Professional Documents
Culture Documents
Plexus 3
Architect 6
Polaris I & S 7
Plafond 8
Podium 9
Celo 10
Cabinett 11
Capella 12
Carat 13
Fasadium 14
Atrium / Loggia 15
Regula 16
Drypac 17
Lighting 18
TEKNOsim 19
07.2014 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB.
Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
l i nda b | prem ax
10
11
Use As a plus feature the Lindab AirGuide system offers read-
8
Air duct
9
Copper pipes
10 Coanda effect
11
12 Cooled air
14
15 Actuators
16 Battery
Air duct
17 Copper pipes
18
Detachable faceplate
10
11
12
13
14
15
16
17
18
Picture 2. When the faceplate is lowered or removed, the battery are accessible from below. AirGuide system is shown
in picture (plus feature).
19
Example: A number of Premax beams are installed in an open-plan office. A separate office is to be fitted into the
14 room. If the climate is to be optimal, the air volume and air distribution needs to be adjusted on the Premax beam that
will be built into the new room (see picture 5). If the air has to be directed in a specific direction, it is also possible to
adjust an asymmetrical distribution pattern (see picture 4). For more information please go to www.lindqst.com.
15
16
17
18
19 Picture 5. A separate office is to be fitted into the room. If the climate is to be optimal, the air quantity and air volume
need to be adjusted for the Premax beam that will be built into the new room.
19
1. Start by calculating the capacity required for the Follow the instructions below to read off the effect from
2 room, to keep a certain temperature. Lindabs the diagram.
TEKNOsim is an excellent tool for this.
2. Calculate which cooling capacity, or read in diagram 1. Calculate trw.
3 1, that is supplied by the ventilation air. 2. Product length L minus 0.3 m, to obtain the active
3. Remaining heat load needs to be cooled by the length Lact.
water circuit in Premax. 3. Divide the primary air flow rate qa by the active length
4 The formula for calculating the capacity of the air:
Lact. Enter the result on the lower axis of diagram 2.
4. Follow the flow line to the right pressure, and then read
Pa = qma x cpa x tra off the specific cooling capacity PLt per active metre.
5. Calculate the temperature difference in water circuit tw
5 Size comparison by tr = 25C with: and find the capacity correction factor etw in diagram 3.
qa = Primary air flow rate 6. Multiply the specific cooling capacity PLt that was
Pa [W] = qa [l/s] x 1.2 tra [K] and read off by etw , trw and active length Lact.
6 Pa [W] = qa [m/h] x 0.33 tra [K]
Minimum flow
7 Definitions:
Please note that flows below the recommended mini- Pa = Cooling capacity air [W]
mum flow, can result in unwanted air in the water pipes. Pw = Cooling capacity water [W]
8 Exciding the nominal flows is not recommandable as the
capacity gains will only be minimal.
Ptot = Cooling capacity total [W]
qma = Air mass flow rate [kg/s]
qa = Primary air flow rate [l/s]
cpa = Specific heat capacity air [1,004 kJ/kg K]
9 Pipe diameter Min flow Nominelt
tr = Room air temperature [C]
12mm 0.025 l/s 0.038 l/s twi = Water inlet temperature [C]
two = Water outlet temperature [C]
10 15mm 0.050 l/s 0.076 l/s
tra = Temp. diff., room air and primary air temp. [K]
trw = Temp. diff., room air and mean water temp. [K]
tw = Temp. diff. water circuit [K]
11 etw = Capacity correction for temperature
eqw = Capacity correction for water flow
PLt = Specific cooling capacity [W/(m K)]
12
Pa [W] Cooling capacity air
Luftens kyleffekt Pa = qa 1,2 tra tra [K]
13 600 10
500
8
14
400
6
15
300
4
16 200
2
17 100
0
18 10 15 20 25 30 35 40 45 50
Primary airLuftflde
flow rate qa [l/s]
19 Diagram 1. C
ooling capacity air Pa as function of the primary air flow rate qa. If the air supply flow is 25 l/s and the temper-
ature difference of the room air and the supply air is tra = 6 K, then the cooling capacity of the air is 180 W.
100
5
NB! A reduction at up
120 Pa to 6% may occure, if
90
100 Pa the AirGuide has been 6
Specific Cooling Capacity PLt [W/(m K)]
80 Pa selected.
60 Pa
80
40 Pa 7
70
Power water (W/C)
60
8
50
9
40
10
30
20 11
0 10 20 30 40 50 60 qa / Lact [l/(s m)]
Air volume (l/s) /m (active length)
Diagram 2. S
pecific cooling capacity PLt as a function of primary air flow rate per active metre at nozzle pressures of 40,
60, 80, 100 and 120 Pa.
12
1,0400
13
1,0200 14
Capacity correction etw
1,0000
15
0,9800
16
0,9600
17
0,9400
18
0,9200 tw
1 2 3 4 5 6
Diagram 3. Capacity correction etw as a function of tw. Only applies for cooling.
19
11
Capacity correction eqw
12 1.10
1.05 Cooling
1.00
13 0.95
0.90
0.85
14 0.80
0.75
0.70
15 0.65
0.60
0.55
16 0.50
0.45
0.40 Heating
17 0.35
0.30
0.25
18
0 0.05 0.1 0.15
Water Flow Rate qw [l/s]
19 Diagram 4. Capacity correction eqw for water flow for both cooling and heating.
0.1
0.09
3
0.08
0.07
4
0.06
0.05
5
0.04
6
0.03
0.025
1 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 70 7
Pressure drop [kPa]
8
[l/s] Heating 12 mm
Lengths [m] 1.2 1.8 2.4 3.0
0.15 9
0.1
10
0.09
0.08
11
0.07
0.06
12
0.05
0.04 13
0.03
14
0.025
0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 2 3 4 5 6 7 8 9 10 15
Pressure drop [kPa] 15
Diagram 5. Pressure drop in water circuit, cooling and heating.
Example 3 Cooling: 16
Premax 2.4 m, which provides on output of 1244 W, Definitions:
15 mm pipes. tw = 3 K, qw = Pw / (cpw tw) qw = Water flow rate [l/s]
qw = 1244 W/(4200 Ws/(kg K) 3 K) = 0.099 I/s Pw = Cooling/heating capacity water [W] 17
The pressure drop in the water is read off as 5.7 kPa. cpw = Specific heat capacity water [4200 Ws/(kg K)]
tw = Temperature difference water circuit [K]
Example 4 Heating: 18
Premax 2.4 m, which provides on output of 1756 W,
12 mm pipes. tw = 10 K, qw = Pw / (cpw tw)
qw = 1756 W/(4200 Ws/(kg K) 10 K) = 0.042 I/s
The pressure drop in the water is read off as 1.3 kPa.
19
1 pt [Pa]
Premax
Pos no: 0 1 2 3 4 5
L < 2.4 m
6 7 8 9
Premax
L < 2.0 m
250
2 200
40
150
3 110
35
100
30
4 80
70
25
60
5 50
20 LWA dB(A)
40
qV [l/s]
6 5 6 7 8 9 10 15 20 25 30 40 50 60 70
3
qV [m /h]
20 30 40 50 60 70 80 100 150 200 250
8 pt [Pa]
Premax _
>
Pos no: 0 1 2 3 4
L
5 6 7 8 9
2.4 m Premax
L > 2,0 m
250
9 200
150 40
10
110 35
100
11 80 30
70
60 25
12 50
20 LWA dB(A)
40
qV [l/s]
13 5 6 7 8 9 10 15 20 25 30 40 50 60 70 100
3
qV [m /h]
20 30 40 50 60 70 80 100 150 200 250 360
14 Diagram 6. Sound effect level LWA and JetCone setting for Premax.
15
16
17
18
19
6
Sound data
Internal sound dampening L 7
Hz JetCone position 63 125 250 500 1000 2000 4000 8000
dB 4 24 15 8 5 8 13 11 16 8
Table 2. Premax's internal sound dampening.
