Professional Documents
Culture Documents
Transformer
Details
Rated Power 30 Mva % Impedance 30 mVA base
Vector Group Dyn1 At Tap-1 14.50 %
At Tap-9 14.00 %
Rated Voltage HV 115 Kv At Tap-21 13.80 %
150.61
Rated Current HV Amp.
CT Ratio HV 400/5 HV Voltage
At Tap-1 126.5 Kv
Rated Voltage LV 13.8 kV At Tap-9 115 kV
1255.1
Rated Current LV Amp. At Tap-21 97.75 kV
CT Ratio LV 2000/5
Apply 3-ph 380 Volts at the Primary side of the Transformer and SHORT all the THREE PHASE LV
after Differential CTs.
= 380 x 150.61
0.14 x 115000
= 3.554 Amps.
= 0.044 Amps.
= 380 x 1255.1
0.14 x 115000
= 29.62 Amps.
Expected Secondary Current of Low side CT
= 29.62 x 5
2000
= 0.0740 Amps.
Now, for checking of Transformer STABILITY, you have to create a fault on outside of the
Differential CTs.
R
Y
B
High Side
CTs
HV
Breaker
Transformer
Neutra
l
CT
LV Breaker Create a FAULT here.
Low Side
CTs
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like
FTs, Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should not operate.
2. REF Relay should not operate.
High Side
CTs
HV
Breaker
Transformer
Neutra
l
CT
LV Breaker
Low Side
CTs
After this, measure the current of High Side CTs and Low Side CTs in all the measurable points like
FTs, Ammeter, Diff. Relay, REF Relay etc.
Result,
1. Diff. Relay should show Differential Current.
2. REF Relay should show Differential Current.
REF Stability
We already checked while doing Transformer Differential Stability, but I am displaying here
another way to do REF stability Phase by Phase.
R
Y
B
High Side
CTs
HV
Breaker
Transformer
Neutra
l
CT
LV Breaker
Create a FAULT here.
Low Side
CTs
Result,
1. REF Relay should not operate.