You are on page 1of 28

CHAPTER 6 - FOUNDATION DESIGN

600. DESIGN PROCEDURE. In this chorage forces to be transferred to


chapter information about the building site and the foundation.
the building structure are combined and used to
determine the size of footings, reinforcing for 3. The required anchorage values are
the foundation, and the size and spacing of an- used in Appendix C, Foundation
chorage used to tie the unit to the foundation. Capacities Tables, to determine the
materials, dimensions, and con-
600-1. GENERAL struction details of the foundation.

A. Foundation Appendices. The foun- C. Design Criteria and Design Loads.


dation design information in Appendices A, B, The design criteria and loads are needed for the
& C may be used to design new foundation Foundation Design Load Tables (Appendix B).
systems or to verify the design of proposed or
existing systems. Appendix A, Foundation 1. Width of Unit. The measured width
Design Concepts, shows design concepts suit- of the manufactured home, con-
able for a variety of manufactured home types verted to a nominal width is needed.
and site conditions. Appendix B, Foundation
2. Height of Unit. The unit is assumed
Design Load Tables, provides design require-
8-0 tall from bottom of floor
ments for anchorage of the manufactured home
framing to eave at roof. Ceilings
to the foundation and recommended footing
may be horizontal (flat) or cathedral
sizes. Appendix C, Foundation Capacities Ta-
sloped.
bles, provides design capacities for foundation
uplift and withdrawal, based on the foundation 3. Design Loads. The design ground
type chosen (wood, concrete masonry or cast- snow load, wind speed, seismic
in-place concrete). ground acceleration and seismic
performance category are needed.
B. Design Verification Sequence. The
Refer to Appendix H to determine
three Appendices (A, B, & C) are intended to
the design load values.
be used in sequence.
D. Effective Footing Area (Aftg). The
1. Appendix A, Foundation Design
footings for the permanent foundation must be
Concepts, is used to identify ac-
sized to prevent sinking or settlement of the
ceptable foundation designs based
manufactured home. Footing area is given the
on the manufactured home type and
abbreviation (Aftg). The values for (Aftg) are
the site conditions.
given in square feet (sf) for pier footings and
2. Appendix B, Foundation Design feet (ft) for wall footing width. Refer to Ap-
Load Tables, is used to determine pendix D for the derivation of equations for the
the required footing sizes and the determination of effective footing areas.
required vertical and horizontal an-

6-1
E. Vertical Anchorage (Av). The manu- been selected from ASCE 7-93 for allowable
factured home must be securely anchored to stress design as follows:
the foundation. One critical anchorage re-
quirement is for the structure to resist uplift 1. The load combination used for The
and overturning from wind activity in the trans- Foundation Design Footing Tables
verse direction. This is vertical anchorage and (Appendix B, Part 1) is:
it can be achieved at the chassis beams or along
longitudinal wall locations, or both locations. DL (heavy) + LL (occupancy) +
It is given the abbreviation (Av), and the (Av) LL (attic) + SL (or min. roof LL).
values are all given in pounds (lbs. per pier or
2. The load combination used for The
lbs. per foot of foundation wall). Refer to Ap-
Foundation Design: Anchorage Ta-
pendix D for the derivation of the equations for
bles (Appendix B, Part 2,3,4) is:
determination of required vertical anchorage
force.
(Wind or Seismic*) DL (light)
F. Horizontal Anchorage (Ah). An-
* Heavy DL was used to calculate the
other critical anchorage requirement is for the
roof and floor inertia forces only.
manufactured home to resist horizontal sliding
forces in both the transverse and longitudinal 600-2 DETERMINATION OF BUILDING
directions. Horizontal forces are a result of WIDTH
wind or seismic activity. Horizontal anchorage
is given the abbreviation (Ah). The transverse A. Building Width for Use of Appen-
or longitudinal direction relates to the direction dix B Tables. The actual measured building
of force application and to the orientation of width must be converted into the nominal
the resistance elements, such as the transverse building width for use in the Foundation De-
vertical X-bracing planes or the longitudinal sign Footing Tables and Anchorage Tables.
walls of the unit respectively (see Figure 1-1). The nominal building width should be calcu-
The values for (Ah) are given in pounds per lated as follows:
foot (lbs./ft.). Refer to Appendix D for the
derivation of equations for determination of 1. To obtain the nominal building
required horizontal anchorage force. width for use in the Foundation De-
sign: use the following information:
G. Loads Included and Load Combina-
tions. All applicable gravity loads (dead, oc- Actual Building Width Nominal Width
cupancy and snow or minimum roof live) and 11-4 to 12-0 12
all lateral loads (wind or seismic) have been 13-4 to 14-0 14
considered in the development of the Founda- 15-4 to 16-0 16
tion Design Load Tables of Appendix B.
Chapter 4 gives a brief description of each load 2. The tables are based upon the width
and Appendix D derives the equations upon of each section as it is transported.
which the magnitude of these loads is deter- A multi-section superstructure clas-
mined for any geographic location and unit sified as a nominal 14-foot width
Type. Appropriate load combinations have could be 26'-8" to 28'-0" in actual
width.

