Stub protection STUB

1MRK 580 022-BEN


Page 1
Issued: January 2001
Status: New
Data subject to change without notice

Features Phase segregated current measurement Activation from line disconnector position

Application The stub protection operates for faults in the are opened. The use of the function can be
parts of 1 1/2 and ring bus station configura- extended to various other purposes, when a
tions, which cannot be protected by the dis- three phase overcurrent protection can oper-
tance protection function if the line isolators ate only under special external conditions.

Design The function operates as a three phase instan- the line disconnector has to be connected to
taneous overcurrent protection. The function the STUB-RELEASE functional input by
is released when the line disconnector is configuration.
open; a normally closed auxiliary contact of
The operating level of the overcurrent protec-
tion is settable over a wide range.

Function block
STUB-
STUB
BLOCK TRIP
RELEASE

xx00000199.vsd

Input and output Table 1: Input signals for the STUB (STUB-) function block
signals Signal Description
BLOCK Block of stub protection
RELEASE Release of stub protection

Table 2: Output signals for the STUB (STUB-) function block


Signal Description
TRIP Trip by stub protection

Technical data Table 3: STUB - Stub protection


Function Setting range Accuracy
Operate current I> (20-300) % of I r +/- 2.5 % of Ir at I Ir
+/- 2.5 % of I at I > Ir
Stub protection STUB
1MRK 580 022-BEN
Page 2

Manufacturer
ABB Automation Products AB
Substation Automation Division
SE-721 59 Vsters
Sweden
Tel: +46 (0) 21 34 20 00
Fax: +46 (0) 21 14 69 18