You are on page 1of 12

providing insights for today’s hvac system designer

Engineers Newsletter volume 44 –4

Chiller Selection Made Easier with myPLV™

manageable method to set minimum tool that bridges the gap between a full
This Engineers Newsletter provides performance standard; however, there is building simulation method and the overly
insight on how the myPLV tool could be general agreement that it is a poor simplistic and often misleading single
used to quickly and accurately
estimate chiller performance and
indicator of chiller energy use in a building. metric methodologies of IPLV, NPLV, or full
payback. Even AHRI Standard 550-590, 2011 load chiller design performance.
recognizes that single-rating metrics,
developed at a standard set of conditions, The team determined that this tool must
does not provide a method of evaluation include the following criteria to provide
With the flood of competing chiller for a particular job. The following is an accurate results:
types, manufacturers and performance excerpt from Appendix D of the Standard. • chiller type and manufacturer agnostic
claims coming to the market in recent
In summary, it is best to use a • annual building load profile
years, the analysis of the chiller with
comprehensive analysis that reflects • local weather
the best payback has become both
the actual weather data, building load
more important to the building owner
characteristics, operational hours, • number of chillers in the system
and more difficult for the designer.
economizer capabilities and energy • chiller performance at appropriate
Comprehensive building modeling tools drawn by auxiliaries such as pumps operating points—both tons and
such as EnergyPlus, TRACE™ or HAP and cooling towers, when calculating temperatures.
that can compute hour-by-hour data the chiller and system efficiency. The
intended use of the IPLV (NPLV) • condenser water system control
provide the most accurate answer, but
rating is to compare the performance strategy
their processes can be quite daunting.
And the time and information needed of similar technologies, enabling a • simple and transparent methodology
for such in-depth analysis may not be side-by-side relative comparison, and
to provide a second certifiable rating • accurate ROI analysis based on
justified during the design process.
point that can be referenced by electrical consumption and demand
Meanwhile, a simpler analysis method
energy codes. A single metric, such charges to guide users in
using generalized single point chiller-
as design efficiency or IPLV shall not best chiller selection
only metrics such as Integrated Part
Load Value (IPLV) or full load be used to quantify energy savings. • easy to use if whole building modeling
performance completely disregard the isn’t feasible
Recently, Trane engineers were challenged
specifics of the chiller(s) application.
to develop a viable alternative to the This Engineers Newsletter provides a
This simpler approach ignores critical existing analysis methods that would technical explanation of the use and
application details such as building load provide an accurate indication of any output of the resulting analysis tool,
profile, local weather and number of chiller's installed energy performance. The myPLV™ (my Part Load Value). The EN will
chillers in the system, among others. mission was to provide accurate chiller describe the approach used to address
It may provide the industry with a performance indicators in an easy-to-use each of the above criteria to compare the
benefit of one chiller selection over
another for a specific building and chiller
plant, be it air-cooled or water-cooled.

© 2015 Trane, a business of Ingersoll Rand. All rights reserved. 1


chiller, specifically, operating
Every AHRI certified chiller
myPLV Overview temperatures and time in each bin.
manufacturer must have the ability to
provide any random operating point
The intent of the myPLV program is to The myPLV tool provides no advantage during certification so to provide the
provide HVAC system designers with an to any one chiller type or manufacturer. selected bin conditions is a reasonable
easy-to-use, spreadsheet-driven It simply provides a bin analysis for the request to any vendor.
application to accurately analyze chiller load profile and chiller performance
performance to determine the best entered by the program user. and associated condenser water
return on investment. temperature. Figure 1 illustrates the
Calculations use the specific chiller
flow of the myPLV analysis method.
The key to the tool’s simplicity is that it performance data provided by the
uses bin energy analysis. The key to the individual manufacturers. It assumes The goal of the myPLV tool is to
tool’s accuracy is that it creates bin the user will request and the evaluate chiller energy (assuming
conditions that are customized to the manufacturers will provide accurate proper plant operation) based on
actual operation of the building and and verifiable chiller performance data performance in a specific building type
at each user-specified chiller load point and climate zone. The tool does not
account for pump or fan energy.
Figure 1. Graphical depiction of the calculation process
User input Program computation myPLV output
(SI or IP units)

