You are on page 1of 47

PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 1/45
Ref. FEED DOC. No. :

SPECIFICATION FOR

132kV GIS

PROJECT : KARBALA REFINERY PROJECT

LOCATION : KARBALA, IRAQ

EMPLOYER : STATE COMPANY FOR OIL PROJECTS (SCOP)

2 14 APR 15 ISSUED FOR CONSTRUCTION I. S. Kim S. B. Choi S. R. Seo J. B. Kim

1 04 MAR 15 ISSUED FOR CONSTRUCTION I. S. Kim S. B. Choi S. R. Seo J. B. Kim

0 17 NOV 14 ISSUED FOR CONSTRUCTION I. S. Kim S. B. Choi S. R. Seo J. B. Kim

A 09 JUL 14 ISSUED FOR APPROVAL I. S. Kim S. B. Choi S. R. Seo J. B. Kim

CHKD REVD APPRD CONFD


REV. DATE DESCRIPTION PRPD
(LS LE) (LS EM) (JV ED) (SCOP)

Joint Venture of Hyundai Engineering & Construction Co., Ltd., GS Engineering & Construction Co., Ltd., SK Engineering
& Construction Co., Ltd., and Hyundai Engineering Co., Ltd.,

Note :
a) Revision bar(vertical line) shall be placed in the right hand margin to indicate where the changes has been made
b) PRPD = Prepared by, CHKD = Checked by, REVD = Reviewed by, APPRD = Approved by, CONFD = Confirmed by

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 2/45
Ref. FEED DOC. No. :

REVISION HISTORY

Rev Date Description Page


A 09 JUL 14 INITIAL ISSUE
0 17 NOV 14 ISSUED FOR CONSTRUCTION
Revised
0 17 NOV 14 9 of 36
3. Service Conditions data has been updated.
Delete:
0 17 NOV 14 5.3 Operating Requirements 13 of 36
Bus bar ~ disengaged positions.
Revise:
5.4 General Design Requirements
0 17 NOV 14 14 of 36
Transformer outgoing feeders shall be maximum “1000A”
to “1250A”.

Revise:
0 17 NOV 14 15 of 36
5.5 Bus Bars
The Gas Insulated Switchgear ~ symbol.
Delete:
0 17 NOV 14 5.7 Circuit Breakers 17 of 36
HV power circuits ~ test/isolated position.
5.7.3 Local control
Revise:
0 17 NOV 14 OPEN/ CLOSE control switch 19 of 36
Delete:
A test facility ~ physical effort.
Revise:
0 17 NOV 14 5.7.4 Disconnect Switches 20 of 36
OPEN/CLOSE control switch
Delete:
0 17 NOV 14 5.8.1 General Interlocks 21 of 36
Mechanical interlocks ~ switch is open
Delete:
0 17 NOV 14 6.1 General 22 of 36
Schemes such that ~ otherwise opened.
Delete:
0 17 NOV 14 6.2.2 Gas Insulated Switchgear Codes of Operation 23 of 36
All of the following control modes ~ Test position.
Delete:
0 17 NOV 14 6.5 Voltage Transformers 25 of 36
The VT primary windings ~ withdrawable.
0 17 NOV 14 Delete: 27 of 36

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 3/45
Ref. FEED DOC. No. :

