302~307, 2006
Sung-Don Cho*
Abstract - The purpose of this paper is to develop an improved three-phase transformer model for
ATP and parameter estimation methods that can efficiently utilize the limited available information
such as factory test reports. In this paper, improved topologically-correct duality-based models are
developed for three-phase autotransformers having shell-form cores. The problem in the
implementation of detailed models is the lack of complete and reliable data. Therefore, parameter
estimation methods are developed to determine the parameters of a given model in cases where
available information is incomplete. The transformer nameplate data is required and relative physical
dimensions of the core are estimated. The models include a separate representation of each segment of
the core, including hysteresis of the core, -i saturation characteristic and core loss.
ATP offers two different transformer models. STC is a The use of an autotransformer makes it possible for a
built-in model. It is limited to single-phase or three-phase high power rating to be constructed as a single unit three-
banks made up of single-phase units. No mutual coupling phase transformer. To develop a model for a three-phase
between the phases can be taken into account. In addition, autotransformer, transformer physical design information
it is not possible to represent the differences between the and characteristic data are needed. However, it is most
positive and the zero sequence paths [1]. unusual to have a case where complete physical design
BCTRAN is the supporting routine of the EMTP information and dimensions are available. Often, all the
program, which creates an impedance or admittance matrix information that we have is what is on the nameplate, or
representation of the transformer, without taking into what is gleaned from the basic factory tests, if those are
account the saturable core effects, from transformer ratings obtainable.
and factory test data. In this model, it is possible to Typical transformer factory test reports available from
represent the differences between the positive and the zero manufacturers consist of data much like what is presented
sequence paths. However, unequal phase reluctances and in Table 1. The available data are kW losses and true RMS
nonlinear interactions between limbs of the core cannot be exciting current at 100% and 110% of the rated voltage.
taken into account [1]. There is no information on transformer core dimension,
Topologically-correct equivalent circuit models can be core material, etc. It should be noted that the RMS
derived from magnetic circuit models using the principle of exciting current taken from factory tests is actually the
duality. This type of model includes the effects of average of the three measured RMS phase currents.
saturation in each individual leg of the core as well as
leakage effects. The equivalent circuits resulting from Table 1. Transformer Test Data
duality transformations are topologically correct lumped- 345000 Grd.Y/118000 Grd.Y/13800 Delta,
parameter representations [2]. Duality-derived models can 3-phase auto-transformer @OA/FOA/FOA
be implemented with standard EMTP elements. However, H-296/394/490MVA, X-296/394/490MVA, Y-
practical application of this model for a three-phase 77/103/128MVA
Open-Circuit Exciting Current No Load Loss
transformer has been hampered by some difficulty in
Test 0.76%@100%V 297.6kW@100%V
obtaining the required model parameters.
1.71%@110%V 402.24kW@110%V
Short-Circuit
Impedance Load Loss
Test
H-X 6.21% @296MVA 378.94kW
@296MVA
* Plant Engineering Team, Samsung Corporation, Korea.
(sungdon.cho@samsung.com)
H-Y 55.9% @296MVA 258.76kW @77MVA
Received: December 1, 2005 ; Accepted: April 12, 2006 X-Y 42.1% @296MVA 237.68kW @77MVA
Sung-Don Cho 303
3. Duality-Based Model
MMF-C
MMF-C
MMF-S
MMF-S
MMF-S
MMF-T
MMF-T
MMF-T
RSC
RSC
RCT
RCT
RTL
RTL
L4 A4 L5 A5 L6 A6
1(k)=v1 /( N) sin(k/40) and 2(k)=v2
L9 L7 L8 L10
A9 A7 A8 A10 /(N)sin(k/40-2/3)
L1 A1 L2 A2 L3 A3
B1(k)=B4(k)=B9(k)= 1(k)/A1 and B7(k)= (1(k)-
2(k))/2/A7)
1 b B1 ( k ) and 1 b B7 ( k )
Notation: A: Area, L: Length, Typical Area ratio: A1~A3=1, 1 ( k ) = 7 ( k ) =
a a
A4~A6=0.5, A7~A8=0.87, A9~A10=0.5, Typical Length ratio:
L1~ L6=1, L7 ~L10=0.67
Fig. 4. Dimension of Shell-form Transformer R1(k) =L1 /(1(k) A1) and R7(k)=L7 /(7(k)A7)
R1 i1 R2 i2 R3 i3
Fig. 5. Magnetic Equivalent Circuit
Minimize f(a,b)=
i1= 1(R1+R4+R9)+R7 (1-2) (1)
[Measured I AVG ,RMS @ 100 %V Calculated I AVG ,RMS @ 100 %V ] 2
10 10
aB (5)
1.8
1.6
Pn ( Bn ) An Ln = 1 b nB An Ln
n =1 n =1 n
1.4
0.8
Minimize f(a,b)=
0.6 2 2
10 10
a Bn a Bn
0.4 P@100%V An Ln + P@110%V An Ln
n=1 1 b Bn n=1 1 b Bn
0.2
Subject to inequality constraints 0 < a and 0 < b < 1
0
0 50 100 150 200 250 300 350 400
H (A / m )
Fig. 6. B-H for Each Section Thus, a= 7071.8 and b =0.4272 are calculated for the
core saturation curve by using the optimization technique.