Building: • maps the location to a weather zone

• location • selects the PNNL building load data

• type • scales its 8,760 load data to the peak cooling load
specified
• peak cooling load
• saves the weather and plant load data
scaled building load scatter plot
(not viewable—displayed here to illustrate initial
data set for plant and chiller load profiles)

Plant • determines how many chillers and tower cells are


needed to satisfy each plant load point (hour)
• number and size of chillers
• applies the tower cell performance and tower control
• tower cell design performance against the outdoor load and wet-bulb temperature
(assuming one tower cell per
chiller) • stores the 8,760 leaving tower water temperature
(entering condenser) along with the individual chiller load
• the cooling tower control results
method
• creates the Plant Loading chart shown Plant loading chart
(viewable in the myPLV Charts tab)

• segments the chiller loads into four operating zones


(bins) based on 8,760 load points
• computes a weighted entering condenser water
temperature and a fractional weighting for each bin
• records the maximum load for each month for electrical
demand computations
• Creates the Chiller Loading chart and
Peak and Bin Loading tables Chiller loading chart
(viewable in myPLV Charts tab)

Peak and Bin Loading tables

User saves the file.


(Files can be saved separately for
analysis of alternative chiller
selections.)

High level data is copied to the


myPLV Bid Form tab
2 Trane Engineers Newsletter volume 44–4 providing insights for today’s HVAC system designer
Building Load Profile. Establishing a Table 1. Building load types included in myPLV
load profile is often the most difficult part Office (with, without econ) 12 hour operation; 5 days a week
of an energy and economic analysis.
Hospital (with, without econ) 24 hour operation; 7 days a week; heavier day occupancy
Fortunately, ASHRAE and Pacific
Northwest National Labs (PNNL) provide a High rise apts (without econ) 24 hour operation; 7 days a week; lighter day occupancy
solution. As a result of various ASHRAE Primary school (with, without econ) 12 hour operation; 5 days a week; seasonal
standards efforts, PNNL has created a
library of annualized load profiles (8,760 Secondary school (with, without econ) 12 hour operation; 5 days a week; seasonal

hours of data) for various building types in Hotel (without econ) 24 hour operation; 7 days a week
all weather zones of interest. The myPLV
tool incorporates 200 of these load
profiles within its database. Each of the Table 2. Weather zones included in myPLV
building types listed in Table 1 has been Zone Very cold Humid (A) Dry (B) Marine (C)
simulated within 20 climatic zones 0 x x
included in the myPLV database (Table 2) 1 x x
resulting in the 200 pre-defined data sets.
2 x x
Users simply select location information 3 x x x
and building type and enter a peak 4 x x x
tonnage for their particular building. The 5 x x x
program scales the PNNL load profile to
6 x x x
the peak cooling tons entered. The
7 x
resulting load profile can be viewed on
charts generated by the tool. 8 x

Most of the building types listed in Table 1 Local Weather. Having representative factor per ASHRAE Standard 90.1,
have profiles both with and without an weather data is key to overcoming the Appendix G for reference.
airside economizer. Those profiles IPLV problem of oversimplified analysis
representing systems without an airside techniques which assume the same chiller An undersized plant is flagged in red
economizer will contain loads during operating conditions from Jeddah, Saudi with a negative oversize factor. In this
cooler outside conditions. Load profiles Arabia to Fairbanks, Alaska and case, the program will produce a
incorporating an airside economizer will everywhere in between. solution; however, it will assume
eliminate most low temperature loads additional chillers are available beyond
since the economizer will satisfy the The myPLV tool uses the 8,760 hour that specified with the input set.
needed cooling. For those chilled-water weather data set (TMY) contained within
the PNNL load profile for a wide range of Cooling tower performance and control
systems that incorporate waterside
weather zones. Users may either enter a impact the operating conditions of the
economizing (free cooling), users may
global location that maps to a standard chiller for water-cooled plants. Users
wish to select load profiles with an airside
weather zone according to the dataset enter design tower performance data
economizer since the chillers will not be
contained in ASHRAE Standard 169, or and selects a cooling tower control
operating to satisfy loads during the
enter the weather zone explicitly by method. Based on this information,
cooler weather conditions.
selecting By Climate Zone in the Region myPLV calculates the entering
A custom load profile can be entered for dropdown. The selected weather condenser water temperature for each
chiller plants with load profiles much conditions (ambient wet bulb and dry bulb) hour of the load profile.
different than the available buildings (i.e., for each operating hour of the year are
process loads or data centers). Custom used to establish the operating conditions Chiller Performance. From the
load profiles can be entered via the for the cooling tower or air-cooled previous input information, the myPLV
Custom Load Input worksheet. Users condenser. determines the weighted average
must enter 8,760 hours (one year) of data, operating conditions for the chillers in
including chiller plant load (tons), as well Chiller Plant Information. The number the plant for bins centered on the 25, 50,
as the outdoor dry bulb and wet bulb of chillers in the system and the capacity 75 and 94 percent chiller load points.
temperatures. The program calculates the of the chillers are needed for myPLV to The program also requires the chiller’s
appropriate chiller submittal points. assess the operating conditions and time full load design performance to assess
for the chiller-specific operating zones or utility demand charges and to ensure an
bins. appropriate chiller is selected to satisfy
the design requirements of the job.
To access the Custom Load Input The program assumes all chillers are equal
worksheet, check the box adjacent to While the use of 25, 50, and 75 percent
capacity. Entering this information
the Region input or choose the Custom load points is similar to IPLV
Load selection in the Region drop down separate from the building peak load
allows the program to account for methodology, the ton-hour values and
list on the myPLV Calculator tab.
oversizing of the plant capacity. The condenser water temperature
program outputs the plant oversizing weightings deviate from IPLV/NPLV to
reflect the application. For the last bin,

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 44–4 3
87.5 percent to 100 percent chiller Figure 2. myPLV user inputs for building and plant configuration
loading is represented by a center-
weighted point at 94 percent.
This better captures the chiller
performance in this region and reduces
error.

Using the 94 percent point instead of


100 results in a five-point rating system
with the fifth point representing the
design conditions for electrical
demand calculation. While not used for
the myPLV energy calculations, this
fifth point assures that the selection
process using myPLV will still result in
an appropriate chiller for the load, lift
and application duty required, and Figure 3. Cooling tower design inputs
provide certified performance
necessary for the system design.

This bin information, along with


alternate pricing requested from the
qualified chiller manufacturer can be
input to calculate the annual energy
usage and investment payback for the
various chiller alternatives—completely
impartial in its analysis.

Figure 4. Submittal point generation in myPLV

myPLV Example
MyPLV is built as a Microsoft Excel®
workbook. The two worksheets that
require user input to perform the
calculations are the myPLV Calculator
and myPLV Bid Form.

myPLV Calculator: Building and


plant configuration. Figure 2 shows
user inputs in blue for the building and
plant configuration in the myPLV
Calculator worksheet. Inputs selected The towers are operated at a fixed The submittal points serve three
for this example include: tower approach setpoint of 7ºF with a purposes:
minimum water temperature of 55ºF. • First, they are used along with the
• Location: Memphis, Tennesse
chillers’ performance at those points
• Building type: Office building with The final step in this worksheet is to determine the chiller’s myPLV
airside economizing (standard generating the submittal points. rating number.
PNNL profile is used) Pressing the Calculate myPLV
Conditions button (Figure 4) • Secondly, they are used in the myPLV
• Chiller type: Water-cooled Bid Form to calculate the chiller
generates the submittal points for the
• Building peak load: 500 tons four load bins and the full load design energy use and cost for a year and a
operating conditions shown (Table 3). simple payback period for investing in
• Number of chillers: 2 more efficient chiller technology.
• Chiller size: 300-ton chillers Table 3. Submittal points generated
• Finally, they can be specified in the
load (%) tons ECWT (ºF) chiller guide specifications as the
Next, the cooling tower design data
25 75 64.3 chiller factory test points to ensure
is input (Figure 3). In this example, two
50 150 77.5 the customer receives the chiller
cooling tower cells are selected at a
performance they purchased at the
design wet bulb condition of 80ºF with 75 225 80.1
most important realistic operating
a 5ºF tower approach. 94 282 79.4
conditions.
100 300 85 (design)

4 Trane Engineers Newsletter volume 44–4 providing insights for today’s HVAC system designer
myPLV Bid Form worksheet: Alternate Figure 5. Data input for alternate chiller performance metrics

chiller performance and payback


analysis. The myPLV program
automatically copies the building and
A
plant setup and the weighted submittal
points to the myPLV Bid Form
worksheet. This worksheet allows users
to perform simple payback analysis
between chillers with varying efficiency
and price.

Figure 5 displays the user-entered chiller B


data (blue fields) used to compute the
alternate chiller comparison C
performance metrics.

To perform a chiller comparison users


gather myPLV point performance and
price information for each chiller
alternate as well as the local utility rates
for the cost of energy consumption and
demand power (e.g., cost per kWh, cost
per kW demand, ratchet rate). For this
example, the needed chiller
performance data corresponds to chiller
operating points shown in Figure 5 (A). The cost for each alternate chiller Note that electrical rates vary
combination can be entered as the actual considerably with as many different rate
An example comparison follows for five full price or the baseline chiller model structures as there are utilities. The
different compressor technology, water- cost can be set to zero, and the computations included in the myPLV
cooled chillers: difference between the baseline chiller spreadsheet attempt to capture only the
and the specific alternate combination basic calculation for a single electrical
• Fixed-speed screw compressor
entered for the other chillers. Either consumption cost per kWh and a single
(Base Scrw FS)
method results in the same values for the demand cost per peak kW.
• Variable-speed screw compressor simple payback computation.
(Scrw VS) Also note that actual building electrical
For each chiller considered, the myPLV demand is based on the building meter,
• Fixed-speed centrifugal compressor
Bid Form computes the following: not just the chiller power draw. The bid
(Cent FS)
form only computes demand cost on an
• myPLV value—a formulation based
• Variable-speed centrifugal incremental per alternate chiller basis.
on the weighted bin performance
compressor (Cent VS)
• Annual kWh energy consumption Finally, the electrical demand
• Variable-speed high efficiency
for the chillers—the sum of the bin calculations use the chiller’s design
centrifugal compressor (HiE Cent kW/ton value since it assumes they will
calculations of ton-hours multiplied by
VS)
the kW/ton performance at that bin. be running at peak conditions when peak
The following electrical cost data is demand points occur. The chiller
• Annual consumption charge—the
demand charges include the impact of
assumed; see Figure 5 (B): product of the annual kilowatt-hours
the ratchet value. The program provides
• $0.12/kWh multiplied by the dollar per kWh
a monthly Peak Loading demand data
specified by the user.
• $10/kW demand table on the myPLV Charts worksheet
• Annual demand charge—a for users who wish to better understand
• 75 percent ratchet summation for 12 months where the the value and effect of the chiller(s)
monthly demand tons which includes demand.
The performance data for the five the ratchet (from the monthly Peak
chillers is entered into the Water Cooled Loading table) is multiplied by the The Save and Send button allows the
Chiller Selection table as a base chiller chillers’ 100 percent load kW/ton and user to save and/or e-mail the myPLV Bid
followed by four optional chillers. As further multiplied by the dollar per kW Form with the job appropriate myPLV
shown in Figure 5 (C), the column labels demand specified by the user. Test and Submittal Points in a separate
can be edited to reflect each alternate. working Excel file.
• Total annual energy charge—
It’s expected that users will enter data computed as the sum of the
for the lowest cost chiller into the consumption and demand costs.
baseline column. The more expensive
• Simple payback in years—the
chillers are assumed to be more efficient
difference in cost (option x - baseline)
than the baseline and therefore may
divided by the difference in the annual
payback with a lower electrical cost.
energy charge (baseline - option x).