Rev Date Description Page


6.7.2 Power Distribution Monitoring and Control
All protection relays ~ by others.
Delete:
0 17 NOV 14 6.7.3 Communication Protocol 27 of 36
Communication systems ~ IEC 61850.
Delete:
0 17 NOV 14 6.9 Control Switches/Push Buttons 28 of 36
Circuit breaker ~ drawings/data sheets.
Revise:
6.10 Indication Lamps
0 17 NOV 14 28 of 36
Trip : Yellow
Trip Circuit health : Blue
Delete:
0 17 NOV 14 6.11 Auxiliary Contracts 29 of 36
Auxiliary contacts ~ as above
Delete:
0 17 NOV 14 6.12 Wiring 29 of 36
All panel ~ the CONTRACTOR.
Delete:
0 17 NOV 14 6.13 Accessories 30 of 36
The Gas Insulated Switchgear ~ tools
1 04 MAR 15 Add: 1.2 Purpose 8 of 46
1 04 MAR 15 Add: 1.3 Definition 8 of 46
Add: 2 Codes and Standards 9 of 46
1 04 MAR 15
IEC 60137 ~ voltage transformers
1 04 MAR 15 Add: 3. Document Precedence 11 of 46
1 04 MAR 15 Add: 4. Specification Deviation/Concession Control 12 of 46
1 04 MAR 15 Add: 5. Quality Assurance and Quality Control 12 of 46
1 04 MAR 15 Add: 6. Documentation 13 of 46
1 04 MAR 15 Add: 7. Subcontractors / Sub-Vendors 14 of 46
1 04 MAR 15 Add: 8. Handling 14 of 46
Add: 11.3 Operating Requirements
1 04 MAR 15 20 of 46
Bus bar ~ disengaged positions.
Add: 11.7 Circuit Breakers
1 04 MAR 15 24 of 46
HV power circuits ~ test.
11.7.3 Local control
1 04 MAR 15 Revise: OPEN/CLOSE OPEN/NEUTRAL/CLOSE 26 of 46
Add: A test facility ~ physical effort.
Revise: 11.7.4 Disconnect Switches
1 04 MAR 15 27 of 46
OPEN/CLOSE OPEN/NEUTRAL/CLOSE

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 4/45
Ref. FEED DOC. No. :

Rev Date Description Page


Add: 11.8.1 General Interlocks
1 04 MAR 15 28 of 46
Mechanical interlocks ~ switch is open
Add: 12.1 General
1 04 MAR 15 30 of 46
Schemes such that ~ otherwise opened.
12.2.2 Gas Insulated Switchgear Codes of Operation
1 04 MAR 15 Add: All of the following control modes ~ Test. 31 of 46
Revise: Breakers and shall be Breakers shall be
Add: 12.5 Voltage Transformers
1 04 MAR 15 33 of 46
The VT primary windings ~ withdrawable.
Add: 12.7.2 Power Distribution Monitoring and Control
1 04 MAR 15 35 of 46
All protection relays ~ by others.
Add: 12.7.3 Communication Protocol
1 04 MAR 15 35 of 46
Communication systems ~ Modbus TCP/IP
Add: 12.9 Control Switches/Push Buttons
1 04 MAR 15 36 of 46
Circuit breaker ~ drawings/data sheets.
Add: 12.11 Auxiliary Contracts
1 04 MAR 15 37 of 46
Auxiliary contacts ~ as above
Add: 12.12 Wiring
1 04 MAR 15 38 of 46
All panel ~ the CONTRACTOR.
Add: 12.13 Accessories
1 04 MAR 15 39 of 46
The Gas Insulated Switchgear ~ tools
1 04 MAR 15 Add: Clause No. 15.3.2 Routine test 42 of 46
1 04 MAR 15 Add: 15.3.3 Field test 42~43 of 46
Revise: 10.1 Operation, Design & Service Life
2 14 APR 15 16 of 45
20 years 25 years
Remove: 15.1 Quality Assurance
2 14 APR 15 The SUPPLIER shall ~ manual operation.(Replaced with 40 of 45
clause 5. Quality Assurance and Quality Control)
Remove:15.2.2 Routine Test
2 14 APR 15 42 of 45
and voltage( as per comment)
Revise: 16. Painting
2 14 APR 15 43 of 45
2342-AA00-JSD-2300-01 IONE-AA00-SP-PR-2300

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 5/45
Ref. FEED DOC. No. :

TABLE OF CONTENTS

1. GENERAL .................................................................................................................... 8
1.1 Introduction ...................................................................................................................8

1.2 Purpose ......................................................................................................................... 8

1.3 Definitions .....................................................................................................................8

2. CODES AND STANDARDS ......................................................................................... 9


2.1 IEC (International Electro technical Commission)......................................................9

2.2 ISO (International Standards Organization) .............................................................. 11

2.3 Additional design specifications ............................................................................... 11

3. DOCUMENT PRECEDENCE ..................................................................................... 11

4. SPECIFICATIONS DEVIATION/CONCESSION CONTROL ...................................... 12

5. QUALITY ASSURANCE AND QUALITY CONTROL ................................................. 12

6. DOCUMENTATION..................................................................................................... 13
6.1 General ........................................................................................................................13

