HIRIP / RTXF 36 kV 40 kA
Leading edge technology
Micafil brand products are the world leader in RIP techno-
logy for oil-free, dry bushings
2 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
High current transformer bushing in detail
Cross-section of the HIRIP bushing 1a
1 Aluminum conductor 1
2 Porcelain insulator 4
5
3 Dry filling Micagel
6
4 RIP condensore core
1b
5 Mounting flange with integrated measuring tap
Partial discharge-free up to double service voltage Micafil RIP high current bushings are specified and tested
High temperature resistance (class E, 120C) according to the latest IEC 60137 and IEEE C57.19.00/01
Low dielectric losses (tan < 0.35 %) standards.
Maintenance free
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 3
General information
Common specifications
Please consult ABB Switzerland Ltd, High Voltage Components for conditions that are outside
of the standard specification above.
Electrical data
The values below are according to IEC 60137 and IEEE C57.19.01
1 2 3 4 5 6 7 8 9 10 11
Reference current
Rated voltage Ur
AC test voltage
AC test voltage
System voltage
ground voltage
BIL 1.2 / 50 s
BIL 1.2 / 50 s
dry and wet
current, 2 s
dry/ w et
Ur / 3
kV kV kV kV kV kV kV kV kA kA kA
36 200 / 7000 36 21 77/70 170 34.5 22 80 / 75 200 7 100 253
36 200 / 11 000 36 21 77/70 170 34.5 22 80 / 75 200 11 100 365
36 200 / 15 500 36 21 77/70 170 34.5 22 80 / 75 200 15 100 490
36 200 / 22 000 36 21 77/70 170 34.5 22 80 / 75 200 22 100 635
36 200 / 26 000 36 21 77/70 170 34.5 22 80 / 75 200 26 100 738
36 200 / 37 000 36 21 77/70 170 34.5 22 80 / 75 200 37 100 1096
4 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 5
Technical data and dimensions
Type Fig. RTXF 36-200/7000 RTXF 36-200/11000 RTXF 36-200/15500 RTXF 36-200/22000 RTXF 36-200/26000 RTXF 36-200/37000
m [kg] 72 77 87 107 114 129 153 163 184 208 222 251 255 273 309 362 387 436
L6 [mm] 1 0 100 300 0 100 300 0 100 300 0 100 300 0 100 300 0 100 300
L [mm] 875 975 1175 875 975 1175 875 975 1175 875 975 1175 875 975 1175 875 975 1175
L1 [mm] 140 240 440 140 240 440 140 240 440 140 240 440 140 240 440 140 240 440
L2 [mm] 486 486 486 486 486 486
Lk [mm] 1080 1080 1080 1080 1080 1080
Lf [mm] 310 310 310 310 310 310
D1 [mm] 1 220 300 400 525 625 835
D2 [mm] 220 300 400 525 625 835
D3 [mm] 3 290 400 535 620 720 930
D4 [mm] 335 450 590 680 780 990
D5 [mm] 1 280 360 470 590 695 905
D6 [mm] 400 480 585 710 815 1025
b1 [mm] 4 20 22 23 23 23 24
b2 [mm] 19 19 19 19 19 19
c1 [mm] 151 234 335 462 557 768
c2 [mm] 70 110 170 200 195 320
h1 [mm] 5/6 52 52 52 52 52 52
h2 [mm] 150 200 250 350 450 550
y1 8 12 20 28 32 44
y2 6 8 10 14 18 22
v [mm] 2 15 20 22 22 22 22
z 12 12 16 16 16 24
Terminal oil side Fig. 5/6 b) Fig. 5/6 c) Fig. 5/6 b) Fig. 5/6 b) Fig. 5/6 b) Fig. 5/6 b)
m = weight b1 =
minimum air side terminal thickness
L6 = current transformer extension b2 =
minimum oil side terminal thickness
L = length of the bushing c1 =
terminal pad distance (air side)
L1 = oil side insulation distance c2 =
inner width of terminal area (oil side)
L2 = air side length of the bushing h1 =
minimum air side connection area width
Lf = minimum arcing distance h2 =
minimum oil side connection area width
Lk = minimum creepage distance y1 =
number of air side connection surfaces each
D1 = maximum diameter of dielectric equipment support with twin thread for 48 mm wide flexible connector
D2 = inside diameter of the flange sealing surface y2 = number of oil side connection surfaces each
D3 = diameter of flange bolt circle with twin thread for 48 mm wide flexible connector
D4 = maximum diameter of flange v = diameter of the holes in the flange
D5 = maximum diameter of head design z = number of holes in the flange
D6 = maximal shed diameter
6 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
A
D6 z
v
D5
D3
D4
19
131,5
90
5
D3
L2
Fig 2 Fig 3
L
20
D1+10 D1
L1 + L6
D2 c1
L6
b2
70178
c2
c1
b2
b1
y1
M1 h1
2
20
M12 M12
85
40
85
40
40
y2 50 y2 50 85
20
20
h2 h2
Air side Oil side Oil side
-2B -2B
44,45
44,45
44,45
100
100
100
y2 44,45 y2 44,45
25,4
25,4
y1 h2 h2
h1
Air side Oil side Oil side
Fig 6a Fig 6b Fig 6c
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 7
Operating current diagrams
f 50 / 60 Hz
If all the connection pads are not occupied, the current could
be limited, since the neighbour conductor will also influence
the thermal behavior of the bushing.
