DWG Number 399A4551 Rev B Released 2/2/2013 Page 1 of 71

SIZE DWG NO SH REV


A 399A4551 1 B
REVISION HISTORY
REV ZONE DESCRIPTION DATE APPROVED
YYYY-MM-DD

A DEVICE SUMMARY SYSTEM 2012-08-16 DRAWN


0420,0426 & 4027 WAS UPDATED SV
AS PER ISS-0015983 AND
ENGINEER
SYSTEM 0419 WAS UPDATED AS
MLL
PER ISS-0015023. REFER ISSUE
NOTES IN DEVICE SUMMARY FOR
DETAILS OF CHANGE.
ECO0069342. SELVAM VELUSAMY.
B DEVICE SUMMARY SYSTEM 4027 2013-01-31 DRAWN
UPDATED PER ISS-0034683. SV
REFER ISSUE NOTES IN DEVICE
ENGINEER
SUMMARY FOR DETAILS OF
MLL
CHANGE. ECO0090025 SELVAM
VELUSAMY.

THIS DOCUMENT SHALL BE REVISED


IN ITS ENTIRETY. ALL SHEETS OF
THIS DOCUMENT ARE THE SAME
REVISION LEVEL AS INDICATED.

REVISION DESCRIPTION IS FULLY


STATED ON FIRST SHEET OF
DOCUMENT
© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


DRAWING TYPE
SIGNATURES
DRAWN B,SAM KAMLESH GE Energy
DRAWN DATE 2012-06-01
GENERAL ELECTRIC COMPANY
CHECKED TS,RAVI
CHECKED DATE
ENGRG B,SAM KAMLESH
Device Summary
ENGRG DATE
FIRST MADE FOR ML: DM:719427 CC:0414
APPLIED PRACTICES ADDITIONAL APPROVALS
SIZE CAGE CODE DWG NO
SEE PLM FOR APPROVAL
INFORMATION A 399A4551
SIM TO: SHEET 1 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 2 of 71

A
SIZE DWG NO SH REV
399A4551 2 B
System Title
0415 CONTROL DEVICES -TURBINE
0416 LUBE OIL SYSTEM
0417 COOL & SEAL AIR SYSTEM
0419 CONTROL AIR
0420 COOLING WATER SYSTEM
0422 GAS FUEL SYSTEM
0426 FIRE PROTECTION SYSTEM
0432 INLET AIR HEATING
0434 HYDRAULIC SUPPLY SYSTEM
0436 HEAT & VENT SYSTEM
0440 LOAD EQUIPMENT
0442 TURBINE & COMPRESSOR WASH
0471 INLET AND EXHAUST
0474 HAZARDOUS GAS DETECTION
0477 FUEL PURGE
0492 PERFORMANCE MONITOR
4027 H2 ACCESSORIES (Ref. G2FA)
4035 FUEL GAS CHROMATOGRAPGH

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 2 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 3 of 71

A
SIZE DWG NO SH REV
399A4551 3 B
NOTES

Rev. "B"

Device PSL-2950 deleted from device system 4027 per ISS-0034683.

Selvam Velusamy,
31JAN13
-----------------------------------------------------------------------------------
Rev. "A"

Devices 23AP-1 & 26AP-1 are deleted from device system 0419 per ISS-0015023.

All devices are Modified in device system 0426 per ISS-0015983.

The devices 90LT-1, PI-CW-4, PI-CW-5, VA32-1, VPR64-2, VR64-10 & VR64-9 are Modified in device system 0420
per ISS-0015983.

Device MIC-292 deleted from device system 4027 per ISS-0015983.

Selvam Velusamy,
16AUG12

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 3 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 4 of 71

A
SIZE DWG NO SH REV
399A4551 4 B
SWITCH SETTINGS
Contact Condition Additional Contacts
NO- Normally open CEC Additional contact:
- Normally closed
Electrically common
NC- Normally closed CES Additional contact:
- Normally closed
Electrically separate
()- Parenthesis indicates sets of OEC Additional contact:
contacts - Normally open
Electrically common
OES Additional contact:
- Normally open
Electrically separate

Example: NORM=(2) NO-CEC

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 4 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 5 of 71

A
SIZE DWG NO SH REV
399A4551 5 B

Device System Settings


20-TQ2-2 0417 SOLENOID VALVE
DE-ENERGIZED:3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
DE-ENERGIZED TO TRIP OPEN VA7-2
20-TQ2-4 0417 SOLENOID VALVE
DE-ENERGIZED : 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED : 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
DE-ENERGIZED TO TRIP CLOSED VA7-3
20AC-1 0471 TURBINE INLET AIR EVAPORATIVE COOLER WATER BLOWDOWN SOLE
DE-ENERGIZED: 1 TO 3 & 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 & 2 TO 1 OPEN; 3 PLUGGED
230 VAC; 50 HZ; 25.00 W;
3-WAY VALVE FOR AUTO H2O BLOWDOWN
DE-ENERGIZED = H20 TO BLOWDOWN
ENERGIZED = H20 TO RECIRCULATION
1 PH
20AC-21 0471 INLET AIR EVAP COOLER MAKEUP WATER SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
230 VAC; 50 HZ; 25.00 W;
1PH
SOLENOID VALVE FOR MAKEUP WATER TO SUMP
20AC-23 0471 INLET AIR EVAP COOLER MAKEUP WATER SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
230 VAC; 50 HZ; 25.00 W;
1PH
SOLENOID VALVE FOR MAKEUP WATER TO SUMP
20AP-1 0419 APU SHUTOFF VALVE.
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
230 VAC; 50 HZ; SINGLE PHASE
PROTECTS DESSICANT FROM OVER TEMPERATURE. CONTROL SIGNAL NAME
IS L20AP1, APU TROUBLE RELAY (SHUT-OFF VALVE CLOSE RELAY). WIRE TO
MKV / MARKVI.
20CB-1 0417 COMPRESSOR BLEED SOL VALVE
NORM=B TO C OPEN; A CLOSED
20CB-2 0417 COMPRESSOR BLEED SOL VALVE
NORM B TO C OPEN; A CLOSED
20CM-1 0417 CASE TEMP. MANAGEMENT FLOW CONTROL DAMPER
FAILED POSITION = CLOSED

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 5 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 6 of 71

A
SIZE DWG NO SH REV
399A4551 6 B

Device System Settings


20CR-15 0426 FIRE PROTECTION SOLENOID
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
24 VDC;
FIRE PROT-CO2 RELEASE SOL VALVE
FM-200 RELEASE SOLENOID VALVE (PEECC)
20FGC-1 0422 FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
20FGC-2 0422 FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
20FGC-3 0422 FUEL GAS CONTROL VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
20FGS-1 0422 FUEL GAS STOP VALVE SOLENOID VALVE
DE-ENERGIZED: 1 TO 2 OPEN
ENERGIZED: 1 TO 2 CLOSED
125 VDC;
20PG-1 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
20PG-2 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
20PG-5 0477 GAS FUEL SYSTEM PURGE SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
PART OF VA13-5
20PG-6 0477 GAS FUEL SYSTEM PURGE AIR SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC;
PART OF VA13-6
20QB-1 0434 LIFT OIL SUPPLY ISOLATION VALVE
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
220 VAC; 50 HZ;
1 PH

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 6 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 7 of 71

A
SIZE DWG NO SH REV
399A4551 7 B

Device System Settings


20TH-1 0432 INLET HEATING CONTROL VALVE TRIP SOLENOID VALVE
125 VDC;
DE-ENERGIZE TO TRIP VA20-1
ENERGIZE TO OPERATE VA20-1
AREA CLASSIFICATION : NON-RATED
PROTECTION METHOD : D-FLAMEPROOF
20TV-1 0434 TURBINE COMPRESSOR IGV SOLENOID VALVE
125 VDC;
20TW-4 0442 OFF-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 20.60 W; 0.1600 A;
PART OF VA16-1
20TW-6 0442 ON-LINE COMPRESSOR WASH WATER INJ SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 20.60 W; 0.1600 A;
PART OF VA16-3
20VG-1 0422 FUEL GAS VENT SOLENOID VALVE TEST
DE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGED
ENERGIZED: 2 TO 1 OPEN; 3 PLUGGED
125 VDC;
20VG-2 0477 FUEL GAS VENT SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 10.60 W; 0.0800 A;
PART OF VA13-8
20VG-4 0477 GAS FUEL VENT SOLENOID VALVE
DE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGED
ENERGIZED: 1 TO 2 OPEN; 3 PLUGGED
125 VDC; 10.60 W; 0.0800 A;
PART OF VA13-13
20VG-8 0422 FUEL GAS VENT SOLENOID VALVE
DE-ENERGIZED: 1 TO 3 OPEN; 2 PLUGGED
ENERGIZED: 2 TO 1 OPEN; 3 PLUGGED
125 VDC;
20VS4-1 0422 FUEL GAS AUXILIARY STOP VALVE
20VS4-4 0422 FUEL GAS SAFETY SHUTOFF VALVE-SOLENOID VALVE
20WDET 0442 SOLENOID, 2 WAY VALVE TO RECIRCULATE WATER BACK TO TANK.
230 VAC; 50 HZ;
DE-ENERGIZED: 1 TO 2 CLOSED
ENERGIZED: 1 TO 2 OPEN
CONTROL SIGNAL NAME IS L20WDET. WIRE TO MK V / MK VI. MK V / MK VI
OUTPUT SIGNAL IS DRY CONTACT.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 7 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 8 of 71

A
SIZE DWG NO SH REV
399A4551 8 B

Device System Settings


23AC-1A 0471 TURBINE INLET AIR EVAPORATIVE COOLER MOTOR HEATER
35.00 W; 230 VAC; 1 PH; 50 HZ;
23AC-1B 0471 TURBINE INLET AIR EVAPORATIVE COOLER MOTOR HEATER
35.00 W; 230 VAC; 1 PH; 50 HZ;
23BL-1 0436 FAN MOTOR HEATER FOR 88BL-1
60.00 W; 230 VAC; 1 PH; 50 HZ;
23BL-2 0436 FAN MOTOR HEATER FOR 88BL-2
60.00 W; 230 VAC; 1 PH; 50 HZ;
23BN-1 0417 SPACE HEATER
100.0 W; 220/240 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88BN-1
23BN-2 0417 SPACE HEATER
100.0 W; 220/240 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88BN-2
23BT-1 0436 HEATER-TURBINE COMPT FAN MOTOR
200.0 W; 230 VAC; 1 PH; 50 HZ;
23BT-2 0436 HEATER-TURBINE COMPT FAN MOTOR
200.0 W; 230 VAC; 1 PH; 50 HZ;
23CM-1 0417 CASE TEMP. MANAGEMENT BLOWER MOTOR SPACE HEATER
120.0 W; 220/240 VAC; 1 PH; 50 HZ;
FOR MOTOR 88CM-1
23HG-1 0440 SPACE HEATER-GENERATOR
2.250 KW; 415 VAC; 3 PH; 50 HZ;
23HG-2 0440 SPACE HEATER-GENERATOR
2.250 KW; 415 VAC; 3 PH; 50 HZ;
23HL-3 0436 SPACE HEATER-ACCESSORY COMPT, LUBE OIL REGION
3.600 KW; 415 VAC; 1 PH; 50 HZ;
USED FOR HUMIDITY CONTROL
23HQ-1 0434 HEATER-HYDRAULIC OIL PUMP MOTOR
60.00 W; 220 VAC; 1 PH; 50 HZ;
23HQ-2 0434 SPACE HEATER-HYDRAULIC PUMP MOTOR
60.00 W; 220 VAC; 1 PH; 50 HZ;
23HT-3A 0436 SPACE HEATER-TURBINE COMPARTMENT
3.600 KW; 415 VAC; 1 PH; 50 HZ;
HEATING FOR HUMIDITY CONTROL
23HT-3B 0436 SPACE HEATER-TURBINE COMPARTMENT
3.600 KW; 415 VAC; 1 PH; 50 HZ;
HEATING FOR HUMIDITY CONTROL
23IC-1 0471 MOTOR HEATER FOR DEVICE 88IC-1
35.00 W; 230 VAC; 1 PH; 50 HZ;
23KE-1 0440 HEATER-GENERATOR COLLECTOR ENCLOSURE
150.0 W; 230 VAC; 1 PH; 50 HZ;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 8 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 9 of 71

A
SIZE DWG NO SH REV
399A4551 9 B

Device System Settings


23QA-1 0416 HEATER-AUX LUBE OIL PUMP MOTOR
100.0 W; 230 VAC; 1 PH; 50 HZ;
23QA-2 0416 SPACE HEATER-AUX LUBE OIL PUMP MOTOR
100.0 W; 230 VAC; 1 PH; 50 HZ;
23QS-1 0416 HEATER-SEAL OIL PUMP MOTOR
60.00 W; 230 VAC; 1 PH; 50 HZ;
23QT-1 0416 IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
23QT-2 0416 IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
23QT-3 0416 IMMERSION HEATER-LUBE OIL TANK
12.00 KW; 400 VAC; 3 PH; 50 HZ;
23QV-2A 0416 SPACE HEATER-FOR 88QV-1A
60.00 W; 230 VAC; 1 PH; 50 HZ;
23QV-2B 0416 SPACE HEATER-FOR 88QV-1B
60.00 W; 230 VAC; 1 PH; 50 HZ;
23TG-1 0416 TURNING GEAR MOTOR HEATER
75.00 W; 220 VAC; 1 PH; 50 HZ;
23TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER
225.0 W; 220/240 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88TK-1
23TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR HEATER
225.0 W; 220/240 VAC; 1 PH; 50 HZ;
MAX WATTAGE
FOR MOTOR 88TK-2
23TW-1 0442 HEATER-WATER WASH PUMP MOTOR
60.00 W; 230 VAC; 50 HZ;
(PART OF 88TW-1)
23VG-1 0436 HEATER-VENTILATION FAN MOTOR (LOAD COMPT)
60.00 W; 230 VAC; 1 PH; 50 HZ;
23VG-2 0436 HEATER-VENTILATION FAN MOTOR (LOAD COMPT)
60.00 W; 230/480 VAC; 1 PH; 50 HZ;
23VS-3 0436 SPACE HEATER-ACCESSORY COMPT, GAS FUEL MOD REGION
3.600 KW; 415 VAC; 1 PH; 50 HZ;
USED FOR HUMIDITY CONTROL
23WK-1 0442 IMMERSION HEATER WATER WASH
45.00 KW; 415 VAC; 3 PH; 50 HZ;
23WK-2 0442 IMMERSION HEATER WATER WASH
45.00 KW; 415 VAC; 3 PH; 50 HZ;
23WS-1 0442 WATER WASH SKID SPACE HEATER
10.00 KW; 415 VAC; 3 PH; 50 HZ;
26TG-1 0416 THERMOSTAT, TURNING GEAR MOTOR WINDING

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 9 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 10 of 71

A
SIZE DWG NO SH REV
399A4551 10 B

Device System Settings


26TW-4 0442 -5 TO 50 MV, TEMPERATURE ELEMENT FOR TANK TEMPERATURE.
TYPE J THERMOCOUPLE
1 ELEMENT;
INCREASING: 180.0 +/- 5.0 F OR 82.22 +/- 2.778 C
DECREASING: 52.0 +/- 2.0 F OR 11.11 +/- 1.111 C
THIRD SET-POINT 75.0 +/- 2 F INCREASING
26VW-3 0442 TEMP. ELEMENT FOR COMPT. SPACE HEATER AND VENT FAN.
TYPE J THERMOCOUPLE
1 ELEMENT;
OPERATE VENT FAN AT 95 DEGREES F INCREASING.
OPERATE SPACE HEATER AT 65 DEGREES F DECREASING.
ALARM AT 43 DEGREES F DECREASING.
ALARM AT 130 DEGREES F INCREASING.
27AD-1 0419 APU LOSS OF POWER ALARM
CONTROL SIGNAL NAME IS L27AD1. WIRE TO MK V / MK VI.
27TF-1 0471 GT AIR FILTER GENERAL ALARM DISPATCHING

1 PH, 2A RESISTIVE, 125VDC, 0.2A INDUCTIVE


NORM=(1) NO;
27WD-1 0442 WATER WASH SKID LOSS OF POWER ALARM RELAY
WIRE TO MKV / MK VI
28FD-15 0415 FLAME DETECTOR COMBUSTION CHAMBER #15
28FD-16 0415 FLAME DETECTOR COMBUSTION CHAMBER #16
28FD-17 0415 FLAME DETECTOR COMBUSTION CHAMBER #17
28FD-18 0415 FLAME DETECTOR COMBUSTION CHAMBER #18
2FP-1A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 1)
(ZONE 1)
INITIAL DISCHARGE
2FP-1AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 1)
(ZONE 1)
EXTENDED DISCHARGE
2FP-2A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 2)
(ZONE 2)
INITIAL DISCHARGE
2FP-2AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 2)
(ZONE 2)
EXTENDED DISCHARGE
2FP-3A 0426 FIRE PROTECTION-INITIAL DISCHARGE TIMER (ZONE 3)
(ZONE 3)
INITIAL DISCHARGE

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 10 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 11 of 71

A
SIZE DWG NO SH REV
399A4551 11 B

Device System Settings


2FP-3AE 0426 FIRE PROTECTION-EXTENDED DISCHARGE TIMER (ZONE 3)
(ZONE 3)
EXTENDED DISCHARGE
30FP-10A 0426 FIRE PROTECTION TRIP CONTACT
ZONE 1 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-
DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
30FP-1A 0426 TROUBLE ANNUNCIATOR CONTACT
NORM=(1) NC; 125VDC CONTACT;
CONTACT WIRED TO TCP AND OPENS TO INDICATE A FAULT IN THE FIRE
PROTECTION SYSTEM
30FP-1B 0426 SUPERVISORY ANNUNCIATOR CONTACT
NORM=(1) NC; 125VDC CONTACT;
CONTACT WIRED TO TCP AND OPENS TO INDICATE THE FIRE PROTECTION
FLUID HAS BEEN ISOLATED FROM THE PROTECTED SPACES
30FP-20A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)
ZONE 2 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-
DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
30FP-2A 0426 TROUBLE ANNUNCIATOR CONTACT
NORM=(1) NC;
CUSTOMER CONTACT. OPENS TO INDICATE A TROUBLE CONDITION WITH THE
FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR 120VAC
30FP-30A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)
ZONE 3 PRE-DISCHARGE CONTACT
NORM=(1) NO-CEC;
CONTACT IS AVAILABLE FOR CUSTOMER USE. CLOSES UPON START OF PRE-
DISCHARGE TIMER. CONTACT RATED FOR 5A@24VDC OR 120VAC.
30FP-3A 0426 SUPERVISORY ANNUNCIATOR CONTACT
NORM=(1) NC;
CUSTOMER CONTACT. OPENS TO INDICATE A SUPERVISORY FAULT
CONDITION WITH THE FP SYSTEM. CONTACT RATED FOR 5A@24VDC OR
120VAC
30GCX-1 4035 FG CHROMATOGRAPH - GC A- TROUBLE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
30GCX-2 4035 FG CHROMATOGRAPH - GC B - TROUBLE ALARM

SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315


30GCX-3 4035 FG CHROMATOGRAPH - GC A - CALIBRATION GAS ERROR ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
30GCX-4 4035 FG CHROMATOGRAPH - GC B - CALIBRATION GAS ERROR ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 11 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 12 of 71

A
SIZE DWG NO SH REV
399A4551 12 B

Device System Settings


30SG-1 0415 DIAGNOSTIC IGNITION EXCITER SWITCH
NORM=NO; CLOSE ON EXCITER FAILURE;
33-TQ2-2 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-2 OPEN
33-TQ2-3 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-2 CLOSED
33-TQ2-4 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 OPEN
33-TQ2-5A 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
33-TQ2-5B 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
33-TQ2-5C 0417 LIMIT SWITCH
LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACTS CLOSE TO INDICATE VALVE VA7-3 CLOSED
33AC-1 0471 INLET AIR EVAP COOLER DRAIN LINE VALVE POSITION SWITCH
SWITCH CLOSED WHEN DRAIN VALVE FULL OPEN.
125VDC, 0.2 MA
NORM=(1) NC-CEC;
33AC-1B 0471 INLET AIR EVAP COOLER DRAIN LINE VALVE POSITION SWITCH
SWITCH CLOSED WHEN DRAIN VALVE FULL OPEN.
125VDC, 0.2 MA
NORM=(1) NC-CEC;
33AC-1C 0471 INLET AIR EVAP COOLER DRAIN LINE VALVE POSITION SWITCH
SWITCH CLOSED WHEN DRAIN VALVE FULL OPEN.
125VDC, 0.2 MA
NORM=(1) NC-CEC;
33CB-1 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-1 VALVE IS OPEN
33CB-2 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-2 VALVE IS OPEN

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 12 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 13 of 71

A
SIZE DWG NO SH REV
399A4551 13 B

Device System Settings


33CB-3 0417 COMP BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-3 VALVE IS OPEN
33CB-4 0417 COMP BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-4 VALVE IS OPEN
33CB-5 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-1 VALVE IS CLOSED
33CB-6 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-2 VALVE IS CLOSED
33CB-7 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-3 VALVE IS CLOSED
33CB-8 0417 COMPRESSOR BLEED VALVE LIMIT SWITCH
NORM=(1) NO;
SWITCH IS CLOSED WHEN VA2-4 VALVE IS CLOSED
33FP-31 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33FP-31E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33FP-32 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33FP-32E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33FP-33 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33FP-33E 0426 FIRE PROTECTION-LOCK-OUT VALVE/LIMIT SWITCH
NORM=(2) NC-OEC;
SUPERVISES DISCHARGE PIPING ISOLATION VALVE. SWITCH IS CLOSED WHEN
VALVE IS OPEN
33PG-1 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 13 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 14 of 71

A
SIZE DWG NO SH REV
399A4551 14 B

Device System Settings


33PG-10 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE OPEN
PART OF VA13-5
33PG-11 0477 FUEL GAS PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE CLOSED
PART OF VA13-6
33PG-12 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES;
CLOSED WITH VALVE OPEN
PART OF VA13-6
33PG-15 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE 55% OPEN;
PART OF VA13-2
33PG-16 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
SPARE
PART OF VA13-2
33PG-2 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE OPEN;
33PG-3 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
33PG-4 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE 17% OPEN;
PART OF VA13-2
33PG-9 0477 FUEL GAS SYSTEM PURGE VALVE LIMIT SWITCH
NORM=(2) NO-CES; CLOSED WITH VALVE CLOSED;
PART OF VA13-5
33TH-3 0432 INLET HEATING ISOLATION VALVE LIMIT SWITCH
NORM=(1) NO-CEC;
CONTACT CLOSED WITH VM15-1 FULL OPEN
AREA CLASSIFICATION : NON-RATED
PROTECTION METHOD : D-FLAMEPROOF
33VG-4 0422 GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE CLOSES
33VG-8 0422 GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE OPENS
33VG-9 0422 GAS FUEL VENT VALVE-LIMIT SWITCH
NORM=(1) NO-CEC;
SWITCH CLOSES WHEN VALVE CLOSES

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 14 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 15 of 71

A
SIZE DWG NO SH REV
399A4551 15 B

Device System Settings


33VS4-1 0422 FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE OPENS
NORM=(1) NO-CEC;
33VS4-2 0422 FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE CLOSES
NORM=(1) NO-CEC;
33VS4-4 0422 FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE OPENS
NORM=(1) NO-CEC;
33VS4-5 0422 FUEL GAS STOP VALVE-LIMIT SWITCH
SWITCH CLOSES WHEN VALVE CLOSES
NORM=(1) NO-CEC;
34AD-1 0419 AIR DRYER
100.0 W; 230 VAC; 1 PH; 50 HZ;
HEATLESS DRYER
34TF-1 0471 TURBINE INLET AIR FILTER-SELF CLEANING SEQUENCER
1 PH
230 VAC; 50 HZ;
39V-1A 0415 VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
39V-1B 0415 VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
39V-2A 0415 VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
39V-2B 0415 VIBRATION SENSOR TURBINE
OUTPUT AT 1``/SEC = 150.0 MV
39V-4A 0440 VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
OR
(OUTPUT AT 25.4 MM/S = 150.0 MV)
LOCATED ON TURBINE END BEARING CAP
39V-4B 0440 VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
OR
(OUTPUT AT 25.4 MM/S = 150.0 MV)
LOCATED ON TURBINE END BEARING CAP
39V-5A 0440 VIBRATION SENSOR GENERATOR
OUTPUT AT 1``/SEC = 150.0 MV
OR
(OUTPUT AT 25.4 MM/S = 150.0 MV)
LOCATED ON COLLECTOR END BEARING CAP

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 15 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 16 of 71

A
SIZE DWG NO SH REV
399A4551 16 B

Device System Settings


39VS-101 0440 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH OR 7874 MV/MM
ALARM @ 0.006`` / 0.1524MM
39VS-102 0440 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH OR 7874 MV/MM
ALARM @ 0.006`` / 0.1524MM
39VS-11 0415 VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
39VS-12 0415 VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
39VS-21 0415 VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
39VS-22 0415 VIBRATION SENSOR (NON-CONTACTING)
OUTPUT AT 1 MIL = 200.0 MV
39VS-91 0440 VIBRATION SENSOR (NON-CONT) GEN COUPLING END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH OR 7874 MV/MM
ALARM @ 0.006`` / 0.1524MM
39VS-92 0440 VIBRATION SENSOR (NON-CONT) GEN COUPLING END
BENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH OR 7874 MV/MM
ALARM @ 0.006`` / 0.1524MM
43MRA-1C 0426 MANUAL DISCHARGE SWITCH (ACCESSORY COMPT)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 1)
43MRA-3A 0426 MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)
43MRA-3B 0426 MANUAL DISCHARGE SWITCH (ACCESSORY MODULE)
LOCATED OUTSIDE NEXT TO ACCESSORY COMPARTMENT DOOR (ZONE 3)
43MRFP-1A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 1)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.
43MRFP-2A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 2)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 16 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 17 of 71

A
SIZE DWG NO SH REV
399A4551 17 B

Device System Settings


43MRFP-3A 0426 FIRE PROTECTION-MANUAL DISCHARGE SWITCH (ZONE 3)
NORM=(2) NC-OEC;
LOCATED ON ELECTRICAL CONTROL CABINET DOOR ON CO2 SKID. SWITCH
HELD OPEN WITH PIN.
43MRP-6A 0426 FIRE PROTECTION-MANUAL RELEASE STATION
NORM=(1) NO;
LOCATED INSIDE PEECC FOR MANUAL RELEASE OF FIRE PROTECTION SYSTEM
43MRT-1A 0426 MANUAL DISCHARGE SWITCH (TURBINE COMPT)
(ZONE1)
LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR
43MRT-1B 0426 MANUAL DISCHARGE SWITCH (TURBINE COMPT)
(ZONE1)
LOCATED ON COMPARTMENT WALL OUTSIDE NEXT TO DOOR
43WK-1 0442 WATER TEMP SETPOINT SWITCH (HOT-COLD)
43WK-2 0442 OPERATION SETPOINT SWITCH (AUTO-MANUAL)
45FA-30A 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
45FA-30B 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
45FA-31A 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
45FA-31B 0426 FIRE DETECTOR-LUBE/HYDRAULIC COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
(LUBE/HYDRAULIC COMP.-ACCESS.MOD-ZONE 3)
45FA-6A 0426 FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
45FA-6B 0426 FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
45FA-7A 0426 FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 17 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 18 of 71

A
SIZE DWG NO SH REV
399A4551 18 B

Device System Settings


45FA-7B 0426 FIRE DETECTOR-FUEL GAS COMPARTMENT
INCREASING: 425.0 F OR 218.3 C
NORM=(1) NO-SPST;
FUEL GAS COMP.-ACCESS.MODULE (ZONE 1)
45FT-1A 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
45FT-1B 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
45FT-20A 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
45FT-20B 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
45FT-21A 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
45FT-21B 0426 FIRE DETECTOR-#2 BEARING AREA (ZONE 2)
INCREASING: 725.0 F OR 385.0 C
NORM=(1) NO-SPST;
#2 BEARING TUNNEL - ZONE 2
45FT-2A 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
45FT-2B 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
45FT-3A 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1
45FT-3B 0426 FIRE DETECTOR-TURBINE COMPARTMENT
INCREASING: 600.0 F OR 315.6 C
NORM=(1) NO-SPST;
TURBINE COMPARTMENT ZONE 1

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 18 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 19 of 71

