SCHEDULE OF LOADS AND COMPUTATION

CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE
DESCRIPTION DESCRIPTION
NO. OUTLET CKT PROTECTION AND CONDUITS NO. OUTLET CKT PROTECTION AND CONDUITS
1 LIGHTING OUTLET 15 220 2,250 10.23 1 LIGHTING OUTLET 15 220 2,250 10.23
15 AMP. 15 AMP.
2 LIGHTING OUTLET 15 220 2,250 10.23 2 LIGHTING OUTLET 15 220 2,250 10.23
PB-1 15 AMP. PB-5 15 AMP.
3 LIGHTING OUTLET 12 220 1,800 8.18 3 LIGHTING OUTLET 12 220 1,500 8.18
15 AMP. 15 AMP.
4 CONVENIENCE OUTLET 4 220 800 3.64 4 CONVENIENCE OUTLET 4 220 800 3.64
20 AMP. 20 AMP.

TOTAL 32.28AMPS TOTAL 32.28AMPS

SIZE OF MAIN CONDUCTOR : SIZE OF MAIN CONDUCTOR :


IL = 32.28 + 10.23 x 1.25 = 45.07 AMP IL = 32.28 + 10.23 x 1.25 = 45.07 AMP
FOR MAIN DISCONNECT: FOR MAIN DISCONNECT:

IS = 32.28 + 10.23 x 2.25 = 55.30 AMP IS = 32.28 + 10.23 x 2.25 = 55.30 AMP

CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE
DESCRIPTION DESCRIPTION
NO. OUTLET CKT PROTECTION AND CONDUITS NO. OUTLET CKT PROTECTION AND CONDUITS
1 LIGHTING OUTLET 15 220 2,250 10.23 1 LIGHTING OUTLET 15 220 2,250 10.23
15 AMP. 15 AMP.
2 LIGHTING OUTLET 15 220 2,250 10.23 2 LIGHTING OUTLET 15 220 2,250 10.23
PB-2 15 AMP. PB-6 15 AMP.
3 LIGHTING OUTLET 12 220 1,500 8.18 3 LIGHTING OUTLET 12 220 1,500 8.18
15 AMP. 15 AMP.
4 CONVENIENCE OUTLET 4 220 800 3.64 4 CONVENIENCE OUTLET 4 220 800 3.64
20 AMP. 20 AMP.

TOTAL 32.28AMPS TOTAL 32.28AMPS

SIZE OF MAIN CONDUCTOR : SIZE OF MAIN CONDUCTOR :


IL = 32.28 + 10.23 x 1.25 = 45.07 AMP IL = 32.28 + 10.23 x 1.25 = 45.07 AMP
FOR MAIN DISCONNECT: FOR MAIN DISCONNECT:

IS = 32.28 + 10.23 x 2.25 = 55.30 AMP IS = 32.28 + 10.23 x 2.25 = 55.30 AMP

CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE
DESCRIPTION DESCRIPTION
NO. OUTLET CKT PROTECTION AND CONDUITS NO. OUTLET CKT PROTECTION AND CONDUITS
1 LIGHTING OUTLET 15 220 2,250 10.23 1 LIGHTING OUTLET 15 220 2,250 10.23
15 AMP. 15 AMP.
2 LIGHTING OUTLET 15 220 2,250 10.23 2 LIGHTING OUTLET 15 220 2,250 10.23
PB-3 15 AMP. PB-7 15 AMP.
3 LIGHTING OUTLET 12 220 1,500 8.18 3 LIGHTING OUTLET 12 220 1,500 8.18
15 AMP. 15 AMP.
4 CONVENIENCE OUTLET 4 220 800 3.64 4 CONVENIENCE OUTLET 4 220 800 3.64
20 AMP. 20 AMP.

TOTAL 32.28AMPS TOTAL 32.28AMPS

SIZE OF MAIN CONDUCTOR : SIZE OF MAIN CONDUCTOR :


IL = 32.28 + 10.23 x 1.25 = 45.07 AMP IL = 32.28 + 10.23 x 1.25 = 45.07 AMP
FOR MAIN DISCONNECT: FOR MAIN DISCONNECT:

IS = 32.28 + 10.23 x 2.25 = 55.30 AMP IS = 32.28 + 10.23 x 2.25 = 55.30 AMP

CIRCUIT NO. OF VOLTS WATTS AMP./ CIRCUIT SIZES OF WIRE


DESCRIPTION
NO. OUTLET CKT PROTECTION AND CONDUITS
1 LIGHTING OUTLET 15 220 2,250 10.23 15 AMP. TOTAL SCHEDULE OF LOADS AND COMPUTATION
2 LIGHTING OUTLET 15 220 2,250 10.23
PB-4 15 AMP. AMP./
PB CIRCUIT SIZES OF WIRE
3 LIGHTING OUTLET VOLTS WATTS CKT
12 220 1,500 8.18 15 AMP. NO. PROTECTION AND CONDUITS
4 CONVENIENCE OUTLET 4 220 800 3.64 20 AMP. PB-1 220 32.28

PB-2 220 32.28


TOTAL 32.28AMPS
PB-3 220 32.28

SIZE OF MAIN CONDUCTOR :


PB-4 220 32.28
IL = 32.28 + 10.23 x 1.25 = 45.07 AMP
FOR MAIN DISCONNECT:
PB-5 220 32.28
IS = 32.28 + 10.23 x 2.25 = 55.30 AMP
PB-6 220 32.28

PB-7 220 32.28

GRAND TOTAL 225.96 AMPS

SIZE OF MAIN CONDUCTOR :


IL = 225.96 + 10.23 x 1.25 = 238.75 AMP
SCALE 1:300 MTS.
FOR MAIN DISCONNECT:

IS = 225.96 + 10.23 x 2.25 = 248.98 AMP