You are on page 1of 30

Air Cooled Water

Chiller and Heat Pump


20kW-860kW

Vicot Air Conditioning Co., Ltd


ABOUT US
Vicot Group is a high-tech corporation specialized in R&D, production, sales and service of renewable
energy products.
The corporation has almost 2000 staff and nine business divisions and/or centers as following: Solar
Thermal Energy Equipment Division, Vacuum Tube Division, Gas Fired Air Conditioning Division, Electrical Air
Conditioning Division, Domestic Marketing & Sales Division, Export & Import Division, Administrative & Human
Resource Center, Company Management Center and General Manager Office.
Our production base locates in Solar City, Dezhou, China, it covers an area of 150,000 m2 with modern
workshops and office buildings of more than 80,000 m2. Annual yield capabilities are as follows: 100,000
electrical AC units; 10,000 gas fired AC units; 200,000 m2 of collectors; 100,000 pieces of tubes; 5,000 standard
sets of solar air conditioning system (20kW/ standard set), 200,000 standard sets of S.A.P central hot water
system (10T/ standard set), 10,000 standard sets of S.A.P central distributed heating system (40kW/ standard
set) and 500 standard sets of solar boiler system (700kW/ standard set). Designed annual production value
reaches RMB 5 billion.
With the mission of “The same breath, energy saving together”, the corporation realizes energy saving
and environment protection by focusing on effective utilization of solar energy, air source energy, geothermal
energy and other renewable energies in cooling, heating and domestic hot water fields, in pursuit of
technology innovations in the field of global renewable energy utilization.
After years’ practice in geothermal chiller & heat pump, air source chiller and heat pump and floor
heating fields, Vicot accumulates rich experience in development and production and reaches a nationally
advanced level. With a total investment of RMB 16 million in April 2008, after 3 years’ collaboration with more
than 20 global universities and research institutes in sequence, Vicot successfully and innovatively launched
solar air conditioning system, S.A.P central hot water system, S.A.P central distributed heating system, solar
boiler system, having more than 150 patents, large scale production of them has been realized, the past and
current scientists and engineers’ cherished wish has been realized. It places China at the world top level in
solar medium temperature application field, it turns the dream into truth, for solar energy scale application in
commercial and industrial field.
In the meantime of developing the technology of world leading new energy product, the corporation
is operated with global advanced ERP technique, UPDI\WMS barcode storage system and ABC cost control
system. Information, logistics and cash flow are highly integrated, which austerely shows its concept of “Quality
based on science, Price optimized for customer”.
Air Cooled Water Chiller & Heat Pump

Contents

Introduction Installation & Maintenance

Features Wiring at Site

Nomenclature Dimension

Variable
Optional accessories performance

Technical specification

19
15
9
8

1 1 2 2 3
Introduction
VICOT air cooled water chiller and heat pump is a new developed generation of VICOT
modular unit. It is energy-saving and convenient in use, with functions of reverse cycle
automatic defrosting, double steps automatic anti-freezing, built-in self-diagnosable
system, and microcomputer controll. It can be applicable to hotels, villas, hospitals,
cinemas, stadiums, recreations, office blocks, factories and so on. It can also provide
chilled water or moderate hot water for industrial purpose.
The unit is installed at outdoor such as roof, floor and porch and does not need machine
room, which saves user's initial investment cost. And also, the unit is easy to install,
manage and maintain.
Product series:
VFS series: mini type, scroll compressor, cooling capacity: 20kW-45kW
VM series: modular type, scroll comperssor, cooling capacity: 65kW-380kW
VM...L series: screw compressor type, cooling capacity: 180kW-860kW

Features
1. Optimized design
VFS series adopt packaged design, with V-shaped condenser, built-in water pump and
expansion tank. It is easy to be installed. Each unit has two or three independent cooling
circuits, easy to maintain.
VM series are modular design and can realize 12 pieces of parallel connection at most.
Use V-shaped or reverse M-shaped condenser according to different capacities and
requirements.
VM...L series use internationally famous brand half-hermatic screw compressor, insuring
its reliablity and stability. It can used in worse working condition.