120
In this case, there is only a minor difference [0.0152
100 0.0112] W between the given core loss and the calculated
core loss. If the ratio() of PH to total core loss and the
80
ratio () of PE to total core loss given to define the
Lambda (Wb-t)
60
frequency-dependent effects of core loss, the equivalent
resistance (RE) for PE is:
40 Leg
M id Lim b
O uter Y ok e RE = V2/(PEAL) = (V @ B)2 / [(PC @ B) (AL)] ()
20
(6)
0
0 50 100 150 200 250 300 350 400
i (A m pere) In [6], the equation for DC hysteresis loss was given as
Fig. 7. -i Magnetization Curves for Each Section Equation (10). From the core loss separation, aa and bb
are obtained.
200
150
aa BMAX
100 PH ( BMAX ) = PC ( BMAX ) PE ( BMAX ) =
1 bb BMAX (7)
50
Line-A
Ampere
0 Line-B
Line-C Fig. 9 shows each core loss curve for the shell-form
-50
transformer.
-100
-150
1.8
-200
0 1 2 3 4 5 6 7
1.6
Radian
0.8
For the detailed model, separation of the core losses is: Fig. 9. Core Loss Curve using Frolich Equation
PC(core loss) = PH(hysteresis loss) +PE(eddy current
loss) The right displacement in the hysteresis loop is linear
and the left displacement is nonlinear in [6]. At zero flux,
From test data, average core losses at 100% voltage and both displacements must be the same and this is a coercive
110% voltage are given as [297600, 402240]W at = force (HC). The coercive force at each loop should be
[51.77, 56.95]Wb-t. determined to meet the power loss PH at the Bmax for each
The calculated average core loss should be: loop.
306 Three-phase Transformer Model and Parameter Estimation for ATP
The displacements at each loop are shown in Figure 10. The simulated results using the model developed here
2
are reasonable and more correct than those of the
BCTRAN-based model. Simulation accuracy is dependent
on the accuracy of the equipment model and its parameters.
1.5
This work is significant in that it advances existing
parameter estimation methods in cases where the available
B (T)
50
5. Conclusion 25
-50 *10 - 3
is shown in Fig. 3. Fig. 11 displays the DC hysteresis loop 0 10 20 30 40 50
(f ile TESTTRS.pl4; x -v ar t) c :LEG2 -N99999 c :LEG7 -BBBBBB
modeled using a Type-60 current source controlled by
TACS. Fig. 12 illustrates the current of the eddy current o: Leg-1 : Mid Limb A-B at 100%V
loss and the resistive hysteresis current. Fig. 13 shows the Fig. 13. Mangnetizing Current Waveforms of Leg 2 and
magnetizing current modeled with a Type-93 nonlinear Mid Limb A-B (Leg-7)
inductance. Fig. 14 and 15 show the line-current and
200
winding-current waveforms. 100
To verify the transformer model developed using TACS, 0
the transformer test report. After all models were -200 *10 -3
0 10 20 30 40 50
implemented and run with ATP, the results of open-circuit (file TESTTRS.pl4; x-var t) c:A138F -A138T c:B138F -B138T c:C138F -C138T
and short-circuit simulations are very close to the test o: Line-A : Line-B : Line-C
report. Fig. 14. Line Current Waveforms for Tertiary at 100% V
1. 6 200
1. 2 100
0
0. 8
-100
0. 4
-200 *10 -3
0. 0 0 10 20 30 40 50
(file TESTTRS.pl4; x-var t) c:A138T -XX0103 c:B138T -B-T c:C138T -C-T
-0. 4
o: Phase-A : Phase-B : Phase-C
-0. 8
Fig. 15. Winding Current Waveforms for Tertiary at 100% V
-1. 2
-1. 6
-4 -2 0 2 4
(f ile TE STTR S .pl4; x -v ar t: LE G 1) t : B 1
References
Fig. 11. DC Hysteresis Loop Generated by ATP
4
[1] H.W. Dommel, EMTP Theory Book, Bonneville
2
Power Administration, Portland, USA, August 1986.
0
[2] G.R. Slemon, Equivalent Circuits for Transformers
-2 and Machines Including Non-Linear Effects,
-4
0 10 20 30 40 50
Proceedings Institution of Electrical Engineers, Vol.
*1 0 - 3
(f ile TE S TTR S . p l4 ; x -v a r t ) t : E D D Y 2 t: H Y SC 2
100, Part IV, 1953, pp. 129-143.
o: iE : iH [3] Working Group C-5 of the Systems Protection
Fig. 12. Eddy Current(iE) and Hysteresis Current(iH) Wave- Subcommittee, Mathematical models for current,
forms at 100%V