Greenhouse Ventilation and Cooling
Greenhouse Ventilation and Cooling
4. Determine the number of fans required. Because fans should not be over 25
feet apart and will be mounted on a 50 foot wall: 50 feet / 25 feet = 2 fans.
5. Determine the minimum size for each fan by dividing the TOTAL CFM by
the number of fans found in step 4: 44,800 cfm / 2 fans = 22,400 cfm per fan.
6. Next determine the pad area. Divide the capacity of all fans by the capacity
of the 4-inch pads per square foot: (22,400 cfm 2 fans) / 250 cfm = 179.2
square feet.
7. Divide this value by the length of the wall to get the required pad height:
179.2 / 50 = 3.6 feet
8. The pump capacity for a 4-inch thick pad is 0.5 gpm per linear foot of pad
and 1-inch water-distribution pipe. The pad length is 50 feet: pump capacity
= 0.5 gpm 50 ft = 25 gpm
9. The sump tank is 0.75 gal/ft2 of 4-inch thick pad. Multiply this value time the
total square feet of pad area found in #6: 0.75 gal/ft2 179.9 ft2 = 134.4
gallons
Table 1. Factor used to correct rate of air removal for elevation above sea level.
feet < 1000 2000 3000 4000 5000 6000 7000 8000
1000
FElev 1.00 1.04 1.08 1.12 1.16 1.20 1.25 1.30 1.36
Table 2. Factor used to correct rate of air removal for interior light level.
FC 4000 4500 5000 5500 6000 6500 7000 7500 8000
FLight 0.80 0.90 1.00 1.10 1.20 1.30 1.40 1.50 1.60
Table 3. Factor used to correct rate of air removal for pad-to-fan temperature rise.
F 4 5 6 7 8 9 10
FTemp 1.75 1.40 1.17 1.00 0.88 0.78 0.70
Table 4. Factor used to correct rate of air removal for pad-to-fan distance.
Feet 20 25 30 35 40 45 50 55 60
Fvel 2.24 2.00 1.83 1.69 1.58 1.48 1.41 1.35 1.29
Feet 65 70 75 80 85 90 95 100
Fvel 1.24 1.20 1.16 1.12 1.08 1.05 1.02 1.00
Two-Stage Evaporative Cooling
Water that leaves a direct evaporative cooler at the bottom of the unit has a
temperature close to that of the wet bulb temperature of the
outgoing airstream. In the two-stage
evaporative cooling setup, that chilled water is then led through an air-to-
water heat exchanger to pre-
cool the hot air before it is cooled down further by the direct
evaporative cooler.
In terms of energy balance, nothing has changed compared to the standard dir
ect
evaporative cooling principle; overall, it is still an adiabatic cooling process. How
ever, whereas the direct evaporative cooler has a uniformly distributed temperature
profile at the side of the outlet air, the two-stage evaporative cooler shows a vertical
temperature gradient: further down the air temperature gradually decreases.
Typically, the lower 60% of the outgoing air has a specific enthalpy lower than that of
the inlet air. Whereas the temperature
of the outlet air from a direct evaporative cooler is restricted to the wet bulb
temperature, in this case, when taking only the lower 50% of the outlet air from the
two-stage evaporative cooler the temperature can even be lower than the initial wet
bulb temperature. The corresponding wet bulb efficiency will then be higher than 100%.
The figure below shows the cooling process of a standard direct evaporative cooler.
The figure below shows the cooling process of the two-stage evaporative cooler in
which
the exact same amount of air is flowing through the system as in the configur
ation above.