2. Automatic intelligent control


Unit's running and management is controlled and finished by microcomputer control
system, being easy to operate.
According to cooling load, controller automatically starts or stop corresponding
compressors, insuring unit is running at most economic state.
Multiple protection functions, like fault self-detecting system, automatic balancing
compressor running time function, anti-freezing function, defrosting function, etc.

3. Intelligent anti-freezing
The unit adopts dual-class or triple-class automatic anti-freezing protection, preventing
the water system from damage once the chilled water inside the pipeline freezes in
winter. When the water temperature rises after automatic heating operation or pump
operation, the unit will automatically exit the anti-freezing control.

1
Air Cooled Water Chiller & Heat Pump

Features

I ntro d u c ti o n
4. Intelligent defrosting
Each module is completely separate with each other, so is the internal cooling system,
and controls the operation of the system independently, not affecting each other on
start-up. It is available to set the parameters required for automatic defrosting according

Featu res
to different climatic conditions (ambient temperature and humidity) to make defrosting
thorough and energy-saving, thereby improving heating efficiency in winter. There is no
significant influence to the indoor air-conditioning temperature.

Nomenclature
5. Easy to install, operate and maintain
Don't need cooling tower and machine room. Users only need to connect power and
water pipes at installation site. Each unit has several cooling circuits. When one of them
is fault, it will not affect others.

Accessories
Nomenclature
VM N 068 M Z

Tech. spec.
Z: Master module
F: Slave module

Variable perf.
M: Reverse M-shaped condenser
V: V-shaped condenser
L: Screw compressor

Cooling capacity kW

Dimension
N: Heat pump
A: Cooling only

VICOT Air Cooled


VM: Modular/screw type Wiring at site
VFS: Mini packaged type

Optional accessories
Inst. & maint.

Water flow switch Rubber absorber

Flexible joint Heat recovery

Water pump Remote controller

2
Technical specification
Specification I - Mini Air Cooled Water Chiller
VFS Series
Model VFSA020V VFSA025V VFSA030V VFSA045V
VFSN020V VFSN025V VFSN030V VFSN045V
Cooling Capacity kW(R22) 20 25 30 45
Heating Capacity kW(R22) 22 28 33 50
Cooling Capacity kW(R407c) 19 24 29 43
Heating Capacity kW(R407c) 21 27 31 48
kW(R22) 6 7.5 9 13.5
Heat Recovery
kW(R407c) 5.7 7.1 8.6 12.8
o
Domestic Hot Water Inlet Temp C 50
(Optional) Outlet Temp o
C 55
Water Flow m3/h 1.1 1.3 1.6 2.4
Water Pipe Size - 1 in 1 in 1 in 1 in
Type - Hermetic Scroll Compressor
Compressor Power Input kW 6.6 8.2 8.3 12.5
Energy Steps - 0-50-100% 0-33-67-100%
Type - Axial Type, Top Discharge
Fan
Power Input kW 0.37*2 0.37*2 0.55*2 0.55*2
Type - Plate Type Shell & Tube
Water-Side
Water Flow m3/h 3.5 4.3 5.2 7.8
Heat Exchanger
Drop Water Side kPa 28 30 32 40
Type - Cycle Pump
Water Pump Power Input kW 0.75 0.92 1.2 1.2
Head mH2O 16 21 26 28
Type - R22/R407c
Refrigerant Charge Amount kg 5.8/5.8 6.8/6.8 7.6/7.6 11.4/11.4
Expansion Device - Capillary
Water pipe connection size G 1-1/4 G 1-1/2
*
Power 3φ-380V-50Hz
Waterproof Class IPX4
Electric-Shock-Proof Class I
Total input kW 8.09 9.86 10.6 14.8
Length mm 1515 1515 1715 1715
Width mm 915 915 1015 1015
Height mm 1785 1785 1785 1785
Weight (net/operating) Kg 450/470 480/500 530/550 580/600
Noise dB(A) 67 67 68 69
Note: 1- Standard cooling work condition: Ambient Temp: DB 35oC, WB 24oC; cooling water inlet 12oC, outlet 7oC.
2- Standard heating work condition: Ambient Temp: DB 7oC, WB 6oC; heating water inlet 40oC, outlet 45oC.
3- The noise data is measured on the average of 1m far away from the unit.
4- Water site max. bearing pressure: 1.0 MPa.
*
Various power supply are optional.

3
Air Cooled Water Chiller & Heat Pump

Technical specification

I ntro d u c ti o n
Specification II - Modular Air Cooled Water Chiller
Modular Series
Economical type Luxury type
Model
VMA065V VMA130V VMA068M VMA108M
VMN065V VMN130V VMN068M VMN108M

Featu res
Refrigerant - R22 R407C R22 R407C R22 R407C R22 R407C
Cooling Capacity kW 65 62 130 124 68 65 108 103
Heating Capacity kW 69 66 136 132 73 69 118 112
Heat Recovery kW 19.5 18.6 39.0 37.2 20.4 19.4 32.4 30.8

Nomenclature
Inlet o
C 50 50 50 50 50 50 50 50
Domestic Hot temperature
Water Outlet o
C 55 55 55 55 55 55 55 55
(Optional) temperature
3
Water Flow m /h 3.4 3.3 6.6 6.3 3.5 3.5 5.6 5.6
Water Pipe Size - 1in 1in 1in 1in 1 in 1 in 1 in 1 in

Accessories
Type - Hermetic scroll compressor

Compressor Power Input kW 4.85*4 5.05*4 4.85*8 5.05*8 10.1*2 10.1*2 8.2*4 8.2*4
0-12.5-25-37.5-50-62.5-
Energy Steps 0-25-50-75-100% 0-50-100% 0-25-50-75-100%
75-87.5-100%
Type Axial Type, Top Discharge
Fan Power Input kW 0.5*2 0.5*2 0.5*4 0.5*4 0.55*2 0.55*2 1.3*2 1.3*2

Tech. spec.
Air Flow m3/h 24100 24100 48200 48200 28000 28000 40000 40000
Type Shell & Tube
3
Water Flow m /h 11 11 22 22 12 12 19 19
Water-side
Heat Exchanger Drop Water
kPa 40 40 40 40 42 42 43 43

Variable perf.
Side
Water Pipe Size - DN125 DN125 DN125 DN125 DN125 DN125 DN125 DN125
Refrigerant Charge Amount kg 18 18 36 36 14 16 21 26
Expansion Device - Capillary Thermal Expansion Valve
Power - 380V/3Ph/50Hz *
Total Power Input kW 20.4 21.2 40.8 42.4 21.3 21.3 35.4 35.4

Dimension
Length mm 2105 2105 2105 2105 2230 2230 2230 2230
Dimension Width mm 1375 1375 2750 2750 1290 1290 1570 1570
Height mm 2050 2050 2050 2050 2050 2050 2150 2150
Net 740 740 1480 1480 830 830 1380 1380
Weight Kg
Operating 760 760 1520 1520 880 880 1460 1460
Wiring at site
Noise dB(A) 68 68 68 68 71 71 73 73
Note: 1- Units above can realize 1-7 units' modular connection and can control energy-regulation automatically.
2- Standard cooling work condition: Ambient temperature DB 35oC, WB 24oC; Cooling water inlet 12oC, outlet 7oC.
3- Standard heating word condition: Ambient temperature DB 7oC, WB 6oC; Heating water inlet 40oC, outlet 45oC.
4- The noise data is measured on the average of 1m far away from the unit.
5- Water site max. bearing pressure: 1.0 MPa.
*
Various power supply are optional.
Inst. & maint.

4
Technical specification
Specification III - Modular Air Cooled Water Chiller
Modular Series
Model VMA180M VMA250M VMA320M
VMA380M
VMN180M VMN250M VMN320M
Refrigerant - R22 R407C R22 R407C R22 R407C R22 R407C
Cooling Capacity kW 180 171 250 238 320 304 380 361
Heating Capacity kW 198 188 275 261 350 333 - -
Total Power Input kW 56.8 57.2 73 73.4 92.8 93.2 114.4 114.8
Type - Parallel Hermetic Scroll Compressor
Input Power x
Compressor kW 12.4*4 12.5*4 (12.4+20.5)*2 (12.5+20.6)*2 20.5*4 20.6*4 25.0*4 25.1*4
Qty
Energy Steps - 0-25-50-75-100%
Type - Axial Type, Vertical Discharge
Input Power x
Fan kW 1.8*4 1.8*4 1.8*6 1.8*8
Qty
Air Flow m3/h 92000 92000 138000 184000
Type - Shell & Tube Shell & Tube Shell & Tube Shell & Tube
Water-Side Water Flow m3/h 31 29.4 43 41.7 55 52.2 66 62.7
Heat Drop Water
kPa 40 40 40 40
Exchange Side
Connection
- DN80 DN80 DN100 DN100
Pipe Size
Charge Amount kg 60 80 110 125
Refrigerant Expansion
- Thermal Expansion Valve
Device
Power - 3φ-380V-50Hz *
Length mm 2290 3270 4020 4750
Dimension Width mm 2190 2190 2190 2190
Height mm 2480 2480 2480 2480
Net 2050 2400 2800 3500
Weight kg
Operating 2250 2620 3050 3750
Noise dB(A) 73 73 75 77
Note:1- Standard cooling work condition: Ambient Temp: DB 35oC, WB 24oC; cooling water inlet 12oC, outlet 7oC.
2- Standard heating work condition: Ambient Temp: DB 7oC, WB 6oC; heating water inlet 40oC, outlet 45oC.
3- The noise data is measured on the average of 1m far away from the unit.
4- Reserve the right to change the parameter without prior notice.
5- Water side max. bearing pressure: 1.0 MPa.
*
Various power supply are optional.

5
Air Cooled Water Chiller & Heat Pump

Technical specification

I ntro d u c ti o n
Specification III - Air Cooled Screw Chiller
Screw Series
Model VMA180L VMA250L VMA320L VMA380L VMA430L
VMN180L VMN250L VMN320L VMN380L VMN430L
Refrigerant - R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a

Featu res
Cooling Capacity kW 180 171 164 250 238 218 320 304 290 380 361 330 430 409 386

Heating Capacity kW 198 188 - 275 261 - 350 333 - 430 409 - 480 456 -

Total Power Input kW 67.1 67.3 61.2 87.6 87.8 71.2 114 114.4 98.6 135.8 136.2 112.3 143 143.4 128.4

Capacity kW 54 51.3 49.2 75 71.4 65.4 96 91.2 87 114 108.3 99 129 122.7 115.8

Nomenclature
Water Flow m3/h 9.4 9.0 8.6 13.1 12.5 11.4 16.8 15.9 15.2 19.9 18.9 17.3 22.5 21.4 20.2
Domestic Hot
o
Water Inlet Temp C 50 50 50 50 50
(Optional) o
Outlet Temp C 55 55 55 55 55

Water Pipe Size - DN50 DN50 DN50 DN50 DN50

Type - Semi Hermetic Screw Compressor

Accessories
Input Power x
Compressor kW 59.9×1 60.1×1 54×1 76.8×1 77×1 60.4×1 103.2×1 103.6×1 87.8×1 121.4×1 121.8×1 97.9×1 128.6×1 129×1 110.4×1
Qty
Energy Steps - 25-50-75-100%

Type - Axial Type, Vertical Discharge


Input Power x
Fan kW 1.8×4 1.8×6 1.8×6 1.8×8 1.8×8
Qty
3
Air Flow m /h 92000 138000 138000 184000 184000

Tech. spec.
Type - Shell & Tube Shell & Tube Shell & Tube Shell & Tube Shell & Tube
Water-Side Water Flow m3/h 31.5 29.9 28.7 43.7 41.6 38.1 55.9 53.1 50.7 66.4 63.1 57.7 75.1 71.5 57.5
Heat
Exchange Drop Water Side kPa 40 40 40 40 40
Connection Pipe
- DN80 DN80 DN100 DN100 DN100
Size

Variable perf.
Charge Amount kg 60 80 110 125 135
Refrigerant
Expansion Device - Thermal Expansion Valve

Power - 3φ-380V-50Hz *

Length mm 2290 3270 4020 4750 5250

Dimension Width mm 2190 2190 2190 2190 2190

Dimension
Height mm 2480 2480 2480 2480 2480
Net 2050 2750 3200 3650 4000
Weight kg
Operating 2150 2900 3350 3850 4200
Noise dB(A) 74 76 76 78 78
o o o o
Note:1- Standard cooling work condition: Ambient Temp: DB 35 C, WB 24 C; cooling water inlet 12 C, outlet 7 C.
2- Standard heating work condition: Ambient Temp: DB 7oC, WB 6oC; heating water inlet 40oC, outlet 45oC. Wiring at site
3- The noise data is measured on the average of 1m far away from the unit.
4- Reserve the right to change the parameter without prior notice.
5- Water side max. bearing pressure: 1.0 MPa.
*
Various power supply are optional.
Inst. & maint.