6.2 Deliverables.................................................................................................................13

7. SUBCONTRACTORS/SUBVENDORS ...................................................................... 14

8. HANDLING ................................................................................................................. 14
8.1 Packaging and Shipping ............................................................................................15
8.2 Preservation and Storage ...........................................................................................16

9. SERVICE CONDITIONS ............................................................................................. 16

10. GENERAL REQUIREMENTS ..................................................................................... 16


10.1 Operation, Design & Service Life ...............................................................................16

10.2 Scope of Supply ..........................................................................................................16

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 6/45
Ref. FEED DOC. No. :

10.3 Plant Utility Voltages and Tolerances ........................................................................17


10.4 Materials ......................................................................................................................18

10.5 Ingress Protection ...................................................................................................... 19

10.6 Deviations, Concessions and Change Control .........................................................19

11. DESIGN REQUIREMENTS FOR GAS INSULATED SWITCHGEAR......................... 19


11.1 General ........................................................................................................................19

11.2 Configuration .............................................................................................................. 19

11.3 Operating Requirements ............................................................................................20


11.4 General Design Requirements ...................................................................................20

11.5 Bus Bars ......................................................................................................................22

11.6 Grounding ................................................................................................................... 23


11.7 Circuit Breakers ..........................................................................................................23

11.8 Interlocks .....................................................................................................................28

12. GAS INSULATED SWITCHGEAR PROTECTION, CONTROL, METERING AND


AUXILIARIES .................................................................................................................... 29
12.1 General ........................................................................................................................29
12.2 Gas Insulated Switchgear Control .............................................................................30

12.3 Gas Insulated Switchgear Metering ...........................................................................31

12.4 Current Transformers .................................................................................................32


12.5 Voltage Transformers .................................................................................................33

12.6 Electrical Protection Relays .......................................................................................33

12.7 Control and Monitoring Interfaces .............................................................................34


12.8 Control Relays.............................................................................................................35

12.9 Control Switches/Push Buttons .................................................................................36

12.10 Indication Lamps ........................................................................................................36


12.11 Auxiliary Contracts .....................................................................................................37

12.12 Wiring .......................................................................................................................... 38

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 7/45
Ref. FEED DOC. No. :

12.13 Terminals .....................................................................................................................38


12.14 Accessories.................................................................................................................39

13. NOISE ......................................................................................................................... 40

14. NAME PLATES AND LABELS ................................................................................... 40

15. INSPECTION & TESTING .......................................................................................... 40


15.1 Inspection ....................................................................................................................40

15.2 Testing .........................................................................................................................40


15.3 Inspection and Test Plan(ITP) ....................................................................................42

15.4 Commissioning and Start-Up .....................................................................................43

15.5 Training and After Sales Support...............................................................................43

16. PAINTING ................................................................................................................... 43

17. SPARE PARTS AND SPECIAL TOOLS ..................................................................... 43

18. GUARANTEE AND WARRANTY ............................................................................... 44

19. PREPARATION SHIPMENT ....................................................................................... 44


19.1 Packaging and Shipping ............................................................................................44

19.2 Preservation and Storage ...........................................................................................45

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 8/45
Ref. FEED DOC. No. :

1. GENERAL

1.1 Introduction

This specification describes the minimum requirements for the design, manufacture, inspection, testing,
painting and supply of 132kV Gas Insulated Switchgear for a new SCOP refinery to be located in Karbala.

This document shall be read in conjunction with other applicable Project Specifications, Project Data
Sheets, Project Drawings and documents.

1.2 Purpose

The purpose of this specification is to ensure consistency in selection and design of low voltage
switchgear and control gear.

1.3 Definitions

For the purpose of this specification, the following definitions shall apply.

COMPANY : State Company for Oil Projects(SCOP)

SUBCONTRACTOR : The party(s) which carry(s) out all or part of the design,
procurement, installation and testing of the System(s) as
specified by the CONTRACTOR / VENDOR.

