation,
Instruction Manual, I.L. 41-412.1K, May 1954.
[5] F. Calero, Development of a Numerical Comparator for Protective
Relaying: Part I, IEEE Transactions on Power Delivery, Vol. 11, No. 3,
pp.12661273, July 1996.
[6] D. Hou, A. Guzmn, and J. Roberts, Innovative Solutions Improve
Transmission Line Protection, proceedings of the 24th Annual Western
Protective Relay Conference, Spokane, WA, October 1997. Available:
http://www.selinc.com/techpprs.htm.
[7] SEL-421 Reference Manual. Available: http://www.selinc.com/
instruction_manual.htm.

X. BIOGRAPHY
Fernando Calero received his BSEE in 1986 from the University of Kansas,
his MSEE in 1987 from the University of Illinois (Urbana-Champaign), and
his MSEPE in 1989 from the Rensselaer Polytechnic Institute. From 1990 to
1996, he worked in Coral Springs, Florida, for the ABB relay division in the
support, training, testing, and design of protective relays. Between 1997 and
2000, he worked for Itec Engineering, Florida Power and Light, and Siemens.
Since 2000, Mr. Calero has been an application engineer in international sales
and marketing for Schweitzer Engineering Laboratories, Inc., providing
training and technical assistance.

Previously presented at the 2009 Texas A&M


Conference for Protective Relay Engineers.
2009 IEEE All rights reserved.
20090812 TP6323-01

You might also like