6
Technical specification
Specification IV - Air Cooled Screw Chiller
Screw Series
Model VMA500L VMA570L VMA640L VMA700L VMA760L VMA810L VMA860L
VMN500L VMN570L VMN640L VMN700L VMN760L VMN810L VMN860L
Refrigerant - R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a R22 R407C R134a

Cooling Capacity kW 500 476 436 570 542 508 640 608 580 700 665 620 760 722 660 810 770 716 860 818 772

Heating Capacity kW 550 522 - 625 594 - 700 666 - 780 742 - 860 818 - 910 865 - 960 912 -

Total Power Input kW 175.2 175.6 142.4 201.6 202.2 169.8 228 228.8 197.2 249.8 250.6 210.9 271.6 272.4 224.6 278.8 279.6 240.4 286 286.8 256.8

Capacity kW 150 142.8 130.8 171 162.6 152.4 192 182.4 174 210 199.5 186 228 216.6 198 243 231 214.8 258 245.4 231.6
3
Water Flow m /h 26.2 25.0 22.8 29.9 28.4 16.6 33.6 31.8 30.4 36.7 34.8 32.5 39.8 37.8 34.6 42.4 40.3 37.5 45 42.8 40.4
Domestic
o
Hot Water Inlet Temp C 50 50 50 50 50 50 50
(Optional) o
Outlet Temp C 55 55 55 55 55 55 55
Water Pipe
- DN80 DN80 DN80 DN80 DN80 DN80 DN80
Size
Type - Semi Hermetic Screw Compressor
76.8 77.0 60.4 76.8 77.0 60.4 103.2 103.6 87.8 103.2 103.6 87.8 121.4 121.8 97.9 121.4 121.8 97.9 128.6 129.0 110.4
Compressor Input Power kW + + + + + + + + + + + + + + + + + + + + +
76.8 77.0 60.4 103.2 103.6 87.8 103.2 103.6 87.8 121.4 121.8 97.9 121.4 121.8 97.9 128.6 129.0 110.4 128.6 129.0 110.4
Energy Steps - 12.5-25-37.5-50-67.5-75-87.5-100%

Type - Axial Type, Top Discharge


Input Power
Fan kW 1.8×12 1.8×12 1.8×12 1.8×14 1.8×16 1.8×16 1.8×16
x Qty
3
Air Flow m /h 276000 276000 276000 322000 368000 368000 368000

Type - Shell & Tube Shell & Tube Shell & Tube Shell & Tube Shell & Tube Shell & Tube Shell & Tube
3
Water-Side Water Flow m /h 87.4 83.2 76.2 99.6 94.7 88.8 111.8 106.2 101.4 122.3 116.2 108.4 132.8 126.2 115.4 141.5 134.6 125.2 150.2 143 135
Heat Drop Water
Exchange Side kPa 43 43 43 44 44 44 44
Connection
- DN125 DN125 DN150 DN150 DN150 DN150 DN150
Pipe Size
Charge
kg 160 190 220 235 250 260 270
Amount
Refrigerant
Expansion
- Thermal Expansion Valve
Device
Power - 3φ-380V-50Hz *

Length mm 6530 7280 8030 8760 9490 9990 10490

Dimension Width mm 2190 2190 2190 2190 2190 2190 2190

Height mm 2480 2480 2480 2480 2480 2480 2480


Net 5450 5900 6350 6800 7250 7600 7950
Weight kg
Operating 5750 6200 6650 7150 7650 8000 8350
Noise dB(A) 81 81 81 82 83 84 85
Note: 1- Standard cooling work condition: Ambient Temp: DB 35oC, WB 24oC; cooling water inlet 12oC, outlet 7oC.
2- Standard heating work condition: Ambient Temp: DB 7oC, WB 6oC; heating water inlet 40oC, outlet 45oC.
3- The noise data is measured on the average of 1m far away from the unit.
4- Reserve the right to change the parameter without prior notice.
5- Water side max. bearing pressure: 1.0 MPa.
*
Various power supply is optional.