9
Noise level Lwoct
For calculation of the noise level
10
Correction Coct (dB) Octave band, average frequency (Hz) Premax L 1.8 m
Hz 63 125 250 500 1000 2000 4000 8000 11
dB 7 -4 -6 -5 -5 -6 -9 -13
12
Correction Coct (dB) Octave band, average frequency (Hz) Premax L > 1.8 m
Hz 63 125 250 500 1000 2000 4000 8000
13
dB 12 -2 -4 -3 -6 -8 -10 -14
Table 3a+3b. P
remax's noise levels Lwoct for each octave band in the beam, are calculated by adding the corrections
Coct from the table above to the sound power level Lwa dB(A). The noise levels are calculated using the 14
following formula: Lwoct = Lwa + Coct
15
Weight and water volume
16
Premax
Weight, kg/m 18 17
Water content, cooling, l/m 0.6
Water content, heating, l/m 0.25
18
Copper pipes, quality EN 12735-2 CU-DHP
Pressure class PN10
Table 4. Premax's weight and water volume.
19
2 C
4 A B
Top
view
F E
5
H
6 D
7
F
E G C
8 B
A
9 D H
10
Figure 1. For A connection, Premax is delivered with Lindab's standard nipple (NPU-125).
11 For B, C, and D connection, Lindab's elbow piece (BU 90) is included.
12
Water connections
13 7
14
Possible Premax connections,
15 air ( A, B, C, D ) and water ( 1, 2, 3, 4, 7, 8 ).
2 1 A:
B:
1,
1,
2,
2,
3,
3,
4, 7, 8
4, 7, 8 3 4
C: 3, 4, 7, 8
16 D: 3, 4, 7, 8
17
8
18
Figure 2. Possible connections, water cooling and heating.
19
6
Connection 7 or 8
7
7 8 8
10
13
Connection A Connection B
14
15
A1 B8
16
17
18
Figure 4. Examples of the most common Premax supply air A and B variants.
Go to next page to see overview of various water pipe connections.
19
2 Valve Actuator
4 10 2
5
Figure 5. Valve with actuator mounted. Figure 6. Illustration of how the valve and actuator is placed
inside the chilled beam, A1 example, Premax.
6
180
Dimensions
7
Examples below show Premax I-60 models with A air connection. For external dimensions, see next page.
8 45
321
260
9
122 92
10
45 45 45
11
Connection 1 or 3 Connection 2 or 4
12 n125
13
45
131
102
151
131
120
n125
14 180
250
15
Connection 7 or 8
16
400
17 125
45
18
200
150
131
120
40
19 592
Figure 7. Premax I-60-A with possible water connections.
16 Air in
Right to alterations reserved
125
l i nda b | prem ax
3
370
4
40
A 5
6
592
(I-62 = 617) 7
I-60: L = 1200, 1800, 2400, 3000 mm; A = 1192, 1792, 2392, 2992 mm.
8
I-62: L = 1200, 1800, 2400, 3000 mm; A = 1242, 1867, 2492, 3117 mm.
40
110
11
98
Premax X-60
12
370
13
14
10
15
599
16
17
X-60: L = 1200, 1800, 2400, 3000 mm; A = 1199, 1799, 2399, 2999 mm. 18
L = Nominal length (order length)
Figure 9. Premax X-60 suspension, dimensions. Suspension components are not supplied as part of the standard
package.
19
0,15m/s
3
3000mm 3000mm
600 600
3000mm 1000mm 500mm 0 3000mm
500mm 1
600 600
0,30m/s
4 0,20m/s
0,25m/s
0,30m/s
0,20m/s
0,15m/s 2000mm 0,20m/s 2000mm
0,25m/s 600
5 0,15m/s 2000mm 0,20m/s 2000mm
0,30m/s
0,15m/s
6 0,25m/s
0,20m/s
1000mm
0,15m/s 1000mm
7 1000mm
0,15m/s
1000mm
9 1000mm 500mm 0 500mm 1000mm golvniv 1000mm 500mm 0 500mm 1000mm golvniv
Figure 10.
1000mm 500mm 0 500mm 1000mm
Figure 11.