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 44–4 5
Figure 6. Summary trends for hours and ton-hrs as a function of outdoor conditions
myPLV Output 70000 350
The remainder of this EN explains ton-hr distribution

ton-hr by integer wet-bulb value


60000 300
some of the intracacies of the myPLV Nbr annual hr
engine to help guide users on input Nbr operating hr
50000 250

number of hours
selections. This adds transparency to
the myPLV calculations. 40000 200

30000 150
Load charts. A review of the load
charts is recommended to ensure the 20000 100
load profile looks appropriate for a
10000 50
particular application. myPLV enables
users to examine plant operation and 0 0
the weather impact via two weather 30 40 50 60 70 80 90 100
and load-related charts shown on the outdoor wet-bulb temperatures (ºF)
myPLV Charts worksheet. The first
Figure 7. Load profile's percentage of cumulative ton-hrs as a function of the outdoor temperature
chart (see Figure 6) describes the
operation of the plant as a function of 100
ton-hr probability for outdoor wet-bulb (%)

the outdoor wet bulb, if the chillers are


water-cooled, or as a function of
80
outdoor dry bulb, if the plant is air-
cooled. To build the chart, myPLV sums
the annual hours (blue line), operating 60
hours (red line), and cooling ton-hrs for
each outdoor temperature value and 40
plots the trend line (black line).

Consider the following when reviewing 20


the example chart:
0
• Does the trend for the number of
30 40 50 60 70 80 90 100
annual and operating hours look outdoor wet-bulb temperatures (ºF)
appropriate with regard to the
outdoor temperature? If the standard building profiles do not Users need to be especially mindful of
• Does the plant shut down adequately reflect local conditions, then a the operation of the building at low
(operating hours goes to zero) at a custom load profile should be temperatures when evaluating a
temperature that makes sense in considered. waterside economizing opportunity.
light of economizer operation?
The second myPLV chart (Figure 7) Also note that the PNNL load profiles
• The peak wet bulb temperature displays the load profile’s percentage of used in myPLV were developed for
varies considerably for dry climates cumulative ton-hr as a function of the ASHRAE Standard 90.1-2010. Per this
and the default selections may not outdoor temperature. One observation ASHRAE Standard, at low temperature
represent local conditions. This from the example chart is that outdoor conditions, mechanical
may only be a problem for the data approximately 12 percent of the cooling ventilation is provided to the rooms. As
near the peak wet bulb conditions. ton-hr occur below a 60ºF wet bulb and a result, there is a natural economizing
This is important to an accurate 100 percent of the ton-hr occur below effect because most of the cooling
analysis because considerations 82ºF wet bulb. load for the building is satisfied at
such as design cooling tower and these conditions. However, if the
design chiller condenser water This chart illustrates the opportunity for actual building has less outdoor air
conditions need to reflect the plant waterside economizing (free cooling). For ventilation or the ventilation is pre-
locale. example, the best opportunity for conditioned to room-neutral
waterside economizing is when outdoor conditions, then a significant chiller
• Is the peak outdoor wet bulb (in
wet-bulb conditions are approximately plant cooling load may exist that the
this case, ~82ºF) representative of
45ºF and below. However, the data on PNNL load profile incorporated in the
the locale that is being reviewed?
this graph indicates the percentage of myPLV tool does not include.
• Is an appropriate design wet bulb annualized cooling load below 45ºF is
specified for the tower selection? near zero—indicating little to no
• Is an appropriate chiller design waterside economizing benefit.
condenser water temperature
specified based on the peak wet
bulb encountered?

6 Trane Engineers Newsletter volume 44–4 providing insights for today’s HVAC system designer
Cooling tower performance and Figure 8. Tower approach assumed for full fan power
control (water-cooled plants).
Cooling tower design performance, 16
operating limits and control method are 50ºF WB
14
required inputs for myPLV to calculate
the correct 8,760 hour chiller load point 12 60ºF WB

tower approach (ºF)


Cooling tower
Entering Condenser Water 10 performance
Temperature (ECWT). With this 70ºF WB curves used for the
8
information the program can generate ecwt prediction.
6 80ºF WB The tower cell
the appropriate submittal point ECWT performance was
data. 4 specified to be a 7°F
approach at a 78ºF
2
As illustrated in the earlier example, wet bulb.
cooling tower design performance is 0
0 25 50 75 100
specified by the user by entering % plant capacity
Design Full Load Tower Wet-Bulb
Approach and the Design Outdoor
controlled to a setpoint condition. As capacity. At these steps, the amount of
Wet-Bulb Temperature (Figure 3).
long as the tower control setpoint is heat rejection to the tower cells is
Tower control is specified by selecting
causing the fan speed to operate redistributed to the additional tower
one of four control methods along with
below its maximum speed, the cooling cells and the active towers’ heat
the corresponding control setpoint and
tower provides a water temperature rejection and therefore the tower
the minimum allowed condenser water
based on the method of control. The approach drops accordingly.
temperature.
lowest ECWT is only used when the
control method causes the tower fans Also note that the tower approach
The program performs two calculations
to operate at maximum speed. increases as the ambient wet bulb
to determine the correct ECWT for
temperature decreases. This is due to
each operating hour and takes the
the reduced latent heat capacity of the
maximum temperature of the two. ECWT Example. Assume the chiller
air at lower temperatures.
plant is operating at a 50-percent load
First, myPLV determines the ECWT point and the tower control is asked to
based on tower performance at full fan supply 75-degree water (see Figure 8). Tower control methods. The
power as illustrated in Figure 8. The If the outdoor wet bulb is 50°F (purple following provides more detail for each
program computes the ECWT as a line), the tower approach would be control method within the myPLV tool.
sum of the ambient wet-bulb 10°F if the tower fans were running full Note that any of the following control
temperature plus the tower approach. speed. This results in a lowest ECWT methods may specify a low ECWT that
Since this computation reflects tower of 60ºF (50°F WB + 10°F approach). cannot be achieved by the cooling
operation at full fan power, the value tower operating at full fan power. In
computed is the lowest ECWT Since the control system calls for 75°F this case the ECWT used by myPLV for
possible. water, the tower fans are slowed (or this load point is the ECWT operating
cycled) until the operating ECWT is at full fan power (the higher value).
The second calculation is based on the 75°F. If, however, the outdoor wet bulb
user selected Cooling Tower Control temperature is 70°F (red line), then the Full tower fan flow. . This selection
Method. The four tower control tower approach is 6°F and the lowest determines the ECWT that results
selections supported are listed below leaving tower temperature at full fan from the cooling tower running at full
and discussed in the next section: flow is 76ºF (70°F WB + 6°F approach). fan speed (lowest ECWT) for each
• chiller tower optimization hour’s conditions (see Figure 8).
In the latter case, myPLV program However, if the result is a temperature
• fixed tower approach returns an operating ECWT of 76ºF, less than the minimum user-specified
• fixed temperature even though the setpoint was 75ºF. value, the temperature will be set to
the minimum value specified.
• full tower fan flow So what causes the saw tooth pattern?
In order to simplify the myPLV
Generally speaking, the operating program, the chiller and tower cell Fixed temperature. This control
ECWT provided by the tower for any sequencing is assumed to occur at the method is typical of many installations
hour may be quite different from the chiller design tonnage. Since three that run the cooling towers to a
entering condenser water temperature chillers were specified for the plant, constant temperature setpoint. This
based on full fan power, since the chillers and tower cells are turned on at selection requires a temperature
cooling tower fans are actively 33 percent and 67 percent of the plant

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 44–4 7
setpoint entry by users. This method of control method creates a minimum The chart is broken up into four bins
control was described in the previous condenser water temperature at all with three dashed vertical lines as
ECWT example. wet-bulb temperatures. Depending on separators. The first vertical line is
the user-specified fixed setpoint, the positioned midway between the 25
Fixed tower approach. This selection submittal point ECWTs may be higher and 50 percent bin points at a 37.5
computes an ECWT equal to the than the other control methods (high percent chiller load (281 tons). The
outdoor wet-bulb temperature value fixed setpoint) or close to the Full second is positioned midway between
plus the tower approach setpoint Tower Fan Flow ECWT (low fixed the 50 and 75 percent bin points at
entered by the user. If this method setpoint). In any case, this minimum is 62.5 percent (469 tons). Finally, the
results in a temperature value less than reflected in the weighted condenser third vertical dashed line is positioned
the minimum user-specified value, the water temperatures for the four binned 12.5 percent to the right of the 75
temperature will be set to the performance points. percent bin point at 87.5 percent (656
minimum value specified. tons).
Chiller Loading Chart. The scatter
For this example, a 55ºF minimum
Chiller-tower optimization. . This plot on the myPLV Charts worksheet
condenser water temperature was
selection simulates a Trane algorithm detailing the myPLV/IPLV entering
specified and therefore, the minimum
for a dynamic and optimally changing condenser water temperatures for the
condenser water temperature for all
ECWT setpoint as a function of chiller chillers deserves some explanation.
the load points was at 55ºF.
loading and ambient wet-bulb Figure 9 shows the chart for a three-
temperature. As with other control chiller plant with the chillers sized at The myPLV and IPLV rating points are
methods, if this method results in a 750 tons. also illustrated on the plot—the blue
temperature value less than the circles and the red open circles
The plot shows the load and ECWT for
minimum condenser water respectively. The blue myPLV circles
each hour of chiller operation. The
temperature specified, the minimum represent the load in tons at the 25, 50,
small blue data points detail those
temperature setpoint value will be 75 and 94 percent load points, and the
conditions where only one chiller is
used. corresponding myPLV submittal point
operating. The maroon points detail the
condenser water temperatures.
The tower control strategies for Chiller operating conditions when two chillers
Tower Optimization, Full Tower Fan are operating, and the green data Note that the myPLV point ECWT are a
Flow, and Fixed Tower Approach will points show where all three chillers are ton-hr weighted temperature of all the
yield similar looking results for running. load points in each bin. The open red
submittal point ECWTs since each of IPLV circles are shown for comparison
In other words, the first chiller runs at
those control methods’ resulting and represent the condenser water
all conditions detailed by the blue,
condenser water temperatures will be temperature for the IPLV rating points.
maroon, and green data points. The
moving with the outdoor wet bulb. The This allows users to determine if there
second chiller runs at the conditions
main difference is how the particular are significant differences between
detailed by the maroon and green data
control mode affects tower fan power IPLV ECWT and actual ECWT.
points. Finally the third chiller only runs
which is not part of the myPLV
at the conditions shown with green
analysis.
data points.
However, the Fixed Temperature
selection can dramatically change the
chiller selection points since this
Figure 9. myPLV/IPLV entering condenser water temperatures for the chiller

Example office building


with economizer and
Note: The chiller-tower optimization three 750-ton chillers
control strategy calculation and, in
some cases, the fixed-tower approach
setpoint may assume the chiller can run
reliably at a condenser water
temperature that is slightly above the
design point. This is typically a good
optimization assumption and may work
well to reduce overall system energy.
However, users should review the
scatter plot of the computed ECWT to
decide if the tower control method or
chiller design point should be modified.

8 Trane Engineers Newsletter volume 44–4 providing insights for today’s HVAC system designer
Air-cooled vs water-cooled. The
myPLV computations become simpler Summary References
when an air-cooled device is [1] ASHRAE/IES 90.1-2010 Energy Standard for
considered. For the case of air-cooled myPLV is based on bin methodology Buildings Except Low-Rise Residential
chillers, the entering condenser that leverages the PNNL Energy Plus Buildings.

temperature comes directly from the modeling results to create an easy-to-


[2] EnergyPlus files developed by Pacific
outdoor dry-bulb temperature in the use methodology to guide chiller
Northwest National Labs (PNNL) The web site
weather data.Therefore, the bin selection based on specific user for the PNNL files can be found at http://
analysis used to compute a weighted conditions. www.energycodes.gov/development/
commercial/90.1_models.
condenser condition is processed
The accuracy for the condenser
directly on the outdoor dry-bulb value,
conditions is achieved by adjusting
in contrast to evaluating a cooling
ECWT for load, outdoor air wet bulb,
tower control method for a water-
and tower control and by the use of
cooled chiller.
ton-hr weighting for the myPLV
submittal points.

These submittal points enable users to


gather actual certified performance
data from chiller manufacturers at
meaningful weighted conditions and
then convert them to energy usage and
cost.

The result is a simple, accurate and


transparent chiller analysis tool that can
be used to analyze any chiller’s
performance to make a more informed
choice for the chiller equipment.

If a complete plant energy analysis is


necessary, a full energy model using a
tool such as TRACE® Chiller Plant
Analyzer should be used for analysis.

Visit www.trane.com/myPLV to
download the latest version of
myPLV™

By Brian Sullivan, systems engineer, and Jeanne


Harshaw, program manager, Trane. You can find
this and previous issues of the Engineers
Newsletter at www.trane.com/engineersnewsletter.
To comment, send e-mail to ENL@trane.com.

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 44–4 9
www.Trane.com/bookstore
Learn HVAC design strategies and earn credit

On-demand continuing education credit Application manuals. Comprehensive


for LEED® and AIA. 90-minute on-demand reference guides that can increase your
programs that are available free of charge. working knowledge of commercial HVAC
New courses include: systems. Topics range from component
combinations and innovative design concepts
• Variable-speed Compressors on Chillers,
to system control strategies, industry issues,
• Coil Selection and Optimization, and and fundamentals. The following are just a
• Evaluating Sound Data. few examples:
• Central Geothermal Systems discusses
All courses are available at proper design and control of central
www.trane.com/continuingeducation. geothermal bidirectional cascade systems
that use borefields. This manual covers
Engineers Newsletters. Quarterly articles central geothermal system piping, system
that cover timely topics related to the design,
design considerations, and airside
application and/or operation of commercial
considerations.
HVAC systems. Subscribe at www.trane.com/
EN. (SYS-APM009-EN, February 2011)

• Chilled-Water VAV Systems


Air conditioning clinics. A series of discusses the advantages and
educational presentations that teach HVAC drawbacks of the system, reviews
fundamentals, equipment, and systems. The the various components that make
series includes full-color student workbooks,
up the system, proposes solutions to
which can be purchased individually. Approved
common design challenges, explores
by the American Institute of Architects for 1.5
(Health, Safety and Welfare) learning units. several system variations, and
Contact your local Trane office to sign up for discusses system-level control.
training in your area. (SYS-APM008-EN, updated May
2012)
Engineers Newsletter Live. A series of 90- • Water-Source and Ground-Source
minute programs that provide technical and Heat Pump Systems examines
educational information on specific aspects of chilled-water-system components,
HVAC design and control. Topics range from configurations, options, and control
water- and airside system strategies to strategies. The goal is to provide
ASHRAE standards and industry codes. system designers with options they
Contact your local Trane office for a schedule can use to satisfy the building
or view past programs by visiting owners’ desires. (SYS-APM010-EN,
www.trane.com/ENL. updated November 2013)

Visit www.trane.com/bookstore for a


complete list of manuals available to
order.

10 Trane Engineers Newsletter volume 44–4 providing insights for today’s HVAC system designer
www.Trane.com/ENL
Mark your calendars 2016 for Engineers Newsletter LIVE!

plan to attend...
2016 Engineers Newsletter Live! system design and operation

If you need
Delivering Performance from Airside
a lot of HVAC insight
Economizers
but have limited time...
New Fan Efficiency Regulations and
Fan Technology Advances RSVP
control strategies

DIY Chiller Plant Performance Modeling:


Easy and Easier

Acoustics in Outdoor Applications

trends and advancements


Contact your local Trane office for event details and
registration or visit trane.com/ENL.

standards and codes

providing insights for today’s HVAC system designer Trane Engineers Newsletter volume 44–4 11
Visit www.Trane.com/TRACE to download your 30-day trial
TRACE™700 v6.3.2 Now Available

The latest version of TRACE 700,


version 6.3.2, allows designers and
engineers to run cooling plants much
closer to optimal behavior with
optimal sequencing type. In addition
we've partnered with Hewlett-Packard
to add sophisticated evaporative
cooling features and improve reports
and expanded energy recovery
options to support growing trends in
data center system design.

ASHRAE Standard 170 ventilation


calculations have been added to offer
direct support when designing for
health care facilities. Choose
ventilation requirements for Standard
170, 62.1 or a combination of both.

Visit www.Trane.com/TRACE to view


version details or download a free 30-
day trial. While you’re there read about
the winning teamwork of Trane C.D.S.
group and industry leaders at the
ASHRAE Energy Modeling Conference
LowDown Show Down.

Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and
A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
office or e-mail us at comfort@trane.com

12 Trane Engineers Newsletter volume 44–4 ADM-APN056-EN (December 2015)

You might also like