6-2
Unit Width Description
Figure 6 - 1

3. The nominal width to be used in the 600-5. DETERMINATION OF DESIGN


Foundation Design Load Tables SEISMIC FACTORS.
should be recorded.
A. Determine Design Seismic Ground
B. Width Illustration. If there is a ques- Acceleration Values.
tion about which dimension is actually the
width of the structure, see Figure 6-1. The 1. Verify the geographic location
width of the home is shown as Wt (nominal where the unit will be sited.
12', 14', or 16'.)
2. Refer to the two Ground Accelera-
600-3. DETERMINATION OF DESIGN tion Contour Maps on pages H-15
GROUND SNOW LOAD. Verify the geo- and H-16 and read (Aa) from map 1
graphic location where the unit will be sited. and (Av) from map 2 for the isobar
Refer to the ground snow load map on pages closest to the site.
H-11, H-12 and H-13, and read the pound per
square foot (psf) isobar for the intended site. 3. The manufactured home is exempt
Note that a mandatory minimum roof live load from seismic requirements if the
may be greater than the roof snow load. Refer map value for (Av) is less than
to section 402-2.A and C for further clarifica- 0.15; therefore, wind becomes the
tion. only lateral load design issue. If
(Av) is equal to or greater than 0.15
600-4. DETERMINATION OF DESIGN seismic provisions must be met
WIND SPEED. Verify the geographic loca- (Section 402-4).
tion where the unit will be sited. Refer to the
wind speed map on page H-14 and read the B. Determine the Required Seismic
MPH wind speed isobar for the intended site. Performance Category.
Note that a minimum wind speed of 80 MPH is
1. A seismic hazard exposure group of
required by the Minimum Property Standards,
(I) is assumed for single family
even if the map isobar shows a smaller MPH
residences.
value. Establish if the site is Inland or Coastal
(section 402-3.B). 2. The seismic value (Av) and the
Seismic Hazard Exposure Group (I)

6-3
are used to assign the manufactured of resistance at the foundation. The
home to a Seismic Performance design and detailing of the unit shall
Category. Refer to the Seismic Per- comply with Section 9.3.6 of ASCE
formance Category Table on page 7-93 for the Seismic Performance
H-17, enter the Table with these Category assigned in step 2 above.
two values and record either (C) or
(D) as applicable. Note that if (C) 601. VERIFYING THE FOUNDA-
is the correct Category, it is re- TION DESIGN CONCEPT (APPEN-
quired to comply with the require- DIX A)
ments for Category (A) and (B) as
well as (C). If Category (D) is the 601-1. LOCATION OF FOUNDATION
correct Category, then the require- SUPPORTS
ments for Category (A) through (D)
must be met. These requirements, A. Definition of Support. Support is
as they pertain to permanent foun- herein defined as the location where the gravity
dations for manufactured housing loads (dead, occupancy, snow, minimum roof
are listed in Section H-300 as a ref- live load) within and applied to the unit are
erence. The Foundation Concepts transferred to the foundation system.
illustrated in Appendix A can meet
the intent of the foundation re- B. Illustration of Support Locations.
quirements of Section 9.7 of ASCE The acceptable locations where foundation
7-93 for Seismic Performance Cate- piers and walls support the unit are illustrated
gories (A) through (D). in Figure 6-2. Terms that appear throughout
Appendices A, B and C are also defined. Some
3. The manufacturer shall verify that or all of the illustrated locations may be used,
the unit provides continuous load but symmetry of the support system must be
paths with adequate strength and maintained. Note that marriage walls may be
stiffness to transfer all forces from continuous walls, or contain specifically lo-
the point of application to the point cated openings with posts at the ends of each

Definition of Terms and Possible Support Locations


Figure 6 - 2

6-4
opening. wall the unit is defined as a
Type Cnw, and no openings can
C. Determine the Location of Founda- be permitted in the marriage
tion Supports. Single-section or multi-section wall. It must be a continous
units are supported by equally spaced piers wall, supported by the floor and
along their chassis beams, by exterior longitu- chassis beam system.
dinal walls or both. Multi-section units may
possibly have additional equally spaced pier Type E or I: A combination of longitudinal
supports along a continuous marriage wall, and exterior walls and equally
have piers placed according to post locations at spaced piers under the chassis
the ends of specific marriage wall openings. beams are used for single-
Select one of the following unit support op- section or multi-section units.
tions: The same discussion regarding
continuous marriage walls and
Type C: Piers are equally spaced along marriage walls with openings
the chassis beams for single- within them, as found under
section units. Additional piers Type C, applies to Type E and
may exist below continuous I.
marriage walls and under posts
at the ends of openings within 601-2 LOCATION OF VERTICAL AN-
the marriage wall, that exist for CHORAGE (Av) IN THE TRANSVERSE
multi-section units. If no sup- DIRECTION.
port exists below the marriage

Overturning and Uplift Resistance Options


Figure 6 - 3

6-5
A. Definition of Vertical Anchorage. 601-2.A. Select one of the following vertical
Vertical anchorage exists in the transverse di- anchorage options:
rection when a mechanical connection is made
between the manufactured home unit and the Type C: Vertical anchorage is along the
foundation to resist wind related overturning chassis beams only, and occurs at
and uplift forces. Overturning is the tendency the equally spaced support piers for
for the unit to rotate about a pivot point either single-section units. Multi-section
at the bearing point between chassis beam and units may utilize the exterior chassis
support pier, or the bearing between the unit beams (2 ties) or all the chassis
and the longitudinal exterior wall. This rota- beams (4 ties) for vertical anchor-
tion lifts the unit off its other bearing points; age to the support piers.
therefore, requiring vertical anchorage (tie-
down) to resist the force. Uplift of the unit oc- Type C1: Vertical anchorage is typically pro-
curs as wind passes over the roof surface, tend- vided by external straps which wrap
ing to lift the unit. Vertical anchorage resists over the top and down the sides of
this force. See Figure 6-3 for illustration of the unit. Short vertical ties, which
both of these effects in the transverse direction. attach directly to the homes exte-
Analysis for both effects in the transverse di- rior wall structure, are a possible al-
rection indicates that overturning forces are ternate. These straps or ties attach
greater than uplift forces. Thus, Appendix B, to concrete dead man footings set
Part 2 Vertical Anchorage Tables are based on at the appropriate depth below
overturning behavior with the knowledge that grade. The straps or ties are gener-
uplift forces will also be handled. Locations ally spaced to match support pier
for this mechanical connection exist either locations; however, variations are
along the chassis beams and/or along the exte- possible. These anchorage types
rior longitudinal walls. Vertical anchorage and are limited to single-section units. It
gravity support may exist at the same locations, is required that the first external
but other combinations of support and anchor- straps or ties be a minimum of 2
age may exist. Connection types include an- feet in from each end of the unit
chor bolts, welds, or a broad range of framing with the remainder equally spaced.
anchors and fasteners common to the wood in-
dustry. A unit that merely sits on its founda- Type E: Vertical anchorage is only along the
tion, does not constitute vertical anchorage of exterior longitudinal walls for sin-
the unit. A physical connection of adequate gle-section units. Multi-section
capacity is required for vertical anchorage to units may vertically anchor to exte-
exist. rior longitudinal walls (2 ties) or
vertically anchor to exterior longi-
B. Determine Locations of Vertical An- tudinal walls and interior chassis
chorage (Av). The character of the foundation beams at the equally spaced piers (4
support Type selected in section 601-1.C must ties).
be reviewed for vertical anchorage capability.
The manufactured home unit may be anchored Type I: Vertical anchorage is along the
by any of the methods described in section chassis beams only, and occurs at
the equally spaced support piers for

6-6
single-section units. Type I vertical 1. Transverse Direction: Anchorage
anchorage differs from Type C ver- location options include 2, 4, or 6
tical anchorage only in its pivot transverse walls (shear walls) or a
point location for overturning. select number of vertical planes of
Multi-section units may utilize the X-bracing (trussing) with galva-
exterior chassis beams (2 ties) or all nized rods, wires or straps. Figure
of the chassis beams (4 ties) for ver- 6-4 illustrates these individual op-
tical anchorage at the equally tions for a single-section unit and
spaced support piers. Figure 6-5 illustrates one combina-
tion of these options, also for a sin-
601-3. LOCATION OF HORIZONTAL gle-section unit. Selection of trans-
ANCHORAGE (Ah) verse horizontal anchorage location
option is not influenced by the se-
A. Definition of Horizontal Anchorage. lection of Type C, E or I unit for
Horizontal anchorage exists when a mechanical support or vertical anchorage in the
connection is made between the manufactured transverse direction as done in sec-
home unit and the foundation to resist sliding tions 601-1 and 601-2.
due to wind or seismic lateral forces. Sliding
can occur in the transverse direction or the lon- 2. Longitudinal Direction: Anchorage
gitudinal direction, and both directions must location options include either the
independently be checked. Sliding involves two exterior longitudinal walls (for
horizontal movement in the transverse or longi- single or multi-section units) or the
tudinal direction of the unit, and if the wind or chassis beam lines (2 for single-
seismic event is of large enough magnitude, section units, or 4 for multi-section
these horizontal forces can result in the unit units), where vertical planes of X-
sliding off its foundation. Anchorage between bracing with galvanized rods, wires
unit and foundation to avoid this situation is or straps are possible. Illustration
accomplished in one of two ways: (1) utilizing of the two choices is shown in Fig-
bolts, welds or other acceptable means to con- ure 6-6 for a single-section unit.
nect the unit to foundation walls that are made Selection of longitudinal horizontal
of concrete masonry, treated wood or concrete, anchorage location option is not in-
or (2) utilizing vertical X-bracing planes of fluenced by the selection of Type C,
galvanized rod or wire diagonal ties or straps E or I unit for support or vertical
between the top side of the steel chassis beams anchorage in the transverse direc-
diagonally down to the top of the concrete tion as done in sections 601-1 and
footings. 601-2.

B. Determine Locations of Horizontal 601-4. FOUNDATION CONCEPT SE-


Anchorage (Ah). Horizontal sliding must be LECTION. Whether designing a new perma-
resisted both in the transverse and longitudinal nent foundation or upgrading an existing foun-
directions. Options for each direction are as dation to a permanent foundation, confirmation
follows: of a foundation concept from Appendix A is
required. The permanent foundation type is a
function of the support option selected in sec-

6-7
tion 601-1.C and the vertical anchorage option chassis beam lines, just as for Type
selected in section 601-2.B. Note: The hori- E, for single-section or multi-
zontal anchorage option is independent of these section units. Vertical anchorage
two issues and does not influence selection of occurs at the equally spaced piers
foundation type. along the chassis beam lines only
for single-section or multi-section
A. Three Basic Foundation Types. A units (2 ties or 4 ties).
summary of the structural characteristics re-
quired for each type of permanent foundation B. Illustration of Foundation Types
system follows: and Concepts. Single-section foundation
types and detailing concepts are illustrated in
Type C: Support and vertical anchorage oc- Figure 6-7 and Appendix A. Multi-section
curs at equally spaced points along foundation types and detailing concepts are
the Chassis beam lines only. This is illustrated in Figure 6-8 and Appendix A. The
true for single-section or multi- meaning of the arrow orientation in both Fig-
section units. ures is as follows:

Type E: Support occurs at the Exterior lon- Symbols: vertical anchorage (uplift
gitudinal foundation walls as well and overturning)
as at equally spaced points along support (gravity)
the chassis beam lines. Vertical an-
chorage occurs continuously along Type C: concepts C2 to C4
the exterior longitudinal foundation
walls for single-section or multi- Type E: concepts E1 and E8 (E2 omitted
section units (2 ties), or a combina- in this revision)
tion of vertical anchorage can occur
continuously along the exterior lon- Type I: included here as possible future
gitudinal foundation walls and design concepts. None were
along the equally spaced pier loca- currently submitted by manufac-
tions along interior chassis beams (4 turers.
ties).
C. Determine Foundation Concept.
Type I: Support occurs at the exterior longi- Based on the foundation type selected, choose
tudinal foundation walls as well as one of the several concept options below:
at equally spaced piers along the

6-8
Sliding Resistance Options - Transverse Direction
Figure 6 - 4

6-9
Sliding Resistance - Combination Option - Transverse Direction
Figure 6 - 5

D. Additional Foundation Types and Type E: concept E3, E4 (single-section)


Concepts. Some combinations of support and concept E3 (multi-section)
vertical anchorage, other than the basic Types concept E5, E6, E7 (multi-
C, E and I. Should that be the case, select one section)
of the concept options below:
Type Cnw: concepts C2, C3, C4 (type Cnw
Type C1: concept C1 (Single-section) stands for a Type C multi-
section with no marriage wall)

Sliding Resistance Options - Longitudinal Direction


Figure 6 - 6

6 - 10
602. USING THE FOUNDATION mine foundation footing sizes required, plus
DESIGN TABLES (APPENDIX B) vertical and horizontal anchorage forces to be
resisted for all the foundation types. This sec-
602-1. GENERAL. The Foundation Design tion gives step-by-step instructions for using
Load Tables (Appendix B) are used to deter- the Foundation Design Load Tables.

Foundation Design Concepts: Single-Section Units


Figure 6 - 5

6 - 11
Foundation Design Concepts: Multi-Section Units
Figure 6 - 6

6 - 12
602-2. FOUNDATION VOCABULARY. for all concrete or masonry pier concepts in
Figure 6-9 illustrates the following foundation seismic regions with Av greater than or equal
terms. to 0.3. The values shown in the Foundation
Design Load Tables are values based on the
A. Pier Foundations. The longitudinal pier spacing in pounds per pier (lbs) for (Av),
variety of spacing of piers under the chassis and square feet for (Aftg), whether exterior,
beam lines as shown in the Foundation Design interior or marriage wall piers.
Load Tables is 4, 5, 6, 7, 8 and 10 feet. If pier
spacings other than those shown are contem- B. Transverse Foundation Walls.
plated, use the next largest spacing (i.e. for 4.5 Transverse foundation walls can occur at the
feet use 5 feet). Piers placed under continuous exterior ends of a single-section or multi-
marriage walls are assumed equally spaced, section unit, as well as at selected interior loca-
while piers must be placed under posts that de- tions along the length of the unit. A continu-
fine the ends of a large opening in a marriage ous concrete footing must exist under the trans-
wall. These openings are assumed to range verse walls regardless of the wall material:
from 10 to 20 feet in 2 foot increments. All concrete, concrete masonry or treated wood.
marriage wall piers are assumed to only par- Interior transverse foundation walls of concrete
ticipate in transferring gravity loads, thus they or masonry can: (1) box around the chassis
do not participate in resistance to overturning beams and provide direct continuous connec-
or sliding. Piers may be made of concrete, con- tion to the floor structure of the unit, or (2) the
crete masonry or steel. Reinforcing is required wall can stop at the underside of the chassis

Foundation Terms
Figure 6 - 7

6 - 13
beams and utilize diagonal steel straps or di- B. Determine Design Ground Snow
agonal wood ties to complete connection be- Load / Minimum Roof Live Load. This step
tween the transverse wall and the units floor has been done in section 600-3 and is required
structure. Appendix A illustrates these ap- for single-section and multi-section units.
proaches. Reinforcement will be required for
most transverse wall concepts. The values C. Occupancy Live Loads. The residen-
shown in the Foundation Design Load Tables tial occupancy floor live load is 40 psf in all
(Appendix B) for horizontal anchorage (Ah) the model codes and has been used as the floor
are values based on pounds per lineal foot live load in the Tables of Appendix B, Part 1.
(lbs./ft.) of wall. Attic live load is assumed to be 10 psf.

C. Longitudinal Foundation Walls. D. Determine Net Allowable Soil Bear-


Longitudinal Structural foundation walls are ing Pressure. The maximum net allowable
provided for foundation Types E and I. A con- soil bearing pressure shall be based on a geo-
tinuous concrete footing must exist under the technical investigation, a national model code
longitudinal foundation walls regardless of the presumptive value, or an assigned value by the
wall material: concrete, concrete masonry or local authority having jurisdiction, as described
treated wood. Reinforcement will be required in Chapter 2. The Tables in this document as-
for all longitudinal wall concepts. The values sume a minimum of 1000 psf. The value for
shown in the Foundation Design Load Tables design should be recorded in the Owners Site
(Appendix B) for: (1) vertical anchorage (Av) Acceptability Worksheet (Appendix E, ques-
are values based on a continuous wall support tion # 10 or #11).
in pounds per lineal foot (lbs./ft.) of wall, (2)
horizontal anchorage (Ah) are values based on E. Determine (Aftg) Value from the
pounds per linear foot (lbs./ft.) of wall and (3) Tables. Refer to Appendix B, Part 1 of the
footing width values are in feet (ft) for (Aftg). Foundation Design Load Tables. Several steps
must be followed to arrive at the pier and/or
602-3. REQUIRED FOOTING AREAS wall footing sizes:
(Aftg) (APPENDIX B, PART 1)
1. Select the correct Table based on
A. General. The foundation must be ca- the foundation type (C, Cnw, E,I or
pable of transmitting the total gravity load to E5; single-section or multi-section)
the soil without exceeding the net allowable and the unit nominal width (12, 14
soil bearing pressure. The gravity loads consist or 16 feet).
of the unit dead weight, snow load or minimum
roof live load, and occupancy live load. Bear- 2. Enter the selected Table with the
ing against the soil is accomplished with square design ground snow load or mini-
concrete footings under piers and continuous mum roof live load. This step is
linear concrete footings under walls. Compli- slightly different depending on unit
ance with this requirement should prevent ex- Type as follows:
cessive differential settlement.

6 - 14
Type C (single-section or multi- have headings for the various
section), Type Cnw, and Type E, I ground snow load and minimum
multi-section: Blocks of values roof live load magnitudes. Select

Example 1: Type: C - Single-Section Unit; Location: Tampa, FL.; Wt = 14 ft.; L = 60 ft.; Roof Slope: 2 in 12; 4
Transverse Shear Walls; Pier Spacing: 5 ft.; Pg = 0 psf.; Min. Roof LL = 20 psf.; V = 100 mph.;
Coastal; Seismic Av = 0.05; Aa = 0.05; Allowable Soil Pressure: 2000 psf.

Example 2: Type: E - Multi-Section Unit; Location: West Yellow Stone, MT.; Wt = 14 ft.; L = 60 ft.; Roof Slope:
2 in 12; 4 Transverse Walls; Pier Spacing: 5 ft; Pg = 70 psf.; V = 80 mph.; Inland; Seismic Av = 0.40;
Aa = 0.40; Allowable Soil Pressure: 2000 psf. Marriage wall opening width = 14-0.

6 - 15
the correct ground snow load block 602-4. REQUIRED VERTICAL AN-
of values. CHORAGE (Av) IN THE TRANSVERSE
DIRECTION (APPENDIX B, PART 2)
Type E or I single-section: Snow
load is included in the loading com- A. General. The foundation must pro-
bination but is not required to move vide enough structural capacity to resist uplift
to the next step. and overturning forces due to wind pressure
and suction. These forces are resisted by con-
3. Select the row for the required net nections to anchors at the piers or to anchors
allowable soil bearing pressure and along the longitudinal foundation walls. Seis-
proceed horizontally until the de- mic inertia forces generated from the ground
sired, or manufacturers recom- acceleration and the mass of roof and floor
mended, pier spacing is located (see planes of the manufactured housing unit were
the Manufacturers Worksheet in not found to control over wind for overturning
Appendix E, item #10 or #11). in the transverse direction, regardless of
Read and record on the Design whether a single-section or multi-section unit
Worksheet (Appendix F) the re- was analyzed, and regardless of seismic, wind
quired footing areas for interior and or snow zone.
exterior pier footings and continu-
ous marriage wall footings (as re- B. Determine Design Wind Speed. This
quired). step has been done in section 600-4, and is re-
quired for single-section and multi-section
4. When the marriage wall of a multi- units.
section unit has a large opening, the
lower portion of the block of values C. Determine (Av) Value from the Ta-
is also required. Re-use the net al- bles. Refer to Appendix B, Part 2 of the Foun-
lowable soil bearing pressure and dation Design Load Tables. Several steps must
move horizontally until the selected be followed to arrive at the Required Vertical
opening width is found. Read the Anchorage in the Transverse Direction:
required effective footing area
(Aftg) for the piers required at the 1. Select the correct Table based on
ends of the opening. Record on the the foundation type (C, C1, E or I
Design Worksheet (Appendix F). for single-section units and C, E or
I for Multi-section units); 2 tie-
Note: For Types E and I, the exte- downs or 4 tie-downs; 12, 14 or 16
rior wall footing is a minimum foot nominal unit width).
1-0 wide for single or multi-
section units. Read the footnotes at 2. Enter the selected Table and move
the bottom of each table for special down the wind speed column until
cases where for certain ground the design wind speed magnitude
snow loads in combination with an (for Inland or Coastal region) is
allowable soil pressure of 1000 psf reached. Read horizontally across
other minimum footing widths are the row until the desired, or manu-
required.

6 - 16
facturer recommended, pier spacing proceed as above to find the correct
is reached. value. For Type E multi-section
units with 4 tie-downs read two val-
3. Read (Av) and record on the Design ues, first for interior pier locations,
Worksheet (Appendix F) the value and second for exterior longitudinal
with its appropriate units as shown wall locations.
in the table. Steps 1 through 3 were
described for Type C, C1 or I sin- D. Comparison With Home Manufac-
gle-section units. For Type E sin- turers Values (Optional). The value for (Av)
gle-section units or multi-section determined from the Tables must be compared
units with 2 tie-downs, values must to the value supplied by the manufacturer. The
be multiplied by the anticipated home manufacturers uplift resistance value
spacing of connections along the must be equal or greater than the vertical an-
exterior longitudinal walls. For chorage requirement from the Tables.
Type C or I multi-section units se-
lect the Table for 2 tie-downs or 4 602-5.REQUIRED HORIZONTAL AN-
tie-downs (whichever applies) and CHORAGE (Ah) IN THE TRANSVERSE
DIRECTION (APPENDIX B, PART 3)

Example 1:
1

Example 2:
1

6 - 17
A. General. The attachment of the unit that in the transverse direction for single-
to the foundation must provide sufficient struc- section units and for multi-section units, it is
tural anchorage for the manufactured home to necessary to check both wind and seismic to
resist sliding forces due to wind pressures and determine which force controls. These hori-
suctions or seismic inertia forces, whichever zontal forces are resisted by connection of the
controls. Analysis, based on the conservative unit to anchors along the exterior walls, plus
load assumptions of this handbook, has shown any additional interior transverse walls; or by

Example 1:

1
2 4
3

Example 2:
1
3 5

6 - 18
connection of the unit to a combination of exte- 2. Enter the selected Table at the far
rior and interior vertical planes of X-bracing at left and move down either the In-
pier locations. Interior transverse walls may be land or Coastal wind speed column,
either full height or short of the chassis beams as appropriate, until the required
and completed with some form of diagonal MPH value is reached. Slide to the
bracing. See illustration of options in Appendix next column to the right within the
C. block of numbers covered by that
wind speed.
B. Determine Design Ground Snow
Load. This step has been done in section 3. Select the next smaller block of
600-3 and is only required for multi-section numbers based on the required
units, where it may influence seismic values. seismic (Aa). Move to the right to
the next column and locate the re-
C. Determine Design Wind Speed. This quired ground snow load. The
step has been done in section 600-4, and is re- seismic (Aa) and ground snow load
quired for single-section and multi-section columns will in many cases include
units. a range of values (i.e. .05-.30, or
0-100 psf respectively, which
D. Determine Design Seismic Ground means that the group of values cov-
Acceleration Values and Required Seismic ers all values in that range). These
Performance Category. This step has been column movements define a unique
done in section 600-5 and is required for sin- pair of rows of values taking into
gle-section and multi-section units. account wind and seismic lateral
forces.
E. Determine Horizontal Anchorage
(Ah) in the Transverse Direction from the 4. Move to the right until the column
Tables. Refer to Appendix B, Part 3 of the for the known unit length is
Foundation Design Load Tables. Several steps reached. The intersection of that
must be followed to arrive at the Required column and the already located
Horizontal Anchorage in the Transverse Direc- rows represents the correct horizon-
tion: tal anchorage values (Ah) for design
in (lbs./ft.). If the values are
1. Select the correct Table based on grayed, seismic controlled the mag-
single-section or multi-section unit, nitude of the values. In the case of
nominal unit width of 12, 14 or 16 two transverse walls, they will be
feet, and whether 2, 4, or 6 trans- located at the ends of the unit. The
verse walls (the handbook has lim- Location column in the Table will
ited the number of transverse walls state end. If 4 or 6 transverse walls
to 6). Note that the foundation type are selected, there will be two rows
does not influence the required of values; one for end walls and one
horizontal anchorage force, thus the for interior walls.
heading for all the Tables read:
Type C, E or I. help: Choosing the number of trans-
verse foundation walls. As a

