Professional Documents
Culture Documents
DATA:
Outdoor condition is 28oC, 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
The Apparatus Dew Point ADP is 8oC
Neglect the cooling coil contact factor.
Note:
The cooling coil output of 38.2 kW is a much higher value than the sensible
heat gain of 10.8 kW.
It should be remembered that the difference is these two values is mostly
from the fresh air cooling load.
It takes quite a lot of energy in summer to cool fresh air coming into air
handling units.
This can be minimised by bringing in minimum fresh air but not too
little otherwise the building will suffer from lack of oxygen and feel stuffy.
Sometimes mistakes are made when sizing cooling apparatus.
If a cooling coil or indoor cooling unit is sized on the sensible heat gain
only without allowing for fresh air load then it will be grossly undersized.
That is why psychrometric charts are required to calculate cooling coil
output including fresh air loads.
So, don’t size cooling coil and indoor cooling units on sensible heat
gain only if there is fresh air coming into the plant.
Size these items of plant using a psychrometric chart.
Determine the supply air temperature and heater battery load using the
following information.
DATA:
Indoor condition: 21oC dry-bulb temperature, 50% saturation.
Outdoor condition: -2oC d.b., 80% saturation.
The outdoor air and recirculated air ratio is 20%/80%.
No preheating or humidification takes place in this simplified example.
Procedure (Winter Cycle)
1. Draw schematic diagram of air-conditioning plant (see above)
4. No Preheater condition P
5. Join points O and R
6. Find the mix point M by measuring the length of the line O-R
and multiply this by the mixing ratio.
On a full size CIBSE psychrometric chart this measures 110mm.
The ratio of recirculated air is 0. therefore; 110mm x
0.8 = 88mm
Measure up the O-R line from point O by 88mm.
This determines point M .
If there is more recirculated air than outside air at the mix point, then
point M will be closer to point R than point O.
7. Find the room ratio.
This is the sensible to total heat ratio.
Neglect signs ie. the total heat for the room will be Sensible loss plus
Latent gain.
Total heat = 18 kW sensible + 4.5 kW latent = 22.5 kW total.
Heat ratio = 18 / 22.5 = 0.8
Plot this ratio on the protractor, top segment, on the psychrometric chart
and transfer this line onto the chart so that it passes through point R.
Hs = ma x Cp ( ts - tr )
where:
Hs = Sensible heat loss (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg
degC)
tr = room temperature
(oC)
ts = supply air temperature
(oC) ..............therefore:
ma = Hs / Cp ( ts - tr )
ma = 18 / 11.615
ma = 1.55 kg/s
Heater Battery Output
The heater battery output is as follows:
where:
H reheater battery = Reheater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
hM = specific enthalpy at condition M (kJ/kg)
5. Find the mix point M by measuring the length of the line O-R and multiply
this by the mixing ratio.
On a full size CIBSE psychrometric chart this measures 85mm.
The ratio of recirculated air is 0.8. …….. therefore; 85mm x 0.8 =
68mm
Measure down the O-R line from point O by 68mm.
This determines point M .
6. Find the room ratio. This is the sensible to total heat gain ratio.
Total heat = 8 kW sensible + 2 kW latent = 10 kW total.
Heat ratio = 8 / 10 = 0.8
Plot this ratio on the protractor, bottom segment, on the psychrometric
chart and transfer this line onto the chart so that it passes through point R.
7. Plot the Apparatus Dew Point ADP of the cooling coil.
This is on the 100% saturation curve. The ADP is 80C.
8. Join points M and ADP.
9. Find the off-coil condition W by measuring the length of the line M-ADP and
multiply this by the cooling coil contact factor..
On a full size CIBSE psychrometric chart this measures 75mm.
The cooling coil contact factor is 0.8. ……….. therefore; 75mm x 0.8 =
60mm.
Measure down along the line M-ADP by 60mm.
This determines point W.
10. Plot the supply air condition S.
The reheater process will be a horizontal line from point W to point S.
Point S is on the room ratio line.
The supply air temperature is 17oC.
ma = Hs / ( Cp ( tr - ts ) )
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01
kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
ma = 8 / ( 1.01 ( 22 - 17 ) )
ma = 1.584 kg/s
where:
H cooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined from
psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined
from psychrometric chart
H cooling coil = 40.4 kW
Heater Battery Output
The heater battery or reheater output is as follows:
H heater battery = ma ( hS - hW)
where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg) determined
from psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg)
determined from psychrometric chart.
H heater battery = 9.5 kW
Example 4. Winter Cycle with Humidifier
An conference room is to be maintained at 21oC dry-bulb temperature, 50%
saturation in winter.
The latent heat gain is 40 Watts per person (see Air Conditioning section).
Determine the preheater and reheater outputs required and the amount of
moisture to be added at the humidifier in litre/hour, by using a psychrometric
chart if the plant schematic is as shown below.
DATA:
Outdoor condition is -2oC, 80% saturation.
The outdoor air and recirculated air ratio is 50%/50%.
Maximum occupancy is 250 people.
The preheater off coil temperature is 5oC.
Supply air quantity is 8 air changes per hour.
Room volume is 20 x 12 x 4m high = 960 m3.
Latent Heat Gain
The latent heat gain = heat gain per person x number of people
Supply air mass flow rate (kg/s) = Supply air quantity (m3/s) / Specific
Volume (m3/kg)
Supply air mass flow rate (kg/s) = 2.13 (m3/s) / 0.87 (m3/kg)
The fresh air flow rate (kg/s) = 2.45 kg/s x 50% = 1.23 kg/s
Winter Cycle Psychrometrics
1. Draw schematic diagram of air-conditioning plant (see above).
2. Plot room condition O, M and R on psychrometric chart.
3. Plot the after Preheater condition P.
The Preheater process will be a horizontal line from O to P and acts
as a frost coil in this case, heating the air to 5oC.
4. Join points P and R.
5. Find the mix point M by measuring the length of the line P-R
and multiply this by the mixing ratio.
The line measures 82mm long.
82 x 0.5 = 41 mm
6. Find the room ratio.
Plot this ratio on the protractor, so that it passes through point R.
Total heat is 17 kW sensible + 10 kW latent = 27kW.
Ratio is 17/27 = 0.63.
7. Find the supply air dry bulb temperature by calculation.
This is found by calculation because we have already calculated
the mass flow rate of supply air from information given in the question.
( ts - tr ) = Hs / ma x Cp
H preheater battery = 8.0 kW
Reheater Battery Output
Humidifier Output
The amount of moisture added to the air may be calculated from the
following formula:
Example 5 Summer Cycle (Air Flows To Be
Calculated)
A Lecture Theatre measures 15 m x 10 m x 6 m high.
It is to be air conditioned in summer so that the room is maintained at 22 oC
dry-bulb temperature, 50% saturation.
Determine the cooling coil and reheater outputs required by using a
psychrometric chart if the plant schematic is as shown below.
DATA:
Outdoor condition is 28oC, 80% saturation.
The Apparatus Dew Point ADP is 7.5oC.
The latent heat gain is 10.0 kW.
The sensible heat gain is 12.0 kW.
Maximum occupancy is 200 people.
The cooling coil contact factor is unknown at present and should be
calculated.
Use CIBSE guide B2 (2001) to determine air flow rates and calculate the
mass flow rate of fresh air and supply air to the room.
The lecture room may be taken as an Assembly hall.
The room is a non-smoking area.
Mass Flow Rates
Information from CIBSE Guide B2 (2001) Table 3.3 is as follows (see
Ventilation – Ventilation rates section);
The recommended outdoor air rate is 8 l/s/person for non-smoking.
Information from CIBSE Guide B2 (2001) Table 3.1 is as follows (see
Ventilation – Ventilation rates section);
Assembly halls and auditorium refers to Table 3.6 (see Ventilation –
Ventilation rates section);
The recommended total air supply rate is 6 – 10 air changes per hour for
high level mechanical strategy.
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01 kJ/kg
degC)
tr = room temperature
(oC)
ts = supply air temperature (oC)
( tr - ts ) = Hs / ( ma x Cp )
( tr - ts ) = 12 / ( 3.00 x 1.01 )
( tr - ts ) = 3.96 deg.C
since tr = 22oC
ts = 22 - 3.96 = 18.04 oC
ts = 18 oC approx.
H cooling coil = 120.0 kW
Reheater Battery Output
The heater battery or reheater output is as follows:
H heater battery = 28.5 kW
Example 6 Summer Cycle and Winter Cycle
A Concert Hall measures 40 m x 20 m x 8 m high.
It is to be air conditioned in summer and winter.
Determine the following:
o Air flow rates
o Supply air temperature by calculation in summer and winter.
o Cooling coil contact factor.
o Cooling coil and reheater outputs in summer
o Humidifier output in litres/hour.
The plant schematic is as shown below.
DATA:
Indoor condition all year - 22oC dB temperature, 50% saturation.
Outdoor condition summer - 28oC dB temperature, 80% saturation.
Outdoor condition winter - -3oC dB temperature, 80% saturation.
Maximum occupancy - 1000 people.
ADP of the cooling coil - 8oC
Fresh air requirement - 12 l/s/person
Supply air rate - 8 air changes per hour.
Frost off coil temperature - 7oC.
Latent heat gain - 40 W/person
Sensible heat gain in summer - 100 W/person + 20.5 kW fabric,
lights, solar & ventilation gains.
Sensible heat loss in winter - 20 W/m3 air volume (estimated)
Fresh air rate = 12 l/s/p x 1000 people = 12,000 l/s = 12.0 m3/s
The specific volume at the outside condition may be determined from a
psychrometric chart.
It is approximately 0.88 m3/kg.
Mass flow rate = Volume flow rate / specific volume
Mass flow rate (Fresh Air) = 12.0 / 0.88 = 13.64 kg/s.
The ventilation supply air rate is taken from table B2.3 and is given as 8 air
changes per hour; the mass flow rate can be calculated.
Volume flow rate (m3/h) = Volume of room (m3) x air change rate
(ac/h)
Volume of room (m3) = 40 x 20 x 8 = 6400 m3
Volume flow rate (m3/h) = 6400 (m3) x 8 (ac/h)
Volume flow rate (m3/h) = 51,200 m3/h
Volume flow rate (m3/s) = 51,200 / 3600 = 14.22 m3/s.
Mass flow rate = Volume flow rate / specific volume
The specific volume at the supply condition may be approximated at this
stage from a psychrometric chart. It can be taken as 0.834 m 3/kg.
Mass flow rate (Supply Air) = 14.22 / 0.834 = 17.05 kg/s.
Heat Gains
Heat Loss
In this example the supply air temperature will be found by rearranging the
following formula:
Hs = ma x Cp ( tr - ts )
where:
Hs = Sensible heat gain to room (kW)
ma = mass flow rate of air (kg/s)
Cp = Specific heat capacity of humid air (approx.1.01
kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
Rearranging the above formula gives:
( tr - ts ) = Hs / ( ma x Cp )
( tr - ts ) = 120.5 / ( 17.05 x 1.01 )
( tr - ts ) = 7.0 deg.C, since tr = 22oC, ts = 22 - 7.0 =
15.0 oC
ts = 15 oC
The processes can now be plotted on a psychrometric chart as shown
below.
1. Points O, M and R can be shown on the chart.
2. Point ADP can be indicated and lines drawn between these points as
shown.
3. The room ratio line can be drawn.
4. Point S is then shown on the chart, on the room ratio line at 18 oC.
5. A horizontal line is then drawn from point S towards the line O – ADP.
6. Point W can then be found where the horizontal line W - S intersects the
line O - ADP.
Reheater Battery Output in Summer
The heater battery or reheater output is as follows:
H heater battery = ma ( hS - hW)
where:
H heater battery = Heater battery output (kW)
ma = mass flow rate of air (kg/s)
hS = specific enthalpy at condition S (kJ/kg)
determined from psychrometric chart.
hW = specific enthalpy at condition W (kJ/kg)
determined from psychrometric chart.
The specific enthalpies at points W and S are shown on the
psychrometric Chart above.
H heater battery = 17.05 ( 34 - 28)
H heater battery = 102.3 kW
Winter Calculations & Process
Winter Cycle Psychrometrics
The processes can now be plotted on a psychrometric chart as shown
below.
1. Points O, M, P and R can be shown on the chart.
2. Join points O and P and P and R.
3. Find the mix point M
The line measures 81mm long.
81 x 0.8 = 65 mm , the distance from point M to R is
65mm.
4. The room ratio is 0.76 from previous calculation. Draw
RRL.
5. Find the supply air dry bulb temperature by calculation.
Supply Air Temperature by Calculation
The temperature of supply air is calculated from the following formula:
Hs = ma x Cp ( ts - tr )
where:
Hs = Sensible heat loss from room (kW)
ma = mass flow rate of air (kg/s) same as
summer rate for constant volume systems.
Cp = Specific heat capacity of humid air
(approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature(oC)
( ts - tr ) = Hs / ma x Cp
( ts - tr ) = 128 / 17.05 x 1.01
( ts - tr ) = 7.43 deg.C
ts = 22 + 7.43 deg.C
ts = 29.43 oC say 29.5 oC.
6. Plot the condition H at 29.5oC dB. on a horizontal line from M.
7. Plot condition S on a vertical line from H on the RRL.
Assume the humidity process is vertical.
DATA:
Outdoor condition is 27oC, 80% saturation.
The Apparatus Dew Point ADP is 8oC
The internal latent heat gain is 40 W per person, plus additional gain of 5
kW.
The internal sensible heat gain is 200 Watts per computer, 100W per
person and 15 W/m2 floor area for lights.
The solar gain through windows is 6.0 kW
Maximum occupancy is 80 people.
Number of computers is 80.
The cooling coil contact factor is 0.8.
Duct and fans gains are 2oC.
Fresh air, recirculated air ratio is 20%/80%.
HEAT GAINS
ma = Hs / ( Cp ( tr - ts ) )
where:
H s = Sensible heat gain to room (kW)
m a = mass flow rate of air (kg/s)
C p = Specific heat capacity of humid air (approx.1.01 kJ/kg degC)
tr = room temperature (oC)
ts = supply air temperature (oC)
where:
Hcooling coil = Cooling coil output (kW)
ma = mass flow rate of air (kg/s)
hM = specific enthalpy at condition M (kJ/kg) determined
from psychrometric chart.
hADP = specific enthalpy at condition ADP (kJ/kg) determined
from psychrometric chart
H cooling coil = 105.4 kW
Reheater Battery Output
The heater battery or reheater output is as follows: H heater battery = ma ( hS -
hD)
where:
H heater battery = 6.5 kW
http://www.arca53.dsl.pipex.com/index_files/psy1.htm