You are on page 1of 23

WP-YDS031-037dW

ENGLISH

INSTALLATION MANUAL
DIGITAL SCROLL SERIES
AIR-CONDITIONER FOUR-WAY CASSETTE

Models:
YDCL-56C(A/B)15A
YDCL-71C(A/B)15A
YDCL-80C(A/B)15A
YDCL-90C(A/B)15A
YDCL-112C(A/B)15A

For correct installation, read this manual before starting installation.


Only trained and qualified service personnel should install, repair or service air conditioning equipment. Users
should not install the air conditioner by themselves.
All pictures are only sketches. If there is any difference between pictures in this manual and the actual shape
of the air conditioner you purchased, the actual shape shall prevail.
CONTENTS

PRECAUTION ........................................................................................................... 4
ACCESSORIES ......................................................................................................... 4
SAFETY PRECAUTION ............................................................................................. 5
INSTALLATION LOCATION ....................................................................................... 6
INDOOR UNIT INSTALLATION ................................................................................. 7
DRAINPIPE INSTALLATION ..................................................................................... 9
REFRIGERANT PIPE INSTALLATION ....................................................................... 12
INSTALLATION OF FLANGE ..................................................................................... 14
INSTALL ELECTRIC THROTTLE PART...................................................................... 16
ELECTRIC WIRING ................................................................................................... 17
CONTROL ................................................................................................................. 20
NETWORK ADDRESS SETTING .............................................................................. 21
TROUBLE SHOOTING .............................................................................................. 22
TEST OPERATION .................................................................................................... 23
PRECAUTION
• This manual is suitable for indoor unit.
• Refer to outdoor unit installation manual to install outdoor unit.
• The indoor unit and the outdoor unit should not share one power supply.

ACCESSORIES

Name Quantity Outline Function

2
part.

pattern 1

4 M5X16
pattern

aterial 1
part.

Gasket 8 .

1 .

4
SAFETY PRECAUTION
• Read the following "SAFETY PRECAUTION" carefully before installation.
• The caution items stated here must be followed because these important contents are related to safety. The meaning
of each indication used is as below.
Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified
by the following indications.

WARNING This indication shows the possibility of causing death or serious injury.

CAUTION This indication shows the possibility of causing injury or damage to properties only.

NOTE:
1. Injury means causing harmed, burned, electrical shocked, but not serious for hospitalization.
2. Damage of property means disrepair of property, material.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation,
care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future
reference.

WARNING

• Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage,
electrical shock or fire.

• Install according to this installation instructions strictly. If installation is defective, it willcause water leakage, electrical
shock or fire.

• Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water
leakage, fire or electrical shock.

• Install at a strong and firm location which is able to withstand the set's weight. If the strength is not enough or
installation is not properly done, the set will drop and cause injury.

• For electrical work, follow the local national wiring standard, regulation and this installation instructions. An
independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in
electrical work, it will cause electrical shock or fire.

• When carrying out piping connection, take care not to let air or other substances other than the specified refrigerant
go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle,
explosion and injury.

• Grounding is necessary. It may cause electrical shock if grounding is not perfect.

• Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.

5
INSTALLATION LOCATION

CAUTIONS
1.Location in the following places may cause malfunction of the machine. (If unavoidable, please consult your local dealer)
a. A place where there is inflammable gas leakage.
b. There is salty air surrounding(near the coast).
c. There is caustic gas(the sulfide, for example) existing in the air (near a hot spring).
d. A place where can not bear the weight of the machine.
e. In kitchen where it is full of oil gas.
f. There is strong electromagnetic wave existing.
g. There is acid or alkaline liquid evaporating.
h. A place where air circulation is not enough.
2. Electrical Insulation must be done on the air conditioner and the building complying to National Regulations

INSTALLATION SPACE
A

Above Above
Ceiling H 100cm 100cm
(Electronic throttle device, for
unit with R22, R407C or R410A only Obstacle

Size
Model
(W)
28~80 2800~8000
90~112 9000~11200

Wall
material Flammable Fire-proof
material structure
B

metal
C Up(B)
Sides(C)

HEIGHT BETWEEN CEILING AND FLOOR

2800-3600W 4500-8000W 9000-11200W

2.7m<H<3m
2.7m<H<3m
3m<H<3.5m

6
INDOOR UNIT INSTALLATION

785(Hook-location)

CAUTION A

Please select a place where sound enough


to bear the indoor unit when installation
The Indoor Unit is possible to fall if the place
is not sound enough.