MANUFACTURER/VENDOR : Supplier of equipment and support services for a


particular piece of equipment/package.

CONTRACTOR : Organization to which SCOP award the Engineering,


Procurement and Construction (EPC) phase.

CONCESSION REQUEST : A deviation requested by the SUBCONTRACTOR or


VENDOR usually after receiving the contract package or
purchase order. Often, it refers to an authorization to use,
repair, recondition, reclaim, or release materials,
components or equipment already in progress or
completely manufactured but which does not meet or
comply with COMPANY requirements. A CONCESSION
REQUEST is subject to COMPANY approval.

SHALL : Indicates a mandatory requirement.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 9/45
Ref. FEED DOC. No. :

SHOULD : Denotes an action or requirement which is not mandatory


but which is strongly recommended.

2. CODES AND STANDARDS


132kV Gas Insulated Switchgear shall be designed, manufactured and tested according to the
requirements of the relevant applicable IEC standards and in compliance with local codes.

The listed standards and Codes, together with their all parts and subparts, shall be applied considering
their latest applicable issue.

The measurement system is the SI metric unit system.

2.1 IEC (International Electro technical Commission)

IEC 60038 IEC standard voltages

IEC 60044 Instrument transformers

IEC 60051 Direct acting indicating analogue electrical-measuring


instruments and their accessories

IEC 60071 Insulation co-ordination

IEC 60073 Basic and safety principles for man-machine interface,


marking and identification – Coding principles for indicators
and actuators

IEC 60085 Thermal evaluation and classification of electrical insulation

IEC 60099 Surge Arresters

IEC 60137 Insulated bushings for alternating voltages above 1000V

IEC 60617 Graphical symbols for diagrams

IEC 61869-1 Instrument transformers – Part 1 : General requirements

IEC 61869-3 Instrument transformers – Part 3 : Additional requirements

for inductive voltage transformers

IEC 60227 Polyvinyl chloride insulated cables of rated voltages up to


and including 450/750V

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 10/45
Ref. FEED DOC. No. :

IEC 60255 Electrical relays

IEC 60269 Low voltage fuses

IEC 60282 High voltage fuses

IEC 60376 Specification and Acceptance of Sulphur Hexafluoride

IEC 60417 Graphic symbols for use on equipment

IEC 60446 Basic and safety principles for man-machine interface,


marking and identification – Identification of equipment
terminals, conductor terminations and conductors

IEC 60480 Guidelines for the checking and treatment of


Sulphur Hexafluoride (SF6) taken from electrical equipment
and specification for its reuse

IEC 60529 Degrees of Protection Provided by Enclosures (IP Code)

IEC 60840 Tests on Cable Accessories

IEC-60850 Communications networks and systems in substations

IEC 60870 Tele-control equipment and systems

IEC 61000 Electromagnetic Compatibility (EMC)

IEC 61010 Safety requirements for electrical equipment for


measurement, control and laboratory use

IEC 61850 Communication networks and systems in substations

IEC 62271-1 HV Switchgear and Controlgear: Common Specifications

IEC 62271-100 HV Switchgear and Controlgear: Alternating Current


Circuit-Breakers

IEC 62271-102 HV Switchgear and Controlgear: Alternating Current


Disconnectors and Earthing Switches

IEC 62271-203 HV Switchgear and Controlgear – Gas-insulated


metal-enclosed switchgear for rated voltages above 52kV

IEC 62271-204 HV Switchgear and Controlgear – Rigid Gas-insulated

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 11/45
Ref. FEED DOC. No. :

transmission lines for rated voltages above 52kV

IEC 62271-207 Seismic qualification for gas-insulated switchgear


assemblies for rated voltages above 52kV

IEC 62271-209 Cable connections for gas-insulated metal-enclosed


switchgear for rated voltages above 52kV – Fluid-filled and
extruded insulation cables – Fluid filled and dry type
cable-terminations.