A
SIZE DWG NO SH REV
399A4551 19 B

Device System Settings


45GHD-1 0426 FIRE DETECTOR-GENERATOR COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
LOCATED IN GEN. COLLECTOR COMP
WIRED TO TCP (125VDC)
45GHD-2 0426 FIRE DETECTOR-GENERATOR COMPARTMENT
INCREASING: 325.0 F OR 162.8 C
NORM=(1) NO-SPST;
LOCATED IN GEN. COLLECTOR COMP
WIRED TO TCP (125VDC)
45HA-IR-7 0474 IR COMBUSTIBLE GAS DETECTOR
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HA-IR-9A 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HA-IR-9B 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HA-IR-9C 0474 IR COMBUSTIBLE GAS DETECTOR - ACCESSORY COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
IR COMBUSTIBLE GAS DETECTOR ACCESSORY MODULE - LOCAL
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HGT-1 0474 HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSURE
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
45HGT-2 0474 HAZARDOUS ATM DETECTOR-GEN TERMINAL ENCLOSURE
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 19 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 20 of 71

A
SIZE DWG NO SH REV
399A4551 20 B

Device System Settings


45HGT-7A 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
45HGT-7B 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
45HGT-7C 0474 COMBUSTIBLE GAS DETECTOR - GEN COLLECTOR COMPARTMENT
HIGH ALARM SETTING AT 10% LEL
HIGH-HIGH ALARM SETTING AT 25% LEL
45HT-IR-1A 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-1B 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-1C 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-1D 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-2A 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 20 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 21 of 71

A
SIZE DWG NO SH REV
399A4551 21 B

Device System Settings


45HT-IR-2B 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-2C 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45HT-IR-2D 0474 IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT
HIGH ALARM SETTING AT 8% LEL
HIGH-HIGH ALARM SETTING AT 17% LEL
IR COMBUSTIBLE GAS DETECTOR - TC EXTRACT DUCT (OUTDOOR UNITS)
24VDC, 0.1 A 4.0MA FOR 0% LEL 20.0MA FOR 100% LEL
INRUSH CURRENT DATA: 1 AMP @ 8VDC FOR 3MS DURATION, , .9 AMP @ 12
VDC FOR 3
45SCC-2A 0426 SMOKE DETECTOR-PEECC
WIRED TO FM200 FIRE PROTECTION PANEL
24VDC/40MA DEVICE
45SCC-2B 0426 SMOKE DETECTOR-PEECC
WIRED TO FM200 FIRE PROTECTION PANEL
24VDC/40MA DEVICE
45SCC-2C 0426 SMOKE DETECTOR-PEECC
WIRED TO FM200 FIRE PROTECTION PANEL
24VDC/40MA DEVICE
45SCC-2D 0426 SMOKE DETECTOR-PEECC
WIRED TO FM200 FIRE PROTECTION PANEL
24VDC/40MA DEVICE
45SCC-A 0426 SMOKE DETECTOR-PEECC
NORM=(1) NC;
WIRED TO LOCAL TURBINE CONTROL PANEL
45SCC-B 0426 SMOKE DETECTOR-PEECC
NORM=(1) NC;
WIRED TO LOCAL TURBINE CONTROL PANEL
45SCC-E 0426 SMOKE DETECTOR-PEECC
NORM=(1) NC;
WIRED TO LOCAL TURBINE CONTROL PANEL
LOCATED IN BATTERY COMPARTMENT

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 21 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 22 of 71

A
SIZE DWG NO SH REV
399A4551 22 B

Device System Settings


49IC-1 0471 INLET AIR SCREW AUGER MOTOR OVERLOAD
RATING: 15.00 A; 230 VAC; 1 PH; 50 HZ; PROTECTS 88IC-1
NORM=(1) NC-CEC; AUXILIARY CONTACTS;;
NORMALLY CLOSED-OPEN ON OVERLOAD
49WS-1 0442 WATER WASH SKID HEATER OVERLOAD
(INTEGRAL PART OF 23WS-1)
4WW 0442 WATER WASH MASTER CONTROL RELAY
CONTROL SIGNAL NAME IS L4WWX. WIRE TO MK V / MK VI. MK V / MK VI
OUTPUT SIGNAL IS DRY CONTACT.
62FP-1A 0426 FIRE PROTECTION-TIMER RESET SWITCH (FOR ALL ZONES)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 1
62FP-2A 0426 FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 2)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 2
62FP-3A 0426 FIRE PROTECTION-CO2 TIMER RESET SWITCH (ZONE 3)
NORM=(1) NO;
SWITCH TO RESET SYSTEM AFTER CO2 DISCHARGE IN ZONE 3
63AD-4 0419 APU LOW PRESSURE SWITCH
DECREASING: 85.00+-5.000 PSIG OR 586.1+-34.47 KPAG
APU LOW PRESSURE ALARM. INDICATES INSUFFICIENT
AIR AVAILABLE FOR NORMAL DEVICE OPERATION. OPENS TO ALARM. SIGNAL
NAME IS L63AD4. WIRE TO MKV / MK VI.
63AG-1A 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AG-1B 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AG-1C 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AG-2A 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AG-2B 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AG-2C 0436 GEAR/LOAD COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-1A 0436 TURBINE COMPARTMENT FAN PRESSURE LOW ALARM
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 22 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 23 of 71

A
SIZE DWG NO SH REV
399A4551 23 B

Device System Settings


63AT-1B 0436 TURBINE (ACCESS) COMPT AIR PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-1C 0436 TURBINE COMPARTMENT FAN PRESSURE LOW ALARM
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-2A 0436 TURBINE COMPARTMENT PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-2B 0436 TURBINE COMPARTMENT PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-2C 0436 TURBINE COMPARTMENT PRESSURE SWITCH
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-3 0436 ACCESSORY COMPARTMENT PRESSURE LOW ALARM
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63AT-4 0436 ACCESSORY COMPARTMENT PRESSURE LOW ALARM
DECREASING: 0.4000 INH2O OR 0.0995 KPA
NORM=NO-CEC;
63BN-1 0417 VENT AIR PRESSURE SWITCH-#2 BEARING AREA
DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA
(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)
NORM=(1) NO;
63BN-2 0417 VENT AIR PRESSURE SWITCH-#2 BEARING AREA
DECREASING: 4.500+-0.1000 INH2O OR 1.120+-0.0249 KPA
(INCREASING: 6.000+-0.3000 INH2O OR 1.493+-0.0747 KPA)
NORM=(1) NO;
63CA-1 0471 INLET AIR FILTER COMPRESSED AIR PRESSURE SWITCH
DECREASING: 60.00+-5.000 PSIG OR 413.7+-34.47 KPAG
NORM=(2) NO-CEC; CLOSED WHEN PRESSURIZED;
0.5A, 125VDC
63CP-6A 0426 FIRE PROTECTION PRESSURE SWITCH
DECREASING: 300.0 PSIG OR 2068 KPAG
NORM=(1) NO;
FM-200 SUPERVISORY PRESSURE SWITCH. MONITORS TANK PRESSURE
63CP-6C 0426 FIRE PROTECTION PRESSURE SWITCH
INCREASING: 90.00 PSIG OR 620.5 KPAG
NORM=(2) NO; MANUAL RESET;
FIRE PROTECTION-FM-200 PRESSURE SWITCH FOR PEECC SENSES FM-200
DISCHARGE. ONE CONTACT TO MCC, ONE CONTACT TO FM-200 PANEL

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 23 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 24 of 71

A
SIZE DWG NO SH REV
399A4551 24 B

Device System Settings


63CP-6E 0426 FIRE PROTECTION PRESSURE SWITCH
INCREASING: 90.00 PSIG OR 620.5 KPAG
NORM=(2) NO; MANUAL RESET;
FIRE PROTECTION-FM-200 PRESSURE SWITCH FOR PEECC SENSES FM-200
DISCHARGE. ONE CONTACT TO MCC, ONE CONTACT TO FM-200 PANEL
63FGD-1 0422 FUEL GAS STRAINER DP SWITCH
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 13.75+-1.250 PSID OR 94.80+-8.618 KPAD)
NORM=(1) NC-OEC; SPDT;
63FP-11A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 1 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
63FP-12A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 2 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
63FP-13A 0426 FIRE PROTECTION-CO2 SELECTOR VLV ACTUATION PRESS SWITCH
INCREASING: 90.00+-20.00 PSIG OR 620.5+-137.9 KPAG
NORM=(2) NO; MANUAL RESET REQUIRED;
CONTACT CLOSES WHEN CO2 PRESSURE IN ZONE 3 ACTUATION LINE RISES
ABOVE PRIMARY SETTING. WIRES TO 45FTX-1 AUX RELAY PANEL.
63GCX-1 4035 CARRIER GAS - LOW PRESSURE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
63GCX-2 4035 CALIBRATION GAS - LOW PRESSURE ALARM
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
63HF-1 0434 HYDRAULIC OIL FILTER DIFF PRESSURE ALARM
INCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD
(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)
NORM=(1) NC-OEC;
63HF-2 0434 HYDRAULIC FILTER DIFF PRESSURE ALARM
INCREASING: 100.0+-3.000 PSID OR 689.5+-20.68 KPAD
(DECREASING: 80.00+-10.00 PSID OR 551.6+-68.95 KPAD)
NORM=(1) NC-OEC;
63HQ-1A 0434 HYDRAULIC OIL SUPPLY PRESSURE SWITCH
DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG
(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)
NORM=(1) NO-CEC;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 24 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 25 of 71

A
SIZE DWG NO SH REV
399A4551 25 B

Device System Settings


63HQ-1B 0434 HYDRAULIC OIL SUPPLY PRESSURE SWITCH
DECREASING: 1450+-25.00 PSIG OR 9997+-172.4 KPAG
(INCREASING: 1550+-25.00 PSIG OR 10687+-172.4 KPAG)
NORM=(1) NO-CEC;
63HQ-6A 0434 LOW HYDRAULIC OIL PUMP PH1-1 INLET PRESSURE
DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)
NORM=(1) NO-CEC;
63HQ-6B 0434 LOW HYDRAULIC OIL PUMP PH2-1 INLET PRESSURE
DECREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(INCREASING: 12.00+-1.000 PSIG OR 82.74+-6.895 KPAG)
NORM=(1) NO-CEC;
63PG-1A 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
63PG-1B 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
63PG-1C 0477 PRIMARY GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
63PG-3A 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: ``D`` - FLAME-PROOF
63PG-3B 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
63PG-3C 0477 GAS FUEL SYSTEM PURGE PRESSURE SWITCH
INCREASING: 50.00+-2.000 PSIG OR 344.7+-13.79 KPAG
(DECREASING: 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG)
NORM=(1) NC-OEC;
63QA-1A 0416 LUBE OIL BEARING HEADER PRESSURE SWITCH-AUX PUMP START
DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG
(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)
NORM=(1) NO-CEC;
63QA-1B 0416 LUBE OIL BEARING HEADER PRESSURE SWITCH
DECREASING: 83.00+-2.000 PSIG OR 572.3+-13.79 KPAG
(INCREASING: 91.00+-2.000 PSIG OR 627.4+-13.79 KPAG)
NORM=(1) NO-CEC;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 25 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 26 of 71

A
SIZE DWG NO SH REV
399A4551 26 B

Device System Settings


63QB-1 0434 BEARING LIFT OIL SUPPLY PRESSURE
DECREASING: 2350+-40.00 PSIG OR 16203+-275.8 KPAG
(INCREASING: 2500+-40.00 PSIG OR 17237+-275.8 KPAG)
NORM=(1) NO-CEC;
63QE-1 0416 EMERGENCY LUBE OIL PUMP RUNNING
INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG
(DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG)
NORM=(1) NO-CEC;
63QQ-21 0416 MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARM
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)
NORM=(1) NC-OEC;
63QQ-22 0416 MAIN LUBE OIL FILTER DIFFERENTIAL PRESSURE-ALARM
INCREASING: 15.00+-1.000 PSID OR 103.4+-6.895 KPAD
(DECREASING: 12.00+-2.000 PSID OR 82.74+-13.79 KPAD)
NORM=(1) NC-OEC;
63QQ-25 0416 SEAL OIL FILTER DIFFERENTIAL PRESSURE SWITCH
INCREASING: 13.00+-1.000 PSID OR 89.63+-6.895 KPAD
(DECREASING: 11.75+-1.250 PSID OR 81.01+-8.618 KPAD)
NORM=(1) NC; SPDT;
63QT-2A 0416 LOW LUBE OIL PRESSURE
DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG
(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)
63QT-2B 0416 LOW LUBE OIL PRESSURE
DECREASING: 8.000+-1.000 PSIG OR 55.16+-6.895 KPAG
(INCREASING: 10.00+-1.000 PSIG OR 68.95+-6.895 KPAG)
63TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW
DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA
(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)
NORM=(1) NO;
63TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER DSCH PRESSURE SW
DECREASING: 25.00+-0.8000 INH2O OR 6.221+-0.1991 KPA
(INCREASING: 28.00+-0.8000 INH2O OR 6.968+-0.1991 KPA)
NORM=(1) NO;
63TW-1 0442 TURBINE/COMPRESSOR WASH WATER PRESSURE
DECREASING: 93.00+-2.000 PSIG OR 641.2+-13.79 KPAG
NORM=(2) NO-CEC;
63TW-2 0442 TURBINE/COMPRESSOR WASH WATER PRESSURE-PUMP TRIP
INCREASING: 4.000 INHG OR 13.55 KPA
NORM=NC-OEC;
OPENS ON INCREASING VACUUM 4 INHGV (DEC PRESS)
CLOSED AT ATMOSPHERIC PRESSURE.
65CM-1 0417 CASE TEMP. MANAGEMENT FLOW CONTROL DAMPER POSITIONER
4.0MA = 0% = 20CM-1 FULL CLOSED
20.0MA = 100% = 20CM-1 FULL OPEN

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 26 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 27 of 71

