Macunte, Junaiden E.

Brion , Ronald P.
Agan, Sean Patrick B. COMPONENTS
Inside a switchboard there will be one or
ELECTRICAL SWITCHBOARD more busbars. These are flat strips of copper
or aluminum, to which the switchgear is
An electrical switchboard is a device that connected. Busbars carry
directs electricity from one or more sources large currents through the switchboard, and
of supply to several smaller regions of are supported by insulators. Bare busbars are
usage. It is an assembly of one or more common, but many types are now
panels, each of which contains switches that manufactured with an insulating cover on
allow electricity to be redirected.. the bars, leaving only connection points
exposed.
The Philippine Electrical Code (PEC) define
switchboard as “a large single panel, frame, The operator is protected
or assembly of panels on which are mounted from electrocution by safety switches
on the face, back, or both, switches, and fuses.
overcurrent and other protective devices,
buses, and usually instruments”.
ENCLOSURE
Modern industrial switchboards are metal
enclosed and of "dead front" construction;
no energized parts are accessible when the
covers and panels are closed. Previously,
open switchboards were made with switches
and other devices were mounted on panels
made of slate, granite, or ebony asbestos
board. The metal enclosure of the
switchboard is bonded to earth ground for
protection of personnel. Large switchboards
may be free-standing floor-mounted
enclosures with provision for incoming
connections at either the top or bottom of the
enclosure.
Sub distribution and the final distribution
The Role of an Electric Switchboard in Power switchboards are, by and large, distributed
Flow all throughout the site.
Electrical power systems work as power is
sent from the utility provider which then in
line moves through an electric switchboard. Conventional distribution switchboards
That switchboards then relays the electricity
throughout a number of circuits. The power Fuse gear, switchgear, and many more are,
is then moved to feeders and then distributed on the whole, situated on the chassis at the
to locations throughout the reach of the rear of the enclosed space. Control devices
power grid. and indications (pushbuttons, lamps, meters,
and so on) are built up on the frontal face of
The main purpose of the board is to control the switchboard.
the flow of power. It divides the main
current supplied to it into several smaller Numerous Benefits
chunks and distributes it to the devices.
The usage of functional distribution
Types of Electric switchboards switchboards has extended to all the levels
of LV electrical distribution, from the main
There are several types of LV switchboard or MLVS to final
electric switchboards based on current distribution switchboards, providing various
rating, construction type, interrupt rating, benefits:
operating type, voltage type, insulation
medium, and others. Inner part of the board  Distribution of electrical
contains several busbars, strips of aluminum switchboard design is fast because it
and copper to which switches are connected. simply involves adding functional
modules
Kinds of distribution switchboards  Manufactured components can be
built up faster
Distribution of the Electrical
Switchboards for particular applications (for The electrical switchboards are very
example: industrial procedures, heating beneficial when properly used.
lifts,) can be situated:

 Next to the main LV switchboard


 Near where the application is
concerned
SWITCHBOARD INSTALLATION & should be carefully checked against the
OPERATION GENERAL diagrams to insure that all connections are
correct and proper.
1. SHIPMENT
DIELECTRIC TEST
The switchboard is assembled, wired,
adjusted, and given complete tests at the The following dielectric test shall be made
factory, to determine the adequacy of insulation.
after which it is inspected and packed for
shipment. GROUNDING

STORAGE BEFORE INSTALLATION Each switchboard assembly may be


provided with a ground bus extending the
Switchboard equipment, should be kept in a full length
dry, clean place. Conditions such as of the complete assembly. The ground bus
dampness caused by rain or change in should be connected to the station ground
temperature, cement dust, etc., should be with as direct a connection
carefully guarded against. Covering the as possible and should not be run in metal
equipment with a temporary shelter or conduit. The grounding conductor should be
tarpaulin capable of carrying the maximum line-to-
is frequently necessary both during storage ground current for the duration of the fault.
and installation.
GROUND FAULT PROTECTION
2. INSTALLATION
Grounded systems where the voltage
Equal care in installation should be used. exceeds 150V to ground and has a capacity
of
SUPPLEMENT 1000 A or more shall have ground fault
Switchboards, which are generally rated relay protection in accordance with the
2500A or less, 36 to 48 inch deep, and do Philippine
not Electric Code.
contain breakers of the drawout design, do
not require imbedded channels . If installed
on a firm level foundation the switchboards
can be mounted and bolted directly to the
concrete.
WIRING
All incoming and outgoing control
connections should be made in accordance
with the
switchboard schematic and wiring diagrams. GUIDE TO SWITCHBOARD
After wiring is completed, all connections MAINTENANCE
MAINTENANCE BENEFITS AND 1. Spare parts for at least those parts of the
FACILITIES switchboard that are vital to operation.

Maintenance Records 2. A well-equipped shop with the following:


A maintenance file should be established
which should include the following: a) A test cabinet or inspection rack for
power circuit breakers;
1. A record of all installed switchboards and b) A source of control power for checking
their maintenance schedule; the operation of electrically-operated
2. Nameplate data of all the equipment and breakers;
its major components, instruction books, c) A selection of test instruments –
renewal parts lists, bulletins and drawings; multimeters, clamp-on ammeters, instrument
3. A list of all items which have to be transformers;
inspected and what adjustments are to be d) Lifting means for handling large breakers;
checked; e) An insulation resistance tester (Megger™
4. A record of past inspections and test or equivalent).
results. Safety Considerations
Only authorized and properly trained
Maintenance Tests
personnel should be permitted to operate or
Maintenance tests are applicable as handle
indicated: any part of the switchboard. Maintenance
employees must follow all recognized safety
1. Insulation resistance tests of the practices. Keep in mind that power circuit
switchboards’ breakers and bus can be breakers are also capable of storing
useful in mechanical energy in the form of contact
determining the condition of the insulation if closing springs. Make sure breakers are
they are performed regularly. open and springs are
properly discharged and/or blocked before
2. High potential tests are not required and working on the mechanism. Always refer to
are not recommended except in special the breaker’s maintenance manual for
circumstances, such as after repairs or specific safety considerations.
modifications to the equipment that included
the primary circuit (bus assemblies).

3. After the switchboard has been serviced


and adjusted, its operation should be
checked before it is returned to service.

Maintenance Equipment
Adequate maintenance equipment should
include: