TSWF - 900.2 - Earthing Calculation For 110kV OHTL - Rev2
TSWF - 900.2 - Earthing Calculation For 110kV OHTL - Rev2
Calculation data:
Based on in-situ testing result the resistance value for along the OHTL varies 21.1-328 m.
Max soil resistivity 328 m is considered for calculation.
110000
3
|30 | = | 3 | = 67 494 = 498.5
2(20.1 + 141.8) + (11.2 + 95.1)
Rev. 2
Earthing Grid calculation Tsetsii Windpark 110kV OHTL
Ig=0.1695kA
1
2 = = 0.96 mm2
104 0+
( )( )
0 +
Ig=0.1695kA
1
2 = = 0.42 mm2
104 0+
( )( )
0 +
2
Because 2 = , minimum diameter of conductor should be higher than 1.1mm. Due to
4
mechanical strength and ruggedness requirement, minimum diameter is 10.5mm. In this project
12mm is selected.
For a 0.102 m (4 in) layer of top soil surfacing, with resistivity of 2500 m, and for an earth with
resistivity of 328 m, the reflection factor K is computed using IEEE Std. 80 Eq.21.
328
0.09 (1 ) 0.09 (1
)
= 1 =1 2500 = 0.734
2 + 0.09 2 0.102 + 0.09
Rev. 2
Earthing Grid calculation Tsetsii Windpark 110kV OHTL
R=15
Ig=Df*Sf*3I0= 1*0.34*498.5=169.5A
Step 7: GPR.
Now it is to compare the product of Ig and Rg, or GPR, to the tolerable touch voltage, Etouch70
GPR =Ig*Rg
1 2 (+2+)2 8
Km =2 [[16 + 4]+ [(21)]] Km=0.751
8
Where
1
Kii = 2 =0.354
(2)
Kh= 1+ =1.225
0
Rev. 2
Earthing Grid calculation Tsetsii Windpark 110kV OHTL
Where
n=na*nb*nc*nd n=1
2
na= na=1.5
Em= 785.031 V
Equation (92) though Equation (94) are used to compute Es, Ls and Ks, respectively. It should be
noted that the value for Ki is still 0.866 (same as for mesh voltage).
1 1 1 1
KS = [2 + + + (1 0.5(2) ] Ks =0.3165
Then
Es = 0.75+0.85 Es = 363.86V
:
1. IEEE std-80;
2. Handbook of Electrical Calculations H. Wayne Beaty, Section14
Rev. 2