A
SIZE DWG NO SH REV
399A4551 27 B

Device System Settings


65EP-18 0417 VALVE POSITIONER FOR PCV
4 MA = 3 PSIG = 100% = VA7-2 FULL OPEN
20 MA = 15 PSIG = 0% = VA7-2 FULL CLOSED
PART OF VA7-2
65EP-19 0417 I/P CONTROLLER, VALVE POSITIONER
4 MA = 3 PSIG = 0% = VA7-3 FULL CLOSED
20 MA = 15 PSIG = 100% = VA7-3 FULL OPEN
PART OF VA7-3
65EP-3 0432 ELECTRO-PNEUMATIC TRANSDUCER
4.0MA = 100% = VA20-1 FULL OPEN
20.0MA = 0% = VA20-1 FULL CLOSED
65EP-G1P 0477 GAS FUEL PURGE VALVE POSITIONER
4.00 +-0.200 MA = 0% STROKE (FULLY CLOSED)
20.00 +- 0.200 MA = 100% STROKE (FULLY OPEN)
PART OF VA13-2
65GC-1 0422 GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 2.500 GPM AT 1000 PSID
RATED FLOW: 9.5 LPM AT 6700 KPAG
65GC-2 0422 GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 1.000 GPM AT 1000 PSID
RATED FLOW: 9.5 LPM AT 6700 KPAG
65GC-3 0422 GAS CONTROL VALVE SERVO VALVE
RATED FLOW: 2.500 GPM AT 1000 PSID
RATED FLOW: 9.5 LPM AT 6700 KPAG
71QH-1 0416 HIGH LUBE OIL LEVEL-ALARM
NORM=(1) NC-OEC;
INCREASING 3.000 +- 0.250`` (76.2 +- 6.35 MM)
DECREASING 1.500 +- 0.500`` (38.1 +- 12.7 MM)
71QL-1 0416 LOW LUBE OIL LEVEL-ALARM
NORM=(1) NO-CEC;
DECREASING 2.000 +- 0.250`` (-50.8 +- 6.35 MM)
INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)
71QL-2 0416 LOW LUBE OIL LEVEL-ALARM
NORM=(1) NO-CEC;
DECREASING 3.000 +- 0.250`` (-76.2 +- 6.35 MM)
INCREASING 1.500 +- 0.500`` (-38.1 +- 12.7 MM)
71TW-1 0442 WATER TANK WATER LEVEL CONTROL
NORM=(2) NC-OEC;
DECREASING: 15+-1 IN H20 OR 3.74 +- 0.25 KPA
MAGNETICIC LEVEL SWITCH SET 15 INCHES ABOVE THE BOTTOM OF THE
WATER TANK.
77HT-1 0415 MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
77HT-2 0415 MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 27 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 28 of 71

A
SIZE DWG NO SH REV
399A4551 28 B

Device System Settings


77HT-3 0415 MAGNETIC PICKUP (OVERSPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
77NH-1 0415 MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
77NH-2 0415 MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
77NH-3 0415 MAGNETIC PICKUP (SPEED)
GAP: 0.0500+-0.0050 IN OR 1.270+-0.1270 MM
77RP-11 0415 SHAFT ANGULAR POSITION INDICATOR (KEYPHASOR) BEARING#1
80AC-3A 0471 INLET AIR EVAP COOLER WATER FLOW SWITCH
CLOSED WHEN WATER IS FLOWING
OPENED WHEN WATER IS NOT FLOWING
NORM=(1) NO-CEC;
SINGLE POLE, DOUBLE THROW
125VDC, 0.5 A MINIMUM RATING
80AC-3B 0471 INLET AIR EVAP COOLER WATER FLOW SWITCH
CLOSED WHEN WATER IS FLOWING
OPENED WHEN WATER IS NOT FLOWING
NORM=(1) NO-CEC;
SINGLE POLE, DOUBLE THROW
125VDC, 0.5 A MINIMUM RATING
80AC-3C 0471 INLET AIR EVAP COOLER WATER FLOW SWITCH
CLOSED WHEN WATER IS FLOWING
OPENED WHEN WATER IS NOT FLOWING
NORM=(1) NO-CEC;
SINGLE POLE, DOUBLE THROW
125VDC, 0.5 A MINIMUM RATING
80HA-FS-7 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 28 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 29 of 71

A
SIZE DWG NO SH REV
399A4551 29 B

Device System Settings


80HA-FS-9A 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HA-FS-9B 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HA-FS-9C 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-1A 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 29 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 30 of 71

A
SIZE DWG NO SH REV
399A4551 30 B

Device System Settings


80HT-FS-1B 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-1C 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-1D 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-2A 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 30 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 31 of 71

A
SIZE DWG NO SH REV
399A4551 31 B

Device System Settings


80HT-FS-2B 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-2C 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80HT-FS-2D 0474 FLOW SWITCH
DECREASING: 2.750+-0.2000 OR 2.750+-0.2000
ASPIRATED COMBUSTIBLE GAS DETECTOR FS
DECREASING SET POINT: 2.75 CFH
INCREASING SET POINT 3.0 CFH
SET POINT TOLERANCE TBD
SET POINT UOM: CFH
NORMAL BIAS (DE-ENERGIZED) (2) NO-CEC
ALARM ON LOW FLOW
80WW-1 0442 FLOW SWITCH-WATER WASH SKID
NORM=(2) NC-OEC;
CONTACT OPENS AT 2 GPM OR 0.45 M3/HR ON INCR FLOW
WATER WASH FLOW EXISTS RELAY TO TURBINE CONTROL SYSTEM AND
CONTROL SIGNAL NAME IS L80WWN. WIRE TO MK V / MK VI.
86WWX 0442 WATER WASH SKID TRIP ALARM RELAY
CONTROL SIGNAL NAME IS L86WWX. WIRE TO MK V / MK VI.
88AC-1A 0471 TURBINE AIR INLET-EVAP COOLER PUMP MOTOR
30.00 HP; 22.37 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
88AC-1B 0471 TURBINE AIR INLET-EVAP COOLER PUMP MOTOR
30.00 HP; 22.37 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
88AD-1 0419 FAN MOTOR, APU HEAT EXCHANGER
2.000 HP; 1.491 KW; 1725 RPM; 230 VAC; 1 PH; 50 HZ;
COOLS APU HEAT EXCHANGER. MOTOR RATING SPECIFIED IS THE MAX HP
EXPECTED.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 31 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 32 of 71

A
SIZE DWG NO SH REV
399A4551 32 B

Device System Settings


88BL-1 0436 COOLING AIR FAN MOTOR-LUBE OIL SKID
5.000 HP; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88BL-2 0436 COOLING AIR FAN MOTOR-LUBE OIL SKID
5.000 HP; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88BN-1 0417 COOLING AIR FAN MOTOR-#2 BEARING AREA
20.00 HP; 14.91 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
15KW
88BN-2 0417 COOLING AIR FAN MOTOR-#2 BEARING AREA
20.00 HP; 14.91 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
15KW
88BT-1 0436 COOLING AIR FAN MOTOR-TURBINE COMPARTMENT
50.00 HP; 1000 RPM; 415 VAC; 3 PH; 50 HZ;
LEFT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAM
88BT-2 0436 COOLING AIR FAN MOTOR-TURBINE COMPARTMENT
50.00 HP; 1000 RPM; 415 VAC; 3 PH; 50 HZ;
RIGHT HAND SIDE FAN MOTOR, LOOKING DOWNSTREAM
88CM-1 0417 CASE TEMP. MANANGEMENT(CLEARANCE CONTROL)BLOWER MOTOR
50.00 HP; 37.28 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
88ES-1 0416 EMERGENCY SEAL OIL PUMP MOTOR
20.00 HP; 14.91 KW; 3000 RPM; 120 VDC;
88FP-1A 0426 FIRE PROTECTION-CO2 REFRIGERATION COMPRESSOR MOTOR
3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;
HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS
88FP-1B 0426 REDUNDANT FP-CO2 REFRIGERATION COMPRESSOR MOTOR
3.000 HP; 2.237 KW; 1425 RPM; 400 VAC; 3 PH; 50 HZ;
HP LISTED IS MAX VALUE. ACTUAL HP MAY BE LESS
88HQ-1 0434 HYDRAULIC SUPPLY PUMP MOTOR
60.00 HP; 44.74 KW; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88HQ-2 0434 HYDRAULIC SUPPLY PUMP MOTOR
60.00 HP; 44.74 KW; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88IC-1 0471 INLET FILTER, DUST COLLECTION SYSTEM SCREW AUGER MOTOR
2.000 HP; 1.491 KW; 415 VAC; 3 PH; 50 HZ;
3 PH
SCREW AUGER MOTOR
88QA-1 0416 AUXILIARY LUBE OIL PUMP MOTOR
125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;
90 KW FOR CE APPLICATIONS
88QA-2 0416 AUXILIARY LUBE OIL PUMP MOTOR
125.0 HP; 93.21 KW; 2900 RPM; 400 VAC; 3 PH; 50 HZ;
90 KW FOR CE APPLICATIONS
88QE-1 0416 EMERGENCY LUBE OIL PUMP MOTOR
20.00 HP; 14.91 KW; 1750 RPM; 120 VDC;
88QS-1 0416 GENERATOR(AUXILIARY) SEAL OIL PUMP MOTOR
30.00 HP; 22.37 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 32 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 33 of 71

A
SIZE DWG NO SH REV
399A4551 33 B

Device System Settings


88QV-1A 0416 LUBE MIST SEPARATOR OR ELIMINATOR MOTOR
5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
88QV-1B 0416 LUBE MIST SEPARATOR MOTOR
5.000 HP; 3.728 KW; 3000 RPM; 400 VAC; 3 PH; 50 HZ;
88TG-1 0416 TURNING GEAR MOTOR
6.400 HP; 4.772 KW; 1500 RPM; 400 VAC; 3 PH; 50 HZ;
88TK-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR
213.0 HP; 158.8 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
160 KW
88TK-2 0417 TURBINE SHELL & EXHAUST FRAME BLOWER MOTOR
213.0 HP; 158.8 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
160 KW
88TW-1 0442 TURBINE/COMPRESSOR WASH WATER PUMP MOTOR
25.00 HP; 18.64 KW; 3000 RPM; 415 VAC; 3 PH; 50 HZ;
20 HP MAY BE USED BASED ON ACTUAL PUMP PERFORMANCE.
88VG-1 0436 LOAD COMPT COOLING AIR FAN MOTOR
7.500 HP; 3.728 KW; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88VG-2 0436 LOAD COMPT COOLING AIR FAN MOTOR
7.500 HP; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
88VW-1 0442 WATER WASH UNIT VENT FAN MOTOR
0.5000 HP; 0.3728 KW; 1725 RPM; 230/480 VAC; 1 PH; 50 HZ;
88WS-1 0442 WATER WASH SKID SPACE HEATER BLOWER MOTOR
0.1000 HP; 0.0746 KW; 1550 RPM; 230/480 VAC; 1 PH; 50 HZ;
8IC-1 0471 INLET AIR SCREW AUGER MOTOR DISCONNECT
15 A
NORM=(3) NC-CEC; PROTECTS 88IC-1;
ALSO DISCONNECTS 23IC-1
90LT-1 0420 COOLING WATER VALVE POSITION REGULATOR - LO HX
4 +- 0.200 MA = 0% STROKE (B-L POSITION, FULL UP)
20 +- 0.200 MA = 100% STROKE (B-R POSITION, FULL DOWN)
90SR-1 0422 STOP/SPEED RATIO VALVE SERVO VALVE
RATED FLOW: 15.00 GPM AT 1000 PSID
RATED FLOW: 56.8 LPM AT 6700 KPAG
90TV-1 0434 INLET GUIDE VANE SERVO VALVE
RATED FLOW: 10.00 GPM AT 1000 PSIG
(38 GPM @ 6895 KPA)
94F-1A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 1)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
94F-1B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 1)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 33 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 34 of 71

A
SIZE DWG NO SH REV
399A4551 34 B

Device System Settings


94F-2A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
94F-2B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 2)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.
94F-3A 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)
NORM=(1) NO; 125VDC CONTACT;
CONTACT IS WIRED TO 45FTX-1 AUX RELAY PANEL AND CLOSES UPON START
OF PRE-DISCHARGE TIMER.
94F-3B 0426 FIRE PROTECTION TRIP CONTACT (ZONE 3)
NORM=(1) NC-OEC; 125VDC CONTACT;
CONTACT IS WIRED TO TCP AND OPENS UPON START OF CO2 DISCHARGE.
95FP-1 0440 GENERATOR AIR GAP FLUX PROBE
95SG-2 0415 IGNITION EXCITER FOR 95SP-2
115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT
1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF
95SG-3 0415 IGNITION EXCITER FOR 95SP-3
115VAC/230 VAC, 50/60HZ, 150VA MAX INPUT
1.5 MIN ON/1.5 MIN OFF/1.5 MIN ON/25 MIN OFF
95SP-2 0415 COMBUSTION CHAMBER SPARK PLUG
95SP-3 0415 COMBUSTION CHAMBER SPARK PLUG
96-TS2P-1A 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG
96-TS2P-1B 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG
96-TS2P-1C 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
PRESSURE TRANSMITER
STAGE TWO NOZZLE OSWC
2-WIRE, LOOP POWERED, ANALOG

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 34 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 35 of 71

A
SIZE DWG NO SH REV
399A4551 35 B

Device System Settings


96-TS2QP-1A 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
96-TS2QP-1B 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
96-TS2QP-1C 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S13 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
96-TS3QP-1A 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
96-TS3QP-1B 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG
96-TS3QP-1C 0417 TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
TRANSMITTER
S9 PRESSURE
2 WIRE, LOOP POWERED, ANALOG

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 35 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 36 of 71

A
SIZE DWG NO SH REV
399A4551 36 B

Device System Settings


96AC-21 0471 INLET AIR EVAP COOLER SUMP WATER LEVEL TRANSDUCER
4.000+-0.0500 MA= 0.0 INH2O OR 0.0 KPA
20.00+-0.1000 MA= 25.00 INH2O OR 6.221 KPA
4MA = 0%
WLKACLL 9.25MA 32.81% WLKACL 11.8MA 48.75%
WLKACH 13.09MA 56.81% WLKACHH 15.65MA 72.81%
20MA = 100%
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM FOR MEASURING SUMP
WATER LEVEL
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96AC-21B 0471 INLET AIR EVAP COOLER SUMP WATER LEVEL TRANSDUCER
4.000+-0.0500 MA= 0.0 INH2O OR 0.0 KPA
20.00+-0.1000 MA= 25.00 INH2O OR 6.221 KPA
4MA = 0%
WLKACLL 9.25MA 32.81% WLKACL 11.8MA 48.75%
WLKACH 13.09MA 56.81% WLKACHH 15.65MA 72.81%
20MA = 100%
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM FOR MEASURING SUMP
WATER LEVEL
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96AC-21C 0471 INLET AIR EVAP COOLER SUMP WATER LEVEL TRANSDUCER
4.000+-0.0500 MA= 0.0 INH2O OR 0.0 KPA
20.00+-0.1000 MA= 25.00 INH2O OR 6.221 KPA
4MA = 0%
WLKACLL 9.25MA 32.81% WLKACL 11.8MA 48.75%
WLKACH 13.09MA 56.81% WLKACHH 15.65MA 72.81%
20MA = 100%
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM FOR MEASURING SUMP
WATER LEVEL
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96AC-22 0471 TURBINE INLET AIR EVAP COOLER CONDUCTIVITY SENSOR/TRANSM
4.000 MA= 0.0 OR 0.0
20.00 MA= 5000 OR 5000
CONDUCTIVITY SENSOR FOR AUTO BLOWDOWN
(UNITS ARE MICRO-MHOS/CM)
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM
POWERED BY 230 VAC, OUTPUTS 24VDC RATED 4-20 MA SIGNAL
4 MA = 0%
20 MA = 100%

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 36 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 37 of 71

A
SIZE DWG NO SH REV
399A4551 37 B

Device System Settings


96AC-22B 0471 TURBINE INLET AIR EVAP COOLER CONDUCTIVITY SENSOR/TRANSM
4.000 MA= 0.0 OR 0.0
20.00 MA= 5000 OR 5000
CONDUCTIVITY SENSOR FOR AUTO BLOWDOWN
(UNITS ARE MICRO-MHOS/CM)
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM
POWERED BY 230 VAC, OUTPUTS 24VDC RATED 4-20 MA SIGNAL
4 MA = 0%
20 MA = 100%
96AC-22C 0471 TURBINE INLET AIR EVAP COOLER CONDUCTIVITY SENSOR/TRANSM
4.000 MA= 0.0 OR 0.0
20.00 MA= 5000 OR 5000
CONDUCTIVITY SENSOR FOR AUTO BLOWDOWN
(UNITS ARE MICRO-MHOS/CM)
PROVIDES SIGNAL TO TURBINE CONTROL SYSTEM
POWERED BY 230 VAC, OUTPUTS 24VDC RATED 4-20 MA SIGNAL
4 MA = 0%
20 MA = 100%
96AP-1A 0492 BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
96AP-1B 0492 BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
96AP-1C 0492 BAROMETRIC PRESSURE TRANSMITTER
4.000+-0.2000 MA= 22.00 INHG OR 74.50 KPA
20.00+-0.2000 MA= 37.00 INHG OR 125.3 KPA
96BD-1 0492 COMPRESSOR BELLMOUTH DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 138.5 INH2O OR 34.46 KPA
96BH-1 0432 INLET HTG CV UPSTREAM PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
96BH-2 0432 INLET HTG CV DOWNSTREAM PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 150.0 PSIG OR 1034 KPAG
96CD-1 0417 COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
96CD-1B 0417 COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 37 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 38 of 71

A
SIZE DWG NO SH REV
399A4551 38 B

Device System Settings


96CD-1C 0417 COMPRESSOR DISCH PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 300.0 PSIG OR 2068 KPAG
96CM-1 0417 CASE TEMP. MANAGEMENT AIR SUPPLY PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 250.0 INH2O OR 62.21 KPA
96CM-2 0417 CASE TEMP. MANAGE. FLOW CONTROL DAMPER POSITION FEEDBACK
4.0 MA = 0% = 20CM-1 FULL CLOSED
20.0 MA = 100% = 20CM-1 FULL OPEN
96CS-1 0492 INLET DIFFERENTIAL PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 INH2O OR 0.0 KPA
20.00+-0.2000 MA= 11.10 INH2O OR 2.762 KPA
96EP-1 0492 EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
96EP-2 0492 EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
96EP-3 0492 EXHAUST DIFFERENTIAL PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 27.70 INH2O OR 6.893 KPA
96FG-1 0422 GAS FUEL UPSTREAM PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 600.0 PSIG OR 4137 KPAG
96FG-2A 0422 INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG
96FG-2B 0422 INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG
96FG-2C 0422 INTERSTAGE FUEL GAS PRESSURE TRANSMITTER
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 500.0 PSIG OR 3447 KPAG
96FLW-1 4035 FG CHROMATOGRAPH - GC A- LOW WOBBE INDEX
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
ENG MIN = 1180
ENG MAX = 1300
96FLW-2 4035 FG CHROMATOGRAPH - GC B - LOW WOBBE INDEX
SIGNAL IS DELIVERED VIA FIBER OPTIC CABLE TO MLI A315
ENG MIN = 1180
ENG MAX = 1300

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 38 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 39 of 71

A
SIZE DWG NO SH REV
399A4551 39 B

Device System Settings


96FM-4 0422 CORIOLIS FLOW METER TRANSMITTER
4.000 MA= 0.0 PPS OR 0.0 KG/SEC
20.00 MA= 50.00 PPS OR 22.68 KG/SEC
HAZARDOUS AREA: ZONE 2
PROTECTION METHOD: D - FLAMEPROOF
96GC-1 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-2 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-3 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-4 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-5 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-6 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-7 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-8 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GC-9 0422 FUEL GAS CONTROL VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96GN-1 0422 GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION
96GN-2 0422 GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 39 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 40 of 71

A
SIZE DWG NO SH REV
399A4551 40 B

Device System Settings


96GN-3 0422 GAS FUEL NOZZLE PRESSURE RATIO TRANSMITTER
4.000 MA= -20.00 PSID OR -137.9 KPAD
20.00 MA= 120.0 PSID OR 827.4 KPAD
COMPARING PCD TO MANIFOLD PRESSURE DIFFUSION
96HF-1 0434 HYDRAULIC OIL FILTER DIFF PRESSURE TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 150.0 PSID OR 1034 KPAD
ALARM AT 100 PSID INCREASING (689 KPA)
96HF-2 0434 HYDRAULIC OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 150.0 PSID OR 1034 KPAD
ALARM AT 100 PSID INCREASING (689 KPA)
96HQ-1 0434 HYDRAULIC OIL SUPPLY PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 2000 PSIG OR 13790 KPAG
ALARM AT 1450 PSIG DECREASING (9997 KPA)
96QH-1 0416 LUBE OIL HEADER PRESSURE TRANSMITTER
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 100.0 PSIG OR 689.5 KPAG
96QL-1 0416 LUBE OIL TANK LEVEL TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
96QQ-1 0416 LUBE OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 30.00 PSID OR 206.8 KPAD
96QQ-2 0416 CONTROL OIL FILTER DELTA P TRANSMITTER
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 30.00 PSID OR 206.8 KPAD
96QV-2 0416 LUBE OIL TANK AIR PRESSURE TRANSDUCER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
ALARM IF TANK PRESSURE FALLS BELOW 3.6 INH20
96SR-1 0422 STOP/SPEED RATIO VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96SR-2 0422 STOP/SPEED RATIO VALVE LVDT
0% STROKE = 0.7 VAC
100% STROKE = 3.5 VAC
96TD-1A 0471 DEW POINT SENSOR/TRANSMITTER
4.000+-0.5000 MA= -49.00 F OR -45.00 C
20.00+-0.5000 MA= 167.0 F OR 75.00 C
230VAC, 4-20 MA OUTPUT SIGNAL

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 40 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 41 of 71

A
SIZE DWG NO SH REV
399A4551 41 B

Device System Settings


96TD-1B 0471 DEW POINT SENSOR/TRANSMITTER
4.000+-0.5000 MA= -49.00 F OR -45.00 C
20.00+-0.5000 MA= 167.0 F OR 75.00 C
230VAC, 4-20 MA OUTPUT SIGNAL
96TD-1C 0471 DEW POINT SENSOR/TRANSMITTER
4.000+-0.5000 MA= -49.00 F OR -45.00 C
20.00+-0.5000 MA= 167.0 F OR 75.00 C
230VAC, 4-20 MA OUTPUT SIGNAL
96TF-1 0471 TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 10.00 INH2O OR 2.488 KPA
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96TF-2A 0471 TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96TF-2B 0471 TURBINE INLET FILTER DIFF PRESSURE TRANSMITTER
ALARM AT 6.00 +- 0.25 INH20 (1.49 +-0.06 KPA)
POWERED BY 24 VDC, 4-20 MA OUTPUT SIGNAL
96TH-1 0432 INLET HEATING CONTROL VALVE POSITION TRANSMITTER
4.0MA = 0% = VALVE VA20-1 FULL CLOSED
20.0MA = 100% =VALVE VA20-1 FULL OPEN
96TV-1 0434 INLET GUIDE VANE LVDT
LVDT POSITION SIGNAL = 0.6 +/- 0.09 VRMS AT FULL LVDT EXTENSION.
CALIBRATE TO PROVIDE SIGNAL OF 0.7 +/- 0.02 VRMS AT IGV FULL CLOSED
(ACTUATOR EXTENDED), AND BETWEEN 2.40 - 3.70 VRMS AT IGV FULL OPEN
(ACTUATOR RETRACTED).
96TV-2 0434 INLET GUIDE VANE LVDT
LVDT POSITION SIGNAL = 0.6 +/- 0.09 VRMS AT FULL LVDT EXTENSION.
CALIBRATE TO PROVIDE SIGNAL OF 0.7 +/- 0.02 VRMS AT IGV FULL CLOSED
(ACTUATOR EXTENDED), AND BETWEEN 2.40 - 3.70 VRMS AT IGV FULL OPEN
(ACTUATOR RETRACTED).
96VC-11 0415 SHAFT AXIAL POSN TRANSMITTER BEARING #1
96VC-12 0415 SHAFT AXIAL POSN TRANSMITTER BEARING #1
96VS-1 0440 SHAFT VOLTAGE TRANSDUCER
30 WATT MAX
VOLTAGE ALARM = 5 VOLTS
CURRENT ALARM = 4 AMPS
96WW-3 0442 PRESS TRANS, ONLINE COMPRESSOR WASH MANIFOLD SUPPLY
4.000+-0.2000 MA= 0.0 PSIG OR 0.0 KPAG
20.00+-0.2000 MA= 150.0 PSIG OR 1034 KPAG
ACV1-1 0434 IGV HYDRAULIC CYLINDER ACTUATOR
SLEW TIME: 4.5 +/-1.5 SECONDS

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 41 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 42 of 71

A
SIZE DWG NO SH REV
399A4551 42 B

Device System Settings


AH1-1 0434 HYDRAULIC OIL ACCUMULATOR
PRECHARGE 800 PSI DRY NITROGEN, 5 GALLONS (5516 KPA)
AL-2 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-27 0471 AC LIGHT-INLET AIR COMPARTMENT
230VAC, 50HZ
1 PH
AL-2A 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-2B 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-31 0471 TURBINE INLET AIR EVAPORATIVE COOLER COMP. AC LIGHTING
230VAC, 50HZ
1 PH
AL-4 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-4A 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-4B 0416 AC LIGHT-ACCESSORY COMPARTMENT
AL-62 0442 AC LIGHT-WATER WASH SKID
AL-63 0442 AC LIGHT-WATER WASH SKID
AL-81 0442 AC LIGHT-WATER WASH SKID
AL-87 0422 AC LIGHT-GAS FUEL MODULE
AL-88 0422 AC LIGHT-GAS FUEL MODULE
APU-LIC-1 0419 APU LOCAL INDICATOR CONTROL
INCREASING: 110.0+-5.000 F OR 43.33+-2.778 C
(DECREASING: 100.0+-5.000 F OR 37.78+-2.778 C)
CONTROLS 88AD-1
APU OVER TEMPERATURE CONTROL SETTINGS
INCREASING: 145.0+-5.000 F OR 62.78+-2.778 C
DECREASING: 142.0+-5.000 F OR 61.11+- 2.778 C
CONTROLS 20AP-1
APU-TC-1 0419 APU TEMPERATURE ELEMENT, PROVIDES SIGNAL FOR APU-LIC-1
AR-2 0416 AC RECEPTACLE-ACCESSORY COMPARTMENT
AR-20 0471 AC RECEPTACLE-INLET FILTER COMPARTMENT
230 V, 50 HZ, 1 PH
GROUNDED
AR-2A 0416 AC RECEPTACLE-ACCESSORY COMPARTMENT
AR-50 0442 AC RECEPTACLE-WATER WASH SKID
ASW-10 0471 AC LIGHT SWITCH-INLET AIR COMPARTMENT
230VAC, 50 HZ,1 PH
ASW-13 0416 AC SW-ACCESSORY COMPARTMENT
ASW-13A 0416 3 WAY EXPLOSION PROOF TUMBLER SWITCH
ASW-14 0471 LIGHT SWITCH
230 VAC, 50 HZ, 1 PH
ASW-31 0442 AC LIGHT SWITCH-WATER WASH SKID
ASW-44 0422 AC LIGHT SWITCH-GAS FUEL MODULE

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 42 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 43 of 71

A
SIZE DWG NO SH REV
399A4551 43 B

Device System Settings


AT-HL-1 0436 AIR TEMPERATURE - LUBE OIL COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-HL-2 0436 AIR TEMPERATURE - LUBE OIL COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-ID-1 0471 AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-ID-2 0471 AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-ID-3 0471 AMBIENT TEMPERATURE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-TC-1 0436 AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-TC-2 0436 AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-TC-3 0436 AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-TC-4 0436 AIR TEMPERATURE-TURBINE COMPARTMENT
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-VS-1 0436 AIR TEMPERATURE- GAS MODULE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
AT-VS-2 0436 AIR TEMPERATURE- GAS MODULE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
BT-GJ1-1A 0440 BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
ALARMS @ 260 F
(126.6667 C)
BT-GJ1-1B 0440 BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
ALARMS @ 260 F
(126.6667 C)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 43 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 44 of 71

A
SIZE DWG NO SH REV
399A4551 44 B

Device System Settings


BT-GJ1-2A 0440 BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
ALARMS @ 260 F
(126.6667 C)
BT-GJ1-2B 0440 BEARING METAL TEMP-GENERATOR BEARING #1
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
ALARMS @ 260 F
(126.6667 C)
BT-GJ2-1A 0440 BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
ALARMS @ 260 F
(126.6667 C)
BT-GJ2-1B 0440 BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
ALARMS @ 260 F
(126.6667 C)
BT-GJ2-2A 0440 BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
ALARMS @ 260 F
(126.6667 C)
BT-GJ2-2B 0440 BEARING METAL TEMP-GENERATOR BEARING #2
TYPE K THERMOCOUPLE
1 ELEMENT;
ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
ALARMS @ 260 F
(126.6667 C)
BT-J1-1A 0415 BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-J1-1B 0415 BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 44 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 45 of 71

A
SIZE DWG NO SH REV
399A4551 45 B

Device System Settings


BT-J1-2A 0415 BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-J1-2B 0415 BEARING METAL TEMP-TURBINE BEARING #1
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-J2-1A 0415 BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-J2-1B 0415 BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-J2-2A 0415 BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-J2-2B 0415 BEARING METAL TEMP-TURBINE BEARING #2
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-TA1-12A 0415 BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-TA1-12B 0415 BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-TA1-6A 0415 BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-TA1-6B 0415 BEARING METAL TEMP-THRUST ACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-TI1-12A 0415 BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
BT-TI1-12B 0415 BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
BT-TI1-6A 0415 BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 45 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 46 of 71

