You are on page 1of 2

SEQUENCE OF EVENT DURING FAULT (ELECTRICAL SIDE)

S.NO DATE TIME


1 8/16/2014 2:09:51
2 8/16/2014 2:09:51
3 8/16/2014 2:09:51
4 8/16/2014 2:09:51
5 8/16/2014 2:09:51
6 8/16/2014 2:09:51
7 8/16/2014 2:09:52
8 8/16/2014 2:09:51
9 8/16/2014 2:09:53
10 8/16/2014 2:09:53
11 8/16/2014 2:09:53
12
8/16/2014 2:09:53
13 8/16/2014 2:09:53
SEQUENCE OF EVENT DURING FAULT (ELECTRICAL SIDE)

EVENT AREA
DIA 1 MAIN#1 CIRCUIT BREAKER 410 DISTANCE PROTECTION 21 OPERATED SWITCHYARD
DIA1 MAIN#2 410 DISTANCE PROTECTION OPERATED SWITCHYARD
MAIN LINE BREAKER 410 R-PHASE CIRCUIT BREAKER OPERN SWITCHYARD
TIE BREAKER 411 R-PHASE CIRCUIT BREAKER OPEN SWITCHYARD
MAIN LINE BREAKER 410 Y AND B-PHASE CIRCUIT BREAKER OPERN SWITCHYARD
TIE BREAKER 411 Y AND B-PHASE CIRCUIT BREAKER OPEN SWITCHYARD
DIRECT TIRP SEND TO ANGUL 400KV SUB STATION THROUGH PLCC SWITCHYARD
MAIN BREAKER 410 AND TIE BREAKER 411 OPEN SWITCHYARD
FROM DAVR EXCITATION FAULTY ON AND TRIP TO GR2 RELAY BTG SWITCHGEAR
186A2,286A2 OPERATED THEN 21KV SIDE GCB OPENED BTG SWITCHGEAR
GENERATOR DIFFRENTIAL PROTECTION OPERATED BTG SWITCHGEAR
GENERATOR DEAD MACHINE PROTECTION OPERATED(50GDM) AND IT TRIPS TO
186A1, 286A1 BTG SWITCHGEAR
HVCB (400KV SIDE ) CIRCUIT BREAKER 412 OPERATED DUE TO 186A1,286A2 BTG SWITCHGEAR