7
Air Cooled Water Chiller & Heat Pump

Variable performace

I ntro d u c ti o n
1.40

Cooling capacity correction coefficient


1.30

1.20 Chilled water inlet 10oC


Chilled water inlet 12oC

Featu res
Chilled water inlet 14oC
1.10
Chilled water inlet 16oC
Chilled water inlet 18oC
1.00 Chilled water inlet 20oC

0.90

Nomenclature
0.80 27 29 31 33 35 37 39 41 43 45
Ambient temperature oC

1.40
Cooling power correction coefficien

Accessories
1.30

1.20
Chilled water inlet 10oC
Chilled water inlet 12oC
1.10 Chilled water inlet 14oC
Chilled water inlet 16oC
1.00 Chilled water inlet 18oC

Tech. spec.
Chilled water inlet 20oC
0.90

0.80 27 29 31 33 35 37 39 41 43 45
Ambient temperature oC

Variable perf.
1.20

1.10
Heating capacity correction coefficien

1.00 Hot water inlet 34oC

Hot water inlet 36oC


0.90 Hot water inlet 38oC
Hot water inlet 40oC

Dimension
0.80 Hot water inlet 42oC

0.70

0.60

Wiring at site
0.50 -11 -9 -7 -5 -3 -1 1 3 5 7 9
Ambient temperature oC

1.20

1.10
Heating capacity correction coefficien

Inst. & maint.

1.00

Hot water inlet 34oC


0.90
Hot water inlet 36oC
0.80 Hot water inlet 38oC
Hot water inlet 40oC
0.70 Hot water inlet 42oC

0.60

0.50
-11 -9 -7 -5 -3 -1 1 3 5 7 9
Ambient temperature oC

8
Dimension
1. VFSN(A)020V, VFSN(A)025V & VFSN(A)030V

Model A B C D E1 E2 F1 F2 F3 F4 G1 G2
VFSN(A)020 1785 915 1515 726 800 840 456 180 206 243 DN32 DN32
VFSN(A)025 1785 915 1515 726 800 840 456 180 206 343 DN32 DN32
VFSN(A)030 1785 1015 1715 926 940 1020 446 181 211 388 DN32 DN32

2. VFSN(A)045V

9
I ntro d u c ti o n Featu res Nomenclature Accessories Tech. spec. Variable perf. Dimension Wiring at site Inst. & maint.
Air Cooled Water Chiller & Heat Pump

10
Dimension
3. VMN(A)065V

4. VMN(A)130V
Dimension
5. VMN(A)068M

6. VMN(A)108M

11
I ntro d u c ti o n Featu res Nomenclature Accessories Tech. spec. Variable perf. Dimension Wiring at site Inst. & maint.
Air Cooled Water Chiller & Heat Pump

12
Dimension
7. VMN(A)180M

8. VMN(A)250M
Dimension
9. VMN(A)320M

10. VMA380M

13
I ntro d u c ti o n Featu res Nomenclature Accessories Tech. spec. Variable perf. Dimension Wiring at site Inst. & maint.
Air Cooled Water Chiller & Heat Pump

14
Dimension
11. VMN(A)180L

12. VMN(A)250L
Dimension
13. VMN(A)320L

14. VMN(A)380L

15
I ntro d u c ti o n Featu res Nomenclature Accessories Tech. spec. Variable perf. Dimension Wiring at site Inst. & maint.
Air Cooled Water Chiller & Heat Pump

16
Dimension
15. VMN(A)430L
Wirings at Site
1. VFSN(A)020, VFSN(A)025, VFSN(A)030 & VFSN(A)045
Wiring Diagram of Terminals in Control Cabinet

Wiring Diagram of Water Pump and Electric Heater in Distributing Box

Note:
1. Number of cores and standard sectional area of power supply cable: 3*10mm2+2*6mm2;
2. Above wiring diagram is only for reference only, it will be different according to actual
starting.
15
Air Cooled Water Chiller & Heat Pump

Wirings at Site

I ntro d u c ti o n
2. VMN(A)065V & VMN(A)130V
Wiring Diagram of Terminals in Control Cabinet

Featu res
Nomenclature
Accessories
Tech. spec.
Variable perf.
Wiring Diagram of Water Pump and Electric Heater in Distributing Box

Dimension
Wiring at site
Inst. & maint.