A
SIZE DWG NO SH REV
399A4551 46 B

Device System Settings


BT-TI1-6B 0415 BEARING METAL TEMP-THRUST INACTIVE
TYPE K THERMOCOUPLE
2 ELEMENTS; UNGROUNDED;
NOT CONNECTED TO TCP
CK-1A 0434 CHECK VALVE
CK-1B 0434 CHECK VALVE
CK-2A 0434 CHECK VALVE
CK-2B 0434 CHECK VALVE
CT-DA-1 0415 COMPRESSOR DISCHARGE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
CT-DA-2 0415 COMPRESSOR DISCHARGE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
CT-DA-3 0415 COMPRESSOR TEMP-DISCHARGE ANNULUS
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
CT-IF-1 0415 COMPRESSOR INLET THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
CT-IF-2 0415 COMPRESSOR INLET THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
CT-IF-3 0415 COMPRESSOR TEMP-INLET FLANGE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
DHCP 4027 HYDROGEN CONTROL PANEL POWER SUPPLY
HYDROGEN CONTROL PANEL SUPPLY POWER TO BE 230 VAC 50 HZ AND 600
WATTS. THIS EQUIPMENT IS TO BE POWERED BY A UPS. REFER TO ML-G2B0
FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.
DL-2 0416 DC LIGHT-ACCESSORY COMPARTMENT
DL-2A 0416 DC LIGHT-ACCESSORY COMPARTMENT
DL-51 0422 DC LIGHT-GAS FUEL MODULE
DL-52 0422 DC LIGHT-GAS FUEL MODULE
DT-GAC-23 0440 GENERATOR COLLECTOR-COLD AIR
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 149 F OR 65 C
DT-GAH-17 0440 GENERATOR COLLECTOR-HOT AIR
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM @ 20 C OR 68 F ABOVE AMBIENT

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 46 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 47 of 71

A
SIZE DWG NO SH REV
399A4551 47 B

Device System Settings


DT-GGC-10 0440 GENERATOR TEMP-COLD GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
(50 C)
DT-GGC-11 0440 GENERATOR TEMP-COLD GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
(50 C)
DT-GGC-12 0440 GENERATOR TEMP-COLD GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
(50 C)
DT-GGC-13 0440 GENERATOR TEMP-COLD GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 122 F
(50 C)
DT-GGH-15 0440 GENERATOR TEMP-HOT GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
(100 C)
DT-GGH-16 0440 GENERATOR TEMP-HOT GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
(100 C)
DT-GGH-18 0440 GENERATOR TEMP-HOT GAS COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
(100 C)
DT-GGH-19 0440 GENERATOR TEMP-HOT GAS COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 212 F
(100 C)
DT-GGK-24 0440 GENERATOR FRAME-COMMON COLD GAS
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALSO IDENTIFIED AS GTG-2
ALARM = 145 F OR 62.78 C

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 47 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 48 of 71

A
SIZE DWG NO SH REV
399A4551 48 B

Device System Settings


DT-GSA-34 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSA-35 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSA-36 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSA-4 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSA-5 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSA-6 0440 GENERATOR TEMP-STATOR COLLECTOR END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSC-20 0440 GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
DT-GSC-21 0440 GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
DT-GSC-22 0440 GENERATOR TEMP-STATOR CENTER
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS; GROUNDED;
ALARM = 264 F OR 129 C
DT-GSF-1 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSF-2 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 48 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 49 of 71

A
SIZE DWG NO SH REV
399A4551 49 B

Device System Settings


DT-GSF-3 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSF-31 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSF-32 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
DT-GSF-33 0440 GENERATOR TEMP-STATOR COUPLING END
100 OHM PLATINUM (DIN 43760) RTD
2 ELEMENTS;
ALARM = 264 F OR 129 C
FB1-1 0416 FAN-LUBE OIL DEMISTER #1
FB2-1 0416 FAN-LUBE OIL DEMISTER #2
FH2-1 0434 HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 3 MICRON
BETA 3 >= 200
FH2-2 0434 HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 3 MICRON
BETA 3 >= 200
FH6-1 0434 IGV SERVO HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 15 MICRON
FH7-1 0422 FUEL GAS SERVO HYDRAULIC OIL SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH7-1)
FH8-1 0422 GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-1)
FH8-2 0422 GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-2)
FH8-3 0422 GAS FUEL SERVO HYDRAULIC SUPPLY FILTER
FILTRATION: 15 MICRON ABSOLUTE
WITH INTEGRAL VISUAL REPLACEMENT INDICATOR (PDI FH8-3)
FI-AC-1 0471 FLOW INDICATOR
0.00 0.00
FLOW INDICATOR FOR EVAP COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 49 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 50 of 71

A
SIZE DWG NO SH REV
399A4551 50 B

Device System Settings


FI-AC-2 0471 FLOW INDICATOR
0.00 0.00
FLOW INDICATOR FOR EVAP COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP
FI-AC-3 0471 FLOW INDICATOR
0.00 0.00
FLOW INDICATOR FOR EVAP COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP
FI-AC-4 0471 FLOW INDICATOR
0.00 0.00
FLOW INDICATOR FOR EVAP COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP
FI-AC-5 0471 FLOW INDICATOR
0.00 0.00
FLOW INDICATOR FOR EVAP COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP
FI-WW-1 0442 WATER WASH SKID - DETERGENT FLOW INDICATOR
0.00 GPM 0.00
(0.0-0.0 LPH)
FLOWTOTALIZER 4027 POWER SUPPLY
HYDROGEN FLOW TOTALIZER POWER REQUIREMENTS
120 V OR 240 V, 16 W, 1 PH
REFER TO MLI-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION
FM-2996A 4027 GAS DRYER BLOWER MOTOR.
0.5000 HP; 0.3728 KW; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
DUAL TOWER GAS DRYER BLOWER MOTOR.
FM-2996B 4027 GAS DRYER BLOWER MOTOR.
0.5000 HP; 0.3728 KW; 1500 RPM; 415 VAC; 3 PH; 50 HZ;
DUAL TOWER GAS DRYER BLOWER MOTOR.
FQIC-2950 4027 HYDROGEN GAS FLOW TOTALIZER
4.000 MA= 0.0 OR 0.0
20.00 MA= 125.0 OR 125.0
FUNCTION: MONITOR HYDROGEN MAKE-UP GAS CONSUMPTION.
4 MA = 0.00 SCFH
20 MA = 125 SCFH
FE-2950 IS THE FLOW ELEMENT
FTG-1A 0422 FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 50 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 51 of 71

A
SIZE DWG NO SH REV
399A4551 51 B

Device System Settings


FTG-1B 0422 FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
FTG-1C 0422 FUEL GAS TEMPERATURE SENSOR
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
FV-1A 0434 HYDRAULIC OIL SUPPLY ISOLATION
VALVE #1
FV-1B 0434 HYDRAULIC OIL SUPPLY ISOLATION
VALVE #2
FV-2A 0434 HYD OIL DISCHARGE ISOLATION VLV
FV-2B 0434 HYD OIL DISCHARGE ISOLATION VLV
FV-3A 0434 ISOLATION VALVE
FV-3B 0434 ISOLATION VALVE
FV-4A 0434 ACCUMULATOR ISOLATION VALVE
VALVE #1
FV-4B 0434 HYDRAULIC BYPASS VALVE
VALVE #2
FY-2971 4027 TURBINE END SCAVENGING SOLENOID
230 VAC; 50 HZ;
SOLENOID IS POWERED BY H2 PANEL UPS.
ENERGIZED TO OPEN SOLENOID VALVE TO INCREASE TE SCAVENGING RATE
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL 20SCAV1 ENERGIZES SOLENOID VALVE
FY-2972 4027 COLLECTOR END GAS SOLENOID
230 VAC; 50 HZ;
SOLENOID IS POWERED BY H2 PANEL UPS.
ENERGIZED SOLENOID VALVE TO PORT GENERATOR CASING GAS TO DEVICE
QT-290A
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL 20CASE1 ENERGIZES SOLENOID VALVE
FY-2973 4027 COLLECTOR END SCAVENGING SOLENOID
230 VAC; 50 HZ;
SOLENOID IS POWERED BY H2 PANEL UPS.
ENERGIZED TO OPEN SOLENOID VALVE TO INCREASE CE SCAVENGING RATE
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL 20SCAV2 ENERGIZES SOLENOID VALVE

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 51 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 52 of 71

A
SIZE DWG NO SH REV
399A4551 52 B

Device System Settings


FY-2974 4027 COLLECTOR END GAS SOLENOID.
230 VAC; 50 HZ;
SOLENOID IS POWERED BY H2 PANEL UPS.
ENERGIZED SOLENOID VALVE TO PORT GENERATOR CASING GAS TO DEVICE
QT-290B
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M`-ENCAPSULATION
SIGNAL 20CASE2 ENERGIZES SOLENOID VALVE
FY-2981 4027 CASE, PURGE, CALIBRATION SOLENOID.
230 VAC; 50 HZ;
DE-ENERGIZED STATE ALLOWS FLOW FROM GEN CASE TO FY-2972 AND FY-
2974. REFER TO SYSTEM P&ID. NOT WIRED TO TCP. SOLENOID IS POWERED
BY H2 PANEL UPS.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD:`M` - ENCAPSULATION
DE-ENERGIZED: 3 TO 1 OPEN, 2 PLUGGED, AL
FY-2996A 4027 DUAL GAS DRYER TOWER 1 SOLENOID
230 VAC; 50 HZ;
POWERED BY GAS DRYER AND CONTROLLED BY GAS DRYER`S PLC. NO MARK
VI INTERFACE.
FY-2996B 4027 DUAL GAS DRYER TOWER 2 SOLENOID
230 VAC; 50 HZ;
POWERED BY GAS DRYER AND CONTROLLED BY GAS DRYER`S PLC. NO MARK
VI INTERFACE.
G023-GC 4035 GAS CHROMATOGRAPH - POWER CONSUMPTION
SOURCE POWER SUPPLIED BY CUSTOMER
1.8 KW, 7.9 AMP, 230 VAC
SINGLE UPS SOURCE REQUIRED PER SITE
230 VAC, 1PH, 50 HZ
GASDRYER 4027 GAS DRYER POWER SUPPLY
415 VAC; 3 PH; 50 HZ; 2500 WATT
REFER TO MLI-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION
LF3-1 0416 LUBE OIL FILTER
FILTRATION: BETA 25 = 200
LF3-2 0416 LUBE OIL FILTER
FILTRATION: BETA 25 = 200
LF3-3 0416 MIST ELIMINATOR
LF3-5 0416 SEAL OIL FILTER
FILTRATION: BETA 25 = 200
LI-FP-1A 0426 CO2 TANK LIQUID LEVEL GAUGE
0.00 PSIG 0.00
(0.0-0.0 KPAG)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 52 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 53 of 71

A
SIZE DWG NO SH REV
399A4551 53 B

Device System Settings


LI-QH-1 0416 LEVEL INDICATOR LUBE OIL TANK
0.00 0.00
-10 TO 6 INCHES
[-254 TO 152 MM]
LOHX-1 0416 MAIN LUBE OIL HEAT EXCHANGER
#1
LOHX-2 0416 MAIN LUBE OIL HEAT EXCHANGER
#2
LSH-2990 4027 LIQUID LEVEL DETECTOR HIGH LEVEL SWITCH
NORM=(2) NC-CEC; CONTACT OPENS ON HIGH LEVEL;
DPDT SWITCH.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
LSH-3401 4027 SEAL OIL DRAIN HIGH LEVEL SWITCH
NORM=(2) NC-CEC; CONTACT OPENS ON HIGH LEVEL;
DPDT SWITCH.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
LSHH-2990 4027 LIQUID LEVEL DETECTOR HIGH HIGH LEVEL SWITCH
NORM=(2) NC-CEC; CONTACT OPENS ON HIGH HIGH LEVEL;
DPDT SWITCH.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
LT-B1D-1 0416 LUBE TEMPERATURE #1 BRG DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LT-B2D-1 0416 LO THERMOCOUPLE #2 BRG DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LT-G1D-A 0416 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)
LT-G1D-B 0416 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
(SPARE)
LT-G2D-A 0416 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
ALARM SETTING IS 200 F (93.3 C)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 53 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 54 of 71

A
SIZE DWG NO SH REV
399A4551 54 B

Device System Settings


LT-G2D-B 0416 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAIN
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
(SPARE)
LT-OT-3 0416 LUBE OIL TANK THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
LOW LUBE OIL TANK TEMPERATURE
- IMMERSION HEATERS ON AT 79 F (26 C)
- START PERMISSIVE LOCKOUT AT OR BELOW 75 F (24 C)
LT-OT-4 0416 LUBE OIL TANK THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
LOW LUBE OIL TANK TEMPERATURE
- IMMERSION HEATERS ON AT 79 F (26 C)
- START PERMISSIVE LOCKOUT AT OR BELOW 75 F (24 C)
LT-TH-1 0416 LUBE SYSTEM TEMP-TURBINE HEADER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
LT-TH-2 0416 LUBE SYSTEM TEMP-TURBINE HEADER-TRIP
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
LT-TH-3 0416 LUBE SYSTEM-TURBINE HEADER TEMP-TRIP
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
HIGH OIL TEMPERATURE: TRIPLE REDUNDANT (LT-TH-1, 2 & 3)
- ALARM AT 165 F (73.9 C)
- TRIP AT 175F (79.4 C)
ME-2996 4027 GAS DRYER INLET HYGROMETER PROBE
4.000 MA= 60.00 F OR 15.56 C
20.00 MA= -60.00 F OR -51.11 C
FUNCTION: PROBE FOR MEASURING INLET GAS DEW POINT ONLY. ALARM
CONTACTS ARE LOCATED ON DEVICE MIC-2996.
MG1-1 0422 GAS FUEL NOZZLE
DIFFUSION
MG1-2 0422 GAS FUEL NOZZLE
PM1

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 54 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 55 of 71

A
SIZE DWG NO SH REV
399A4551 55 B

Device System Settings


MG1-3 0422 GAS FUEL NOZZLE
PM4
MG2-4 0422 CORIOLIS GAS FUEL FLOW METER
MIC-2996 4027 GAS DRYER DEW POINT SENSOR
NORM=(2) NC; CONTACT OPENS AT SET POINT;
HIGH DEW POINT ALARM, SIGNAL NAME = 30DRYMH, SET AT +20 F
INCREASING.
DEW POINT SENSOR FAULT, SIGNAL NAME = 30DRYFAULT
PDI-FG-3 0422 GAS FUEL STRAINER DIFFERENTIAL PRESSURE INDICATOR
0.00 0.00
0.0 - 25.0 PSID
(0.0-172.4 KPAD)
PDI-HQ-4 0434 IGV HYDRAULIC OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 0.00
PDI-QQ-21 0416 LUBE OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
PDI-QQ-22 0416 LUBE OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
PDI-QQ-25 0416 SEAL OIL FILTER DIFFERENTIAL PRESSURE INDICATOR
0.00 PSID 25.00
(0.0-172.4 KPAD)
PDI-TF-CF 0471 PRESSURE DIFFERENTIAL INDICATOR
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
PDI-TF-OF 0471 OVERALL FILTERHOUSE PRESSURE DROP
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
PDI-TF-SF 0471 SELF CLEANING FILTER PRESSURE INDICATOR
0.00 10.00
0-10 IN. W.C [0-2.49 KPA]
PDS-TF-1A 0471 PRESSURE DIFFERENTIAL SWITCH
0.00 10.00
NO INTERFACE WITH TCP
0 - 10 IN. W.C. [0-2.49 KPA]
PDSL-3402 4027 SEAL OIL DIFFERENTIAL PRESSURE LOW SWITCH
DECREASING: 4.500+-0.0900 PSID OR 31.03+-0.6205 KPAD
NORM=(1) NC-CEC; OPENS TO ALARM LOW DP;
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF AND
HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 55 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 56 of 71

A
SIZE DWG NO SH REV
399A4551 56 B

Device System Settings


PDSL-3406 4027 SEAL OIL DIFF PRESSURE LOW-LOW, START DC PUMP
DECREASING: 3.500+-0.0900 PSID OR 24.13+-0.6205 KPAD
NORM=(1) NC-CEC; OPENS TO START DC SEAL OIL PUMP;
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF AND
HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PDT-292 4027 GENERATOR ROTOR FAN PRESSURE DIFFERENTIAL
4.000 MA= 0.0 INH2O OR 0.0 KPA
20.00 MA= 30.00 INH2O OR 7.465 KPA
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PDT-3402 4027 SEAL OIL DIFFERENTIAL PRESSURE, SEAL OIL VS GAS PRESSURE
4.000 MA= 0.0 PSID OR 0.0 KPAD
20.00 MA= 15.00 PSID OR 103.4 KPAD
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
CONTROL VALVE PDCV-3401 SET TO 5.5 PSID (37.9 KPAD)
PH1-1 0434 MAIN HYDRAULIC OIL SUPPLY PUMP
32 GPM @ 2750 PSIG (18961 KPA)
MAX VOLUME STOP SET FOR MAXIMUM VOLUME CAPACITY
PH2-1 0434 AUXILIARY HYDRAULIC OIL SUPPLY PUMP
32 GPM @ 2750 PSIG (18961 KPA)
MAX VOLUME STOP SET FOR MAXIMUM VOLUME CAPACITY
PI-AC-1 0471 PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PRESSURE INDICATOR FOR EVAPORATIVE COOLER
MINIMUM STATIC PRESSURE RATING OF 125 PSIG
VISUAL READOUT, NO SIGNAL TO TCP
PI-AP-1 0419 APU PRESSURE INDICATOR - PREREGULATOR
0.00 PSIG 300.00
0 - 2068 KPAG
PI-AP-2 0419 APU PRESSURE INDICATOR - DRYER INLET
0.00 PSIG 300.00
0 - 2068 KPAG
PI-AP-3 0419 APU PRESSURE INDICATOR - DRYER DISCHARGE
0.00 PSIG 160.00
0 - 1103 KPAG
PI-CA-2 0471 PRESSURE INDICATOR
0.00 PSIG 150.00
(0.0-1034 KPAG)
PRESSURE INDICATOR FOR SELF CLEANING AIR SUPPLY

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 56 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 57 of 71

A
SIZE DWG NO SH REV
399A4551 57 B

Device System Settings


PI-CW-4 0420 COOLING WATER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-CW-5 0420 COOLING WATER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-D5 0422 FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)
PI-FG-1 0422 GAS FUEL SUPPLY PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)
PI-FG-2 0422 GAS FUEL INTERVALVE (P2) PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)
PI-FP-1A 0426 CO2 TANK PRESSURE INDICATOR
0.00 PSIG 0.00
(0.0-0.0 KPAG)
PI-FP-6A 0426 PRESSURE INDICATOR
0.00 PSIG 700.00
(0.0-4826 KPAG)
PI-GC-1 4035 GAS CHROMATOGRAPH SAMPLE PRESSURE GAUGE - 1
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-GC-2 4035 GAS CHROMATOGRAPH SAMPLE PRESSURE GAUGE - 2
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-HQ-1 0434 HYD PUMP #1 PRESSURE DISCHARGE INDICATOR
0.00 PSIG 6000.00
PI-HQ-2 0434 HYD PUMP #2 PRESSURE DISCHARGE INDICATOR
0.00 PSIG 6000.00
PI-HQ-3 0434 HYDRAULIC LOW PRESSURE INDICATOR
0.00 PSIG 2000.00
PI-HQ-6A 0434 HYD PUMP #1 PRESSURE INLET INDICATOR
0.00 PSIG 160.00
PI-HQ-6B 0434 HYD PUMP #2 PRESSURE INLET INDICATOR
0.00 PSIG 160.00
PI-PG-1 0477 PRESSURE INDICATOR
0.00 PSIG 160.00
PI-PM1 0422 FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)
PI-PM4 0422 FUEL GAS PRESSURE INDICATOR
0.00 PSIG 600.00
(0.0-4137 KPAG)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 57 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 58 of 71

A
SIZE DWG NO SH REV
399A4551 58 B

Device System Settings


PI-QA-1 0416 MAIN LUBE OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-QA-1A 0416 LUBE OIL HEADER PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-QA-2 0416 LUBE OIL PUMP#2 PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-QB-1 0434 LIFT OIL PRESSURE INDICATOR
0.00 PSIG 6000.00
PI-QE-1 0416 EMERGENCY LUBE OIL PUMP PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-QS-1 0416 SEAL OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-QS-2 0416 SEAL OIL PUMP PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-QT-2A 0416 GENERATOR BEARING LUBE OIL PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-QT-2B 0416 GENERATOR BEARING LUBE OIL PRESSURE INDICATOR
0.00 PSIG 60.00
(0.0-413.7 KPAG)
PI-QV-1 0416 MIST ELIMINATOR FILTER HOUSE PRESSURE INDICATOR
0.00 0.00
0.0 - 50 INCHES H2O
[0.0 - 1270 MM H2O]
PI-WW-1 0442 WATER WASH SKID PRESSURE INDICATOR
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-WW-10 0442 PRESSURE GAUGE - WATER WASH
0.00 PSIG 200.00
(0.0-1379 KPAG)
PI-WW-11 0442 PRESSURE GAUGE - WATER WASH
0.00 PSIG 100.00
(0.0-689.5 KPAG)
PI-WW-12 0442 PRESSURE GAUGE - WATER WASH
0.00 PSIG 100.00
(0.0-689.5 KPAG)
PQ1-1 0416 LUBE OIL MAIN PUMP
RATED FLOW: 1050 GPM AT 112 PSIG (2900 RPM)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 58 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 59 of 71

A
SIZE DWG NO SH REV
399A4551 59 B

Device System Settings


PQ1-2 0416 LUBE OIL MAIN PUMP
RATED FLOW: 1050 GPM AT 112 PSIG (2900 RPM)
PQ2-1 0416 LUBE OIL EMERGENCY PUMP
RATED FLOW: 600.0 GPM AT 30 PSIG (1750 RPM)
PQ3-1 0416 SEAL OIL PUMP
RATED FLOW: 118.0 GPM AT 110 PSIG (2900 RPM)
PQ3-2 0416 SEAL OIL PUMP
RATED FLOW: 65.00 GPM AT 90 PSIG (2900 RPM)
PS-3404 4027 SEAL OIL INLET PRESS LOW, START DC PUMP
DECREASING: 90.00+-1.000 PSIG OR 620.5+-6.895 KPAG
NORM=(1) NC-CEC; OPEN TO ALARM AND START DC SO PUMP;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
DEAD BAND .85 PSIG TO 2.9 PSIG
PSL-2930 4027 H2 SUPPLY PRESSURE LOW
DECREASING: 110.0 PSIG OR 758.4 KPAG
(INCREASING: 125.0 PSIG OR 861.8 KPAG)
NORM=(1) NC-CEC; CONTACT OPENS ON LOW PRESSURE;
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PT-2950 4027 GENERATOR GAS PRESSURE
4.000 MA= 0.0 PSIG OR 0.0 KPAG
20.00 MA= 100.0 PSIG OR 689.5 KPAG
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PT-G1-1 0422 GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
PT-G1-2 0422 GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
PT-G1-3 0422 GAS FUEL PURGE THERMOCOUPLE
TYPE K THERMOCOUPLE
LOCATED ON DIFFUSION GAS MAINFOLD
QT-290A 4027 CELL #1 TRANSMITTER SIGNAL
4.000 MA= 70.00 OR 70.00
20.00 MA= 100.0 OR 100.0
4MA= 70 AND 20MA=100 (H2 IN AIR),
TE LOW LOW PURITY RUNBACK SETTING- 80% H2 DEC
TE LOW PURITY- 85% H2 DEC
CASE LOW LOW PURITY RUNBACK SETTING- 90% H2 DEC
CASE LOW PURITY - 95% H2 DEC
INCREASE SCAVENGING AT LOW ALARMS, RESET ALARM AT + 2%
4MA=0%

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 59 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 60 of 71

A
SIZE DWG NO SH REV
399A4551 60 B

Device System Settings


QT-290B 4027 CELL #2 TRANSMITTER SIGNAL
4.000 MA= 70.00 OR 70.00
20.00 MA= 100.0 OR 100.0
4MA= 70 AND 20MA=100 (H2 IN AIR),
CE LOW LOW PURITY RUNBACK SETTING- 80% H2 DEC
CE LOW PURITY- 85% H2 DEC
CASE LOW LOW PURITY RUNBACK SETTING- 90% H2 DEC
CASE LOW PURITY - 95% H2 DEC
INCREASE SCAVENGING AT LOW ALARMS, RESET ALARM AT + 2%
4MA=0%
RS-485-1 4035 SERIAL PORT
FOR CUSTOMER USE
RS-485-2 4035 SERIAL PORT
FOR CUSTOMER USE
SLA-1C 0426 FIRE ALARM STROBE & HORN (ACCESSORY COMPT)
24 VDC
EXTERNAL STROBE/HORN
(GAS COMP/ ACCESS.MODULE-ZONE 1)
SLA-1D 0426 FIRE ALARM STROBE & HORN (ACCESSORY COMPT)
24 VDC
INTERNAL STROBE/HORN
(GAS COMP. - ACCESS.MODULE-ZONE 1)
SLA-3A 0426 FIRE ALARM STROBE & HORN (ACCESSORY MODULE)
24 VDC
EXTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
SLA-3B 0426 FIRE ALARM STROBE & HORN (ACCESSORY MODULE)
24 VDC
EXTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
SLA-3C 0426 FIRE ALARM STROBE & HORN
24 VDC
INTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
SLA-3D 0426 FIRE ALARM STROBE & HORN
24 VDC
INTERNAL STROBE/HORN
(LUBE/HYDRAULIC COMP.-ACCESS.MODULE-ZONE 3)
SLCC-6A 0426 FIRE ALARM STROBE & HORN
24 VDC
PEECC INTERIOR STROBE/HORN

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 60 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 61 of 71

A
SIZE DWG NO SH REV
399A4551 61 B

Device System Settings


SLCC-6B 0426 FIRE ALARM STROBE & HORN
24 VDC
PEECC EXTERIOR STROBE/HORN
SLCC-6C 0426 FIRE ALARM STROBE & HORN
24 VDC
PEECC EXTERIOR STROBE/HORN
SLT-1A 0426 FIRE ALARM STROBE & HORN (TURBINE COMPT)
24 VDC
EXTERNAL STROBE/HORN
(TURBINE COMPT-ZONE 1)
SLT-1B 0426 FIRE ALARM STROBE & HORN (TURBINE COMPT)
24 VDC
EXTERNAL STROBE/HORN
(TURBINE COMPT-ZONE 1)
TC-2996A 4027 DESICCANT BED #1 TEMPERATURE SWITCH
INCREASING: 400.0 F OR 204.4 C
NORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.
FUNCTION: HEATER PROTECTION
TC-2996B 4027 DESICCANT BED #2 TEMPERATURE SWITCH
INCREASING: 400.0 F OR 204.4 C
NORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.
FUNCTION: HEATER PROTECTION
TI-AP-1 0419 APU TEMPERATURE INDICATOR
0.00 F 250.00
0 - 121.1 C
TI-QA-1 0416 LUBE OIL HEADER TEMPERATURE INDICATOR
20.00 F 240.00
(-6.667-115.6 C)
TI-QL-1 0416 LUBE OIL TANK TEMPERATURE INDICATOR
20.00 F 240.00
(-6.667-115.6 C)
TI-WW-1 0442 WATER WASH TANK TEMPERATURE INDICATOR
0.00 F 250.00
(-17.78-121.1 C)
TT-CM-1 0417 CASE TEMP. MANAGEMENT AIR SUPPLY TEMP. TRANS.

