Professional Documents
Culture Documents
Geh275. Olympianpdf PDF
Geh275. Olympianpdf PDF
G E N E R A T I N G S E T
GEH275 (3-Phase)
50 HZ
STANDBY 275 kVA / 220 kW
PRIME 250 kVA / 200 kW
FEATURES
GENERATING SET EXHAUST SYSTEM
Complete system designed and built at ISO9001 Heavy duty industrial capacity exhaust silencer
certified facility (approximately 10 dB reduction) supplied loose
Factory tested to design specifications at full load
conditions
COOLING SYSTEM
Standard ambient temperatures up to 50 C (122 F)
Fully engineered with a range of options
Fan, fan drive and charging alternator fully guarded
and accessories
Coolant drain valve
ENGINE Antifreeze protection coolant
Industrial water cooled diesel engine
Isochronous electronic speed control CIRCUIT BREAKER
3-pole miniature circuit breaker (mcb) < 160 amps
Governor, electronic
Electrical system, 24 VDC and 3-pole molded case circuit breaker (mccb)
WARRANTY
Baseframe incorporates heavy-duty fabricated steel
All equipment carries full manufacturer's warranty.
fuel tank, 8 hours running capacity
W H E R E T H E W O R L D T U R N S F O R P O W E R
5 0 H z S T A N D B Y 2 7 5 k V A / 2 2 0 k W
P R I M E 2 5 0 k V A / 2 0 0 k W
ENGINE
Manufacturer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Perkins
Model. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1306-E87TA330
Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-Cycle
Aspiration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Turbocharged
Cylinder configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . In-line 6
Displacement L (cu in) . . . . . . . . . . . . . . . . . . . . . . . . . . 8.7 (531)
Bore/stroke mm (in). . . . . . . . . . . . . . . . . . . . . . 117/136 (4.6/5.4)
Compression ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16.9:1
Engine speed rpm
50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
L W
50 Hz
Generator Technical Data 415/240V 400/230V 380/220V 230/115V 220/127V 220/110V 200/115V
Motor Starting Capability:
Self Excited (kVA) 623 585 536 585 686 536 585
AREP Excited*** (kVA) 746 701 642 701 822 642 701
PM Excited**** (kVA) 746 701 642 701 822 642 701
Full Load Efficiency
Standby % 92.4 92.4 92.1 92.4 92.4 92.1 92.4
Prime % 92.7 92.7 92.5 92.7 92.7 92.5 92.7
Reactances (per unit) Xd 2.69 2.90 3.21 2.90 2.40 3.21 2.90
Saturated X'd 0.12 0.13 0.14 0.13 0.11 0.14 0.13
Reactances X"d 0.073 0.079 0.088 0.079 0.065 0.088 0.79
are shown Xq 1.62 1.74 1.93 1.74 1.44 1.93 1.74
applicable to the X"q 0.091 0.098 0.109 0.098 0.081 0.109 0.098
standby rating X2 0.082 0.088 0.098 0.088 0.073 0.098 0.088
X0 0.005 0.005 0.006 0.005 0.004 0.006 0.005
t'd t" t'do ta
Time Constants:
100 ms. 10 ms. 2175 ms. 15 ms.
****With AREP Excited Option AR20A/AR21A
****With PMG Excited Option AR18A/AR19A
RATING DEFINITIONS
STANDBY PRIME POWER
These ratings are applicable for supplying These ratings are applicable for supplying
continuous electrical power (at variable load) in continuous power (at variable load) in lieu of
the event of a utility power failure. No overload commercially purchased power. There is no
is permitted on these ratings. When used at limitation to the annual hours of operation and
standby rating the alternator will be peak this model can supply 10% overload power for
continuous rated (as defined in ISO8528-3). 1 hour in 12 hours.
5 0 H z S T A N D B Y 2 7 5 k V A / 2 2 0 k W
P R I M E 2 5 0 k V A / 2 0 0 k W
www.CAT-ElectricPower.com
LEHF2645-02 (06/04) Materials and specifications are subject to change without notice.
The International System of Units (SI) is used in this publication.