375
To take precautions against typhoon/earth
quake.
Be sure to install strictly according to related 778(Hook-location)
(Electronic throttle device, for
specification. Wrong installation will cause unit with R22, R407C or R410A only
the unit to fall.
940(Panel)

185 (Electronic throttle device, for


170
80 unit with R22, R407C or R410A only
106 300 100

( D)
E)
106

C
240

30
A

30
1 38

186
166
128

73

38)
39
20

Panel
Hole
32)

130
Hole
Model (W) A B C D E 32 18
( 100)
28~80 2800~8000 196 230 130 9.5 19.0 16.0
1 30
2 00

90~112 9000~11200 246 310 180 9.5 19.0 16.0


R22/R407C R410A

Select installation location considering piping and wiring connection after the Indoor Unit has been hanged. Then decide
the piping wiring leading direction.
• Be sure to lead the refrigerant pipes, drain pipes and connection wires out to its connection location before hanging
the unit if the opening on the ceiling has been decided.
• Confirm sizes of the indoor unit and ceiling opening with the attached installation paper pattern. (Please fix the paper
pattern below the body with M5X16 screws (4)).

7
CEILING HOLE AND THE HOOK INSTALLATION

Preparation Work on the Ceiling

• Installation method should be changed under the different construction structure. Please consult the professional for
the detailed information.
• After opening a hole, the ceiling should be horizontal and strong to prevent vibration.
1- Cut the beams at the hole and remove them.
2- Reinforcing the beams that have been cut and the beams fixing the ceiling.

Installation of the hanging screw bolt


Bolt with M10 whorl is to be used. The center distance between the bolts is decided by the size of the unit . Use the
following method to install:

Wooden construction New Concrete Bricks

Put the square timber over the roof beam, then install the Inlaying or embedding the screw bolts.
hanging screw bolts.

insertion)

Ceiling

Hanging Screw Bolt

For finished concrete bricks Steel roof beam structure

Install the hanging hook with expansible bolt into the Install the supporting angl steel.
concrete deep to 45~50mm to prevent loose.

Supporting
angle steel

Overhanging the indoor unit

Adjust the gasket (down side) to 138mm over the ceiling.


138mm

8
• Install the hanging bolt into T groove of the hanging tool. Overhang the indoor unit and ensure it is level using a level
indicator.

43mm
1
Ceiling 2 30mm
10 Gasket

installing-ear

PANEL INSTALLATION (SOLD SEPARATELY)

• Panel installation should be done after piping and wiring.


• Refer to panel installation manual for detailed information about installing the panel.
• Be sure that the indoor unit and ceiling hole installation size is right before installation.

CAUTION
Be sure to seal the connection parts between the panel - the ceiling and the panel - the indoor unit ,or even
small gaps may cause wind/water leakage or condensing water.

DRAINPIPE INSTALLATION

CAUTION
Be sure to follow this Installation Manual during drainage installation, the drainpipe must have the
heat insulation to prevent condensing.

• The drain pipe of indoor unit must have the heat insulation , or it will condense dew, as well as the connections of the
indoor unit.
• The declivity of the drain pipe downwards should not be over 1/100, and no winding and bending.
• The total length of the drain pipe when pulled out traversely shall not exceed 20m , when the pipe is over long, a prop
stand must be installed every 1.5 to 2m to prevent winding.
• Refer to the following figures about the installation of the pipes.
• Do not impose any pressure on the connection part of the drainage pipe.

9
1.5m~2m
Support Bend

Fold

VP30

DRAINAGE PIPE MATERIAL, HEAT-INSULATING MATERIAL

The listed material should be used:

Drainage Pipe
Material Polyvinyl chloride pipe ( 32mm outer diameter)

Heat Insulation
Foamed polyethylene insulation plate (10mm thickness)
Material

FLEXIBLE HOSE

Measure diameter of the hard pipe using cutting method, and adjust the joining angle.
• Pull out the flexible hose, do not over deform than illustrated below.
• Be sure to bind it with the attached band.
• Please place the flexible hose horizontally.
20

Core shift adjustment

Hose band

Bend 45ºC(Maximum) Flexible Hose

Indoor Unit
45 o

CONNECTION PROCEDURE

Connect the transparent pipe with the polyvinyl chloride pipe.


• Use polyvinyl chloride glue at the connection part of the drainage pipe, be sure no water leakage.
• Paste glue at the front 40mm of the polyvinyl chloride pipe, insert it into the transparent pipe.
• It needs 10 minutes for the glue to dry. Do not impose pressure on the connection during the drying period.

10
HEAT INSULATION

Wrap the flexible hose carefully with the attached heat insulation material from the start to the end (to indoor part)

Flexible Hose Hose band

Attached Heat-insulation Field-arranged Heat- Polyvinyl Chloride Pipe


Material insulation Material

DRAINAGE UPWARD

To make sure that the drainage pipe would not slant downward, lead
it upward to a height 360mm maximum, then downward lead it.

60mm
Belo

00mm
Belo
Below
100mm

Indoo nit

Ceiling

DRAINAGE TEST

Check whether the drain pipe is unhindered before testing.


1) Stow water from sprue to check.
2) Stow 600cc water with pot or hose from sprue slowly , preventing touching the drain pump motor.
3) After the preparation work , disconnect the water level switch ,power 220-240VAC to L - N of terminal board, and
the drain pump start up immediately.
4) After drain pump run 2 min.,reset the water level pin, and the drain pump motor will stop after running 1 min..

Sprue

MOTOR SOUND TEST

The drainage test is doing during checking the drain pump motor running sound.
Reset the water level switch connection to the original position after the drainage test.

11
REFRIGERANT PIPE INSTALLATION

CAUTION
Ventilate the air if there was any refrigerant leakage during the installation.
Leaked refrigerant will generate poisonous gas if meeting fire.

Make sure there is no refrigerant leakage after the installation.


Leaked refrigerant will generate poisonous gas if meeting fire.

ALLOWED LENGTH AND DROP OF PIPES

Requirements are different when installing the outdoor unit, please refer to outdoor unit installation manual for detailed
information.

MATERIAL AND SIZE OF THE PIPES

Three length (3m,5m,10m) of pipes are available to purchase.

Refrigerant R22/R407C R410A


19.0 16.0
Size(mm)
9.53 9.53

REFRIGERANT VOLUME TO BE ADDED

Refrigerant volume to be added is calculated according to outdoor unit installation manual (R407C). Be sure to add
refrigerant measuring by a scale.

CAUTION
• If the added refrigerant volume is inadequate (too much or insufficient), the compressor malfunction will be
caused. Be sure to calculate the refrigerant volume carefully.
• The service man should write down the piping length and the added refrigerant volume in the nameplate, which
is on the electric control box cover of outdoor unit, for diagnosing the compressor and refrigeration circulation
malfunction.

CONNECTION OF THE REFRIGERANT PIPE

• Two wrenches should be used when connecting the pipes.


• The tightening torque is shown below:

9.53 24.5(2.5kgf.m) 29.4(3.0kgf.m)


19.0 98.8(10.0kgf.m) 117.7(12.0kgf.m)

12
AIR PURGING

Use a vacuum pump, to vacuum from the gas side refrigerant adding mouth of the outdoor unit.
• Don't use the refrigerant of the outdoor unit to do the vacuum. (A certain volume of refrigerant had been added into the
outdoor unit in factory.)

OPEN/CLOSE THE VALVES

Open/Close the spools or the valves of outdoor unit with a Ø 5mm hexagon spanner.

LEAKAGE TEST

Test if there is any leakage on the connections of the piping with soap water.

HEAT INSULATION

Heat insulation for the gas and liquid pipe separately.


Heat insulation should be fully and carefully done, because the liquid side pipe and gas side pipe are easy to condense
water due to low temperature when cooling.
• Heat proof above 120 C material should be used at the gas side pipe.
• The indoor unit connection parts should be no-gap heat-insulated with the attached heat insulation materials.

Wrap to the foot of the piping

Field Piping side


Unit Body
Attached Heat Insulation Material

13
INSTALLATION OF FLANGE

Fresh air is intaken by indoor fan motors or ducted fan motor devices on field. The positions of fresh air intakecan be
changed according to the installation of ductable fan motor.

96 4- Ø 6 Hole
57 80

Ø75

80

96
Note:
1. The device can be installed in ceiling cassette type indoor units (several-direction flow).
2. When installing the device, duct is needed on field and the rated diameter is 75mm.

When metal duct pass through wooden wall, electric insulation must be add between duct and wall.
The duct must be pulled out downside to prevent rain and water entering.
Net cover must be set at places where duct explodes to outdoor air to prevent birds and animals entering.

1. Removal the hole on the board.


The hole is oppose to drainage pipe
Drainage pipe
Figure 1

Refrigerant Pipe

Hole

Insulation Material(Inside)
Board

No insulation material inside,


Removal with Pincher only removal board
Removal with Pincher
or Incisel with knife
Removal with Pincher

Commissure

Insulation Material(Inside) Commissure


Board

Board

14
Stick insulation material 4 at indoor hole

Installation Type 1 Installation Type 2


Put the insulation material 4 on the Stick insulation material
interface of the hole as shown in at the opening part of the
Figure 4, then stick on the inside and board
surface of the board. The interface of
the hole can not have gap.
Board
Insulation Material
(Inside) Board
Figure 2
Edge

Insulation Material

About 10 mm
Insulation Material

Ensure the interface of insulation material 4 closely contacts with


the inside insulation material and the board.

Use screw 2 (M4X12, 4 Pieces) to install flange at the hole, and then stick insulation material 3.

Flange 1
Flange 1

Screw 2

Insulation Material 3 (M4 x 12,4 pieces)


Insulation Material 3

Screw 2
(M4 x 12,4 pieces)

Figure 3

Install duct (the rated diameter: Ø 75)


1. Connect the duct to the flange. (The flange is assembled with the interface of duct).
2. After connection, use the ethylene tape (provided on field) to wrap the joint to prevent air-leakage.

Flange Wrap the joint to prevent air-leakage

Ø 75 Duct (on field)

Airproof adhesive tape

NOTE:
1. All ducts must be completely heat-insulated.
2. The following phenomenon are not allowed when installing duct:
A) Bend too much B) Too many bender C) Diameter reduce

Wrong Wrong Wrong

15
ELECTRIC WIRING

! WARNING

Specified power cables should be used. Do not apply any pressure on the terminals used to
connect.
Improper connection may cause fire.

Grounding must be properly done.


The grounding wire should be away from gas pipes, water pipes, telephone, lightening rods or other
grounding wires. Improper grounding may cause electric shock.

Electric Wiring must be done by professionals. Use a separate circuit according to national regulations.
If the wiring capacity is not enough, electric shock or fire may occur.

CAUTION
Be sure to Install Current Leakage Protection Switch, Or electric shock may occur.

CAUTION
• Power cord is to be selected according to national regulations.
• Outdoor unit power cord should be selected and connected according to the outdoor unit installation manual.
• Wiring should be away from high temperature components, or the insulation layer of the wires may melt down.
• Use wire clamp to fix the wires and terminal block after connection.
• Control wire should be wrapped together with heat insulated refrigerant pipes.
• Connect the indoor unit to power only after the refrigerant has been vacuumed.
• Don't connect the power wire to the signal wire connection end.

The Specification of Power

TYPE 28~112
ACITY(W) 2800~11200
PHASE 1-PHASE
POWER
FREQUENCY T
CIRCUIT BREAKER/FUSE (A) 5/3
2
(mm ) 2.0
2
INDOOR/OUTDOOR (mm ) 2.0
CONNECTING
2
WIRING (mm ) SIGNAL
1.0

17
Indoor unit power supply and the signal wire wiring

• The indoor unit power source should not be shared with outdoor unit.
• The indoor units that connect to the same outdoor unit should use the same power source, creepage protector and
main switch.
• The indoor power wire should be connected to the L, N terminal , and the indoor/outdoor signal wire should adopt the
2-core screened wire . The indoor /outdoor signal wire should be connected to A, B terminal and should be corresponding
with the A, B of the outdoor terminal. Connect the screened layer to (E).

Outdoo nit

Outdoor Power
Supply Creepag rotection Groun ire Wir istributio ox
Switch

Groun ire

Indoor/Outdoor
Signa ire
(2-cor creene ire)
Indoo nit
Indoo ower
Supply Creepage Protection
Switch

Indoo nit
Connec los nd
o h creene ire

Caution:
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed
wiring according to the National Wiring Regulation.

Wiring Chart

Power 220-240V 50Hz

INDOOR UNIT

CENTRAL CONTROL
MONITOR(CCM)
COMPUTER

INDOOR UNIT
OUTDOOR UNIT

INDOOR UNIT

the shielded twisted-pair wire

Caution:
The reserved function is indicated in broken line table,users can select it when necessary.

18
Indoor/Outdoor Unit Signal Wire

Connect the wire according to their numbers.


Wrong connection may cause malfunction .

Wiring Connection

Seal the wiring connection with the insulation material , or the condensing dew will be caused.

Panel Wiring

Connect the Swing Motor terminal block according to the Panel Installation Manual.

Terminal Board Diagram

Please refer to the indoor unit wiring diagram for the wiring.
Note: The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and
set system address and network address of indoor units.

Single phase indoor unit

P Q (E) X Y (E)

TO INDOOR POWER
220-240V 50/60Hz TO OUTDOOR To Central Control Monitor
COMM. BUS (CCM)COMM. BUS
To wire controller
Please adopt the shielded twisted-pair wire, The reserved wire control function is indicated
and connect the shielded layer to (E) in broken line table,users can purchase
the wire controller when necessary

19
CONTROL

Please number the indoor units during the installation . For example, for the first outdoor unit ,the number of the first
indoor unit is 1-1, the second indoor unit is 1-2, and the set address is 1 and 2 respectively , the others is analogical.

POWER_S 16-31 NUM_S


F 012 F 012

BC E

BC E
3456

3456
D

D
789A 789A

0-15
ENC1 ENC2

16-31 NUM_S 16-31 NUM_S

F 012 F 012
BC E

BC E
3456

3456
D

D
789A 789A

0-15 0-15
ENC2 ENC2

Model 1 show the address '0-F' respectively, Model 2 show the address '0-F' respectively,
that is, '0-15' indoor unit that is, '16-31' indoor unit

CAUTION
1.The system together have 32units(0-31),everyone has only system addresscode,
If two addresses are the same in one system , the abnormal operation will occur.
2.Please switch off the power before setting,otherwise the unexpected error will occur.

ENC2 TOGGLE SWITCH FOR SETTING ADDRESS


'0-F' show the address '0-F' respectively, that is, '0-15' indoor unit (together 16 units), and the others follow the
analogy. If two addresses are the same in one system , the abnormal operation will occur.

TOGGLE SWITCH For set horsepower

Note: The horsepower has Code Capacity (Horsepower)


been set before leaving the 0 2200W (0.8HP)
factory, anyone can't modify it
except the maintenance
1 2800W (1.0HP)
person. 2 3600W (1.2HP)
3 4500W (1.5HP)
4 5600W (2.0HP)
5 7100W (2.5HP)
6 8000W (3.0HP)
7 9000W (3.2HP)
8 11200W (4.0HP)

20
NETWORK ADDRESS SETTING

Every air-conditioner in network has only one network address to distinguish each other. Address code of air-conditioner
in LAN is set by code switch on Network Interface Module (NIM), and the set range is 0-63.

