You are on page 1of 5

Designers always should remember that

Design = Analysis + Member Design + Connections

98 Tips
BY JAMES M. FISHER, P.E., PH.D., AND MICHAEL A. WEST, P.E., AIA

for Designing Structural Steel

D
DESIGNERS OFTEN SPEND most of their time on analysis and member strength design, and an insufficient amount of time on connections
and design considerations other than strength. This article provides a compendium of these other design considerations, offering guidance to
designers so that they may achieve economical designs for steel structures. The suggestions provided are based on our 75 years of
combined experience in the design of structural steel. Further suggestions were taken from Economy in Steel by Charles J. Carter,
S.E., P.E., Ph.D., Thomas M. Murray, P.E., Ph.D., and William A Thornton, P.E., Ph.D., published in Modern Steel Construction, April
2000 (available at www.modernsteel.com/backissues).
General Considerations connections. Essential parameters are permissible variations in
1) Design for serviceability first, then check strength. The overall depth, flange tilt, and the position of the web in the
emphasis for design should be on serviceability, constructability wide-flange shape. Recognizing these allowable variations
and design details, in addition to strength. from square and true will guide designers to design connec-
2) Communicate with fabricators, detailers and erectors. The tions that are complete and relatively easy to fit up. Allowance
EOR should consult with and listen to the fabricators, detailers, for the variations must be included in the connection design.
and erectors because they all have practical knowledge, gained in This is usually accomplished with gaps for shims, and oversized
the day-to-day experiences of putting together many projects. You, and slotted holes.
the engineer, should take advantage of this knowledge. Fabrica- 5) Keep the design simple. Simplicity of design avoids field
tors, detailers, and erectors often have excellent ideas and sugges- errors. Quoting Fazlur Khan, Strive for structural simplicity.
tions that will improve any project. By following their recommen- 6) Provide understandable plans. This will avoid detailing and
dations design costs often can be reduced by focusing your efforts field errors.
productively, thus increasing your profitability on the project as 7) Make sure the drawings show all requirements unique to the
well as those of the fabricator, detailer, and erector. project. This will avoid confusion and save you time in the end.
3) Read the AISC Code of Standard Practice. It is important 8) Indicate if camber is required. Do not specify camber if the
for you to understand the relationships among the parties to the required camber is less than in. Small camber amounts are not
design and construction process for structural steel. practical. Do not round up camber amounts, and use approxi-
4) Read ASTM A6. An understanding of steel mill production mately 80% of the calculated simple span camber because the
tolerances will play a major role in the design and detailing of end connections will provide some restraint.
steel frames and their connections. Designers should be famil- 9) Provide column schedules in the plans. Column schedules
iar with mill tolerances when selecting members and designing are the best way of presenting your column requirements.

{
Things You Should Know About Code of Standard Practice for Steel RCSC. The Research Council on Struc-
ASTM International. This organization, Buildings and Bridges. Also referred to tural Connections (www.boltcouncil.org)
formerly know as the American Society as the Code and COSP, this document publishes the Specication for Structural
for Testing and Materials, establishes is published by AISC and available as a Joints Using ASTM A325 or A490 Bolts.
standards for the manufacture and test- free download at www.aisc.org/code. That document is available as a freeload
ing of numerous materials including OSHA. Created in 1970, the Occupa- download at www.aisc.org/freepubs.
steel. ASTM A6, Standard Specication tional Safety and Health Administra- Specication for Structural Steel
for General Requirements for Rolled tion of the U.S. Department of Labor Buildings. Also referred to as the
Structural Steel Bars, Plates, Shapes, establishes and enforces workplace Specication, this ANSI-approved
and Sheet Piling, is available for pur- standards governing worker health and AISC document is updated every ve
chase at www.astm.org. safety. Regulations and other resources years and is available as a free down-
are available at www.osha.gov. load at www.aisc.org/freepubs.

30 MODERN STEEL CONSTRUCTION SEPTEMBER 2010


Welds and Welding
16) Make sure there is adequate access for welding. Very 21) Avoid the weld all around symbol. Welding all
embarrassing if you dont. See Figures 8-9 and 8-10 in the around may violate the AISC Specification, for example,
AISC Manual for guidance. causing undercut when the weld wraps around a cor-
17) Keep fillet weld sizes at or below 516 in. Larger weld sizes ner. Many times welding all around is not necessary for
generally require multiple passes and may require increased strength.
levels of inspection and thus add cost. 22) Avoid welding to galvanized surfaces. The galvaniz-
18) Use multi-pass fillet welds rather than groove welds. Fillet ing must be removed prior to welding and touch up with
welds require less preparation than groove welds and thus are less cold galvanizing compound is generally required. Special
labor intensive. They also may require less weld metal. ventilation is then required in the shop, and all of these
19) Weld on only one side of a piece if possible. There are many items add cost.
cases where weld is needed on only one side of a piece, for example, 23) Eliminate overhead welding. Overhead welding is dif-
column base plates and both transverse and bearing stiffeners. ficult. Horizontal and flat positions use the base metal to
20) Use intermittent fillet welds when possible. Weld volume support the molten weld pool and thus allow easier weld-
can be reduced using intermittent, rather than continuous, filet ing and promote higher quality.
welds; however, for fatigue situations intermittent welds will have
a lower fatigue life than continuous welds.

10) Use maximum practical column lengths. There are sev- If the floor framing is moment welded at the columns, the weld
eral splice heights that could be used in the design and erection shrinkage alone may be enough to make it difficult to erect the
of steel buildings. The most common and the preferred method upper levels of floor framing.
is the two-story tier. OSHA permits steel to be erected without 11) Make sure you indicate all of the structural steel work
netting so long as the distance to the platform below does not on the structural drawings, limiting reference to Architec-
exceed 30 ft. Using two-story tiers and decking the upper floor tural and M-E-P drawings to describe the work. This pro-
first, the decking crew is protected from falling objects. It also is vides clarity and will provide for the best bids on a project.
easier for the erector to stabilize the shorter columns as compared 12) Minimize changes. Changes cost everyone on a project
to a three-story tier. time and money.
The three floor per tier arrangement is nearly as unfavor- 13) Release for mill orders and detailing only when com-
able as a four floor per tier arrangement. One exception to this plete. If not complete, inform the architect, contractor and
is when the number of floors results in a single-story column fabricator of the areas that are not yet complete. This saves
at the top of the frame. One often sees a top level column 10 time and money. If you fast-track the project, plan on revisions
or 11 ft long due to this condition. Depending on the fram- and the extra cost of changes. See Section 3.6 of the AISC Code
ing arrangement, we often prefer to eliminate this last column of Standard Practice (COSP) for further material on this topic.
splice and elect to use a three-level tier, particularly if the col- 14) Answer the detailers questions promptly; this means
umn size is the same or nearly the same. This is with the full really fast. The EORs costs, just like those of the fabricator,
recognition that the top level of framing may take a little more detailer, and erector, are a function of the time spent on the
work to erect. project. Developing a structural system in which the fabricator,
There are advantages to starting with a one-story tier at the detailer, and erector are in sync can save significant coordi-
base of the frame, followed by two-story tiers, in that the effi- nation time after the release of construction documents. The
ciency of erection is the same as the two-story tier after the first EOR also can contribute to construction efficiency by review-
story is erected. In addition, the first story columns are gener- ing shop drawings and answering questions for the fabricator,
ally much heavier than the second story columns due to drift detailer, and erector in a timely manner. Remember Benjamin
control. Weight savings are possible when the base column is Franklins observation:Time is money.
a one-story tier. 15) Approve shop drawings in a timely manner. This allows
Four-story tiers should not be used unless absolutely neces- the fabricator to schedule the work in the shop most efficiently.
sary. It is very difficult to stabilize these long columns during The schedule for submittals and approvals should be estab-
erection and it is also difficult to adjust plumbness. Once the lished early in the project. See Section 4.4 of the COSP for
lower one or two levels are bolted or welded as the case may be, further material on this topic.

Steel Construction Manual,


also known as the Manual.
Now in its 13th Edition, it is
published by AISC. The Man-
ual features property tables
for U.S. rolled shapes and
includes numerous reference
documents, such as the AISC
COSP and Specication and
{
it will become a real struggle to get upper floor framing to fit.

James M. Fisher, P.E., Ph.D.,


and Michael A. West, P.E.,
AIA, are principals with
Milwaukee-based Computer-
ized Structural Design S.C.
This article is condensed from
the RCSC Specication. It material they presented at
is available for purchase at NASCC: The Steel Confer-
www.aisc.org/manual. ence in May 2010.

SEPTEMBER 2010 MODERN STEEL CONSTRUCTION 31


General Connection Considerations beam depth. Connection designs can be provided using con-
24) Time spent on connection design should be consistent nection tables; however, avoid the one size fits all approach. It
with time spent on analysis and member design. Remem- is not appropriate to say that all W14 beams should have a par-
ber that the majority of shop and field labor is in the connec- ticular connection. The size range of W14 beams is significant, as
tions. Approximately 30% of the cost of structural steel relates to is the case for many other nominal beam depths.
material costs. The rest is highly dependent on connection costs. 31) Avoid multiple linked tables. Tables should be referenced
Spend time thinking through the connections. back to the plan, where beam reactions are shown, so that the
25) Make framing decisions along with connection decisions. correct connections get matched to the right locations. Take care
For optimum connections the framing members must be com- to avoid presentation of the connection requirements in multiple
patible. You cannot select members and connections indepen- linked tables as this is simply an invitation to make an error. The
dently of one another. presentation of these connection designs or connection require-
26) Use field-bolted moment connections. This reduces cost, ments should be as straightforward as possible so that the detailing
because bolting is less affected by weather than welding. process can move forward in an orderly way. The documents must
27) If you are not designing the connections, show all reactions be presented in a clear fashion to minimize or eliminate errors.
on the drawings: axial, shear, moment, and transfer forces for 32) Group connection requirements by strength, not nomi-
the full set of forces in each load combination provided. This is nal beam depth. Connections always should be grouped by
a requirement of the COSP and will save time on the project. This strength and not by nominal beam depth. The tabulated connec-
topic is discusse in detail in Part 2 of the Manual. tions should be matched to framing by comparing the tabulated
28) Design connections for the actual forces. Designing for connection strength to the connection reactions shown in the
the actual forces can greatly reduce the cost of connections framing plans. For instance, a three-row double angle connec-
and reduce the number of RFIs. Designing to develop member tion with -in.-diameter bolts might correspond to some heavy
strength should be limited to those conditions required by the W12 beams, but also to some light W18 beams.
building code or the design. 33) Show beam reactions on the plans. This will result in opti-
29) Do not specify a percentage of the tabulated Maximum mum connection design, as described above.
Total Uniform Load. When beams are selected for service- 34) Use AISC standard details: Use of standard connections
ability considerations, minimum depth or shape repetition, the reduces costs and confusion. Typical connections are double-
uniform load tables will often result in far heavier connections angle (bolted/bolted or bolted/welded), single-angle (for beam to
than would be required by the actual design loads. This is an beam), single-plate (for beam to beam, both square and skewed),
unfavorable condition that can result in uneconomic structures. and shear end-plate (heavy skewed connections). Refer to Sec-
The uniform load tables also are inappropriate for relatively tion 10 of the AISC Manual.
short spans. Short spans have very high load capacities that often 35) Be aware of OSHA Subpart R rules for steel erection.
result in connections in excess of what would be required by the OSHA 1926.756(c)(1) prohibits double connections at columns
actual design loads. In short beams where the uniform design and/or at beam webs over a column where all the bolts are com-
load (UDL) method is specified, it is frequently necessary to mon to both connections, unless means is provided to secure the
extend webs and cope bottom flanges so that there is sufficient first beam erected from falling away when the second beam is
connection depth. All of this is inappropriate if one considers the erected. Figures 2-13 through 2-17 in AISC Detailing for Steel
actual design loads. Using the UDL method for girders is also Construction, Third Edition, provide common solutions that con-
a concern. Non-uniform loading may result in an end reaction form to the rule. If staggered connections are used, check that
greater than that of 50% of the total uniform load taken from the the T-dimension can accommodate the extra row of bolts. Other
Maximum Total Uniform Load Table from Part 3 of the AISC OSHA Subpart R rules are cited in this article and the complete
Manual. Likewise in composite beams, specifying either the end list is available at www.osha.gov.
reaction using the Maximum Total Uniform Load Table or per- 36) Show special connections. This reduces connection costs,
haps a percentage greater than 50% at each end may be inac- RFIs and provides clear requirements for the bidders.
curate in some cases. Using UDL is a shortcut that may result in 37) Provide moment envelopes for moment connection
girder and composite beam connections that are undersized with design. This reduces connection costs, RFIs, and provides clear
respect to the actual required loads. requirements for the bidders.
30) Avoid one size fits all connection tables for a nominal

Bolted Connections 49) Limit bolt grades and sizes. Fewer bolt sizes increases shop
47) Make sure that there is adequate access for bolting. Very efficiency in drilling and punching. Also, quality assurance is
embarrassing if you dont. See the AISC Manual Tables 7-16 and simplified with fewer bolt sizes and grades on a given project.
7-17 for entering and tightening clearances. 50) Use ASTM A325 bolts if possible. A325 bolts provide the
48) Limit bolt diameters to 118 in. Diameters of 34 in. or 78 in. best fastener value, because they are the most common.
are generally preferred. Diameters greater than 118 in. require 51) Use snug-tightened joints when possible. Do not specify
specialized equipment. Note that bolts larger than 1 in. require slip critical joints unless they are required. Remember that slip
increased edge distances and increased spacing between bolts. critical joints are perform tasks and require continuous in-
process inspection.

32 MODERN STEEL CONSTRUCTION SEPTEMBER 2010


38) Provide forces for braced frame and truss connection Member Design
design. This will result in optimum connection design. 54) Minimize the number of anchor rods per column (the OSHA
39) Maximize work requiring intermittent rather than con- minimum is four) and use simple arrangements. Increasing the
tinuous inspection. As codes and standards have evolved, the number of anchor rods in a base connection increases the odds
amount of third party inspection has increased. These inspections that there will be problems with the alignment of the rods and the
are in addition to the quality control work of the contractors and base plate holes. If possible use doubly symmetric arrangements.
can impose a significant burden on the project. The types of con- 55) Check that beams do not have to be severely coped, espe-
nections used will affect the amount of third party inspection work cially with both top and bottom copes. This occurs when deep
that has to be performed in the field and the associated costs. members frame into shallow members.
Inspection is covered in Chapter 17 of the International 56) Use materials that are readily available. If materials are
Building Code and in Chapter N of the 2010 AISC Specification not available long lead times are required. Consult with your
for Structural Steel Buildings. For a discussion of inspection local fabricator and the AISC website (www.asic.org) as to
terminology and requirements, see Quality Time, Modern material availability.
Steel Construction, March 2010 (available at www.modern- 57) Check for camber differences on adjacent members, espe-
steel.com/backissues). cially when adjacent parallel member ends are staggered.
40) Minimize work requiring continuous inspection. The This can cause severe deck installation problems.
opposite of the above. 58) Make sure members have sufficient width for elements
41) Watch out for W6 and W8 columns. The relatively small bearing on them. Very embarrassing if you dont. Joists should
inter-flange distance can cause connection problems. be aligned, not staggered at common supports so the deck layout
42) Dont require bolting and welding to the same member. is easier.
Fabricators prefer designs that will allow the material to flow 59) Run cantilevered roof beams over column tops whenever
continuously through the shop. That means your design should possible. This is a safety issue for erection. However, flange
not require welding to a column or a beam if the design also squareness on the beam is a concern that must be addressed.
requires drilling or punching holes in the same member. Drill 60) Have steel deck span all in the same direction if possible.
and punch lines are different lines than the welding lines and This reduces deck layout costs.
it costs money to transfer a column or beam from one line to 61) Avoid moment connections into the weak axis of columns.
another. The material will not flow smoothly through the shop Moment connections into the weak axis of columns can cause
if such transfers must be made. a multitude of field problems. The ratio of Ix to Iy makes rigid
43) Show all forces for a complete load path and try to provide an frames with weak axis columns very inefficient.
equilibrium condition at each joint. If you are not designing the 62) Use W12 minimum depth beams for floor framing. Use
connections, this will reduce confusion for the connection designer, W14 sections if the supporting girder requires a large cope on
because it permits a check for static equilibrium at a joint. the beam. This is recommended so the standard connections will
44) Transfer forces should include all drag strut forces and fit on the T-dimension of the web.
diaphragm connection details. These are of course necessary 63) Shop weld short cantilevers when possible. Cantilevers
for a complete design of connections. can be an erection safety issue because the cantilever is not fully
45) Consider modifying work points for extreme connection supported until the moment connection is completed. OSHA
geometry. This can greatly reduce connection costs. Extra column 1926.756(a)(2) requires that the minimum bolts for a cantilever
or beam steel may be required but overall a cost savings is gener- be evaluated by a competent person. Field welded cantilevers
ally recognized. Examples of this are moving truss end connection typically require shoring or some other type of support until the
work points to the face of the supporting columns and spreading flange welds are made. Either bolted moment connections or
truss web member end work points for ease of assembly. continuous beam construction is preferred for erection. Design of
46) Avoid through plates on HSS columns. Single plate shear bolted moment connections is more efficient when actual design
connections can be welded directly to the HSS face thus mak- loads are used instead of the default design requirement of full
ing it unnecessary to slot the HSS and insert a plate. See AISC Mp of the section. Short cantilevers can be welded directly to the
Steel Design Guide 24, available at www.aisc.org/epubs as a free column, completely eliminating the need for any field connec-
download for AISC members and for purchase by others. tion work. The only concern is whether or not the pieces can be
readily stacked and shipped. Of particular concern is that these
pieces are not symmetrical and not balanced about the column
centerline. Thus, the stability of these pieces during the erection
52) Minimize slip-critical connections. Limit slip criti- of the frame must be addressed by the erector.
cal connections to cases where they are required by AISC/ 64) Avoid beams with 4-in. flanges at:
RCSC, which include oversize holes or slotted holes not per- Spandrel beams with adjustable edge form.
pendicular to the load. See RCSC Specification, Section 4.3. Beams requiring bolted flange connections.
53) Use N type bolts rather than X bolts. This saves Locations where joists frame from each side.
detailing time and inspection costs. However if X bolts are 65) When using composite beams:
used, note that because the threaded length is constant for Use section stiffness to limit deflection and avoid large cambers.
each diameter (RCSC Specification Table C-2.1), a quick Use actual required percent of composite to limit studs.
check will determine the minimum ply thicknesses for the Avoid studs on infill beams parallel to deck ribs.
use of X bolts.

SEPTEMBER 2010 MODERN STEEL CONSTRUCTION 33


66) Design considerations for connections: 74) Repeat plate thicknesses rather
End plates may be limited by bolts or col- than using different thicknesses. This
umn flange bending capacity, but are effec- will simplify detailing and fabrication.
tive for frame stability during erection. 75) Repeat member sizes whenever pos-
CJP welds are a no brainer but gen- sible. Least weight is not least cost. This
erally more expensive. saves both detailing and fabrication time.
Top and bottom bolted flange plates are In addition, a larger order of the same size
an option if less than Mp is required, members may have a reduced cost.
but column flange squareness and per- 76) Consider making beams continuous
missible variations in beam must be and stacking columns when long can-
addressed in the details. tilevers are required. This will result in
67) Size columns to avoid reinforcement. simpler connections and will be fast and safe
This reduces fabrication costs. Use the to erect. However, flange squareness on the
AISC Clean Columns program available beam is a concern that must be addressed.
as a free download at www.steeltools.org. 77) Maximize prefabrication and shop
68) Use HSS when appropriate for tall work. This reduces costs.
columns. This will reduce costs particu- 78) Minimize field work. This reduces costs.
larly in one- and two-story structures. 79) Select members with favorable
69) Eliminate web penetrations if pos- (constructible) geometry. This accom-
sible; if unavoidable, design and locate modates connection design, fit up and
them in the construction documents. bearing requirements.
Unreinforced penetrations are preferred. 80) Limit galvanized members to 40 ft
Avoiding or standardizing unreinforced maximum. Most galvanizing tanks have a
web penetrations will reduce costs. maximum length of 40 ft. One can double
70) Repeat column base plate details, and dip but the overlap may be objectionable.
minimize thicknesses. This will reduce 81) Minimize the need for stiffeners
detailing, fabrication and erection costs. and doubler plates. (See also clean col-
71) Minimize the number of column umns, above.) This greatly reduces costs
splices. This will reduce costs. It is esti- (see table).
mated that one bearing splice requires
Estimated Steel Requirements for Stiffeners
roughly 500 lb of steel, and that one
moment splice requires about 2,000 lb 1 pair of llet welded stiffeners 300 lb
of steel. See previous discussion on two- 2 pair of llet welded stiffeners
600 lb
story vs. four-story tiers. (at top and bottom girder anges)
72) Reduce beam and joist spacing in 1 pair of groove welded stiffeners 1,000 lb
snow drift areas. This is less expensive 2 pair of groove welded stiffeners
2,000 lb
than changing the deck thickness. (at top and bottom girder anges)
73) Use beams rather than joists when 1 doubler plate 350 lb
many concentrated loads are present
or when concentrated load locations 82) Avoid members meeting at acute
are not known. Beams provide the best angles. When they do, it causes detail-
solution when concentrated load locations ing and connection design nightmares.
are not precisely known, or when concen- Use a header at an obtuse angle or skew
trated loads are likely to be relocated. the framing.
KCS-joists also may be effective, however,
additional webs may be needed.

Erection Considerations 87) Provide for construction tolerances


83) Provide permanent bracing that can in your design. Allow for mill and fabri-
be used as temporary bracing when cation tolerances by using shims and over-
possible. Saves the erector time and cost. size or slotted holes where required.
84) Provide straightforward connections 88) Check cumulative tolerances. Accu-
that can be erected without added mulation of tolerance variations can cause
temporary provisions. Saves the erector fit-up problems.
time and cost. 89) Check to see that the tolerances
85) Make sure that all beams can be specified match your expectations of
brought into place without inter- the final product. Know the tolerances
ference. Saves time and cost, and is a for all of the materials that connect to or
safety issue. abut the structural steel.
86) Make sure that all beams can be 90) Minimize the amount of loose
brought into place without having to material for details. This will save time
spread columns apart. Saves time and and cost.
cost, and is a safety issue.
34 MODERN STEEL CONSTRUCTION SEPTEMBER 2010

You might also like