Fig. 7
8 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
Current curve RTXF 36200/7000, drawing no. 1ZCD061816, diagram no. HLJK014604
Tair (C) Tair (C) Tair (C) Tair (C) Tair (C) Tair (C) Tair (C) Tair (C) Tair (C)
8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5 8.5
60 60 60
8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
60 60 60
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
70 70 70
6.5 6.5 6.5 6.5 80 6.5 806.5 6.5 80 6.5 6.5
Current curve RTXF 36200/11 000, drawing no. 1ZCD061556, diagram no. HLJK014614
60 60 60
12.0 12.0 12.0 12.0 60
12.0 60
12.0 12.0 60 12.0 12.0
70 70 70
60 60 60
11.0 11.0 11.0 11.0 11.0
70 11.0
70 11.0 70 11.0 11.0
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
80 80 80 70 70 70
10.0 10.0 10.0 10.0 80
10.0 80
10.0 10.0 80 10.0 10.0
80 80 80
90 90 90
9.0 9.0 9.0 9.0 909.0 909.0 9.0 90 9.0 9.0
90 90 90
8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0 8.0
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 9
Current curve RTXF 36200/15 500, drawing no. 1ZCD061820, diagram no. HLJK014624
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
15.0 15.0 80 15.080 80 15.0 15.0 15.0 15.0 15.0 70 15.070 70
80 80 80
14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0 14.0
80 80 80
13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0 13.0
Current curve RTXF 36200/22 000, drawing no. 1ZCD061826, diagram no. HLJK014634
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 10
Current curve RTXF 36200/26 000, drawing no. 1ZCD061855, diagram no. HLJK014644
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
24.0 24.0 80 24.080 80 24.0 24.0 24.0 24.0 24.0 24.0
70 70 70
80 80 80
22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0 22.0
80 80 80
Current curve RTXF 36200/37 000, drawing no. 1ZCD061892, diagram no. HLJK014654
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
Ir (kA)
11 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
Ordering information
Type designation
Reference current with current transformer extension = 0 mm, maximum daily mean oil temperature = 90 C
and maximum daily mean air temperature = 70 C in bus duct, frequency = 50 Hz
Ordering number
Ordering type number (part 1)
The ordering number comprises two parts: Designation Ordering type number
Part 1 HIRIP RTXF 36 200 / 7000 1ZCD 061 816
- Ordering type number, which specifies the bushing type HIRIP RTXF 36 200 / 11000 1ZCD 061 556
Example
Part 1: RTXF 36 200 / 11000 - 1ZCD 061 556
Part 2: porcelain insulator color brown
current transformer extension 0 - R0011
terminal geometry version 1
The complete ordering number is: 1ZCD 061 556 R0011
12 HIRIP/RTXF 36kV40kA | ABB Switzerland Ltd, Micafil High Current Transformer Bushings
Other Micafil RIP bushings
There are no understandings, agreements representations, arising from course of dealing or usage of trade, are made
or warranties, expressed of implied, including warranties of regarding the information, recommendations, descriptions
merchantability of fitness for a particular purpose other than and safety notations contained herein.
those specifically set out by an existing contract states the
entire obligation of seller. The contents of the document shall In no event will ABB Switzerland Ltd, High Voltage Compo-
not become part of or modify any prior or existing agreement, nents be responsible to the user in contract, in tort (including
commitment, or relationship. negligence), strict liability or otherwise for any special, indirect,
incidental or consequential damage or loss whatsoever inclu-
The information, recommendations, description, and safety ding but not limited to damage to or loss or use equipment,
notations in this document are based on our experience and plant or power system, cost of capital, loss of profits or
judgement. This information should not be considered to be revenues, cost of replacement power, additional expenses
all-inclusive of covering all contingencies. If further information in the use of existing power facilities, or claims against the
is required, ABB Switzerland Ltd, High Voltage Components user by its customers resulting from the use of the information,
should be consulted. recommendations, description, and safety notations contained
herein.
No warranties, expressed, or implied, including warranties of
fitness a particular purpose or merchantability, or warranties
ABB Switzerland Ltd, Micafil High Current Transformer Bushings | HIRIP/RTXF 36kV40kA 13