100 OHM PLATINUM (MINCO PB) RTD


1 ELEMENT; UNGROUNDED;
4.0 MA = -58 F OR -50 C
20.0 MA = 302 F OR 150 C
TT-IB-1 0415 TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 61 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 62 of 71

A
SIZE DWG NO SH REV
399A4551 62 B

Device System Settings


TT-IB-2 0415 TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-IB-3 0415 TURBINE TEMP-INNER BARREL
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-S13-1 0417 THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
STAGE 13 FLOW TEMPERATURE
TT-S2Q-2 0417 THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
EJECTOR EXIT TEMPERATURE
TT-S2Q-3 0417 THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
S2N SUPPLY TEMPERATURE (WYE CONNECTION LHS)
TT-S2Q-4 0417 THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
S2N SUPPLY TEMPERATURE (WYE CONNECTION RHS)
TT-S9-1 0417 THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
STAGE 9 FLOW TEMPERATURE
TT-TC-1 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-10 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-11 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-12 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-13 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-14 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 62 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 63 of 71

A
SIZE DWG NO SH REV
399A4551 63 B

Device System Settings


TT-TC-15 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-16 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-2 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-3 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-4 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-5 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-6 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-7 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-8 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-TC-9 0415 TURBINE CASING THERMOCOUPLE - 1ST STG SHROUD
TYPE K THERMOCOUPLE
UNGROUNDED;
TT-WS1AO-1 0415 TURBINE TEMPERATURE-WHEELSPACE 1ST STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS1AO-2 0415 TURBINE TEMPERATURE-WHEELSPACE 1ST STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS1FI-1 0415 TURBINE TEMPERATURE-WHEELSPACE 1ST STG FWD INNER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS1FI-2 0415 TURBINE TEMPERATURE-WHEELSPACE 1ST STG FWD INNER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS2AO-1 0415 TURBINE TEMPERATURE-WHEELSPACE 2ND STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 63 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 64 of 71

A
SIZE DWG NO SH REV
399A4551 64 B

Device System Settings


TT-WS2AO-2 0415 TURBINE TEMPERATURE-WHEELSPACE 2ND STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS2FO-1 0415 TURBINE TEMPERATURE-WHEELSPACE 2ND STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS2FO-2 0415 TURBINE TEMPERATURE-WHEELSPACE 2ND STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS3AO-1 0415 TURBINE TEMPERATURE-WHEELSPACE 3RD STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS3AO-2 0415 TURBINE TEMPERATURE-WHEELSPACE 3RD STG AFT OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS3FO-1 0415 TURBINE TEMPERATURE-WHEELSPACE 3RD STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-WS3FO-2 0415 TURBINE TEMPERATURE-WHEELSPACE 3RD STG FWD OUTER
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-1 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-10 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-11 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-12 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-13 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-14 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-15 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-16 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 64 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 65 of 71

A
SIZE DWG NO SH REV
399A4551 65 B

Device System Settings


TT-XD-17 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-18 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-19 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-2 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-20 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-21 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-22 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-23 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-24 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-25 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-26 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-27 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-28 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-29 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-3 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 65 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 66 of 71

A
SIZE DWG NO SH REV
399A4551 66 B

Device System Settings


TT-XD-30 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-31 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-4 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-5 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-6 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-7 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-8 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
TT-XD-9 0415 EXHAUST TEMPERATURE THERMOCOUPLE
TYPE K THERMOCOUPLE
1 ELEMENT; UNGROUNDED;
VA13-1 0477 FUEL GAS SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
VA13-13 0477 FUEL GAS SYSTEM PURGE VALVE
NORM=OPEN
PM4 VENT VALVE
VA13-15 0422 GAS FUEL VENT VALVE
NORM=NO
VA13-18 0422 GAS FUEL VENT VALVE
NORM=NO
VA13-2 0477 FUEL GAS SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
VA13-5 0477 GAS FUEL SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
VA13-6 0477 GAS FUEL SYSTEM PURGE VALVE
NORM=CLOSED; VALVE TO CLOSE IN 4 SECONDS MAX
VA13-8 0477 FUEL GAS SYSTEM PURGE VENT VALVE
NORM=OPEN
D5 VENT VALVE

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 66 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 67 of 71

A
SIZE DWG NO SH REV
399A4551 67 B

Device System Settings


VA16-1 0442 OFF-LINE COMPRESSOR WASH WATER INJ (PNEUMATIC) VALVE
NORMAL = CLOSED; ENERGIZE TO OPEN
REQUIRES 80 PSIG (MINIMUM) INSTRUMENT AIR FOR ACTUATION
VA16-3 0442 ON-LINE COMPRESSOR WASH WATER INJ (PNEUMATIC) VALVE
NORMAL = CLOSED; ENERGIZE TO OPEN
REQUIRES 80 PSIG (MINIMUM) INSTRUMENT AIR FOR ACTUATION
VA2-1 0417 COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
VA2-2 0417 COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
VA2-3 0417 COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
VA2-4 0417 COMPRESSOR BLEED VALVE
FAILED POSITION = OPEN
VA20-1 0432 INLET HEATING CONTROL VALVE
4.0 INCH STROKE
LINEAR TRIM CHARACTERISTIC
10.0 INCH ANSI FLANGE CONNECTION
FAILED POSITION = OPEN
VA32-1 0420 COOLING WATER CONTROL VALVE-LUBE OIL COOLER FLOW
SET 130 +- 3.000F OR 54.44 +- 1.666C
VA36-1 0477 FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXH VALVE
PART OF VA13-1; VALVE TO CLOSE IN 4 SECONDS MAX
VA36-10 0477 3-WAY PILOT OPERATED QUICK EXHAUST VALVE
PART OF VA13-6
VALVE TO CLOSE IN 4 SECONDS MAX
VA36-2 0477 FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXH VALVE
PART OF VA13-2; VALVE TO CLOSE IN 4 SECONDS MAX
VA36-9 0477 FUEL GAS SYSTEM PURGE VALVE ACTUATOR QUICK EXHAUST VALVE
PART OF VA13-5
VA40-1 0432 INLET HEATING CONTROL VALVE VOLUME BOOSTER
VA42-1 0432 INLET BLEED HEAT QUICK EXHAUSTER VALVE
VA7-2 0417 CONTROL VALVE
BYPASS FLOW CONTROL
FAILED POSITION = OPEN
VA7-3 0417 CONTROL VALVE
SUCTION ISOLATION FLOW CONTROL
FAILED POSITION = CLOSED
VAB1-1 0434 HYDRAULIC OIL SYSTEM AIR BLEED VALVE (MAIN)
VAB2-1 0434 HYDRAULIC OIL SYSTEM AIR BLEED VALVE (AUX)

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 67 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 68 of 71

A
SIZE DWG NO SH REV
399A4551 68 B

Device System Settings


VAD-2 0419 Air Processing Unit Drain Valve
1 PH
230 VAC; 50 HZ;
ELECTRONIC SOLENOID DRAIN VALVE OPERATED BY TIMER.
VCK7-1 0417 TURBINE SHELL & EXHAUST FRAME BLOWER CHECK VALVE
VCK7-3 0417 TURBINE SHELL COOLING AIR BLOWER CHECK VALVE
VGC-1 0422 FUEL GAS CONTROL VALVE
SLEW TIME = 1.00 +/-0.150 SECONDS
3.00 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
VGC-2 0422 FUEL GAS CONTROL VALVE
SLEW TIME = 1.000 +/-0.150 SECONDS
3.0 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
VGC-3 0422 FUEL GAS CONTROL VALVE
SLEW TIME = 1.00 +/-0.150 SECONDS
3.00 IN. MAXIMUM STROKE
HYDRAULIC EFFECTIVE AREA 2.54 IN^2
VH3-1 0434 INLET GUIDE VANE DUMP VALVE
VH5-1 0422 GAS FUEL DUMP VALVE-STOP/SPEED RATIO VALVE
VH5-2 0422 GAS FUEL DUMP VALVE-CONTROL VALVE
VH5-3 0422 GAS FUEL DUMP VALVE-CONTROL VALVE
VH5-4 0422 GAS FUEL DUMP VALVE-CONTROL VALVE
VM15-1 0432 INLET HEATING ISOLATION VALVE
10.0 INCH ANSI FLANGE CONNECTION
MANUAL BUTTERFLY VALVE
NORMAL POSITION = OPEN
VPR17-3 0417 PRESSURE REGULATOR
SET 80.00 PSIG OR 551.6 KPAG
ACTUATION AIR
PART OF VA7-2
VPR17-4 0417 PRESSURE REGULATOR
SET 15.00 PSIG OR 103.4 KPAG
SIGNAL AIR
PART OF VA7-2
VPR17-5 0417 PRESSURE REGULATOR
SET 80.00 PSIG OR 551.6 KPAG
ACTUATION AIR
PART OF VA7-3
VPR17-6 0417 PRESSURE REGULATOR
SET 15.00 PSIG OR 103.4 KPAG
SIGNAL AIR
PART OF VA7-3

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 68 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 69 of 71

A
SIZE DWG NO SH REV
399A4551 69 B

Device System Settings


VPR2-1 0416 LUBE OIL HEADER PRESSURE REGULATOR VALVE
SET 33.00+-2.000 PSIG OR 227.5+-13.79 KPAG
VPR3-1 0434 COMPENSATOR-HYDRAULIC OIL SUPPLY PUMP (IN PUMP)
SET 2750+-50.00 PSIG OR 18961+-344.7 KPAG
LOW PRESSURE SETTING: 1800 PSIG
VPR3-2 0434 COMPENSATOR-HYDRAULIC OIL SUPPLY AUX PUMP
SET 2750+-50.00 PSIG OR 18961+-344.7 KPAG
LOW PRESSURE SETTING: 1800 PSIG
VPR4-3 0434 HYDRAULIC SUPPLY PRESSURE REGULATING VALVE #1
SET 1625+-25.00 PSIG OR 11204+-172.4 KPAG
VPR4-4 0434 HYDRAULIC SUPPLY PRESSURE REGULATING VALVE #2
SET 1625+-25.00 PSIG OR 11204+-172.4 KPAG
VPR41-1 0432 TURBINE IAH CONTROL VALVE I/P INST AIR PRESSURE REG
SET 45.00+-2.000 PSIG OR 310.3+-13.79 KPAG
20TH-1 TRIP SOLENOID MUST BE ENERGIZED TO SET VPR41-1 PRESSURE
OUTPUT WITH GAGE
VPR54-22 0477 REGULATOR - GAS FUEL PURGE CONTROL VALVE
SET 90.00+-2.000 PSIG OR 620.5+-13.79 KPAG
PART OF VA13-2
VPR54-3A 0477 FILTER AIR PRESSURE REGULATOR
FILTER AIR PRESSURE REGULATOR
SET AT 85 +/- 5 PSIG OR 586 +/- 34.5 KPA
PRIMARY GAS PURGE VALVES
VPR64-2 0420 COOLING WATER CONTROL VALVE-AIR SUPPLY REG VALVE
SET 35.00+-3.000 PSIG OR 241.3+-20.68 KPAG
VPR67-1 0419 AIR FILTER BLOWDOWN REGULATOR VALVE
SET 110.0+-5.000 PSIG OR 758.4+-34.47 KPAG
VPR74-1 0442 PRESS REGULATOR, ONLINE COMPRESSOR WASH MANIFOLD SUPPLY
80 PSIG +/- 5 PSIG
VPR76-1 4035 FUEL GAS SAMPLE PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
VPR76-2 4035 FUEL GAS SAMPLE PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
VPR77-1 4035 CARRIER GAS - PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
VPR78-1 4035 CALIBRATION GAS - PRESSURE REGULATING VALVE
SET TO VENDOR REQUIREMENTS
REFER TO SERVICE MANUAL
VQC-1 0434 VARIABLE FLOW CONTROL VALVE
GT #1 BRG. LIFT OIL

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 69 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 70 of 71

A
SIZE DWG NO SH REV
399A4551 70 B

Device System Settings


VQC-2 0434 VARIABLE FLOW CONTROL VALVE
GT #1 BRG. LIFT OIL
VQC-3 0434 VARIABLE FLOW CONTROL VALVE
GT #2 BRG. LIFT OIL
VQC-4 0434 VARIABLE FLOW CONTROL VALVE
GT #2 BRG. LIFT OIL
VQC-5 0434 VARIABLE FLOW CONTROL VALVE
GENERATOR BRG. LIFT OIL - TURBINE END
VQC-6 0434 VARIABLE FLOW CONTROL VALVE
GENERATOR BRG. LIFT OIL - COLLECTOR END
VR-31 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR-31E 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR-32 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR-32E 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR-33 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR-33E 0426 RELIEF VALVE
SET 450.0 PSIG OR 3103 KPAG
HYDROSTATIC RELIEF VALVE FOR DISCHARGE PIPING
VR14-1 0419 APU PRESSURE RELIEF VALVE
SET 150.0+-1.000 PSIG OR 1034+-6.895 KPAG
DRYER TOWER RELIEF VALVE
VR14-2 0419 APU PRESSURE RELIEF VALVE
SET 150.0+-1.000 PSIG OR 1034+-6.895 KPAG
DRYER TOWER RELIEF VALVE
VR21-1 0434 MAIN HYDRAULIC OIL SUPPLY PUMP PRESSURE RELIEF VALVE
SET 3025+-100.0 PSIG OR 20857+-689.5 KPAG
VR22-1 0434 AUXILIARY HYDRAULIC OIL SUPPLY PUMP PRESSURE RELIEF VALV
SET 3025+-100.0 PSIG OR 20857+-689.5 KPAG
VR23-2 0434 HYDRAULIC SUPPLY LOW PRESSURE RELIEF VALVE
SET 1815+-25.00 PSIG OR 12514+-172.4 KPAG
VR64-10 0420 COOLING WATER PRESSURE RELIEF VALVE- LO COOLER
SET 150.0+-5.000 PSIG OR 1034+-34.47 KPAG
VR64-9 0420 COOLING WATER PRESSURE RELIEF VALVE- LO COOLER
SET 150.0+-5.000 PSIG OR 1034+-34.47 KPAG

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 70 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR


DWG Number 399A4551 Rev B Released 2/2/2013 Page 71 of 71

A
SIZE DWG NO SH REV
399A4551 71 B

Device System Settings


VS4-1 0422 FUEL GAS STOP VALVE
VS4-4 0422 FUEL GAS STOP VALVE
VSR-1 0422 STOP/SPEED RATIO VALVE
SLEW TIME = 0.500 +/- 0.250 SECONDS
90 DEGREES ROTATION MAX. STROKE 6.0 INCHES
HYDRAULIC EFFECTIVE AREA 7.67 IN^2
ZS-2996 4027 DUAL GAS DRYER PLC`S LIMIT SWITCH
THIS LIMIT SWITCH IS POWERED BY THE GAS DRYER AND FOR THE GAS
DRYER`S ON BASE PLC. THE PLC AND LIMIT SWITCH DO NOT TALK WITH THE
MARK VI, INTERNALLY CONTROLLED.

© COPYRIGHT 2012-2013 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES.All rights reserved. The information contained herein is GE Energy GAS Proprietary
Technical Information that belongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, which has been provided solely for the express reason of
restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving the same to have agreed to make no
duplication, or other disclosure, or use whatsoever for any, or all such information except as expressly authorized in writing by the General Electric Company,GE Energy
(USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)


GE Energy GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

DRAWN B,SAM KAMLESH


A 399A4551

SHEET
DRAWN DATE 2012-06-01 71 of 71

GE Proprietary Information - Class II (Internal) US EAR - NLR