You are on page 1of 12

User manual

for the operator

Controls for THISION L ECO

www.elco.net 9B.52.19.00 / 02.16


1
Table of contents

Table of contents ..................................................................... 2

Basics Summary description.................................... 3


Safety........................................................... 3

Operation Description of display................................... 4


Description of display and keyboard............ 5
Display read-out........................................... 6
Basic operations........................................... 7
Selecting programs...................................... 7

Programming of end-users Menu structure at Basic level....................... 8


Parameters end users (blue screen)............ 9

Water pressure Filling the heating system............................. 10

Maintenance Decommissioning......................................... 11
Error............................................................. 11
Maintenance................................................. 11
Warranty....................................................... 11

2
General

Summary description, safety


These operation instructions describe In case you smell gas: Protection for corrosion
the functioning and the operating of - No naked flames! Do not smoke! Do not use any sprays, chlorine
the ELCO THISION L ECO boilers. - Do not operate electrical containing agents, solvents, paint etc.
This manual is for the end user. For switches for lights or any other around the boiler or around the air
installation and servicing there is an appliance intake supply entrance of the boiler.
installation & servicing instructions - Do not use a telephone These substances have negative
manual for the installer. - Turn off gas supply at meter influences on the boiler and can lead
Read this manual fully before operating - Open windows and doors to corrosion resulting in failure of the
the boiler. In case of doubt or errors - Notify any persons in the boiler.
contact your installer. building and leave the building at
ELCO reserves the right to change the once Checking the water pressure
specifications and dimensions without - Call Gas company or installer Check the water pressure in the central
prior notice. only when outside the building heating installation regularly.
Use only potable water for filling.
Safety Additives only after clearance by
The device may be operated only by ELCO.
authorized persons who have been Contact your installer in case of doubt.
instructed on the operation and use
of the device. Improper use may Description of the boiler
cause damage to the device and / or The ELCO THISION L ECO boiler
to the connected installation. is a room sealed, condensing and
modulating central heating boiler and
The appliance is not to be used by meets the European requirements
children or persons with reduced (CE). A declaration of conformity is
physical, sensory or mental available on demand from the supplier.
capabilities, or lack of experience
and knowledge, unless they The efficiency of the boiler is very
have been given supervision or high and the radiation convection and
instructions. standby losses very low. The emission
of noxious substances is far below the
Children being supervised are not to fixed standards so the boiler meets the
play with the appliance. requirements of today.

Work on the boiler must be carried If changes are made to the boiler
out by a competent person, using construction the boiler no longer
correctly calibrated instruments complies with the CE requirements.
with current test certification. When
replacing parts use only ELCO
Service parts.
Contact details for ELCO can be
found on the back page of this
manual.

3
Operation

Description of display
Open the flap by pushing right next of The boiler has a pilot-control. This
the flap on the round button to reach control takes care of most of the
the display and keybord. manual settings but also provides
numerous settings to adjust the control
exactly to the installation and user
requirements.

Display
The LCD screen is backlit. The light
is activated by pushing one of the
9 10 11 12 13 buttons.

There are 3 light colours available. The


various colours indicate the following:
1 5
Blue Basic level
Green Setting level
2 6 Red Problem display (flashing)

3 7 Having pressed a button, the screen


light stays on for 2 minutes (blue
4 8 screen) or 20 minutes (green screen).

Boiler symbols are not visible in


case of a single boiler or when
Screen explanation
no bus communication cable is
connected (Error code M024sc08).
1. CH-program active

2. DHW-program active

3. Clock program active

4. Pump continuously active or pumps


active during frost protection

5. Boiler off at outside temperature


> T-day (when day temperature is
active) or
> T-night (when night temperature
is active)

6. System pump on

7. Burner on. Starts flashing during


heat demand, continuous when
burner is on

8. Chimney sweep function (100%


power for emission measurement)

9. Boiler address:
1 = Cascade Master
2.8 = Cascade Slaves
ABCD
EFGH 10. Identification burner inside boiler

11. Night temperature active

12. Day temperature active

13. 2 text lines with 8 characters each.


The operational status, messages and
possible errors are displayed here.
4
Operation

Description of display and keyboard


Operational status
- Standby Standby. Boiler is ready for operation.

Standby
- Vent.Phase Ventilation stage
- Ignition phase Ignition stage
- Burner lit CH Burner active for heating
- Burner lit DHW Burner active for hot water
- CH T > Tset Burner off on account of too high flow temperature CH
- Overrun CH Overrun time pump over CH
- Overrun DHW Overrun time pump over DHW
- Service Boiler needs maintenance. Contact installer
- Frost Burner active for frost protection

Value increase / change


Emission measurement Back / correction
+
Backward Forward
OK

Reset* R - Confirm selection

Value decrease / change

The keyboard consists of a logical


button allocation for menu control,
confirmation, and correction and
emission measurement.

* Reset only functions in case of an


Error or Message. If reset is rapidly
pressed over a short period of time,
the device will block completely.
Only loss of power (unplug) will
restart the device completely.
Recommendation: First identify the
fault by finding the fault code in the
fault-code list in the problem-shooting
chapter and solve the problem.

The main switch is located on the right


hand side of the keyboard. This switch
controls the 230V power supply (L and
N).
8X.44.08.00 / 05.11

On/Off

T4 Open- General
LPG Out Therm purpose
On/Off

Heat T3 T10 0-10Volt LWCO


demand DHW
signal

2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 13 14
8X.44.09.00 / 05.11

Bus

5
Operation

Display read-out
The standard read-out offers 3
information screens.
Switching to different screen scan be
found using the + or - button
1
1. “Good”- read-out
Good with actual day and time (see

Good
above)

we 10:17
2
2. Operational status
Refer to chapter 9.1 for explanation
of texts
Standby

3
3. Technical read-out
Actual water flow temperature. (T1

20.0 °C in °C) and water pressure (P in bar).

1.65 bar

6
Operation

Basic operations
Selecting programs
Switching on the Heating, DHW and
Pump program
By switching on the functions ( ,
and/or ) the boiler is turned on.

Proceed as follows:
From the standard display with
illuminated display:
1. Press the right arrow button:
Basic The display shows: Basic settings;

Settings
2. Press the OK button;

3. Press the right arrow button:


The display shows: CH prog off;

CH prog
4. Press the + button:
The display shows: CH prog on;

off 5. Press the OK button;

6. Repeat the procedure from point 3.


In this way the functions DHW and
Pump can be switched on.
CH prog 7. Press the return button to go back

on
to the standard display.

Depending which programs are


switched on the corresponding symbols
will be shown:

CH

DHW

Pump

7
Operation

Menu structure at Basic level


Menu structure

There are 2 setting levels


1. Basic level (manager/user):
Blue screen
2. Setting level (Installer):
Green screen

With the illumination switched off,


first press on one of the buttons to
switch the illumination on and then
continue with the setting. Having
pressed the last button, the blue
illumination will switch off after 2
min.

Menu structure at Basic level


Good

Operational status Basic setting Timeprog. options Param Mode Info

Tech. Read-out

CH prog Set Date and time Boiler param Cascade

DHW prog Timeprog. CH Other

Pump prg. Timepr. DHW

Timepr. CH

Timep. DHW

CH temp

DHW temp

Units
Remark: Depending which
Language
parameter settings are set, some
options will not be displayed.
Restore Defaults

With the arrow buttons you can go Refer to the Parameters chapter for all
through the different chapters. parameters and related settings.

Press OK to select or to confirm a


change.

With the + and - button you can


increase or decrease a selected
value.

Back to previous screen or standard


read out: Press this ‘return-button’.

8
Parameters end users (blue screen)

Basic display “dark”


- Press on one of the buttons to switch the illumination on (blue screen). Overview of commissioning
- Press the + or - button to go to the “Operational status” read-out parameters
- Press arrow button to the right to go to the required menu (arrow to the low The parameter lines with a grey
goes back) background only become visible at the
- Press OK to select the required menu technician level.
- Press the arrow button to the right to go to the required parameter (arrow to the The complete parameter list becomes
low goes back) visible at the technician level.
- Use the + and - button to change the value
- Press OK to confirm the new value
- Use the retrun button to go back to menu or standard read-out.
Having pressed the last button, the blue illumination will switch off after 2 min.

Basic settings Basic settings


PARA factory setting Description Range
CH prog off CH-program on/off
DHW prog off DHW-program on/off
Pump prg off Pump program (frost protection) on/off
Timerpr CH off Clock program CH on/off
Timerp DHW off Clock program DHW on/off
"Adjusted maximum flow temperature in °C
CH temp 85 10-90
(only active with connected outdoor sensor & P101=0)"
DHW temp 65 Adjusted maximum DHW temperature in °C (only visible when P100>0 and T3 is connected) 10-80
Units SI Selection possibility units SI=Europe, Imp(erial)= USA SI/Imp
GB, NL, I, D, F,
Language GB Language selection
PL, TR, RUS, UA
Restore defaults Reset of the factory settings (dependant of selected level)
Timeprog options Clock program options
PARA factory setting Description Range
Set date and time
Set Time 00:00 Actual time setting in hours and minutes
Set Date DD-MM-YY Actual date setting day-month-year
Daylight saving Europe Zone for daylight saving Off-Eur-USA
12/24hrs 0-24h 12-hour (AM/PM) or 24-hour display AM/PM-24h.
Date format DD-MM-YY Reproduction of date display (DD-MM-YY, MM-DD-YY, YY-MM-DD)
Time prog CH (only visible when NOT OpenTherm or 0-10V)
Day temperature according heating line in °C "10-30
Day temp T-day 20
(if outdoor sensor is NOT connected: max flow temp.) (10-90)"
Night temp T-night 15 Night temperature according heating line (Eco) in °C 10-30
Select Preset Preset 1 Choice for the preselected time programm CH 1 or 2
See table time programs CH
mo1 off It is possible to select 4 switch moments (steps of 30 min.) per day.
Adjust Timeprog
03:00 Choice: day temperature, night temperature, off, - - -
Copy function to next day: after switch moment 4.
Store Preset Store of the adjusted time program for CH
Timepr DHW (only visible when NOT OpenTherm)
Select Preset Preset 1 Choice for the preselected time programm DHW 1 or 2
See table time programs DHW
mo1 off It is possible to select 4 switch moments (steps of 30 min.) per day.
Adjust Timeprog
03:00 Choice: on, off, - - -
Copy function to next day: after switch moment 4.
Store Preset Store of the adjusted time program for DW
Param Mode Parameter chapter
PARA factory setting Description Range

Boiler param Boiler parameters


P132 1 Pump continuously 1-2
1:Unit pump P1
2 Unit pump P1 and installation pump P3
Info Information
Cascade Information of cascade system
T3 xx.x°C DHW temperature T3 in external cylinder in °C (if connected and P100 is selected for DHW)
T4 xx.x°C Outdoor temperature T4 in °C (if connected)
T10 xx.x°C Temperature T10 sensor in low velocity header in °C
Boiler Information of the boiler
T3 xx.x°C DHW temperature T3 in external cylinder in °C (if connected and P100 is selected for DHW)
Others
Stand-by xx h Number of hours stand by
Burn. On xx h Number of running hours with burner on
Service xx h Number of running hours to go for maintenance interval
Ignition xx Number of times ignition
Faults xx Number of times in error

9
Water pressure

Filling the heating system


When the screen shows ‘FILL’ the Fill the heating system only
water pressure is too low. Press, if with drinking water. Refer to the
necessary the + or - button to read out Water Quality chapter for quality
the water pressure. Please contact requirements of the filling water in
your installer/supervisor to check the the installation manual.
installation and top up.

Water pressure
Screen display
+
Good Operation Technical Description Action
OK Read-out status read-out
- FILL FILL xx.x°C Water pressure is 0 bar,
Top up water
dd 00:00 Bx12sc03 P0,0 boiler off
Water pressure above
FILL FILL xx.x°C 0.7 bar. The boiler is off. Top up water until

FILL dd 00:00 Bx12sc03 P>0,7 The automatic venting


program starts
approx. 1,7 bar

Automatic venting
Block. Vent xx.x°C program, afterwards Top up water until
dd 00:00 Prog. P>1,2 (approx. 13 min.) boiler is approx. 1,7 bar
on standby
Water pressure is good.
Good xx.x°C
(variable) Boiler standby or in None
dd 00:00 P>1,0 <4,0
normal operation
Block. xx.x°C Water pressure too high, Drain water until
dd 00:00 P>4,0 boiler off due to blocking approx. 1,7 bar
Water pressure is good.
Good xx.x°C
(variable) Boiler operates normally None
dd 00:00 P<3,7
again
Message/ FILL Water pressure too low.
xx.x°C Top up water until
Block. Message Boiler is limited to 50%
P<1 >0,7 approx. 1,7 bar
dd 00:00 Mx24sc14 load

Venting program
When, on filling the system, the water Interrupting the venting program (not
pressure rises above 0.7 bar, the recommended) is only possible from
venting program will start automatically. the setting level by pressing OK during
The program lasts approx. 13 minutes the venting program.
and in doing so, turns the pump on
and off and, if fitted, the three-way For boiler checks please refer to the
valve every 80 seconds to remove the chapter Checks prior to commissioning.
remaining air from the boiler. All venting For any checks or setting changes,
points still have to be vented when refer to the Basic Settings chapter.
filling the installation. The boiler will be
on standby after the venting program.

The automatic venting program only


vents the boiler and not the rest of

Block.
the installation.

Read-out 1 (Good status) displays


we 10:17 Block. with actual day and time on the
screen.

Read-out 2 (operational status)


displays Vent Prog on the screen.

Vent [From Good press the – button 1x:


Vent Prog is now displayed]

Prog.
10
Maintenance

Decommissioning, error, maintenance and warranty


Maintenance works Decommissioning Error, maintenance and warranty
- Switch the boiler to stand-by In some cases it might be necessary If a fault is detected the boiler will be
operating mode; to put the complete boiler out of blocked. This will be reflected, with an
- Use the ON/OFF switch (A) to turn operation. The boiler is put out of E for Error, a B for Blocking or M for
the boiler off; operation by switching off the three Message and a number code on the
functions ( , and/or ). display.
You can try to reset the boiler by
Proceed as follows: pressing the Reset key once. If the
From the standard blue screen display: problem remains please contact your
1. Press the right arrow button: installer and inform them about the
Screen displays: Basic setting; fault and give them the number code.
2. Press OK; If, on the screen the message
Screen displays: CH prog on; “Service” appears, the installer must
3. Press the - button: perform maintenance according to the
Screen displays: CH prog off; installation and service manual. Please
4. Press OK; contact your installer or service
5. Repeat procedure from point 3 provider.
onward.
- Interrupt the power supply to the This switches off the functions DHW We advise you to obtain a service
boiler, by operating the mains circuit prog and Pump prog respectively. contract with your installer for regular
breaker in the boiler room. maintance and adjustment to keep your
8X.44.08.00 / 05.11

On/Off
6. Press the return button to return to
On/Off
LPG - Interrupt the gas supply to the
T4
Out
Open-
Therm
General
purpose
the standard display. boiler safe and in good condition.
Heat boiler.T3 T10 0-10Volt LWCO
If you discover any leaks from the
demand DHW
signal
During emptying of the boiler, it is ELCO recommends leaving the power
3 4 5 6
possible that a part of the heating
1 2 3 4 5 6 7 8 9 10 11 12 13 14

switch switched on to ensure that the boiler contact your installer.


water stays behind. Make sure that any boiler pump(s) and three-way valve (if
remaining heating water cannot freeze, fitted) are automatically activated to The casing of the boiler can be cleaned
in case of a frost hazard. prevent them from sticking. The frost with a normal non abrasive cleaning
8X.44.09.00 / 05.11

Bus

protection remains active. Leave gas agent.


supply open.
The warranty terms and conditions are
If frost, during the period when the provided on the warranty card which is
boiler is out of operation, is likely, supplied with the boiler.
then you are advised to remove the
power from the boiler and drain the
boiler(s) and installation. In this
case: close the gas valve.

11
Service:

12 www.elco.net

You might also like