Professional Documents
Culture Documents
P A C K A G E User Manual
Version 2.2
OMICRON Test Universe
2
Table of Contents
Table of Contents
1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1.1 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
1.2 Scope of Advanced Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2 Advanced TransPlay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
2.1 The Advanced TransPlay Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.1.1 Detail View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.1.2 Time Signal View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
2.1.3 Measurement View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
2.1.4 Report View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.2 Example:
Distance Relay with a Transient Playback . . . . . . . . . . . . . . . . . . . . . . .21
2.2.1 Wiring Between Protection Relay and CMC . . . . . . . . . . . . . . . .22
2.2.2 Starting Advanced TransPlay from the OCC . . . . . . . . . . . . . . .22
2.2.3 Setting up the Test Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
2.2.4 Configuring the Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.2.5 Defining the Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
2.2.6 Running the Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
2.2.7 Defining the Test Report Format . . . . . . . . . . . . . . . . . . . . . . . .27
3 Advanced Distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.1 Advanced Distance Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.1.1 Shot, Search and Check Test Modes . . . . . . . . . . . . . . . . . . . . .29
3.1.2 Relative Test Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3.1.3 Constant Source Impedance Model . . . . . . . . . . . . . . . . . . . . . .32
3.1.4 Load Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3.1.5 Testing Multiple Fault Loops in one Test Module . . . . . . . . . . . .32
3.1.6 User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
3
OMICRON Test Universe
4
Table of Contents
5
OMICRON Test Universe
6
Table of Contents
7
OMICRON Test Universe
8
Introduction
1 Introduction
The OMICRON Test Universe Advanced Protection manual is an add-on
manual to the OMICRON Test Universe Protection manual. It describes all
components of the Advanced Protection Package that are not already
documented for the Protection Package. It includes general information about
the additional test modules as well as one or more specific test examples using
those test modules.
Full scope of
Advanced
= +
Protection
Protection Advanced Protection
P A C K A G E P A C K A G E
9
OMICRON Test Universe
1.1 Preface
We assume that you understand and are comfortable using the Windows
operating system1. Please take time to become familiar with your computer's
operating system before using OMICRON Test Universe.
This manual uses the following conventions:
Mouse
Click Press and release the primary mouse button. The primary
mouse button is the button you use most often. For most
people, this is the left mouse button.
Right-click Press and release the secondary mouse button. The secondary
button is the button you use least often. For most people, this is
the right button.
Double-click Press and release the primary mouse button twice.
Drag Move the mouse while you hold down the primary mouse
button.
Release Remove your finger from a mouse button.
Scroll Scroll bars along the right and bottom sides of a window can be
used to move the contents up and down and left and right within
the window. To use a scrollbar, either click and hold one of the
arrow buttons at either end of the bar, or drag the scroll bar
slider.
10
Introduction
Test modules
Advanced TransPlay Universal tool to import, edit, and output transient data
to a test object.
The transient data files were created from real or
simulated fault occurrences beforehand and are
available as a data file in either COMTRADE, PL4 or
TRF format.
The main application area is the reproduction of real
fault occurrences. The fault occurrences recorded with
the integrated fault recorder of the protection device are
transmitted to a PC and stored in a corresponding file
format.
11
OMICRON Test Universe
12
Advanced TransPlay
2 Advanced TransPlay
Advanced TransPlay is used to import, edit and output transient data to a test
object. These transient data were created from real or simulated fault
occurrences beforehand and are available as a data file.
The main application field is seen in the reproduction of real fault occurrences.
The fault occurrences recorded with the integrated fault recorder of the
protection device are transmitted to a PC and stored in a corresponding file
format.
Of course, this data may also originate from another source than a fault recorder
as long as is is available in a compatible file format.
The following file formats used to import transient signals are supported:
Comtrade format with the following files:
- CFG: COMTRADE configuration file for the description of the failure
report channels (signal names, sample frequency etc.)
- DAT: COMTRADE file with the sample values of the failure report
channels.
- HDR: "Header file", that contains any data-related text that is not used
by the software.
L4 format with a PL4 file
TRF format with a TRF file
A detailed description about the supported file formats can be found in the
Advanced TransPlay online help under the table of contents entry "File Formats
and Size".
Using this data, a protection device can be optimally tested and adjusted under
real operation conditions.
Advanced TransPlay is also a suitable tool for testing protection devices (e.g.,
with simulated data) during the process of development.
The data output is started either via an external trigger (e.g., GPS), via binary
inputs, by pressing a key or immediately after pressing the S T A R T / C O N T I N U E
button.
Afterwards, the reaction of the test object is compared with given nominal values
or binary signals (reaction saved in the data record or user-defined) and
assessed in the test report.
13
OMICRON Test Universe
Detail View
Measurement View
Report View
All settings necessary for the test are made in the Detail View. In the Detail View
the transient analog signals are routed individually to the analog CMC output
channels, the binary signals are interconnected and the trigger conditions are
defined.
The Time Signal View is active after loading (importing) a data record. This view
displays the transient current and voltage signals and the binary signals, if
available.
It is now possible using Advanced TransPlay to edit this data record and to adapt
it for the planned test. Any time sections can be repeated (e.g. to extend the
prefault time), state transitions can be marked, and new binary signals can be
inserted.
The nominal values for the time measurements are defined in the Measurement
View. During the test, each measurement condition is analyzed for the
observance of the tolerances and assessed with "Passed" or "Failed".
The test results are displayed in the Report View. The contents of the Report
View can be either defined by the user or standard default settings can be used.
14
Advanced TransPlay
Analog Outputs
The Analog Outputs tab contains a table for setting the output magnitudes of
the available generators.
This table has five columns: Signal, Channel, Scale, Minimum, and Maximum.
Each line corresponds to one used analog output.
After loading a data file, the table is filled with the information stored in the data
record. The signals are routed to the analog outputs of the CMC on the basis of
the signal names. This assignment can be changed at any time. The Scale
column can be used to increase or decrease the voltage and current values that
are to be output. The result of the scaling is displayed in the Minimum and
Maximum fields.
Binary Outputs
The Binary Outputs tab shows the available binary outputs (as defined in the
hardware configuration) and what is interconnected with the binary signals.
Trigger
The Trigger tab defines the start conditions for the output of the transient
signals.
15
OMICRON Test Universe
Figure 2-1:
Validity of trigger Test start
conditions
Test 1 Test 2 Test 3
General Tab
The General tab contains specifications for the entire test, such as the number
of test repetitions and the time between the individual test repetitions.
Additionally, the sampling rate can be specified with which the transient signals
are output.
16
Advanced TransPlay
Cursor Slider
The sliders act as anchor points for the measuring cursors. In addition they are
used to move the cursor horizontally along the time axis. This is done either by
using the cursor arrow keys of the PC keyboard or by clicking and dragging with
the mouse to the position of your choice.
If you prefer to use the cursor arrow keys on your PC keyboard, use the <Tab>
key or <Shift> + <Tab> to switch between the cursor sliders.
17
OMICRON Test Universe
Data Markers
In the Original mode repetition type data markers can be defined and displayed.
The data markers are represented by vertical lines in the diagram and with their
names in the state diagram. The representation of the lines can be individually
defined by the user.
State Markers
State markers are defined in the Expanded mode. As with the data markers,
they are depicted by vertical lines and their names.
18
Advanced TransPlay
19
OMICRON Test Universe
In the second table, binary signals are used for time comparison (Table 2-2).
If the start condition and the stop condition are the same a measurement of 0 s
is recorded. It is not searched for a second appearance of a condition, i.e. the
time between the first and the second 0 -> 1 transition of a binary signal is not
measurable; the first 0 -> 1 transition fulfills both measurement conditions. In
order to measure such a condition the cursor measurement function in the Time
Signal View can be used.
Table 2-2:
Additional terms in the Additional terms in the measurement table 2
measurement table 2
Signal Binary signal which is to be played back in order to be
compared with the reference signal. Here, all the binary signals
which are set in the HCC dialog are available.
Reference Binary signal from the data record or self-defined signal which
signal serves as a reference for the comparison with the signal to be
played back.
Tact Here the measured time for the edge change of the played
back signal is entered. The edge change time with the
maximum deviation in relation to the reference signal is
entered for binary signals with several edge changes.
Tdev The (greatest) measured deviation of Tact in relation to Tnom
(this value can be either positive or negative).
20
Advanced TransPlay
2.2 Example:
Distance Relay with a Transient Playback
Sample files:
AdvTransPlay-Transient_Playback.tra
AdvTransPlay-Transient_Playback.occ
Comtrade Example.cfg
Comtrade Example.dat
Stored at: ...OMICRON Test Universe installation path\
Test Library\Samples\SW Manual Examples\Advanced Protection
Task
A distance relay is to be tested with a transient "play back" test. The test file is
in COMTRADE format (Comtrade Example.cfg) and was created from a
fault recording. The prefault time should be extended to at least one second.
Also a measurement condition for the trip signal of the relay should be defined.
9 Solution
The OMICRON Test Universe offers a dedicated test module Advanced
TransPlay to "play back" any transient fault recording or simulation. This is the
only module that can fulfill the above task completely.
Assuming that this transient "play back" test is to become part of a complete
automatic test for a distance relay, this test module will be embedded into a test
document for the OMICRON Control Center.
If this test is a once-off test, the Advanced TransPlay module could also be used
in a stand-alone configuration, i.e. without the Control Center.
21
OMICRON Test Universe
1. Connection of the CMC to the parallel port of the PC for data exchange:
Output of the data for simulation, loading of the binary signals.
2. Connection of the analog outputs of the CMC to the transducer inputs of
the test object in order to read out the simulated currents and voltages.
3. Connection of the binary outputs and transistor outputs of the CMC to the
binary inputs of the test object to read out binary signals to the test object.
4. Connection of the binary inputs of the CMC to the binary outputs of the
test object to load the binary signals of the test object (therefore the
reactions to the output data).
22
Advanced TransPlay
23
OMICRON Test Universe
24
Advanced TransPlay
5. Specify 50 repetitions.
Note that the value for "Time" and "Duration" is automatically entered from
the present position of the markers.
Figure 2-5:
Defining the signal to be
repeated
6. Click O K .
7. Select "expanded" as display mode (1).
Figure 2-6:
Complete signal with
prefault extended
25
OMICRON Test Universe
) This function enables the definition of any signal to be measured: From, To, the
nominal trip time and the deviation in the negative and positive direction. The
actual measured "trip" time, actual deviation and the assessment will be shown
after a test has been performed.
26
Advanced TransPlay
) The trip signal measurement together with an assessment will be shown in the
Measurement View.
) Note that if the signal has been zoomed, it will also be shown in this zoomed
state in the Report View.
27
OMICRON Test Universe
28
Advanced Distance
3 Advanced Distance
Advanced Distance is used for comprehensive element evaluations in different
automatic testing modes (Shot, Search, Check) in the Z-plane with graphical
characteristic display. Allows standard test templates with relative test points to
test any distance relays setting.
29
OMICRON Test Universe
Search Test
At a Search Test, zone reaches are determined automatically. Zone transitions
are searched along search lines specified in the impedance plane, using an
optimized algorithm. It is possible to define a series of search lines in a single
step. All defined search lines are stored in a table for automatic processing.
Figure 3-2:
Advanced Distance -
Search Test
30
Advanced Distance
Check Test
At a Check Test, test points are automatically set at the tolerance boundaries of
zones. The setup is done with test lines (check lines) similar to a Search Test,
but test points are only set at the intersections of the check lines with the zone
tolerances. The Check test is an efficient overall test of the relay with minimum
testing time. This gives a quick verification of whether the specifications are met,
particularly for routine tests.
Figure 3-3:
Advanced Distance -
Check Test
Adding test points and test lines to the tables is possible in a variety of ways.
Parameters can be precisely defined by numerical inputs, or specified by
pointing to certain locations in the characteristic diagram. A magnetic cursor
supports the choosing of useful values. Mouse commands, context menus and
keyboard shortcuts facilitate data input.
A test in Advanced Distance can have any combination of Shot, Search, or
Check tests. At test execution, the whole test settings are processed
sequentially.
This versatile system offers a wide range of testing possibilities. Using this, it is
easy to comply with testing philosophies and regulations.
31
OMICRON Test Universe
32
Advanced Distance
Test View
This view holds the test point tables for the Shot, Search, and Check tests and
the impedance plane. Test definitions are made in this view. During and after the
test execution, this view displays the results numerically in the tables and
graphically in the impedance plane.
Z/t Diagram
This view shows the graded trip time curve over the impedance along a certain
line. The actual line is determined by pointing in the impedance plane or by a
selection in one of the test tables. It is also possible to define test points and view
the assessments in the diagram.
Vector Diagram
The vector diagram shows the phasors of the voltages and currents, both for the
phase quantities and the sequence components. The corresponding numerical
values are displayed in the attached table.
33
OMICRON Test Universe
Task
A Siemens 7SA511 distance relay is to be tested. The automatic test should:
Perform a Shot Test at 50% in Zone 1 as well as 75% in Zone 2 and 3 on
the line angle for all fault loops.
Verify the reaches on the line angle to be within the tolerance limits for all
zones and for all fault loops.
Determine the exact reach of the relay on the reactive and resistive axis
for all zones for an A-N and a B-C fault.
The Siemens 7SA511distance relay has several settings that are given.
General Settings:
Inom: 1A
Vnom: 110 V (L-L)
fnom: 0 Hz
Line angle: 60
Re/Rl: 0.9
Xe/Xl: 0.9
Potential Transformers are connected on busbar
Current Transformer starpoint is on line side
34
Advanced Distance
9 Solution
The OMICRON Test Universe offers a dedicated test module - Advanced
Distance - for testing the impedance measurement function of distance relays.
This module models the transmission line protected by a distance relay. It is
recommended that this module be used to test the distance function. A manual
test of this function is possible, but can prove to be very laborious and time
consuming.
Individual fault shots can be placed anywhere in the impedance plane with the
single shot. The Check Test places shots at the impedance tolerance limits of
each zone to verify that the reach is within the tolerance limits. The exact reach
can be determined with the Search Test.
Because an automatic test should be carried out, use the OMICRON Control
Center so that the test can then be integrated with the tests for all the auxiliary
functions of a distance relay (e.g., Fusefail [or LOP], Manual Close [or SOTF],
Auto-reclose, Powerswing detection, etc.)
The Advanced Distance module could also be used stand-alone.
35
OMICRON Test Universe
36
Advanced Distance
37
OMICRON Test Universe
2
3
4
38
Advanced Distance
39
OMICRON Test Universe
40
Advanced Distance
Figure 3-7:
Characteristic Editor for
the test object
parameters
3. Click the predefined shape for quadrilateral characteristics (fig. 3-7, 1).
4. Enter the settings for the first line element. The directional line in the fourth
quadrant: R = X = 0; angle = -45.
The line element selected is highlighted in the graphic.
Line elements are defined by an angle from the horizontal plus any point in
the R/X plane through which the line passes. This point can either be entered
in Cartesian or polar co-ordinates.
5. Enter the second line element, which is the resistive blinder:
R = 1.25 ; X = 0 ; Angle = 90.
Note: Always enter the line elements in a counter-clockwise fashion around
the characteristic. Tip: draw the expected characteristic on paper before
entering it into the software.
6. Enter the third line element, which is the reactive blinder:
R = 0 ; X = 2.5 ; Angle = 0.
7. Enter the fourth line element, which is the resistive blinder in the third
quadrant: R = -1.25; X = 0; Angle = 90.
8. Click O K .
41
OMICRON Test Universe
Figure 3-8:
Zone Settings page in
the Distance
Protection Parameters
dialog box.
The zone settings for
the first zone and the
1 3 2
tripping zones are
entered
42
Advanced Distance
43
OMICRON Test Universe
44
Advanced Distance
1 3
1. Specify the test model "Constant test current" with a test current of 2A.
Please refer to the online help for more detailed information on the test
models available.
2. Specify the fault inception mode as "random" with "DC-Offset" cleared. Again
refer to the online help for more detailed information on this function.
3. Specify the test times:
- Prefault = 0.5 s
- Max. fault time = 4 s
Ensure that the maximum fault time is set longer than the slowest tripping
element of the relay.
- Postfault = 0.1 s
This setting might have to be increased for electromechanical relays, to
allow the relay to reset properly and to cool down.
45
OMICRON Test Universe
46
Advanced Distance
The column width of the test point table can be adjusted by dragging the split
bar in the column header.
Figure 3-12: o
47
OMICRON Test Universe
48
Advanced Distance
Figure 3-13:
Check Test View
49
OMICRON Test Universe
50
Advanced Distance
51
OMICRON Test Universe
Z/t diagram
In this view, the trip time is plotted vs. impedance for any specified test line. The
stepped time grading characteristic of the relay can clearly be seen. The
impedance and time tolerance bands can also be identified.
Tests can be executed from this view graphically in the same way as for a Shot
Test.
Figure 3-15:
Z/t diagram
52
Advanced Distance
53
OMICRON Test Universe
54
Advanced Distance
Task
A Distance relay requires the circuit breaker status to perform correctly.
9 Solution
The test set CMC 256 offers a CB simulation, which emulates the action of the
auxiliary contacts (52a / 52b) of a circuit breaker during tripping and closing.
The test Module CB Configuration is used to set up the parameters and the
mode of operation for this CB simulation. Its intended use is for protection
testing, whre certain relays need feedback from a CB for proper operation of the
protection function.
The Advanced Distance test module serves to test the impedance measurement
function of distance relays. This module models the transmission line protected
by a distance relay. It is recommended that this module be used to test the
distance function. A manual test of this function is possible, but can prove to be
very laborious and time consuming.
Individual fault shots can be placed anywhere in the impedance plane with the
single shot. The check test places shots at the impedance tolerance limits of
each zone to verify that the reach is within the tolerance limits. The exact reach
can be determined with the search test.
Because an automatic test should be carried out, use the OMICRON Control
Center so that the test can then be integrated with the tests for all the auxiliary
functions of a distance relay (e.g., Fusefail [or LOP], Manual Close [or SOTF],
Auto-reclose, Powerswing detection, etc.).
The Advanced Distance module could also be used stand-alone.
55
OMICRON Test Universe
56
Advanced Distance
Figure 3-20:
Binary Outputs
57
OMICRON Test Universe
58
Advanced Distance
59
OMICRON Test Universe
1 2
60
Advanced Differential
4 Advanced Differential
The Advanced Differential software is a family of test modules for testing
differential protection relays. Specific test modules were developed to test
specific features of a differential relay: Diff Configuration, Diff Operating
Characteristic, Diff Trip Time and the Diff Harmonic Restraint.
The Advanced Differential modules are typically used from within the OMICRON
Control Center (OCC). The test modules are embedded as objects into the OCC
test document.
Relay
The OCC test document allows multiple modules to be controlled together with
sequential testing of the chosen protective functions. For example, all common
settings for a specific device can be controlled globally and do not have to be
entered for each successive test module.
The OCC test document provides the tests results and format of the data to be
contained in the test report. This allows creation of a customized report that
includes the test data, graphics, text fields and text editing by the user.
Once the test document is complete, the OCC will run the embedded tests and
automatically include the results in the report.
The test document provides two functions:
the test specifications or protocol, and
the report format.
All test data is captured and maintained so the report format can be easily
changed, saved, and reused at any time, thus making summary reports and
detailed reports available from the same document.
61
OMICRON Test Universe
4.1 Overview
All differential modules have a similar user interface and can be easily
understood as soon as one of the modules has been learned. All differential
modules use the same dialog for setting the parameters of the protection device,
the protected object, and other relevant system settings. The settings data is
managed globally and made available to each of the test modules.
The test modules differ from each other by the types of characteristics that are
tested with the particular module.
Configuration
Operating Characteristic
Trip Time Characteristic
Harmonic Restraint
62
Advanced Differential
63
OMICRON Test Universe
64
Advanced Differential
Task
A tester has the task to perform a secondary test during commissioning of the
transformer differential protection SEL 587 in the substation Center of the Power
Supply XYZ Corporation. This is the main protection for the transformer working
in bay = T01, as shown in the figure below.
The CMC 156 test set and the CMA 156 six-phase current amplifier are
available as test equipment.
Relay
For our example, a typical delta-wye power transformer will be considered. This
protected object defines our testing task when the protection relay and its
settings are applied. Care must be taken in the test setup due to the individual
relay manufacturers setting parameters. These details make for a successful
test.
65
OMICRON Test Universe
66
Advanced Differential
Figure 4-1:
Background to the
shape of the operating I_Diff / I_N
characteristic.
3
M agnet izat ion
The operating Load t ap changer
characteristic which is to Int erposing transf ormer
be set in the differential Dif f _sum
charact eristic
relay must lie above the
operational differential 2
sum characteristic.
Tripping range
Blocking range
1
0
0 2 4 6 8 I_Bias / I_N
Trip times
The testing and documentation of the trip times of the differential protection
working as the main protection on the transformer is necessary under all
circumstances.
Use the Diff Trip Time Characteristic test module.
67
OMICRON Test Universe
110KV
B/L2
2windings Y
Nyn0 25MVA
12.2 0
Final values
1.000 V
3.200 A
C/L3
68
Advanced Differential
In this example we want to import the test object parameters from a file.
69
OMICRON Test Universe
70
Advanced Differential
Table 4-1:
Vector group Object Type Setting Phasor Reference
terminology
HV LV HV LV HV LV
D 0 Y 0 D Y0 0 0
D 0 Y 30 D Y1 0 30 lag
D 0 Y330 D Y 11 0 30 lead
The selection of the single-phase fault type in a test module does not mean that
a ground current (zero-sequence current) is simulated correctly. Indeed, the
parameter Starpoint Grounding is critical here. This means that a zero-sequence
current can only flow in a winding if the starpoint is effectively grounded to
the selected fault side for the Diff Configuration module
the reference side of the Diff Operating Characteristic or the Diff Trip Time
module.
Figure 4-4:
Single pole error and
current distribution with
a grounded starpoint.
Figure 4-5:
Single pole error and
current distribution with
a non-grounded
starpoint.
In the second case, it is assumed that the zero sequence current comes from
the other side, meaning that the circuit is grounded at the other point.
71
OMICRON Test Universe
When the option for "Use Ground Current Measurement Inputs" is selected, the
zero sequence current for each winding is simulated on the configured current
output.
Enter the nominal values of the ground current transformer, if these are
connected to the relay, the zero sequence current is measured from the
differential relay, and the zero sequence current is used in the calculation.
Note: One transformer starpoint has to be grounded in order to check the box
for the ground current measurement input.
72
Advanced Differential
73
OMICRON Test Universe
Figure 4-7:
Protection Device List box for the Ibias calculation Reference Winding is the winding used for the
page of the Differential of the protection device test current reference calculation of Idiff and
Protection Parameters Ibias pairs. This is for testing the operating
dialog box characteristic and the trip time characteristic;
the fault will always be placed on this side.
Maximum duration of test currents being output, if the differential relay does not trip.
Delay Time is the time between two automatic test steps or shots.
Reference winding:
The currents measured by differential relays are different in their absolute value
and phase under normal operation and cannot be used directly for the
calculation of the Idiff and Ibias values.
Therefore, the protection relay has to define a reference winding to normalize
the currents to the same phase shift and eliminate the zero-sequence current.
In order to be able to test the operating characteristic this reference has to be
defined to the test module.
In principle, it makes no difference which side of the transformer is defined as
the reference side, but the current distribution in the single phases and their
absolute values and phase shifts are different for each reference winding
depending on the vector group for single-phase and two-phase faults.
74
Advanced Differential
Figure 4-8:
Measured currents with
nominal operation
Ibias Calculation:
The Ibias quantity - sometimes referred to as the stabilizing or restraint quantity
- is used to compare against the Idiff quantity for the tripping decision. The
calculation method for this quantity Ibias has to be determined from the relay
manufacturer and cannot be set arbitrarily. Knowing this setting is of critical
importance for the test of the operating characteristic.
Note: Presently, only relays can be tested that calculate the Ibias and Idiff values
from currents which are zero-sequence and vector group compensated.
Table 4-3:
Calculation methods for Method Manufacturer
the biasing quantities
Siemens K1 = 1,
( Ip + Is )
---------------------------
K1 GEC, SEL K1 = 2
AEG K1 = 2
( Ip + Is )
--------------------- AEG three-winding K1 = 3
K1
conventional relays K1 = 1
GE Multilin SR 745 K2 = 1
( Ip + Is K2 )
-----------------------------------------
K1 K1 = 2, three-winding K1 = 3
75
OMICRON Test Universe
Standardize Using:
The absolute value (standardization) of the currents to be compared takes place
at the protected object nominal current or the current transformer nominal
current of the most powerful winding (depending on the relay manufacturer).
InomInterposingTransformer
-------------------------------------------------------------------------------
InomTransformer
Note: These parameters are essential and have to be determined from the relay
manufacturer if they are not known. Arbitrary specification leads to undefined
results.
Figure 4-9:
Measured currents for
nominal operation of a
delta winding
transformer.
76
Advanced Differential
Figure 4-10:
Connection of the test
devices to a
conventional differential
relay with symmetrical
bias winding and test
with deactivated
transformer model
77
OMICRON Test Universe
Figure 4-11:
Zero-sequence
elimination IL-I0,
reference side = primary
side (HV)
In the primary winding
flows a zero-sequence
current.
( I L1 + I L2 + I L3 )
Zero-sequence current: I 0 = -------------------------------------------
-
3
From this, the following calculated phase currents I L are obtained for the
differential values:
3 31 2
primary (HV): I LP = 0 --> I' LP = 0 1 = 1
0 01 1
2 20 2
secondary (LV): I LS = 1 --> I' LS = 10 = 1
1 10 1
0
Id iff = I' LP + I' LS = 0
0
4
I sta b = I' LP + I' L S = 2
2
78
Advanced Differential
Note: Because of the selected type of zero-sequence elimination, the relay now
detects a biasing quantity in all 3 phases and gets less sensitive by the factor 3/
2 for the operating characteristic test.
YD interposing transformer:
(Zero Sequence Elimination by a Delta Winding). A delta winding represents a
short-circuit to zero-sequence current. This means, if such a winding is present,
no zero-sequence current will flow at the in-feed side for a single-phase fault at
the grounded side. The following figure shows that the interposing transformer
circuit with the delta winding performs the zero-sequence elimination. For
conventional relays, these interposing transformers are present as hardware; for
different numerical relays, they are simulated by the software. This information
needs to be taken from the relay documentation or has to be determined from
the manufacturer.
Figure 4-12:
Zero Sequence
Elimination by YD
interposing
transformers, reference
side = secondary side
(LV)
Entering the characteristic is done with lines, which have to be derived from the
relay parameters.
79
OMICRON Test Universe
1. Start with the second line, because the lines Idiff = Idiff> = 0.30 (first line) and
Idiff = Idiff>> 3.00 (last line) are automatically added.
The second line has Idiff / Ibias = slope1 = 25% to the intersection with the
third line. The knee-point is Ibias = 2.0.
Table 4-4:
Calculation of the end Start point End point
point of the 2nd line
(intersection with the Idiff = 0 Idiff2 = 0.5
third line):
Ibias = 0 Ibias2 = 2.0
Idiff2 = 0.25Ibias2
Idiff2 = 0.25 x 2.0 2. Click the A D D button to get this data into the table of defined lines.
-> Idiff2 = 0.50
80
Advanced Differential
3. Enter the 3rd line Idiff / Ibias = slope 2 = 50%. The line needs to be defined to
the intersection of line Idiff>> = 3.0.
Table 4-5:
Calculation of the end Start point End point
point of the 3rd line
(the intersection with Idiff2 = 0.50 Idiff3 =3.0
Idiff >>).
Ibias2 = 2.0 Ibias3 = 7.0
4. Click the A D D button to get this data into the table of defined lines.
The characteristic definition should look similar to what is presented in
figure 4-14.
Figure 4-14:
Characteristic
Definition page of the
Differential Protection
Parameters dialog box
with two lines defined
81
OMICRON Test Universe
Allowed Tolerances
Graphic is updated
when the "Add" button is
pressed.
2. Click the A D D button to get this data into the image for the harmonic settings.
The Idiff data are automatically provided from the Protection Device settings.
82
Advanced Differential
Test the correct setting of the differential protection with an external A-N fault on
the low voltage side with a test current of 1.0 In and 1.5 In (protected object). In
this special case, check the differential current, which has to be zero. Enter the
test title "Diff Configuration Test", the test results with title, test points and the
measuring values Idiff and Ibias in tabular form for the documentation of the
performed tests into the test document.
83
OMICRON Test Universe
84
Advanced Differential
For three-winding
transformers, the third
winding can have a load
current in addition to the
wanted external fault,
providing currents on all
three windings at the
same time.
3. Select the Test Data tab of the OMICRON Diff Configuration Test View.
4. Check the fault type A-N (L1-E) and enter the test current, Itest = 1.0I/In.
5. The test current Itest refers to the faulted phase current of the LV side with its
reference calculated from the HV winding. In this example case it
corresponds to a phase A line current on the LV side with Itest = 1048 A.
6. Click A D D to enter Itest to the list of test points and then repeat this step to
enter Itest = 1.5 I/In, as shown in figure 4-18.
85
OMICRON Test Universe
Figure 4-18:
Test data input in the
Diff Configuration
module
3. Check Idiff and Ibias and enter the Idiff / Ibias measured values in the
corresponding fields. These are read from the relays communication
program or display.
86
Advanced Differential
6. With this the first test is finished. Close the application and return to the OCC.
87
OMICRON Test Universe
Test the operating characteristic of the differential protection using the Shot Test
with the B-C (L2-L3) and A-N (L1-E) fault types, the static output test, and the
Search Test with the ABC (L1-L2-L3) fault type.
Insert the test modules in the OCC test document and define the test points and
report format. This should effectively verify and document the Differential
Operating Characteristic for each fault loop within the tolerances previously
specified for the protection device.
88
Advanced Differential
89
OMICRON Test Universe
90
Advanced Differential
A fault for the operating characteristic test is simulated in the protected zone
based on the reference winding with Idiff / Ibias pairs. From this, test currents are
applied to the selected winding pairs: one in-feed is the network on the reference
winding itself; the other in-feed is the network on the second winding or a
selectable one for a three-winding transformer. Therefore, for a three-winding
transformer, one winding has zero current. The different Idiff / Ibias calculated
currents are generated by the change in the network in-feed parameters.
91
OMICRON Test Universe
Figure 4-24:
Results of the B-C
(L2-L3) fault test for the
test document
92
Advanced Differential
When switching the error type, the type of zero sequence current elimination can
sometimes lead to changes in the characteristic line. This is because of the
different current distributions of the individual lines (refer to section Step 4:
Defining the settings for the protection device on page 73").
The line selective operation for protective devices: the relay trips whenever the
Idiff and Ibias pairs of the three phases lie in the trip range. Figure 4-25 shows
how the characteristic line shifts if the individual phases have different current
quantities.
Figure 4-25:
Shifting of the trip 7
characteristic line Idiff Ibias = 12
(simultaneous test on 6 Idiff = 3,5
two different points in
5
the Diff-Bias plane, in
particular by single pole 4
ground faults) Ibias = 6
Idiff = 1,75
3
0
0 5 10 15 20
Ibias
For example, mark a test point on the characteristic boundary at the second line
segment in the stabilizing (biasing) region. Reference the defined test point to
the size of the phase current. The other value pairs will lie in the trigger region.
This effect is automatically compensated for and the shape of the changed
characteristic line displayed.
Testing A-N (L1-E) fault with the Shot Test
Use the Shot Test for the fault type A-N (L1-E) by copying the last instance of
the test module. In this manner, the general parameters remain the same.
1. Single-click the last embedded test module (Diff Operating Characteristic
module) within the test document.
2. (Optional) Select E D I T | O B J E C T > O P E N / P R O P E R T I E S . . . and the
View tab.
3. (Optional) Change the settings to display it as an icon and press O K .
4. Select E D I T | C O P Y to copy the test module.
5. On a new line in the test document, select E D I T | P A S T E to insert this copy
of the test module.
6. Start the OMICRON Diff Operating Characteristic test module.
93
OMICRON Test Universe
94
Advanced Differential
95
OMICRON Test Universe
Calculated test
currents to be output
according to the set
Idiff / Ibias values and
the selected fault
type
96
Advanced Differential
Figure 4-28:
OMICRON Diff
Operating
Characteristic test
module inserted into a
test document
97
OMICRON Test Universe
98
Advanced Differential
Numeric input of the Adding or removing Marked test lines in the graphic control
test line test points to/from
the list
99
OMICRON Test Universe
100
Advanced Differential
Figure 4-31:
Test document
containing three
different OMICRON Diff
Operating
Characteristic tests
101
OMICRON Test Universe
Measure the trip times of the differential protection for a three-phase fault A-B-
C at Idiff = 0.5 I/In to Idiff = 3.0 I/In in 6 steps, under the condition Idiff = Ibias (test
line slope = 1).
102
Advanced Differential
103
OMICRON Test Universe
2. Exit the Diff Trip Time test module and return to the OCC and the test
document.
104
Advanced Differential
Figure 4-35:
Report View of the
specified Diff Trip Time
characteristic test
105
OMICRON Test Universe
Determine the harmonic restraint threshold of the SEL 587 differential protection
2nd and 5th harmonic settings for a three phase A-B-C (L1-L2-L3) fault type.
The sweep tests should be performed from Idiff = 0.4 I/In to Idiff = 2.9 I/Ini in 6
steps. Customize a report form "Diff_Rest" to display the test module, test
settings, and all test results into the test document.
106
Advanced Differential
107
OMICRON Test Universe
108
Advanced Differential
13.Select the test module and E D I T | C O P Y to copy the test module for a Shot
Test.
14.On a new line in the test document, select E D I T | P A S T E to insert this copy
of the test module.
15.Double-click this copy to start the Harmonic Restraint test module.
16.Clear the results of the last test using T E S T | C L E A R in order to perform
the Shot Test.
109
OMICRON Test Universe
The tolerance band for the threshold value for the inrush
stabilizati.on (2nd harmonic) and for testing of the marked points
110
Advanced Differential
Figure 4-40:
Results of the Harmonic
Restraint Search Test
are displayed next to the
test points
5. Close the OMICRON Diff Harmonic Restraint test module. This returns you
to the OCC and the test document.
111
OMICRON Test Universe
Figure 4-41:
Report View of the
specified test of the Diff
Harmonic Restraint
module
112
Advanced Differential
This view shows an overview of the specified tests. It does not show all of the
tests that were defined for the Advanced Differential example.
The status of each test is given as well as the names of the reports used.