Note:
1. Number of cores and standard sectional area of power supply cable: 3*10mm2+2*6mm2;
2. Above wiring diagram is only for reference only, it will be different according to actual
starting.
16
Wirings at Site
3. VMN(A)068M, VMN(A)108M, VMN(A)180M,
VMN(A)250M, VMN(A)320M & VMA380M
Wiring Diagram of Terminals in Control Cabinet

Wiring Diagram of Water Pump and Electric Heater in Distributing Box

Number of cores and standard sectional area of power supply cable:


VMN(A)180M: 3*70mm2+2*35mm2; VMN(A)250M: 3*120mm2+2*70mm2;
VMN(A)320M: 3*185mm2+2*95mm2; VMA380M: 3*185mm2+2*95mm2.

17
Air Cooled Water Chiller & Heat Pump

Wirings at Site

I ntro d u c ti o n
4. VMN(A)180L, VMN(A)250L, VMN(A)320L, VMN(A)380L & VMN(A)430L
Wiring Diagram of Terminals in Control Cabinet

Featu res
Nomenclature
Accessories
Tech. spec.
Variable perf.
Wiring Diagram of Water Pump and Electric Heater in Distributing Box

Dimension
Wiring at site
Inst. & maint.

Number of cores and standard sectional area of power supply cable:


VMN(A)180L: 3*95mm2+2*50mm2; VMN(A)250L: 3*120mm2+2*70mm2;
VMN(A)320L: 3*185mm2+2*95mm2; VMN(A)380L: 3*240mm2+2*120mm2.

18
Installation & maintenance
• Preparation
1.After arriving the installation site, check all the items of the unit carefully
according to the packing list if there is damage, lack of parts or damage during
transport.
2.The user must provide a rigid nondeforming foundation or concrete footings,
based on the size of the unit four positioning hole; the foundation of the unit
can also be framework structure, framework should be placed on main beam or
column, and be capable of bearing the weight 150% heavier than the unit. The
horizontal level should have no slope.
3. For easy handling, users should use the crane, the machine should properly
protected by soft material on the point of force applied, and also be in balanced
status during handling to avoid possible damage.
Hoisting Graph
VFSN(A)020V, VFSN(A)025V, VFSN(A)030V,
VMN(A)130V
VFSN(A)045V & VMN(A)065V

VMN(A)180M(L), VMN(A)250M(L),
VMN(A)068M&VMN(A)108M
VMN(A)320M(L), VMN(A)380M(L) & VMN(A)430L

4. Choose the Installation Place


Units can be installed indoor or outdoor , should consider the following factors:
1) Keep unit from the places of easy accumulation of leaves, insects or other
dirty thing to avoid blocking of heat exchanger.
2) Try to avoid as much as possible the direct sunshine on the machine when
installs the machine.
3) Drain slot should be made in the surrounding of machine to drain the
condensed water.
4) Should keep more than 1.6meter space surrounding the machine for the good
air circulation and easy access of maintenance.

19
Air Cooled Water Chiller & Heat Pump

Installation & maintenance

I ntro d u c ti o n
5) 3.0 to 3.5meters space should be kept above the machine to avoid return air.
6) 10 to 20mm rubber isolator should be fixed between the machine and the
foundation.
5. Foundation diagram

Featu res
VFSN(A)020V, VFSN(A)025V, VFSN(A)030V & VFSN(A)045V

Nomenclature
Accessories
Reserved center holes φ100 (bolt M16)

Tech. spec.
Variable perf.
Model VFSN(A)020V VFSN(A)025V VFSN(A)030 VFSN(A)045
A(mm) 800 800 940 940
B(mm) 840 840 1020 1020

VMN(A)065V

Dimension
Wiring at site

Reserved center holes φ100 (bolt M16)


Inst. & maint.

Note: N is the quantities of parallel units.

20
Installation & maintenance
VMN(A)130V

Reserved center holes


φ100 (bolt M16)

Note: N is the quantities of parallel units.

VMN(A)068M & VMN(A)108M

Reserved center holes


φ100 (bolt M16)

Note: N1 is the quantities of VMN(A)068M, N2 is the quantities of VMN(A)108M.

21
Air Cooled Water Chiller & Heat Pump

Installation & maintenance

I ntro d u c ti o n
VMN(A)180M, VMN(A)250M, VMN(A)320M & VMA380M

Featu res
Reserved center holes
φ100 (bolt M20)

Nomenclature
Accessories
Note: n is the quantities of parallel units.

Model VMN(A)180M VMN(A)250M VMN(A)320M VMA380M

Tech. spec.
A(mm) 1500 1000 1400 1200
B(mm) 395 635 610 575
N1 1 2 2 3

Variable perf.
VMN(A)180L, VMN(A)250L, VMN(A)320L, VMN(A)380L & VMN(A)430L

Dimension
Reserved center holes
φ100 (bolt M20)

Wiring at site
Inst. & maint.

Note: n is the quantities of parallel units.

Model VMN(A)180L VMN(A)250L VMN(A)320L VMN(A)380L VMN(A)430L


A(mm) 1500 1000 1400 1200 1400
B(mm) 395 635 610 575 525
N1 1 2 2 3 3

22
Installation & maintenance
• Standard connections of pipeline of multiple modules

Equal pipe road system of three modules

Water outlet
Blind flange
Water inlet
Blind flange

Equal pipe road system of three modules

Water outlet

Blind flange

Water inlet

• Notices during installation


The machine installation and piping system layout should be carried out by professional
people according to national and local HVAC regulation. It should be carried out according
to related technical specification and requirement and the building structure for piping
system, in the process of installation, please pay attention to the followings:
1. Design the pipelines reasonably: avoid bending as much as possible, no piping in the
shape of “U” or “ M ” to avoid discharging block and water resistance increase; keep slant
in horizontal pipes in order to facilitate air discharge; fix air discharge valve in the highest
point of water system.
2. Install water filter ( ≥40 mesh) in the front of water inlet pipe, to avoid pipe block
and machine damage; the water piping must have leakage testing and cleaned when its
finished, then the pipe can be connected with machine.
3. Water pipe must be well insulated to keep good cooling/heating performance and save
energy.

23
Air Cooled Water Chiller & Heat Pump

Installation & maintenance

I ntro d u c ti o n
4. Choose proper water pump for water supplying system to ensure the difference between
actual water supply amount and unit acquiring water supply amount is less than 10%.
5. Adopting shock absorption flexible joint for chilled water inlet/outlet pipe and water
pump connection to avoid shock transmission in operation. The pipe and water pump
should have its own holder, to avoid force bearing on machine.

Featu res
6. Install expansion tank on the water return pipe, for the waterflow amount change due
to ambient temperature change, the position of which should be 1 to 1.5meter higher than
the highest point of the system, the volume of water tank should be 1/10 of that of total

Nomenclature
system, the chilled water pipe and water expansion tank should be insulated.
7. Install waterflow switch on water out pipe (paddle flowmeter), avoid of damage to unit
due to lack of water. Discharge air inside to water system before operation to avoid damage
of machine.
8. Install water discharge tap or valve in the lowest point of water system, so as to release

Accessories
all the water inside of water system and water side heat exchanger (refer to the water
release mark on machine) when long time not in use in winter to avoid pipe damage
caused icing.
9. Chilled water system

Tech. spec.
Variable perf.
Dimension
Wiring at site
Inst. & maint.

24
The Same Breath,
Energy Saving Together.

VICOT AIR CONDITIONING CO., LTD


Add: Hongdu Road, Dezhou Eoonomic Development Zone, Shandong Province,
China. Post Code: 253022
Sales Tel: +86-8235 5566/68/76 Fax: +86-8235 7911
Email: export@vicot.com.cn Http://www.vicot com cn

2014.01
Vicot reserves the right of modification without prior notice

You might also like