Load Profile: Why Do The Calculation?
Load Profile: Why Do The Calculation?
Load Profile
From Open Electrical
Contents
1 Introduction
1.1 Why do the calculation?
1.2 When to do the calculation?
2 Calculation Methodology
2.1 Step 1: Prepare the Load List
2.1.1 Calculating the Consumed Load VA
2.2 Step 2: Construct the Load Profile
2.3 Step 3: Calculate Design Load and Energy Demand
2.3.1 Design Load
2.3.2 Design Energy Demand
3 Computer Software
4 What Next?
Introduction
The energy load profile (hereafter referred to as simply
"load profile") is an estimate of the total energy
demanded from a power system or sub-system over a
specific period of time (e.g. hours, days, etc). The load
profile is essentially a two-dimensional chart showing
the instantaneous load (in Volt-Amperes) over time,
and represents a convenient way to visualise how the
system loads changes with respect to time.
A load profile needs to be constructed whenever the sizing of energy storage devices (e.g. batteries) is required.
The calculation can be done once preliminary load information is available.
https://wiki.openelectrical.org/index.php?title=Load_Profile 1/5
2/8/2018 Load Profile - Open Electrical
Calculation Methodology
There are two distinct methods for constructing a load
profile:
The first step is to transform the collected loads into a load list. It is similar in form to the electrical load schedule,
but is a little simplified for the purpose of constructing a load profile. For instance, instead of categorising loads by
their load duty (continuous, intermittent or standby), it is assumed that all loads are operating continuously.
However, a key difference of this load list is the time period associated with each load item:
In the autonomy method, the associated time period is called the "autonomy" and is the number of hours that the
load needs to be supported during a power supply interruption. Some loads may only be required to ride through
brief interruptions or have enough autonomy to shut down safely, while some critical systems may need to operate
for as long as possible (up to several days).
In the 24 hour profile method, the associated time period is represented in terms of "ON" and "OFF" times. These
are the times in the day (in hours and minutes) that the load is expected to be switched on and then later turned off.
For loads that operate continuously, the ON and OFF time would be 0:00 and 23:59 respectively. A load item may
need to be entered in twice if it is expected to start and stop more than once a day.
For this calculation, we are interested in the consumed apparent power of the loads (in VA). For each load, this can
be calculated as follows:
Pl
Sl =
cos ϕ × η
https://wiki.openelectrical.org/index.php?title=Load_Profile 2/5
2/8/2018 Load Profile - Open Electrical
The load profile is constructed from the load list and is essentially a chart that shows the distribution of the loads
over time. The construction of the load profile will be explained by a simple example:
Load Autonomy
Description
(VA) (h)
DCS Cabinet 200 4
ESD Cabinet 200 4
Telecommunications
150 6
Cabinet
Computer Console 90 2
https://wiki.openelectrical.org/index.php?title=Load_Profile 3/5
2/8/2018 Load Profile - Open Electrical
For the 24 Hour method, energy rectangles are constructed with the periods of time that a load is energised (i.e. the
time difference between the ON and OFF times).
Design Load
The design load is the instantaneous load for which the power conversion, distribution and protection devices
should be rated, e.g. rectifiers, inverters, cables, fuses, circuit breakers, etc. The design can be calculated as
follows:
Sd = Sp (1 + k g )(1 + k c )
Sp is the peak load apparent power, derived from the load profile (VA)
kg is a contingency for future load growth (%)
kc is a design margin (%)
It is common to make considerations for future load growth (typically somewhere between 5 and 20%), to allow
future loads to be supported. If no future loads are expected, then this contingency can be ignored. A design margin
is used to account for any potential inaccuracies in estimating the loads, less-than-optimum operating conditions
due to improper maintenance, etc. Typically, a design margin of 10% to 15% is recommended, but this may also
depend on Client preferences.
Example: From our simple example above, the peak load apparent power is 640VA. Given a future growth
contingency of 10% and a design margin of 10%, the design load is:
The design energy demand is used for sizing energy storage devices. From the load profile, the total energy (in
terms of VAh) can be computed by finding the area underneath the load profile curve (i.e. integrating instantaneous
power with respect to time over the autonomy or 24h period). The design energy demand (or design VAh) can then
be calculated by the following equation:
Ed = Et (1 + k g )(1 + k c )
Et is the total load energy, which is the area under the load profile (VAh)
kg is a contingency for future load growth as defined above (%)
kc is a design contingency as defined above (%)
Example: From our simple example above, the total load energy from the load profile is 2,680VAh. Given a future
growth contingency of 10% and a design margin of 10%, the design energy demand is:
Computer Software
https://wiki.openelectrical.org/index.php?title=Load_Profile 4/5
2/8/2018 Load Profile - Open Electrical
The load profile is normally done manually with the help of a spreadsheet. Since it's such a simple calculation, it's
hard to argue that special software is warranted.
What Next?
The load profile is usually an intermediate step in part of a larger calculation (for example, AC UPS System or
Solar Power System calculations). Alternatively, constructing a load profile may be the first step to analysing
energy use, for example in energy efficiency applications.
Category: Calculations