1000mm 500mm 0 500mm 1000mm
600 600
3000mm 3000mm
11 0,30m/s
600
0,30m/s
600
600
0,25m/s 0,25m/s
0,30m/s 0,30m/s
12 0,20m/s
0,25m/s
2000mm 0,20m/s
0,25m/s 0,30m/s
2000mm
0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
0,20m/s
13 0,15m/s 0,15m/s
0,15m/s 0,15m/s
1000mm 0,15m/s 1000mm
14
1000mm 1000mm
15
Air flow 14 l/s/active m golvniv Air flow 17 l/s/active m golvniv
17
1000mm 500mm 0 500mm 1000mm 1000mm 500mm 0 500mm 1000mm
0,30m/s 0,30m/s
0,25m/s 0,25m/s
19 Figure 10-13. Air velocities between supply air beams at a separation
0,30m/s
0,20m/s Standard air pattern profile (nozzles at a 2000mm
of 600 mm.
0,30m/s
0,20m/s
30 angle). Nozzle pressure of 60 Pa. 2000mm
0,25m/s 0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
l i nda b | prem ax
0,15m/s 0,15m/s
3
3000mm 3000mm
600 600
0,30m/s
0,25m/s
0,30m/s
0,25m/s
4
0,20m/s 2000mm 0,20m/s 2000mm
5
0,15m/s 0,15m/s
6
1000mm 1000mm
7
Air flow 20 l/s/active m Air flow 23 l/s/active m
8
floor
golvniv floor
golvniv
Figure 14-15. Air velocities between supply air beams at a separation of 600 mm.
0,15m/s 10
Standard0,20m/s
air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
0,25m/s
0,30m/s 3000mm 3000mm
1200 1200 11
0,25m/s 0,25m/s
12
0,20m/s 0,20m/s
2000mm 2000mm
13
0,15m/s 0,15m/s
14
1000mm 1000mm
15
Air flow 8 l/s/active m Air flow 11 l/s/active m
floor
golvniv floor
golvniv
16
1000mm 500mm 0 500mm 1000mm 1000mm 500mm 0 500mm 1000mm
17
Figure 16. Figure 17.
18
3000mm 3000mm
1200 1200
0,30m/s
Figure 16-17. Air velocities between supply air beams at a separation
0,30m/s
Standard air pattern profile (nozzles at a 30 angle).
of 1200 mm.
Nozzle pressure of 60 Pa.
0,25m/s
19
0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
0,15m/s 0,15m/s
1000mm 1000mm
guarantees the Coanda effect and a fan-shaped air pat- were made with a cooled supply air (t room air supply
tern in all cases. The fan-shaped air pattern ensures air air) of 5 C and 500mm
cooling in0 the water
500mm circuit (t room
1000mm air
2 1000mm 500mm 0 500mm 1000mm
velocities in the living area that are half those obtainedgolvniv
1000mm
3
3000mm 3000mm
1200 1200
3000mm 3000mm
0,30m/s
4 0,30m/s 1200
0,25m/s
1200
0,25m/s
0,20m/s 0,30m/s 0,20m/s
2000mm 2000mm
0,30m/s
5 0,25m/s
0,25m/s
golvniv
1000mm 500mm 0 500mm 1000mm
golvniv
10
1000mm 500mm 0 500mm 1000mm 1000mm 500mm 0 500mm 1000mm
3000mm 3000mm
1200 1200
3000mm 3000mm
11 0,30m/s
1200
0,30m/s
1200
0,25m/s 0,25m/s
12 0,25m/s 0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
0,15m/s 0,15m/s
13
1000mm 1000mm
0,15m/s 0,15m/s
14
1000mm 1000mm
15
golvniv golvniv
floor
golvniv
1000mm 500mm 0 500mm 1000mm
floor
golvniv
17
1000mm 500mm 0 500mm 1000mm 1000mm 500mm 0 500mm 1000mm
18
19 Figure 18-21. Air velocities between supply air beams at a separation of 1200 mm.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
1800
3000mm
1800
3000mm
3
0,25m/s
4
3000mm 3000mm
1800 1800
0,20m/s 0,20m/s
2000mm 2000mm
0,25m/s
0,20m/s 0,20m/s
5
2000mm 2000mm
0,15m/s 0,15m/s
6
1000mm 1000mm
0,15m/s 0,15m/s
7
1000mm 1000mm
Air flow 8 l/s/active m Air flow 11 l/s/active m
8
floor
golvniv floor
golvniv
golvniv
1000mm 500mm 0 500mm 1000mm
golvniv
9
Figure 22. Figure 23.
10
1000mm 500mm 0 500mm 1000mm 3000mm 1000mm 500mm 0 500mm 1000mm 3000mm
1800 1800
0,25m/s
11
3000mm 3000mm
0,30m/s
1800 1800
0,20m/s 0,25m/s
0,25m/s
2000mm 0,20m/s 2000mm
0,30m/s
0,20m/s 0,25m/s
12
2000mm 0,20m/s 2000mm
0,15m/s 0,15m/s
13
1000mm 1000mm
0,15m/s 0,15m/s
14
1000mm 1000mm
15
golvniv golvniv
floor
golvniv
1000mm 500mm 0 500mm 1000mm
floor
golvniv
16
1000mm 500mm 0
1800
500mm 1000mm 3000mm 1000mm 500mm
1800
0 500mm 1000mm 3000mm
17
Figure 24. Figure 25.
18
3000mm 3000mm
0,30m/s 0,30m/s
1800 1800
0,25m/s 0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
0,30m/s
Air velocities between supply air beams at a separation of 0,30m/s
Figure 22-25. 1800 mm.
0,25m/sStandard air pattern profile (nozzles at a 30 angle). Nozzle0,25m/s
pressure of 60 Pa.
19
0,20m/s 2000mm 0,20m/s 2000mm
0,15m/s 0,15m/s
Right to alterations reserved 21
1000mm 1000mm
2000mm 0,20m/s 2000mm
0,15m/s 0,15m/s
3 1800
3000mm
1800
3000mm
4 0,30m/s 0,30m/s
0,25m/s 0,25m/s
0,20m/s 2000mm 0,20m/s 2000mm
5
0,15m/s 0,15m/s
6
1000mm 1000mm
7
Air flow 20 l/s/active m Air flow 23 l/s/active m
8
floor
golvniv floor
golvniv
10
11
Figure 26-27. Air velocities between supply air beams at a separation of 1800 mm.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
12
13
14
15
16
17
18
19
3000mm 3000mm 3
0,20m/s
0,15m/s
0,20m/s 0,20m/s
4
0,15m/s 0,15m/s
0,20m/s 2000 mm 2000 mm
0,15m/s 5
350
6
1000mm 1000mm
floor
golvniv floor
golvniv
8
wall wall
9
Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
1400-1600
3000mm 11
800-1100
0,20m/s 12
0,15m/s 2000 mm
13
0,20m/s
0,15m/s
14
1000mm
15
floor
golvniv
16
wall
17
Vgg 1000 mm 2000 mm 3000 mm
Figure 30.
18
Figure 28-30. Air velocities below s supply air beam, where the air flow is 8 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
19
3 3000mm 3000mm
4 0,20m/s 0,20m/s
6 1000mm
1000mm
8 floor
golvniv floor
golvniv
wall wall
9
Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
Air velocities at wall / throw.
11 1700-1900
3000mm
1000-1300
12
0,25m/s
0,20m/s
0,20m/s 2000 mm
0,15m/s
13
0,15m/s
14
1000mm
15
16 golvniv
floor
17 wall
Vgg 1000 mm 2000 mm 3000 mm
Figure 33.
18
19 Figure 31-33. Air velocities below s supply air beam, where the air flow is 11 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
3000mm 3000mm 3
0,20m/s 0,20m/s
4
0,15m/s 2000 mm 0,15m/s 2000 mm
0,20m/s
0,15m/s
0,25m/s
0,20m/s 5
350
0,15m/s
6
1000mm 1000mm
floor
golvniv floor
golvniv
8
wall wall
9
Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
Air velocities at wall / throw.
1700-1900
3000mm 11
1000-1300
12
0,25m/s
0,20m/s
0,20m/s 2000 mm
0,15m/s
13
0,15m/s
14
1000mm
15
golvniv
floor 16
wall
Vgg 1000 mm 2000 mm 3000 mm
17
Figure 36.
18
Figure 34-36. Air velocities below s supply air beam, where the air flow is 14 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
19
3 3000mm 3000mm
4 0,20m/s
0,15m/s
0,20m/s
0,15m/s
0,20m/s
2000 mm 0,25m/s 2000 mm
0,15m/s 0,20m/s
5 0,15m/s
350
6
1000mm 1000mm
8 floor
golvniv floor
golvniv
wall wall
9
Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
11 1800-2000
3000mm
1100-1400
12
0,25m/s 0,20m/s 2000 mm
13 0,20m/s
0,15m/s 0,15m/s
14
1000mm
15
16 golvniv
floor
17 wall
Vgg 1000 mm 2000 mm 3000 mm
Figure 39.
18
19 Figure 37-39. Air velocities below s supply air beam, where the air flow is 17 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
3000mm 3000mm
3
0,20m/s 0,20m/s 4
0,20m/s 0,15m/s 0,15m/s
2000 mm 0,25m/s 2000 mm
0,15m/s 0,20m/s
0,15m/s 5
350
1000mm
6
1000mm
golvniv
floor floor
golvniv
8
wall wall
9
Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
1900-2100
3000mm 11
1200-1500
12
0,25m/s 0,20m/s 2000 mm
0,20m/s
0,15m/s 0,15m/s 13
14
1000mm
15
golvniv
floor 16
wall
Vgg 1000 mm 2000 mm 3000 mm
17
Figure 42.
18
Figure 40-42. Air velocities below s supply air beam, where the air flow is 20 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
19
3 3000mm 3000mm
4 0,20m/s 0,20m/s
0,15m/s 0,15m/s
0,20m/s
2000 mm 0,25m/s 2000 mm
0,20m/s
5 0,15m/s
0,15m/s
350
6
1000mm 1000mm
8 floor
golvniv floor
golvniv
wall wall
9 Vgg 1000 mm 2000 mm 3000 mm Vgg 1000 mm 2000 mm 3000 mm
10
11 2000-2200
3000mm
1300-1600
12
0,25m/s 0,20m/s 2000 mm
13 0,20m/s
0,15m/s 0,15m/s
14
1000mm
15
16 floor
golvniv
17 wall
Vgg 1000 mm 2000 mm 3000 mm
Figure 45.
18
19 Figure 43-45. Air velocities below s supply air beam, where the air flow is 23 l/s per active metre.
Standard air pattern profile (nozzles at a 30 angle). Nozzle pressure of 60 Pa.
2
1300 1000
5
4500
4500
0,20m/s 0,20m/s
9
3270 3270
Figure 46. Figure 47. Default Setting Angled Nozzles (or AirGuide).
10
Throw and spreading 300 mm under the ceiling. Throw and spreading 300 mm under the ceiling.
11
2000 1100
12
13
14
4500
4500
0,20m/s 0,20m/s
15
16
3270
18
3270
4 Product:
Premax I-60-12-125-A2-1.8 m 40
Air quantity: 15 l/s
Nozzle pressure: 60 Pa
5
Designations Plus features:
AirGuide
6 Product/Version: Premax I or X Regula Secura
Type: 60, 62 Heating
Connection diam. water, [mm]: 12 or 15 Cooling control valve
7 Connection diam. air, [mm]: 125 Cooling actuator
Coupling options: A, B, C, D Heating control valve
Coupling options, exhaust: E, F, G, H Heating actuator
8 Water:
Length, [m]:
1, 2, 3, 4, 7, 8
1.2 m, 1.8 m, 2.4 m and 3.0 m Accessories:
Regula Combi: 40
Plus features: See page 7
9 Angled Nozzles: 30 (default), 16, 0 Product:
AirGuide:30-10 Premax I-60-12-125-A1-3.0 m 10
10 Plus features:
AirGuide
Regula Combi
11 Regula Secura
Cooling control valve
Cooling actuator
12 Accessories:
Tectite tool: 1
Order code
13
ProductPremax I-60 12 125 A1 1.8 80 20
Type:
14 I-60, I-62
I = Integrated, lay-in
X-60
15 X = i.e. hidden T-bar, edge DS
Water connection:
12 mm, 15 mm
16 Air connection:
125 mm
17 Connection type:
A1, A2, A3, A4, A7, A8, B1, B2, B3, B4,
B7, B8, C3, C4, C7, C8, D3, D4, D7, D8
18 Product length:
1.2 m - 1.8 m - 2.4 m - 3.0 m
Static nozzle pressure (Pa):
19 Air volume (l/s):