6 - 19
guide, increasing the number of be required. Multi-section units
transverse foundation walls reduces may be stable enough so that only
the force per anchor/connection and two transverse foundation walls are
permits an increased spacing be- required. Long, narrow single-
tween anchors. Thus, the user section units, or units in windy or
should begin with the fewest num- high seismic areas, may require
ber of transverse walls - two (2). more than two transverse walls.
Comparison of (Ah) with the hori-
zontal anchorage capacities in Ap- F. Comparison with Manufacturers
pendix C can be simultaneously Values (Optional). The value for the horizon-
verified during the completion of tal anchorage force required for design in the
the Design Worksheet (Appen- transverse direction must be compared to the
dix F). A greater number of trans- value supplied by the manufacturer. The manu-
verse foundation walls (4 or 6) may facturers horizontal anchorage value must be

Horizontal Anchorage with X-bracing - Transverse Direction


Figure 6 - 8

6 - 20
equal to or greater than the horizontal anchor- 2. To use Vertical X-Bracing Planes
age requirements from the Tables. See the with steel straps or rods instead of
Manufacturers Worksheet, item # 16(c) and transverse foundation walls. This
example number 1 in Appendix G. method is possible for Foundation
Concepts C1, C2, E1, E3 and E4
G. Horizontal Anchorage with Diago- only. The required Horizontal An-
nal bracing atop transverse shear walls or chorage Table value of (Ah) must
complete Vertical X-Bracing planes. Diago- be modified as follows:
nal members may be used to complete trans-
verse walls that stop at the underside of the a. Select the required (Ah) value
chassis beams, or complete X-bracing can be from the Table for two (2)
used in lieu of shear walls for transverse foun- transverse foundation walls for
dation walls. Refer to the Transverse Founda- single-section or multi-section
tion Wall Concepts for Types C, E and I in units.
Appendix A, and example number 2 in Appen-
dix G. b. Multiply (Ah) times (Wt), re-
gardless if single-section or
1. To use diagonal steel straps or multi-section unit and then mul-
wood diagonals to complete the tiply that by 2. Finally divide
transverse foundation walls. The that total by the unit length (L)
required Horizontal Anchorage Ta- to generate a horizontal force
ble value of (Ah) for single-section (H) in pounds per foot of unit
or multi-section units must be con- length. The equation follows:
verted to a diagonal tension (Tt) to
size the strap. Ah Wt 2
H (lbs./ft. of length) =
L
a. Multiply the required (Ah) by
(Wt) to calculate the total hori- c. Multiply (H), horizontal force,
zontal force at the transverse by the spacing between vertical
wall under a pair of chassis X-bracing planes to determine
beams. Note: two sets of diago- the horizontal force (C) to be re-
nals, using this force, are re- sisted at each X-brace location.
quired for multi-section units. Thus, for multi-section units (C)
is the applied force at both X-
b. Divide this value by the cosine bracing locations in the vertical
of the angle of the diagonal to plane. This spacing should be
arrive at the tension (Tt) in the some multiple of the pier spac-
diagonal. See Figure 6-10 for ing. The equation follows:
an illustration of this condition.
The equation is as follows: C (lbs./X-brace) = H spacing

Ah Wt d. Divide (C), horizontal force, by


Tt =
cos t the cosine of the angle of the di-
agonals as illustrated in Figure

6 - 21
6-10, to arrive at the required C. Determine Design Wind Speed. This
diagonal tension force in step has been done in section 600-4 and is re-
pounds. The equation follows: quired for single-section or multi-section units.

C D. Determine Design Seismic Ground


Tt (lbs./ diagonal) =
cos t Acceleration Values and Required Seismic
Performance Category. This step has been
e. Compare the required tension done in section 600-5 and is required for sin-
force (Tt) and the required hori- gle-section or multi-section units.
zontal force per X-brace (C)
with the rated capacities sup- E. Determine Design Horizontal An-
plied by the manufacturer in the chorage (Ah) in the Longitudinal Direction
Manufacturers Worksheet, from the Tables. Refer to Appendix B, Part 4
items #16(c and e). See Figures of the Foundation Design Load Tables. Sev-
6-4 and 6-5 for illustrations. eral steps must be followed to arrive at the Re-
quired Horizontal Anchorage in the Longitudi-
602-6 REQUIRED HORIZONTAL AN- nal Direction:
CHORAGE (Ah) IN THE LONGITUDI-
NAL DIRECTION (APPENDIX B, PART 1. Select the correct Table based on
4). single-section or multi-section unit
and nominal unit width (Wt) of 12,
A. General. The attachment of the unit 14 or 16 feet. Note that the founda-
to the foundation must provide sufficient struc- tion type does not influence the re-
tural anchorage for the manufactured home to quired horizontal anchorage force in
resist sliding forces due to wind pressures and the longitudinal direction, thus the
suctions, or seismic inertia forces, whichever heading for the Tables read: Type
controls. Analysis, based on the conservative C, E or I.
assumptions used in this handbook, has shown
that wind or seismic may control in the longi- 2. Enter the selected Table and move
tudinal direction for single-section or multi- down the left-most column until the
section units, thus it is necessary to check both required Seismic (Aa) value is
wind and seismic for all units. These horizon- reached. This defines a large block
tal forces are resisted by connection of the unit of values. Move to the right to the
to anchors in the exterior longitudinal walls, or next column and locate the required
by connection of the unit to vertical planes of ground snow load. This defines a
X-bracing under and along the chassis beams smaller block of values. Move to
(between piers). the next column to the right and lo-
cate the inland or coastal block of
B. Determine Design Ground Snow values and lastly find the required
Load. This step has been done in section wind speed within that same col-
600-3 and is required for single-section or umn. This now defines a single row
multi-section units. of values that represents compari-
son of seismic and wind effects.

