1 Input data
Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 36 3/4
Effective embedment depth: hef = 9.000 in.
Material: ASTM F 1554
Proof: Design method ACI 318-14 / CIP
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.750 in.
Anchor plate: lx x ly x t = 14.000 in. x 16.000 in. x 0.750 in.; (Recommended plate thickness: not calculated
Profile: Rectangular HSS (AISC); (L x W x T) = 14.000 in. x 4.000 in. x 0.375 in.
Base material: uncracked concrete, 4000, fc' = 4,000 psi; h = 24.000 in.
Reinforcement: tension: condition B, shear: condition A;
edge reinforcement: >= No. 4 bar
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 12/22/2021
E-Mail:
4 2
Anchor reactions [kip]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 2.300 6.768 0.500 6.750
2 2.300 6.768 0.500 6.750 x
Tension
3 2.300 6.768 0.500 6.750
4 2.300 6.768 0.500 6.750
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kip] Capacity f Nn [kip] Utilization bN = Nua/f Nn Status
Steel Strength* 2.300 14.529 16 OK
Pullout Strength* 2.300 28.569 9 OK
Concrete Breakout Strength** 9.200 47.779 20 OK
Concrete Side-Face Blowout, direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (anchors in tension)
Variables
Ase,N [in.2] futa [ksi]
0.33 58
Calculations
Nsa [kip]
19.372
Results
Nsa [kip] f steel f Nsa [kip] Nua [kip]
19.372 0.750 14.529 2.300
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1
Company: Page: 3
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 12/22/2021
E-Mail:
Variables
y c,p Abrg [in.2] la f'c [psi]
1.400 0.91 1.000 4,000
Calculations
Np [kip]
29.152
Results
Npn [kip] f concrete f Npn [kip] Nua [kip]
40.813 0.700 28.569 2.300
Ncbg = (AA ) y
Nc
Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-14 Eq. (17.4.2.1b)
f Ncbg ≥ Nua ACI 318-14 Table 17.3.1.1
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h2ef ACI 318-14 Eq. (17.4.2.1c)
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √f'c hef ACI 318-14 Eq. (17.4.2.2a)
Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
8.000 0.000 0.000 9.000 1.250
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [kip]
990.00 576.00 1.000 1.000 0.925 1.000 34.346
Results
Ncbg [kip] f concrete f Ncbg [kip] Nua [kip]
68.256 0.700 47.779 9.200
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1
Company: Page: 4
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 12/22/2021
E-Mail:
4 Shear load
Load Vua [kip] Capacity f Vn [kip] Utilization bV = Vua/f Vn Status
Steel Strength* 6.768 7.555 90 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 27.074 95.558 29 OK
Concrete edge failure in direction y+** 27.074 21.118 129 not recommended
* anchor having the highest loading **anchor group (relevant anchors)
Variables
Ase,V [in.2] futa [ksi]
0.33 58
Calculations
Vsa [kip]
11.623
Results
Vsa [kip] f steel f Vsa [kip] Vua [kip]
11.623 0.650 7.555 6.768
( )
1
y ec,N = 2 e'N ≤ 1.0 ACI 318-14 Eq. (17.4.2.4)
1+
3 hef
y ed,N = 0.7 + 0.3 (
ca,min
1.5hef )
≤ 1.0 ACI 318-14 Eq. (17.4.2.5b)
y cp,N = MAX (
ca,min 1.5hef
cac
,
cac )
≤ 1.0 ACI 318-14 Eq. (17.4.2.7b)
1.5
Nb = kc l a √fc hef
'
ACI 318-14 Eq. (17.4.2.2a)
Variables
kcp hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.]
2 8.000 0.000 0.000 9.000
Calculations
ANc [in.2] ANc0 [in.2] y ec1,N y ec2,N y ed,N y cp,N Nb [kip]
990.00 576.00 1.000 1.000 0.925 1.000 34.346
Results
Vcpg [kip] f concrete f Vcpg [kip] Vua [kip]
136.512 0.700 95.558 27.074
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1
Company: Page: 5
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 12/22/2021
E-Mail:
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1b)
f Vcbg ≥ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
AVc0 = 4.5 c2a1 ACI 318-14 Eq. (17.5.2.1c)
( )
1
y ec,V = 2e'v ≤ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
y ed,V = 0.7 + 0.3 (ca2
1.5ca1 )
≤ 1.0 ACI 318-14 Eq. (17.5.2.6b)
y h,V = √
1.5ca1
ha
≥ 1.0 ACI 318-14 Eq. (17.5.2.8)
' 1.5
Vb = 9 l a √fc ca1 ACI 318-14 Eq. (17.5.2.2b)
Variables
ca1 [in.] ca2 [in.] ecV [in.] y c,V ha [in.]
12.000 9.000 0.000 1.400 24.000
Calculations
AVc [in.2] AVc0 [in.2] y ec,V y ed,V y h,V Vb [kip]
648.00 648.00 1.000 0.850 1.000 23.662
Results
Vcbg [kip] f concrete f Vcbg [kip] Vua [kip]
28.157 0.750 21.118 27.074
6 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate
assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and
for plausibility!
• Condition A applies when supplementary reinforcement is used. The Φ factor is increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1
Company: Page: 6
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: | Date: 12/22/2021
E-Mail:
7 Installation data
Anchor plate, steel: - Anchor type and diameter: Heavy Hex Head ASTM F 1554 GR. 36 3/4
Profile: Rectangular HSS (AISC); 14.000 x 4.000 x 0.375 in. Installation torque: -
Hole diameter in the fixture: df = 0.813 in. Hole diameter in the base material: - in.
Plate thickness (input): 0.750 in. Hole depth in the base material: 9.000 in.
Recommended plate thickness: not calculated Minimum thickness of the base material: 10.000 in.
7.000 7.000
3.500
4 2
8.000
9.000 x
8.000
3 1
3.500
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti.us Profis Anchor 2.8.1