Cables
Power Supply Cables
12x6 48 V RAYCAP CU/XLPE/CWS/LSZH/STA/LSZH
Cable structure
Multi-core cable with copper Conductor: Annealed bare copper round stranded compacted class 2 IEC 60228
round compacted conductors, of nominal cross-section equal to 6 sq.mm
XLPE insulation, Copper Insulation: XLPE according to IEC 60502-1 of 0.5 mm nominal thickness.
wire shield, LSZH sheath, Core identification: Blue – black (1), Blue – black (2), Blue – black (3),
galvanized steel tape armour, Blue – black (4), Blue – black (5), Blue – black (6)
LSZH oversheath Sheath: LSZH compound
Sheath colour: Black
Copper Shield: Copper wires helically applied over core and wrapped with a
copper tape of 0.1 mm nominal thickness laid in open helix.
Nominal cross section including copper tape (sq.mm): 3.1
Sheath: LSZH compound
Sheath colour: Black
Armour consisting of galvanized steel tape of 0.2 mm nominal thickness applied
helically with overlap
Sheath: LSZH type ST8 according to IEC 60502-1 of 1.8 mm nominal thickness
with UV additive.
Sheath colour: Black
General Description
Type of cable: XLPE/CWS/LSZH/STA/LSZH
Rated voltage Uo/U (Umax): 48 V
Number of cores x Nominal cross-section: 12x6 mm²
Approximate cable overall diameter: 24.05 (± 1.5) mm
Approximate cable overall weight: 1.3 kg/m
Nominal drum length (Tolerance): 500 m (± 5%)
Marking
Oversheath marking by embossing or ink (Manufacturer’s option) as follows:
RAYCAP 2013* 12x6 48 V RAYCAP CU/XLPE/CWS/LSZH/STA/LSZH
* Year of manufacture
Meter marking at one-meter intervals by ink on oversheath
Notes
Flame retardant according to IEC 60332-3-24
Minimum bending radius during installation: 8 x D
Insulation voltage test: 220 V DC for 5 min according to IEC 60502-1
Operation ambient temperatures range: -40oC to 70oC
Installation temperature: -5oC to 70oC
Information contained in this document is subject to change at any time without notice.
Release-3