6 - 22
3. Select the column which represents suffice as shear walls in the longi-
the length of the unit. The intersec- tudinal direction. See example
tion of that column and the already number 1 in Appendix G. For Type
determined row locates the required C units, vertical X-bracing planes
horizontal anchorage value (Ah) in under and along the exterior chassis
the longitudinal direction along two beam lines (between piers) are re-
lines; either the two exterior longi- quired. See Section 602-6.F for
tudinal walls for Type E or I or guidance.
along the two exterior chassis
beams for Type C. F. Horizontal Anchorage with X-
bracing for the Longitudinal Direction. Di-
Help: for Type E or I units, longitudinal agonal members under and along the exterior
exterior walls will exist, and will chassis beams may also be used in lieu of exte-

Example 1:
1
2 3

Example 2:
1

2 3

6 - 23
rior longitudinal shear walls. If galvanized Ah L
B(lbs./X-brace) =
steel diagonal members are used instead of full n
height exterior foundation walls, the required
Horizontal Anchorage Table value of (Ah) Note: For multi-section units
must be modified as follows: using all four (4) chassis beam lines
as vertical X-bracing lines, divide
1. Select the required (Ah) value from the above equation by 2 (see Fig.D-
the Tables in Part 4, Appendix B for 26 for an example).
single-section or multi-section
units. 3. Divide (B) by the cosine of the an-
gle of the diagonals as illustrated in
2. Multiply (Ah) times the manufac- Figure 6-11, to arrive at the required
tured home unit length (L) and di- diagonal tension force in pounds.
vide by the selected number of X- The equation follows:
brace locations (n) along one exte-
rior chassis beam to generate the to- B
TL (lbs./ diagonal) =
tal horizontal force (B) to be re- cos L
sisted at each X-brace location
along each chassis beam for single- 4. Compare the required tension force
section units, and along each exte- (TL) and the horizontal force to each
rior chassis beam for multi-section X-brace (B) with the rated capaci-
units. As an example, there are ties supplied by the manufacturer in
three (n = 3) X-brace locations the Manufacturers Worksheet,
along each chassis beam for the sin- items #16(c and e), or supplied by
gle-section unit in Figure 6-6. The another vendor.
equation follows:
603. USING THE FOUNDATION

Horizontal Anchorage with X-bracing - Longitudinal Direction


Figure 6 - 9

6 - 24
CAPACITIES TABLES (APPEN- 1. For longitudinal foundation walls,
DIX C) compare the required value for (Av)
with the numbers in the columns in
603-1. GENERAL. The Foundation Capaci- Table C-1 (for foundation Type E).
ties Tables in Appendix C will be used to find
the required size and depth of footings, the re- a. Find a number in the table that
quired sizes and spacing of anchors, and neces- is greater than (Av). There may
sary reinforcement. There are three conditions be several numbers that meet
that will be investigated: 1) Vertical Anchorage this criteria.
( uplift and overturning) requirements for lon-
b. Any number that is greater than
gitudinal foundation walls and piers, 2) Hori-
(Av) means that the foundation
zontal Anchorage (sliding) in the transverse
type and footing width (found at
direction (for transverse foundation walls that
the top of the column) can be
function as shear walls), and 3) Horizontal An-
used. The number (hw) in the
chorage (sliding) in the longitudinal direction
column on the left indicates how
(for longitudinal foundation walls that function
deep the footing should be
as shear walls).
placed to resist the uplift and
603-2. REQUIRED VERTICAL AN- overturning force. Example cal-
CHORAGE: LONGITUDINAL FOUNDA- culations are included in Ap-
TION WALLS AND PIERS pendix C if alternate footing
widths are desired.
A. Determining Footing Depth for
Longitudinal Foundation Walls and Piers. 2. For isolated pier foundations and
This involves selecting sufficient counter- concrete tie-down blocks (Concept
weight of material dead loads (wall or pier, Type C1), compare the value for the
footing and soil) to resist the required uplift. required (Av) with the numbers in
The field officer determines how deep the foot- the columns in Table C-2 (for foun-
ings must be placed. In frost-prone areas, the dation Types C or I and type E with
footing must at least be placed below the ex- 4 tie downs).
treme frost depth below grade (map, page H-4).
a. Find a number in the table that
In windy or seismic areas, it may also be nec-
is greater than (Av). There may
essary to place the footing deeper in the soil
be several numbers that meet
than frost protection alone would require.
this criteria.
Burying the footing deeper gives it greater
withdrawal resistance--it is harder to pull it out b. Any number that is greater than
of the soil. (Av) means that the width of the
square footing (found at the top
B. Determine Required Withdrawal
of the column) can be used. The
Resistance. It is necessary to compare the val-
number hw in the left-hand col-
ues obtained from the Foundation Design Load
umn indicates how deep the
Table for (Av) with Tables C-1 or C-2 of Ap-
footing should be placed to pro-
pendix C.
vide adequate withdrawal resis-

6 - 25
tance. Example calculations are ments, based on the anchor bolt
included in Appendix C if alter- diameter selected in Table C-3.
nate footing widths are desired.
The same Table C-2 can con- d. Refer to the illustration next to
servatively be used for concrete Table C-2 for the required foot-
deadman footing sizes for con- ing reinforcement.
cept Type C1.
e. Refer to the Foundation Type
C. Foundation System Verification. C1 (Appendix A) Design Con-
The HUD field office should verify that the cept for the tie-down bar size.
foundation system selected has sufficient depth
to withstand uplift. Regardless of the required f. Sample calculations are in-
depth for uplift or overturning, the footing cluded in Appendix C if alter-
must always be placed below the extreme frost nate reinforcement sizes, spac-
depth below grade. ings or material grades are de-
sired.
D. Determine Required Anchorage and
Reinforcement for Longitudinal Foundation 2. For longitudinal foundation walls,
Walls and Piers. The field officer will now start with Table C-4A for concrete
verify the kinds of anchorage (steel anchor or concrete masonry walls, or C-4B
bolts) and reinforcement (steel reinforcing for a treated wood wall.
bars) that will be needed to tie together the
a. Compare the required value for
footing, wall or pier, and the unit itself. The
(Av) with the numbers in the
field officer will refer to Table C-3: Vertical
left hand column of Table C-4.
Anchor Capacity for Piers and Table C-4A or
C-4B: Vertical Anchor Capacity for Longitudi- b. Find a number that is greater
nal Foundation Walls (Appendix C). than the required (Av).
1. For piers, use Table C-3. c. Read across the column and
find:
a. Compare the required value of
(Av) with the capacity numbers. 1) For masonry and concrete
foundations (Table C-4A):
b. Find a capacity number that is
greater than the required value (a) Anchor bolt size and
for (Av). The number of anchor spacing.
bolts is listed at the top of the
column. The diameter of the (b) From Table C-3A, rein-
anchor bolt is listed in the left forcing-bar size, lap
column. splice, and hook length.
c. Move to Table C-3A to find the 2) For treated wood founda-
reinforcing size, lap splice, and tions (Table C-4B):
reinforcing-bar hook require-

6 - 26
(a) The required nailing. 4. The required anchorage for the
transverse foundation wall can be
(b) The minimum plywood read across the columns for:
nailer thickness.
a. Masonry and Concrete Founda-
(c) The required anchor bolt tions (Table C-5A):
size and spacing.
1) Anchor bolt diameter.
3) Example calculations are
included in Appendix C if 2) Reinforcing bar size.
alternate reinforcement
sizes, spacings or material 3) Anchor bolt spacing.
grades are desired.
4) Based on the anchor bolt
603-3. REQUIRED HORIZONTAL AN- size, refer back to Table
CHORAGE: TRANSVERSE FOUNDA- C-3A to obtain the follow-
TION WALLS ing values:

A. Horizontal Anchorage in the Trans- (a) Minimum lap splice.


verse Direction. This involves connections to
avoid sliding between the unit and its founda- (b) Reinforcing bar hook.
tion. The field officer will compare the re-
b. Treated Wood Foundations
quired value for (Ah) with Tables C-5 of Ap-
(Table C-5B):
pendix C: Horizontal Anchor Capacity for
Transverse or Longitudinal Foundation Walls. 1) Required nailing.
See example number 1 in Appendix G.
2) Minimum plywood nailer
1. Compare the required value for thickness.
(Ah) with the numbers in the left
hand column of Table C-5A or 3) Anchor bolt diameter.
C-5B.
4) Anchor bolt spacing.
2. Find a number that is greater than
the required (Ah). 5. Example calculations are included
in Appendix C if alternate rein-
3. If none of the numbers is greater forcement sizes, spacings or mate-
than (Ah), go back to Section rial grades are desired.
602-5.E and increase the number of
transverse foundation walls until the 603-4 REQUIRED HORIZONTAL AN-
required value of (Ah) is small CHORAGE: LONGITUDINAL FOUNDA-
enough to be used in the Horizontal TION WALLS
Anchor Capacities Tables C-5A or
C-5B. A. Horizontal Anchorage in the Longi-
tudinal Direction. This involves connections

6 - 27
to avoid sliding between the unit and its foun- compare the required horizontal anchorage
dation in the longitudinal direction. The field value at each diagonal with Table C-5A of Ap-
officer will check compliance with the required pendix C to verify adequacy of connection be-
value for (Ah) in the longitudinal direction tween diagonal and footing. See example
with Tables C-5 of Appendix C: Horizontal number 2 in Appendix G.
Anchor Capacity for Transverse or Longitudi-
nal Foundation Walls. The process is identical 1. Transverse Direction. Use the hori-
with that of section 603-3 for transverse walls zontal anchorage force (C) per di-
and will not be repeated here. See example agonal found in section 602-5.G.2.c
number 1 in Appendix G. and Figure 6-10.

603-5 DIAGONALS USED TO COM- a. Compare the value for (C) with
PLETE TRANSVERSE WALLS the bottom number in the left
hand column of Table C-5A.
A. Horizontal Anchorage. Determine The capacity listed for 1/2"
the required horizontal anchorage force by bolts at a 12" spacing is equal to
multiplying the required (Ah) by the unit width the single-bolt capacity for an-
(Wt). Reference section 602-5.G.1.a and Figure chorage of diagonals.
6-10 for the required horizontal force (Ah)
(Wt). b. Divide (C) by the number in the
table to determine the number of
1. Compare this value with the bottom bolts required for diagonal an-
number in the left hand column of chorage.
Table C-5A. The capacity listed for
1/2" bolts at a 12" spacing is equal c. Refer back to Table C-3A, to
to the single-bolt capacity for hori- obtain the following values:
zontal anchorage of diagonals.
1) Minimum lap splice.
2. Divide (Ah) (Wt) by the number
in the table to determine the number 2) Reinforcing bar hook.
of bolts required for diagonal an-
2. Longitudinal Direction. Use the
chorage.
horizontal anchorage force (B) per
diagonal found in section 602-6.F
603-6 REQUIRED VERTICAL X-
and Figure 6-11..
BRACING PLANES IN THE TRANS-
VERSE AND/OR LONGITUDINAL DI- a. Repeat steps (a.) to (c.) as for
RECTIONS IN PLACE OF TRANSVERSE the transverse direction, using
WALLS (B) instead of (C).
A. Horizontal Anchorage with Diago- 603-7. CONCLUSION. Values for the veri-
nal Members. This involves connection of the fication of the manufactured home foundation
ends of the diagonal straps to the unit and to have now been obtained.
the foundation. The HUD Field Office will

6 - 28

You might also like