2. Before the entire test plan can be executed from the test document, any
existing test results in the individual test reports need to be cleared. To do so,
use the T E S T | C L E A R A L L pull-down menu item. Moreover, the test
equipment can be checked before running the overall test.
113
OMICRON Test Universe
114
Synchronizer
5 Synchronizer
Synchronizing relays are used to assist:
connecting a generator to the network or power grid
reestablishing the connection between two parts of the network
manually closing of breakers and
performing a synchronism check.
Synchronizing relays are designed to measure two voltages with respect to
phase angle, frequency, and magnitude to safeguard against the
interconnection of two unsynchronized systems.
Figure 5-1:
Typical tests for a
synchronizing relay
CLOSE ENABLE
Synchronizing relays are also used in switching operations to link two parts of a
system which are already synchronously connected via other paths in the
system.
115
OMICRON Test Universe
5.1 Application:
Connecting a Generator to the Grid
When connecting a generator to the network, the synchronizing relay has to
control starting up the generator and switching it onto the network at the right
point in time.
The relay commonly used for this duty gives a three-fold check:
1. phase angle difference,
2. voltage difference and
3. frequency difference.
The relay sends a close signal to the breaker when all of the values fall within
the set limits and maintain these values for a user-defined period of time. If any
of the conditions are not met, some synchronizing relays use adjustment
commands which are sent to the valve actuators of the generators in an attempt
to achieve the proper conditions. In other cases where the conditions are not
met, the relay provides a fault signal.
5.2 Example:
ELIN SYN3000 Digital Synchronizing Relay
Sample files:
SYN3000_function.snc
SYN3000_adjustment.snc
SYN3000-CMC256.ohc
SYN3000.rio
Stored at: ...OMICRON Test Universe installation path\
Test Library\Samples\SW Manual Examples\Advanced Protection
Figure 5-2 shows a simple wiring diagram of how the ELIN SYN3000 Digital
Synchronizing relay might be employed to connect a generator to the power
grid. In this particular example, only one phase of the network power grid is used
as the reference. The reference phase is compared to a phase of the generator.
116
Synchronizer
Figure 5-2:
Example of connecting
a generator to the power
grid
The SYN3000 relay for this example is running in the mode for Generator to Bus
Bar or Power Line.
Table 5-1:
SYN3000 Relay Relay Settings
Settings
SYS1: Maximum Synchronization V1max = 110 V
SYS1: Minimum Synchronization V1min = 90 V
Max. Diff. Volt inductive +dVmax = 6 V
Max. Diff. Volt capacitive -dVmax = 5 V
Max. Diff. Frequency High +dfmax = 0.25 Hz
Max. Diff. Frequency Low -dfmax = 0.25 Hz
Max. Permissible Phase Angle PHImax = 3
CB Dead Time Compensation tCB-comp = 100 ms
Voltage adaption kv2 = 200 ms
117
OMICRON Test Universe
One of the three CMC 256 voltage outputs represents the voltage phase
of the network power grid, a second one the voltage phase of the
generator.
Binary Output 1 is used for the SEL1 (Start and Release) control signal of
the relay, telling it when to attempt synchronization and when to stop.
Four of the CMC 256 binary inputs (inputs 1-4) monitor the adjustment
control signals from the relay to the generator for increasing/decreasing
the voltage or frequency of the generator.
A fifth CMC 256 binary input (input 5) monitors the circuit breaker (CB)
close command from the relay.
The CMC 256 also provides an Auxiliary DC voltage which can be used
to power the relay.
118
Synchronizer
Note: Figure 5-3 does not show the computer or laptop that is connected to the
CMC 256 and runs the Synchronizer test module. Make sure that this is also
attached to the CMC 256 while wiring the relay.
2. Enter the system parameters for the ELIN SYN3000 relay as shown in
figure 5-4 and table 5-3. Figure 5-4 shows the standard page for the system
parameters.
119
OMICRON Test Universe
Figure 5-4:
Standard page for the
system parameters in
the test object
parameters dialog
Table 5-3:
Data for the test object Synchronizing Parameters
system parameters
System 1
Rotation sense A-B-C
Connected voltages A-B
System 2
Rotation sense A-B-C
Connected voltages A-B
Settings
CB Closing Time 100.0 ms
(from Test Object block "CB Configuration")
Transformer group Phase shift 0.00
Start/Release Continuous
3. Enter the parameters for the synchronizing window for the ELIN SYN3000
relay as shown in figure 5-5 and table 5-4. Figure 5-5 shows the standard
page for the synchronizing window.
120
Synchronizer
Figure 5-5:
Standard page for the
synchronizing window
in the test object
parameters dialog
Table 5-4:
Data for the test object Synchronizing Window
synchronizing window
| f max | 30 mHz
V> 6V
Phi () 3
f< -250 mHz
f> 250 mHz
| f min| 30 mHz
V< -5 V
Phi tolerances: Relative 3%
Absolute 0.6
f tolerances: Relative 3%
Absolute 3 mHz
V tolerances: Relative 3%
Absolute 60 mV
Min Sync Time: Time 1.25 s
Min Sync Time: Tolerance 5%
121
OMICRON Test Universe
122
Synchronizer
Figure 5-7:
Binary / Analog Inputs
tab of the hardware
configuration
5. On the Binary Outputs tab (figure 5-8) configure output 1 for the SEL1
control signal of the relay.
Figure 5-8:
Binary Outputs tab of
the hardware
configuration
123
OMICRON Test Universe
5.2.5 Verifying the Wiring Between the Relay and the CMC
At this point in time, it is prudent to check the physical wiring one more time to
make sure that it corresponds to section 5.2.1 Emulation with CMC Test Set
on page 118. In any event, the physical wiring should be in agreement with the
hardware configuration.
1. Verify that the voltage inputs of the relay are connected to the corresponding
voltage outputs of the CMC according to our configuration shown in 5-6.
Ensure that the voltage "inputs" of the relay are properly grounded according
to their configuration.
2. Verify that the binary control signals of the relay are connected to the
appropriate binary inputs of the CMC according to our configuration shown
in 5-7.
3. Verify that the start signal of the relay is connected to the appropriate binary
output of the CMC according to our configuration shown in 5-8.
2. Enter appropriate values for the SYN3000 relay for the pre-synchronization
time, the post-synchronization time, the maximum synchronization time, and
the delay time between test points.
The minimum post-synchronization time is defaulted to the CB closing time,
which was configured as part of the test object.
Table 5-5:
Time settings Time Parameters
Pre-sync 1.000 s
Post-sync 100.0 ms
Max-sync 60.00 s
Delay 200.0 ms
124
Synchronizer
The values entered in the Settings tab determine how long it will take to test a
single test point. If synchronization is achieved between the two systems, the
total test time for a test point is:
Synchronized: Delay time (if not the first test point)
+ the pre-synchronization time
+ the synchronization time
+ the post-synchronization time
= total test time
During a test when synchronization is achieved, the synchronization time will be
less than the maximum synchronization time. The minimum post-
synchronization time should be equal to or larger than the CB closing time. The
CMC does not output any voltages during the delay time.
If synchronization is not achieved, the total test time for a test point is:
Not Synchronized: Delay time (if not the first test point)
+ the pre-synchronization time
+ the max-synchronization time
= total test time
125
OMICRON Test Universe
126
Synchronizer
1. Enter the information into the respective text boxes for V, f, Phi (),
or V, f, Phi (), or a combination of the two.
V, f, Phi (): Represent the difference between the System
1 reference value and the System 2 test point.
V, f, Phi (): Represent actual values to be output for the
System 2.
Relative: Means that the test points are stored in the test
document as a percentage relative to the
synchronizing window.
Once the information for a test point is acceptable, click the A D D button.
2. Position the mouse pointer in the synchronization graph (to the right).
Right-click at a point to obtain a context menu. One of the items allows
you to add that test point to the test table.
3. <Ctrl> + left-click adds a point to the table immediately.
The test table has a context sensitive menu that is accessible with a right mouse
click. An important feature is being able to show or hide columns to help control
how much information is displayed to the person testing.
The synchronization graph also has a context sensitive menu that is accessible
with a right mouse click. It allows you to select points for the test table, test points
directly, and to zoom in the various areas. It can also be used to display grid lines
to aid in test point selection.
TEST AT Displays the voltage and frequency parameters of the
selected test points.
ADD TESTPOINT The specified point is added to the test table.
ZOOM IN Permits a given area of the dV / df plane to be enlarged
for more refined selection of test points.
ZOOM OUT Permits a given area to be viewed in context with
neighboring areas of the dV / df plane. This is mostly
used to obtain an overview of the dV / df plane.
ZOOM MODE Changes the mode for zooming.
ZOOM ALL Permits the entire dV / df plane to be viewed. It zooms out
on the chart and includes all defined test points.
SHOW GRID Displays the markings for the dV axis and the df axis of
the dV / df plane.
127
OMICRON Test Universe
128
Synchronizer
Figure 5-11:
Synchronization graph
for FunctionTest in
Synchronizer
129
OMICRON Test Universe
After outputting the appropriate voltages for a test point, the test point is
assessed as either passing (green "+") or failing (red "x"). The assessment is
based on the expectations for the test point. Some points are expected to
achieve synchronization (Nominal Response: Sync) while some are not
(Nominal Response: No Sync).
For example, test points within the synchronizing window should achieve
synchronization in the specified period of time if the relay is working properly.
Likewise, test points outside of the synchronizing window are expected to
exceed the maximum synchronization time without achieving
synchronization. If these expectations hold true after outputting the
appropriate voltage to the relay, the test point passes.
In addition to the assessment in the test table, test points are assessed as
either passing (green "+") or failing (red "x") in the graph. Again, the
assessment is based on the expectation.
130
Synchronizer
Figure 5-13:
Test points assessed as
passed in the graph of
the Function tab
131
OMICRON Test Universe
132
Synchronizer
133
OMICRON Test Universe
When a test point lies inside of the synchronization window and the relay is told
to start:
1. The Synchronizer test module verifies that extraneous commands
(V>, V<, f>, f<) are issued.
2 a) Because the test point is within the synchronizing window, the relay can
issue the CB close command and the Synchronizer test module enters
the post-synchronization mode.
b) If the CB command is not received within the maximum synchronization
time, the Synchronizer test module issues the Release command.
3. The Synchronizer test module evaluates the time (t sync) elapsed between
the Start command and the CB close command. It is important for the test
point pass/fail assessment to know the voltage, frequency, and phase angle:
- when the Start command is issued to the relay.
- when the relay issues the CB close command.
- when the CB actually closes.
The test points are output by the CMC test equipment for specific periods of
time. The output times are specified in the Settings tab (refer to section 5.2.6).
In the Signal View you can view the exact behavior of the binary signals for a
specific test point.
134
Synchronizer
135
OMICRON Test Universe
Figure 5-16:
Synchronization graph
for the test points
In addition to the assessment in the test table, test points are assessed as
either passing (green "+") or failing (red "x") in the graph. Again, the
assessment is based on the expectation.
136
Synchronizer
Figure 5-18:
Synchronization graph
showing the movement
of the test points to
within the
synchronization window
137
OMICRON Test Universe
Figure 5-19:
Synchronoscope for an
individual test point
138
Synchronizer
139
OMICRON Test Universe
140
Annunciation Checker
6 Annunciation Checker
Today's protection relays are able to emit hundreds of different signals and
measured values. Especially during station commissioning it is necessary to
check the correct assignment of signals and measured values to the different
locations. Annunciation Checker enables the user to generate the signals and to
check their correct appearance at the respective locations. It is possible to
prepare the signals in a test document and to adapt them to the actual substation
equipment even during testing.
Figure 6-1:
Annunciation Checker,
overview
4 1
3 2
Test View 1
Detail View 2
141
OMICRON Test Universe
Report View
The Report View shows the test results. Using the report settings the
appearance of the elements contained in the report can be customized to meet
the user's needs.
Test View
This dialog is used to enter the signals and locations, set the LEDs and expected
states and display the assessment results.
The test module is able to generate up to 9 locations and 200 signals. Moreover,
the course of the test can be viewed in the status display.
Figure 6-2:
Test View 1 2
1 Add signals
2 Add locations
3 Status display
142
Annunciation Checker
Detail View
This view is used for the following:
To predetermine the type of signal to be output at the analog outputs of the
CMC.
The following three selections are available:
Shot Signal output is limited by time or stopped by trigger
condition. Duration and prefault current are
adjustable.
Steady state Continuous signal output.
no output No signal output. It is only possible to define
instructions and pop-up messages.
To set the magnitude, phase angle and frequency of the analog CMC outputs
required to generate the message.
For this purpose, 9 different set modes are available for selection:
1. Direct (Line-Neutral)
Input of line-neutral voltages, currents and frequencies.
2. Line-Line
Input of line-line voltages, currents and frequencies.
3. Symmetrical Components
Input of positive, negative and zero sequence voltages and currents.
4. Powers
Input of real and reactive powers and line-neutral voltages.
5. Fault Values
Input of fault voltage and fault current.
6. Z-I const.
Input of the fault type and the fault impedances at constant test current.
7. Z-V const.
Input of the fault type and the fault impedances at constant test voltage.
8. Z%-I const.
Input of the fault type and the fault impedances in percent of the tripping
zones at constant test current.
9. Z%-V const.
Input of the fault type and the fault impedances in percent of the tripping
zones at constant test voltage.
143
OMICRON Test Universe
4 5
144
Annunciation Checker
145
OMICRON Test Universe
-Q1 -Q2
-Q8 -T05
146
Annunciation Checker
Figure 6-6:
Annunciation locations Annunciation locations
Protection relay Terminal strip X20 Local control System control room
The following explanation describes the commissioning test for feeder =E01 of
a multifunctional relay using the Annunciation Checker test module with a test
document created in the OMICRON Control Center. Although your specific
application will require some modification, the general procedure still stays the
same.
Commissioning testing of a protection relay requires the following:
- All messages and measured values transmitted from the protection device to
the various annunciation locations.
- All locations where the messages and measured values are displayed.
- The test settings required to generate the corresponding messages and
measured values.
147
OMICRON Test Universe
148
Annunciation Checker
Figure 6-7:
General test object
settings
149
OMICRON Test Universe
5
1
6
1 Line length and line angle. The transformer connection settings have
effect on the postfault voltage or current direction.
2 Tolerance limits, required for the comparison of nominal and actual
values.
3 The grounding factor is used for the simulation of single-pole faults. Its
definition varies between the different relay manufacturers.
4 Used for relays that consider the arc resistance for the modelling.
5 Display of impedances as primary values.
6 Voltage correction if the impedances are related to the relay's nominal
current of 5A.
150
Annunciation Checker
2. Edit the pick-up and drop-off characteristics of the protection device in the
Zone Settings tab.
Figure 6-9:
Zone Settings
151
OMICRON Test Universe
3. The new block is now displayed as a subitem of Custom in the tree structure.
4. Highlight the new block in the tree structure and open the block details by
selecting B L O C K | D E T A I L .
Figure 6-11:
Block details: ID and
name
5. Assign a unique ID and a name to the block to allow clear distinction of the
block.
152
Annunciation Checker
In the new block you can now create parameters that can be accessed via a link.
6. Create a new parameter in the selected block by selecting P A R A M E T E R |
ADD.
7. Select the data type of the parameter and assign a unique ID.
The data types String, Enumeration, Boolean, Integer and Real are available
for selection. The parameter's data type has to be selected in advance.
However, it can also be changed afterwards.
8. Select P A R A M E T E R | D E T A I L to open the dialog for the parameter details
and enter the name and a description and define the availability and the value
properties.
Figure 6-12:
Parameter details
2
1
153
OMICRON Test Universe
154
Annunciation Checker
Figure 6-14:
Table View of the test
steps
3. Use the Add Signal button to create new messages and enter their names
in the Test Step column.
4. In the LED column enter the number of the LED which is used to indicate the
message.
Comment: One test module allows a maximum of 200 messages.
In the table you can predetermine the expected signal states for the respective
locations.
Figure 6-15:
Table View with
messages and locations
5. Locate the concerning message and location. In their cross-point you can
select or deselect the message using the check box on the very left-hand
side of the column. In the cell right next to the checkbox you can enter the
nominal state of the message expected at the respective location.
155
OMICRON Test Universe
3 4
156
Annunciation Checker
157
OMICRON Test Universe
Figure 6-18:
Input fields for voltages
and currents 6
If values are displayed as absolute values, the created link to overcurrent I> is
displayed on gray background.
158
Annunciation Checker
3
1
159
OMICRON Test Universe
4. Click with the right mouse button on the value of Phi Z and select a
predefined angle.
The input field for ITest can be linked to user-defined values.
5. Click with the right mouse button on the current ITest and open the
LinkToXRIO dialog. In the tree structure of this dialog open the branch
"Custom | Special parameters" and then select the defined overcurrent
parameter I>.
6. Enter a factor (e.g. 1.100) for that value and leave the dialog by clicking O K .
Figure 6-22:
LinkToXRIO dialog
If values are displayed as absolute values, the created link to overcurrent I> is
displayed on gray background.
160
Annunciation Checker
161
OMICRON Test Universe
162
Annunciation Checker
1
2
3 4
7 5 6
1 Navigation arrows
2 Instructions area
3 Display of the message (signal under test)
4 Display of the annunciation location
5 Display of expected state
6 Display of actual state (measured value)
7 If checked, the software automatically moves to the next message or
location
8 Buttons for manual test assessment
3. Start the test for the messages by pressing the Shot button.
During the test, the labelling of the "Shot" button changes to "Shot running"
to indicate that the test is currently running.
The assessment buttons are activated after the test step is finished.
163
OMICRON Test Universe
164
Annunciation Checker
Figure 6-27:
Extract of a test report
165
OMICRON Test Universe
Input data:
110kV system, compensated.
Line:
1
Z Line = 0.408 km
0
Z Line = 1.12 km
1
Line = 72.9
Line
0 = 78.7
Length: 50 km
600A
K nI = -------------
1A
110kV
K nV = ----------------
100V
General Parameters
Settings
I nom Line angle RE /RL XE /XL PT location CT grounding
(secondary)
1A 72.9 0.277 0.605 at line dir. line
Tolerances
Time Impedance Current Voltage
relative 1% 5% 5% 5%
absolute 70ms 50m 50mA 5V
166
Annunciation Checker
Pick-up
Voltage-controlled overcurrent pick-up
Pick-up value Voltage [V/Vn] Pickup/dropout ratio
I>> [I/In] 1.8 0.8 0.95
I> [I/In] 0.5 0.8 0.95
V
Vn
0.8
I
0.5 2.2 In
Distance protection
Reach:
Z1 = 85% ZLine
Z2 = 120% ZLine
Z3 = 200% ZLine
Z1B = 120% ZLine
RLB = 6 (primary)
X/R=1.5
167
OMICRON Test Universe
Directional characteristic
Directional characteristic (cross-polarization)
2nd quadrant 4th quadrant
Angle [] 120 -22
168
Annunciation Checker
Autoreclosure
Test sequence Dead time Reach
Z2
Z1
Z1B
Grounding switch
Manual
close
169
OMICRON Test Universe
170
Annunciation Checker
171
OMICRON Test Universe
172
Transient Ground Fault
173
OMICRON Test Universe
Figure 7-1:
Example of a ground
fault relay connected to
one of the feeders of the
network power grid
All of the monitored currents are connected in parallel and their sum sent into
the relay. Likewise, all of the voltages are connected in series and their sum sent
into the relay.
In a balanced three-phase system, the summation of the currents from each
phase is zero. Likewise, the summation of the voltages from each phase is also
zero.
However, when one of the phases is grounded or is otherwise unbalanced with
respect to the other phases, the summation of currents and voltages is no longer
zero. There will be current flowing into the neutral, or ground. This is what the
ground fault relay detects.
When a ground fault is detected, the relay can be used to isolate parts of the
network to prevent damage to equipment, such as the transformer or generator.
174
Transient Ground Fault
Figure 7-2 shows the OMICRON Test Universe environment for checking the
ground fault relay.
The fourth CMC 256 voltage output can be used to represent the zero-
sequence voltage
VA + VB + VC
--------------------------------
-
3
Three CMC 256 current outputs represent the monitored currents of the
three phases of the network power grid.
Figure 7-2 does not show the computer or laptop that is connected to the
CMC 256 and runs the Transient Ground Fault test module. Make sure that this
is also attached to the CMC 256 while wiring the relay.
175
OMICRON Test Universe
176
Transient Ground Fault
3. Mark the checkbox to use the test object settings for the nominal frequency.
177
OMICRON Test Universe
Feeder B
Feeder A
178
Transient Ground Fault
179
OMICRON Test Universe
180
Transient Ground Fault
181
OMICRON Test Universe
When the waveforms are generated by the CMC and applied to the ground
fault relay, you can readily see whether the relay trips or not. Immediately,
you can determine whether or not the relay functions as expected.
182
Transient Ground Fault
183
OMICRON Test Universe
184
VI-Starting
8 VI-Starting
The test module VI Starting tests the voltage-dependent overcurrent starting
function (VI starting function).
VI Starting can be used with all 3-phase OMICRON test sets. It provides the
following tests:
Testing a specified VI-characteristic (test mode Verify Characteristic).
- Automatic testing of multiple points.
- Manual testing of single test points.
A characteristic diagram shows the VI characteristic and the test points. The
results (pick-up and drop-off values) are displayed in the test point table and
in the characteristic diagram, and are documented in the report. Additionally,
the signals which are emitted to the test object can be observed in a vector
diagram and a Time Signal View.
Automatic searching of the VI characteristic (test mode Search
Characteristic).
The search test automatically determines the pick-up and the drop-off
characteristic without specifying any test object specific parameters. For this,
the software automatically searches essential pick-up and drop-off values
and calculates the complete characteristic for these results.
Output of static values.
This mode is useful for debugging.
185
OMICRON Test Universe
6
4
2
7
1 3
186
VI-Starting
The pick-up is approached with shots, giving the relay time to reset in-between.
Once the pick-up is found, the drop-off is determined by varying the quantity
along a ramp.
The step size in which the quantity is varied is automatically determined by the
software.
During a test, the process of varying the test quantity can be observed in the
characteristic diagram and the Vector View.
The figure below illustrates the method. It shows how point a is tested.
Figure 8-2:
The process of varying VI Characteristic Voltage applied to the test object
the test quantity. (current value is constant)
voltage
3
a 4 6
2 5
The vertical dashed line is the test line. Along this line, the test quantity is varied.
This line is displayed in light blue in the characteristic diagram in the Test View,
and a bullet represents the actual test quantities. The horizontal dashed line
represents the pick-up voltage. The test voltage starts at the maximum and is
first decreased after each shot by a coarse step size (1). After the first pick-up
(2), the voltage is set back one step. To find the exact pick-up value, the voltage
is now again decreased in fine steps until the pick-up value is found (4). To
determine the drop-off value, the voltage is now ramped back (5) until the drop-
off occurs (6).
The procedure with varied current at constant voltage is analogous.
187
OMICRON Test Universe
Task
A tester has the task of performing both an automatic characteristic test and a
search test for a voltage-controlled overcurrent starting function with the test
module VI Starting.
The relay under test is a 7SA5 type device from SIEMENS and the test set used
is a CMC 156.
188
VI-Starting
The correspondence between the parameters in the relay setting program and
the parameters in the VI Starting test object settings is clear. Other relays
providing this function use similar names for the parameters, so it should be just
as simple to find the values for the test object settings. In this example, the
values can be taken directly from the relay setting program without further
calculations.
Figure 8-4:
VI Starting parameters
in the test object.
189
OMICRON Test Universe
190
VI-Starting
Figure 8-5:
Test View after a
characteristic test.
The progress of the test is displayed in the characterictic diagram by the light
blue test line with the bullet on it, which represents the actual V-I quantities
emitted during testing. The vector diagram indicates the relationship of the
voltages and the currents to each other and the value table in the Vector View
displays the exact numeric values of test quantities.
The assessment refers to the pick-up values only, since specifications are
generally only available for the pick-up characteristic.
191
OMICRON Test Universe
The progress of the test is displayed by the test line and the moving bullet. As
soon as the values become available, the calculated characteristics are
updated, according to the data available at this moment. In the table, the
parameters of the pick-up and the drop-off characteristic are displayed. For
more details about the search procedure, refer to the online help.
192
Single Phase Testing and Output of Fault Quantities
193
OMICRON Test Universe
Figure 9-2:
Voltages and currents
for phase-to-phase
faults
194
Single Phase Testing and Output of Fault Quantities
In the case of the phase-to-ground faults example, the fault quantities are the
phase-to-ground voltage and the phase current of the faulted phase.
In the case of the phase-to-phase example, the phase-to-phase voltage of the
faulted phases and the currents in the faulted phase, comprise the fault
quantities. The two-phase currents appear in the phase diagram as two currents
with identical magnitude and opposite sign. In fact, it is one current that flows into
the relay at the one phase and out of the relay at the other. Therefore, also in
this case, one source is sufficient to produce this test current.
The test software set up this way performs the output of the fault quantities
through the single-phase sources without further user interaction. The remaining
operation of the test module remains unchanged, which means the specification
of the characteristic and the setting of the test points are done as if the relays
were three-phase connected. The user has only to check that the sources are
connected correctly to the terminals of the relay, according to the fault type. The
(Advanced) Distance test software reminds the user with a message that the
wiring has to be modified accordingly at the start of the test and at any change
of the fault type.
195
OMICRON Test Universe
The maximum test current of 12.5A is absolutely sufficient for this case.
Therefore it is possible to connect four current sources in series, providing a
driving voltage of up to 60V (peak value). With the CMC 256 test set, balancing
resistors to assure a leveled voltage distribution when connecting current
sources in series are no longer needed.
196
Single Phase Testing and Output of Fault Quantities
The available power from the voltage sources in this test set is not determined
from the current rating of the amplifiers, but from the respective power supply.
The maximum current can be obtained from a single source with the wiring
shown.
The mapping of the fault quantities to the single-phase sources is done in the
dialog for the analog outputs.The signals I Fault and V Fault are selected for
their respective current and voltage source.
Figure 9-4:
Hardware
Configuration, Analog
Outputs tab: Mapping of
the fault quantities in the
Advanced Distance test
modules
Figure 9-5:
Example of wiring for an
A-N (L1-E) fault shown
with a special case of an
A-N (L1-E) fault Test Relay
set under
test
Figure 9-6:
Example of wiring for an
phase-phase fault
shown with a special
case of a C-A fault Test Relay
(L3-L1) set under
test
197
OMICRON Test Universe
198
Single Phase Testing and Output of Fault Quantities
199
OMICRON Test Universe
200
File Name Extensions within OMICRON Test Universe
Hardware Configuration
filename.OHC OMICRON Hardware Configuration (import/export
from HCWs General tab)
Test Object
filename.RIO The term RIO stands for Relay Interface by
OMICRON.
RIO, was developed out of a need for a uniform data
format for parameters of protective relays produced
by different manufacturers. RIO provides a common
structure to allow functionally similar relays from
diverse manufacturers to be tested with similar test
procedures. Moreover, RIO permits relay
characteristics to be imported into the Test Universe
software from external sources.
filename.XRIO XRIO represents the second generation of RIO file
technology. The term RIO stands for Relay Interface
by OMICRON, a technology that was already
available with previous Test Universe versions. The X
denotes "extended".
201
OMICRON Test Universe
Test Modules
filename.ADT Advanced Distance
filename ANNUCH Annunciation Checker
filename.BDF Differential
filename.CBS Circuit Breaker Simulation
filename.DST Distance
filename.GRF Transient Ground Fault
filename.HRT (Advanced Differential) Diff. Harmonic Restraint
filename.MEA EnerLyzer
filename.MET Meter
filename.NSI NetSim
filename.OAR Autoreclosure
filename.OTF (Advanced Differential) Diff. Operating Characteristic
filename.OUC UCA-CMC Configuration
filename.OVT Overcurrent
filename.PQT PQ Signal Generator
filename.PRA Pulse Ramping
filename.QCM QuickCMC
filename.RMP Ramping
filename.SEQ State Sequencer
filename.SNC Synchronizer
filename.TRA Advanced TransPlay
filename.TRD Transducer
filename.TST (Advanced Differential) Diff. Trip Time
filename.VGT (Advanced Differential) Diff Configuration
filename.VSR VI-Starting
IEC 61850
filename.OSV Samples Values Configuration
(IEC 61850-9-2 LE Configuration Module).
filename.OGC GOOSE configuration file
filename.OUC GSSE configuration file
202
File Name Extensions within OMICRON Test Universe
Test Tools
filename.BIO Binary I/O Monitor
filename.HOU Harmonics
filename.LST TransPlay
filename.TYP TypConverter
203
OMICRON Test Universe
204
Contact Information / Technical Support
Asia, Pacific
OMICRON electronics Asia Ltd, Hong Kong
Phone: +852 2634 0377
E-Mail: support@asia.omicron.at
Web: www.omicron.at
205
OMICRON Test Universe
206
Index
D
B DAT (file format in Advanced TransPlay) . . . 13
balanced 3-phase system (Ground Fault) . . 174 data markers (Advanced TransPlay) . . . . . . 18
dead zones (Synchronizer) . . . . . . . . . . . . 121
Diff Configuration test module . . . . . . . . 12, 63
Diff Harmonic Restraint test module . . . . 12, 64
C Diff Operating Characteristic test module 12, 63
Diff Trip Time test module . . . . . . . . . . . 12, 64
CB Configuration difference
example with Advanced Distance . . . . . . 55 phase angle, voltage or frequency
CFG (file format in Advanced TransPlay) . . . 13 (Synchronizer) . . . . . . . . . . . . . . . . . . . . 116
Characteristic Editor (Advanced Distance) . . 41 differential protection relays . . . . . . . . . . . . . 61
check test (Advanced Distance) . . . . . . . 11, 31 differential schemes (Advanced Differential
circuit breaker modules) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CB closing functionality (Synchronizer) . 126 distance relay with transient playback
COMTRADE (working example Advanced TransPlay) . . . 21
file name extension CML . . . . . . . . . . . . 203 distance testing . . . . . . . . . . . . . . . . . . . . . . 11
Comtrade
file formats used in Advanced TransPlay 13
connecting
protection relay to CMC test set
(Advanced Differential) . . . . . . . . . . . . . . 68 E
protection relay to CMC test set e-mail
(Advanced Distance & CB Configuration) 56 OMICRON address . . . . . . . . . . . . . . . . 205
protection relay to CMC test set
(Advanced Distance) . . . . . . . . . . . . . . . . 36
protection relay to CMC test set
(Advanced TransPlay) . . . . . . . . . . . . . . . 22
protection relay to CMC test set
(Synchronizer) . . . . . . . . . . . . . . . . . . . . 118
207
OMICRON Test Universe
M
G magnetizing currents (Diff Operating
Characteristic) . . . . . . . . . . . . . . . . . . . . . . . 63
generator message
connecting a generator to the grid checking (Annunciation Checker) . . . . . 141
(Synchronizer) . . . . . . . . . . . . . . . . . . . . 116 multi-functional relays
GPS tested with Advanced Differential . . . . . . 62
as trigger to start data output (Advanced
TransPlay) . . . . . . . . . . . . . . . . . . . . . . . . 13
ground fault (Ground Fault test module) . . . 173
Ground Fault test module . . . . . . . . . . . . . . . 12
grounding of CT (Advanced Differential) . . . . 65
N
natural phase quantities (display in Advanced
Distance VI monitor) . . . . . . . . . . . . . . . . . . . 53
H
HDR (file format in Advanced TransPlay) . . . 13
hotline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
O
output of fault quantities . . . . . . . . . . . . . . . 193
overcurrent starting function (voltage-depen-
dent, VI Starting) . . . . . . . . . . . . . . . . . . . . 185
I over-excitation
inrush-restraint and stabilization against
Ibias calculation (Advanced Differential) . . . . 75 over-excitation (Advanced Differential) . . 67
ID
block ID (Test Object) . . . . . . . . . . . . . . 152
Idiff / Ibias
plane (Diff Operating Characteristic) . . . . 63
value pair (Diff Trip Time) . . . . . . . . . . . . 64
P
ignore before PDF
in Advanced TransPlay Measurement file name extension . . . . . . . . . . . . . . . . 204
View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 phase-selective (Advanced Differential) . . . . 76
impedance post-sync time (Synchronizer) . . . . . . . . . . 124
constant source impedance model pre-sync time (Synchronizer) . . . . . . . . . . . 124
(Advanced Distance) . . . . . . . . . . . . . . . . 32
setting as percentages of zone reaches
(Advanced Distance) . . . . . . . . . . . . . . . . 11
208
Index
209
OMICRON Test Universe
T (cont.) W
transient data winding ratio mismatch due to tap-changer
working with t.d. (Advanced TransPlay) . 11 position (Diff Operating Characteristic) . . . . 63
transient ground fault (Transient Ground wring
Fault) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173 protection relay to CMC test set
transient playback (Advanced Differential) . . . . . . . . . . . . . . 68
distance relay with transient playback protection relay to CMC test set
(working example Advanced TransPlay) . 21 (Advanced Distance & CB Configuration) 56
trigger protection relay to CMC test set
trigger options in Advanced TransPlay . . 15 (Advanced Distance) . . . . . . . . . . . . . . . . 36
trip times testing (Advanced Distance) . . . . . 34 protection relay to CMC test set
(Advanced TransPlay) . . . . . . . . . . . . . . . 22
protection relay to CMC test set
(Synchronizer) . . . . . . . . . . . . . . . . . . . . 118
U
unsynchronized systems (Synchronizer) . . 115
X
XML
V file name extension . . . . . . . . . . . . . . . . 204
VI characteristic (VI Starting) . . . . . . . . . . . 186 XRIO
VI monitor (Advanced Distance) . . . . . . . . . . 53 file name extension . . . . . . . . . . . . . . . . 201
VI Starting test module . . . . . . . . . . . . . . . . . 11
voltate-dependent overcurrent starting function
(VI Starting) . . . . . . . . . . . . . . . . . . . . . . . . . 185
Y
YD interposing transformer
(Advanced Differential) . . . . . . . . . . . . . . . . . 79
Z
Z/t diagram (Advanced Distance) . . . . . . 33, 52
zero sequence current elimination
(Diff Operating Characteristic) . . . . . . . . . . . 93
zero sequence elimination (Advanced
Differential) . . . . . . . . . . . . . . . . . . . . . . . . . . 77
zero-sequence current (Advanced
Differential) . . . . . . . . . . . . . . . . . . . . . . . . . . 71
zone settings (Advanced Distance) . . . . . . . 40
Z-plane
test in Z-plane (Advance Distance) . . . . . 29
210