www.hilti.us Profis Anchor 2.7.

5
Company: Page: 1
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 55 5/8
Effective embedment depth: hef = 150 mm
Material: ASTM F 1554
Proof: Design method ACI 318-14 / CIP
Stand-off installation: - (Recommended plate thickness: not calculated)
Profile: no profile
Base material: cracked concrete, , fc' = 6237 psi; h = 230 mm
Reinforcement: tension: condition B, shear: condition B;
edge reinforcement: none or < No. 4 bar
Corner reinforcement acc. to ACI 318-14 Section 17.5.2.3 (c) present

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

2 Load case/Resulting anchor forces


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 12.830 13.570 13.570 0.000

max. concrete compressive strain: - [‰]


max. concrete compressive stress: - [N/mm2]
resulting tension force in (x/y)=(0/0): 0.000 [kN]
resulting compression force in (x/y)=(0/0): 0.000 [kN]

3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* 12.830 56.548 23 OK
Pullout Strength* 12.830 104.243 13 OK
Concrete Breakout Strength** 12.830 39.986 33 OK
Concrete Side-Face Blowout, direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


Nsa = Ase,N futa ACI 318-14 Eq. (17.4.1.2)
f Nsa ≥ Nua ACI 318-14 Table 17.3.1.1

Variables
Ase,N [mm2] futa [N/mm2]
146 517.11
Calculations
Nsa [kN]
75.397
Results
Nsa [kN] f steel f Nsa [kN] Nua [kN]
75.397 0.750 56.548 12.830

3.2 Pullout Strength


NpN = y c,p Np ACI 318-14 Eq. (17.4.3.1)
Np = 8 Abrg f'c ACI 318-14 Eq. (17.4.3.4)
f NpN ≥ Nua ACI 318-14 Table 17.3.1.1

Variables
y c,p Abrg [mm2] la f'c [psi]
1.000 433 1.000 6237
Calculations
Np [kN]
148.918
Results
Npn [kN] f concrete f Npn [kN] Nua [kN]
148.918 0.700 104.243 12.830

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

3.3 Concrete Breakout Strength

Ncb = (AA ) y
Nc
Nc0
ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1a)
f Ncb ≥ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)

Variables
hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm] y c,N
150 0 0 100 1.000

cac [mm] kc la f'c [psi]


- 24 1.000 6237

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
114725 202500 1.000 1.000 0.833 1.000 120.993
Results
Ncb [kN] f concrete f Ncb [kN] Nua [kN]
57.123 0.700 39.986 12.830

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 13.570 29.405 47 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 13.570 79.972 17 OK
Concrete edge failure in direction x+** 13.570 15.193 90 OK
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength


Vsa = 0.6 Ase,V futa ACI 318-14 Eq. (17.5.1.2b)
f Vsteel ≥ Vua ACI 318-14 Table 17.3.1.1

Variables
Ase,V [mm2] futa [N/mm2]
146 517.11
Calculations
Vsa [kN]
45.238
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
45.238 0.650 29.405 13.570

4.2 Pryout Strength

Vcp = kcp [(AA ) y


Nc
Nc0
ed,N y c,N y cp,N Nb] ACI 318-14 Eq. (17.5.3.1a)
f Vcp ≥ Vua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)

( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)

y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)

Variables
kcp hef [mm] ec1,N [mm] ec2,N [mm] ca,min [mm]
2 150 0 0 100

y c,N cac [mm] kc la f'c [psi]


1.000 - 24 1.000 6237

Calculations
ANc [mm2] ANc0 [mm2] y ec1,N y ec2,N y ed,N y cp,N Nb [kN]
114725 202500 1.000 1.000 0.833 1.000 120.993
Results
Vcp [kN] f concrete f Vcp [kN] Vua [kN]
114.246 0.700 79.972 13.570

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

4.3 Concrete edge failure in direction x+

Vcb = (AA ) y
Vc
Vc0
ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1a)
f Vcb ≥ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-14 Eq. (17.5.2.1c)

( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
y ed,V = 0.7 + 0.3 ( ca2
1.5ca1 )
≤ 1.0 ACI 318-14 Eq. (17.5.2.6b)

y h,V = √1.5ca1
ha
≥ 1.0 ACI 318-14 Eq. (17.5.2.8)

(( ) )
0.2
l 1.5
Vb = 7 e √da l a √f'c ca1 ACI 318-14 Eq. (17.5.2.2a)
da

Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
128 100 0 1.000 230

le [mm] la da [mm] f'c [psi] y parallel,V


127 1.000 16 6237 1.000

Calculations
AVc [mm2] AVc0 [mm2] y ec,V y ed,V y h,V Vb [kN]
56064 73728 1.000 0.856 1.000 33.334
Results
Vcb [kN] f concrete f Vcb [kN] Vua [kN]
21.704 0.700 15.193 13.570

5 Combined tension and shear loads


bN bV z Utilization bN,V [%] Status
0.321 0.893 5/3 98 OK

bNV = bzN + bzV <= 1

6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.).
This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is
assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum
required anchor plate thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the
rigid base plate assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the
existing conditions and for plausibility! 
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout
Strength. Refer to your local standard.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant
standard!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.7.5
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 1/23/2018
E-Mail:

7 Installation data
Anchor plate, steel: - Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 55 5/8
Profile: - Installation torque: -
Hole diameter in the fixture: - Hole diameter in the base material: - mm
Plate thickness (input): - Hole depth in the base material: 150 mm
Recommended plate thickness: - Minimum thickness of the base material: 173 mm
Drilling method: -
Cleaning: No cleaning of the drilled hole is required

Coordinates Anchor mm
Anchor x y c-x c+x c-y c+y
1 0 0 - 128 - 100

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted
prior to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the
data you put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be
put in by you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly
with regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an
aid to interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or
suitability for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan