Features Phase segregated current measurement Activation from line disconnector position
Application The stub protection operates for faults in the are opened. The use of the function can be
parts of 1 1/2 and ring bus station configura- extended to various other purposes, when a
tions, which cannot be protected by the dis- three phase overcurrent protection can oper-
tance protection function if the line isolators ate only under special external conditions.
Design The function operates as a three phase instan- the line disconnector has to be connected to
taneous overcurrent protection. The function the STUB-RELEASE functional input by
is released when the line disconnector is configuration.
open; a normally closed auxiliary contact of
The operating level of the overcurrent protec-
tion is settable over a wide range.
Function block
STUB-
STUB
BLOCK TRIP
RELEASE
xx00000199.vsd
Input and output Table 1: Input signals for the STUB (STUB-) function block
signals Signal Description
BLOCK Block of stub protection
RELEASE Release of stub protection