Toggle switch set


Network address code
S1 S2
012 012
F F

3456
3456

DE
DE
00~15

BC
BC
1 2 78 78
9A 9A

012 012
F F

3456
3456

DE
DE

16~31

BC
BC

1 2
78 78
9A 9A

012 012
F F

3456
3456

DE
DE

32~47

BC
BC

78 78
1 2 9A 9A

012 012
F F

3456
3456

DE 48-63
DE

1 2

~ BC
BC

78 78
9A 9A

21
TROUBLE SHOOTING

Nº Type Contents LED Lamp flash Remarks

The evaporator sensor


check point is abnomal, After the malfunctions
1 Malfunction Run lamp flashes disappear, it restores
or room temp.sensor is at 2.5Hz.
abnormal. automatically.

Indoor/outdoor unit The timer lamp After the malfunctions


2 Malfunction communication is abnormal. flashes at 2.5Hz. disappear, it restores
automatically. T
Condenser sensor check After the malfunctions
3 Malfunction point is abnormal or outdoor All the indoor alarm disappear, it restores
temp. sensor is abnormal. lamps flash at 0.5Hz. automatically.

If the malfunctions can t be


solved in three min. all the
4 Malfunction Water level switch Alarm lamp flashes indoor alarm lamps flash at
is abnormal. at 2.5Hz. 0.5Hz. Turn off the power to
restore.

When the indoor unit turns to


Defrost lamp flashes heating mode or is turned off,
5 Alarm Mode conflict. at 2.5Hz. the alarm will disappear.

22
TEST OPERATION

1. The test operation must be carried out after the entire installation has been completed.
2. Please confirm the following points before the test operation:
• The indoor unit and outdoor unit are installed properly.
• Tubing and wiring are correctly completed.
• The refrigerant pipe system is leakage-checked.
• The drainage is unimpeded.
• The heating insulation works well.
• The ground wiring is connected correctly.
• The length of the tubing and the added stow capacity of the refrigerant have been recorded.
• The power voltage fits the rated voltage of the air conditioner.
• There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units.
• The gas-side and liquid-side stop valves are opened.
• The air conditioner is pre-heated by turning on the power.
3. According to the user s requirement, install the remote controller frame where the remote controller s signal can reach
the indoor unit smoothly.
4. Test operation
Set the air conditioner under the mode of "COOLING" with the remote controller, and check the following points per the
"Owner's Manual" If there is any malfunction, please resolve it through chapter "Trouble shooting".

1) The indoor unit


a. Whether the switch on the remote controller works well.
b. Whether the buttons on the remote controller works well.
c. Whether the air flow louver moves normally.
d. Whether the room temperature is adjusted well.
e. Whether the indicator lights normally.
f. Whether the temporary buttons works well.
g. Whether the drainage is normal.
h. Whether there is vibration or abnormal noise during operation.
I. Whether the air conditioner heats well in the case of the HEATING/COOLING type.
2) The outdoor unit
a. Whether there is vibration or abnormal noise during operation.
b. Whether the generated wind, noise, or condensed water by the air conditioner have influenced your neighborhood.
c. Whether any of the refrigerant is leaked.

CAUTION
Protection function will delay the startup of compressor for 3 minutes in case the unit is turned on immediately after power
on or restarted after shutdown.

23
DE - COMMISSIONING DISMANTLING & DISPOSAL
This product contains refrigerant under pressure, rotating parts, and electrical connections which
may be a danger and cause injury!
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.

Read the Manual Risk of electric shock Unit is remotely controlled


and may start without warning
1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas
isolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For points of connection refer
to unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be
re-used, if appropriate, or returned to the manufacturer for disposal.Under No circumstances should refrigerant be vented to atmosphere. Where
appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governing
disposal of oily wastes.
3. Packaged unit can generally be removed in one piece after disconnection as above. Any fixing down bolts should be removed and then unit lifted from
position using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit
weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.

WP-YDS031-037-dW

ENGLISH