2.2 ISO (International Standards Organization)

ISO 9001 Quality Management Systems – Requirements

2.3 Additional design specifications

The present design rules are complemented by the following additional project design
specifications and documents:

IONE-AA00-SP-EL-1001 Specification for Electrical System

IONE-AA00-SP-EL-1011 Specification for PMS & ECS

The following not electrical documents are also referenced:

IONE-AA00-SP-PR-0001 Basic Design Data

3. DOCUMENT PRECEDENCE
The VENDOR shall notify the COMPANY/CONTRACTOR of any apparent conflict between this
specification, the related data sheets, the Codes and Standards and any other specification noted herein.
Resolution and/or interpretation precedence shall be obtained from the COMPANY/CONTRACTOR in
writing before proceeding with the design/manufacture.

The specifications and codes referred to in this specification shall, unless stated otherwise, be the latest
approved issue at the time of the Purchase Order placement.

In case of conflict, the order of precedence shall be:

a) Equipment Data Sheets

b) Single Line Diagrams

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 12/45
Ref. FEED DOC. No. :

c) This Specification

d) Other Specifications and Standards related to the Project

e) Industry Codes and Standards

4. SPECIFICATIONS DEVIATION/CONCESSION CONTROL


Deviations from this specification are only acceptable where the MANUFACTURER has listed in his
quotation the requirements he cannot, nor does not wish to comply with, and the
COMPANY/CONTRACTOR has accepted in writing the deviations before the order is placed.

In the absence of a list of deviations, it will be assumed that the MANUFACTURER complies fully with this
specification.

Any technical deviations to the Purchase order and its attachments including, but not limited to, the Data
Sheets and Narrative Specifications shall be sought by the VENDOR only through Concession Request
format. Concession requests require CONTRACTOR’S and COMPANY’S review/approval, prior to the
proposed technical changes being implemented. Technical changes implemented prior to COMPANY
approval are subject to rejection.

5. QUALITY ASSURANCE AND QUALITY CONTROL


The VENDOR shall have in effect at all times, a QA/QC program, which clearly establishes the authority
and responsibility of those responsible for the quality system. Persons performing quality functions shall
have sufficient and well defined authority to enforce quality requirements that initiate, identify, recommend
and provide solutions to quality problems and verify the effectiveness of the corrective action.

A copy of the VENDOR’S QA/QC program shall be submitted to the COMPANY with its Quotation for
CONTRACTOR’S review and concurrence prior to award.

The VENDOR shall identify in purchase documents to its SUBVENDORS all applicable QA/QC
requirements imposed by the CONTRACTOR, and shall ensure compliance thereto. On request,
VENDOR shall provide objective evidence of its QA/QC surveillance of its SUBVENDOR’S activities.

The VENDOR shall submit certified reports of production tests as soon as the tests are completed
satisfactorily.

The COMPANY/CONTRACTOR reserves the right to inspect materials and workmanship at all stages of
manufacture and to witness any or all tests. The VENDOR, 30 days after award but prior to the pre-

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 13/45
Ref. FEED DOC. No. :

inspection meeting, shall provide the CONTRACTOR with a copy of its Manufacturing and Inspection
Plan for review and inclusion of any mandatory COMPANY/CONTRACTOR witness points.

6. DOCUMENTATION

6.1 General

VENDOR shall submit the type and quantity of drawings and documentation for CONTRACTOR’S
Authorization or information as listed in the individual Material Requisitions and Purchase Orders.

Mutual agreement on scheduled submittal of drawings and engineering data shall be an integral
part of any formal Purchase Order.

Comments made by Contractor on drawing submittal shall not relieve VENDOR or SUBVENDORS
of any responsibility in meeting the requirements of the specifications. Such comments shall not be
construed as permission to deviate from requirements of the Purchase Order unless specific and
mutual agreement is reached and confirmed in writing.

Each drawing shall be provided with a title block in the bottom right-hand corner incorporating the
following information:

a) Official trade name of the company.

b) VENDOR’S drawing number.

c) Drawing title giving the description of contents whereby the drawing can be identified.

d) A symbol or letter indicating the latest issue or revision.

e) PO number and item tag numbers.

Revisions to drawing shall be identified with symbols adjacent to the alterations, a brief description
in tabular form of each revision shall be given, and if applicable, the authority and date of the
revision shall be listed. The term “Latest Revision” shall not be used.

6.2 Deliverables

Unless otherwise stated in the Purchase Order, the MANUFACTURER shall at least supply the
following documents. The language used shall be English.

a) Single-line diagram

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 14/45
Ref. FEED DOC. No. :

b) Schematic diagrams of all different types of circuits

c) Final assembly arrangement drawing showing main circuits, main dimensions, floor plan and
shipping sections

d) Heat dissipation data

e) DC load requirements.

f) Component specifications or catalogues.

g) Minimum clearances around the assemblies for ventilation and safety during operation and
maintenance

h) Total mass of the assembly and of the individual shipping sections

i) Transport, installation, commissioning, operation and maintenance instructions, limited and


specific to the assembly and its components

j) List of spare parts (commissioning & two years operations)

k) List of applicable certificates

l) Test report of the final routine testing.

All documents shall show the relevant order number, item and MANUFACTURER’S references and
shall be distributed as specified in the Purchase Order.

Graphic symbols for electrical diagrams shall be according to IEC 60617. Device code numbers
shall be as per IEEE C-37.2.

7. SUBCONTRACTORS/SUBVENDORS
The vendor shall assume unit responsibility and overall guarantee for the equipment package and
associated equipment. The vendor shall transmit all relevant purchase order documents including
specifications to his sub vendors and subcontractors. It is the vendor’s responsibility to enforce all
purchase order and specification requirements on his sub vendors and subcontractors. The vendor shall
submit all relevant sub vendor and subcontractor drawings and engineering data to the contractor. The
vendor shall obtain and transmit all sub vendor and subcontractor warranties to the
CONTRACTOR/COMPANY, in addition to the system warranty.

8. HANDLING

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 15/45
Ref. FEED DOC. No. :

8.1 Packaging and Shipping

After inspection and test, equipment shall be completely free of water and dry before start of
preparation for shipment.

Preparation for shipment shall be in accordance with the VENDORS standards and as noted
herein. VENDOR shall be solely responsible for the adequacy of the preparation for shipment
provisions with respect to materials and application, and to provide equipment at the destination in
ex-works condition when handled by commercial carriers.

Adequate protection shall be provided to prevent mechanical damage and atmospheric corrosion
in transit and at the jobsite.

Preparation for shipment and packing will be subject to inspection and rejection by
COMPANY’S/CONTRACTOR’S inspectors. All costs occasioned by such rejection shall be to the
account of the VENDOR.

After inspection and test, equipment shall be completely free of water and dry before start of
preparation for shipment.

Equipment shall be packed, securely anchored, and skid mounted when required. Bracing,
supports, and rigging connections shall be provided to prevent damage during transit, lifting, or
unloading. All temporary bracing/supports shall be marked "REMOVE BEFORE EQUIPMENT
COMMISSIONING AND STARTUP."

Separate, loose, and spare parts shall be completely boxed. Pieces of equipment and spare parts
shall be identified by item number and service and marked with CONTRACTOR’S order number,
tag number, and weight, both inside and outside of each individual package or container. A bill of
material shall be enclosed in each package or container of parts.

Exposed finished and machined surfaces, including bolting, shall be given a coating of rust
inhibiting compound. Internal metal surfaces shall be sprayed or coated with a suitable rust
preventative prior to shipment. Openings shall be suitably tagged to indicate the rust preventative
applied.

Mechanical seal assemblies shall be fully protected from rusting and entry of moisture and dirt.

One complete set of the installation, operation, and maintenance instructions shall be packed in
the boxes or crates with equipment. This is in addition to the number called for in the Purchase
Order.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 16/45
Ref. FEED DOC. No. :

8.2 Preservation and Storage

Equipment and materials shall be protected to withstand ocean transit and extended period of
storage at the jobsite for a minimum period of 12 months. Equipment shall be protected to
safeguard against all adverse environments, such as: humidity, moisture, rain, dust, dirt, sand, mud,
salt air, salt spray, and seawater.

9. SERVICE CONDITIONS
The following site conditions shall apply;

f) Design temperature (dry bulb) : +55

g) Maximum summer temperature (dry bulb) : +55

h) Maximum winter temperature (dry bulb) : -8.5

i) Maximum relative humidity : 50%

j) Indoor or inside building

Switchgear room : 30 / Max. 40 Max. humidity at 50%

Battery room : 25 / Max. 25 Max. humidity at 50%

Cable room 40 / Max. 50 Max. humidity at 50%

Earthquake or seismic rating : S=0.43 for short period & S=0.118 at 1sec.

Site Class D

Unless specification otherwise environmental condition shall be in accordance with the Specification
“Basic Design Data”(IONE-AA00-SP-PR-0001).

10. GENERAL REQUIREMENTS

10.1 Operation, Design & Service Life

HV switchgear shall be designed for minimum life duration of 25 years in the environment and for
the duty specified herein and on the Project data Sheets.

Switchboards shall be designed to operate continuously without maintenance for 3 years, minimum.

10.2 Scope of Supply

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 17/45
Ref. FEED DOC. No. :

The Gas Insulated Switchgear shall consist of complete factory assembled units except where
section breaks are required for transportation. Each unit shall be complete with, but not limited to,
the following equipment and requirements:

a) Switchgear arrangement as specified in Project data sheets and drawings

b) Circuit breaker remote control panel

c) Data communications interface equipment for remote control from the Distributed Control
System(DCS).

d) Provision of data communications facilities for remote monitoring and control of circuit
breakers/contactor feeders and power system parameters via an external Power Distribution
Control (PDC) system (by others).

e) Inspection and Testing

f) Protective coating and painting in accordance with project specification

g) Packaging, shipping and storage

h) Spare Parts

i) Special Tools

j) Documentation, drawings and certification

k) Field supervision and service

l) The following will be provided by others, unless otherwise specified in the data sheets:

Incomer bus ducts/cables, glands and termination kits

Feeder power cables, glands and terminations kits

Power Management System

10.3 Plant Utility Voltages and Tolerances

10.3.1 System Parameters

Frequency 50Hz

Nominal Voltage 132kV rms

Highest system voltage 145kV

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 18/45
Ref. FEED DOC. No. :

Bus Continuous Rating As per Singleline

Bus Tie As per Singleline

Circuit Breaker Continuous Rating - Incoming and


Outgoing Feeders As per Singleline

Circuit Breaker Continuous Rating - Transformer


Feeders As per Singleline

Lightning Impulse Insulation level to earth 650kV

Power Frequency withstand voltage to earth 275kV

Equipment short time withstand current (1sec) As per Singleline

Supply Voltage/Frequency Variation +/- 5% / +/-2.5%

10.4 Materials

The materials of construction for the equipment shall be as specified in the equipment data sheets
and this specification. When materials are not specified, the materials proposed in the offer shall
be suitable for the environmental, operating and design conditions

All materials, equipment or supplies furnished under this specification shall be the product of a
manufacturer who is experienced in the design and construction of such materials, equipment, or
supplies, and who has furnished similar materials, equipment, or supplies that have been in
satisfactory operation for a minimum of three years, preferably in similar environmental conditions,
to establish its reliability.

In the case of materials which are specified in the Specification or reference documents, alternate
materials may be offered. Any such alternatives shall be clearly indicated in the Bid, along with any
cost adjustments and technical data supporting the alternative. Alternative materials shall be
subject to COMPANY/CONTRACTOR’s written approval.

All materials shall be new, free of defects and be identifiable against their certification.

The gas shall fulfill the requirements of IEC publications 60376 and 60480.

Flexible connections and adjustable mountings shall also be provided to compensate for

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 19/45
Ref. FEED DOC. No. :

reasonable tolerances in the manufacture of associated equipment to which SF6 switchgear may
be connected.

10.5 Ingress Protection

All equipment covered by this specification shall have an ingress protection of at least:

Hermetically enclosed gas compartment for indoor use : IP41

Cable compartment cover : IP31

Low voltage compartment : IP31

Control and indication panel : IP31

Equipment for outdoor use : IP55

10.6 Deviations, Concessions and Change Control

The SUPPLIER shall refer to the Material Requisition for the procedure for raising deviations or
concession requests to the technical content of this specification.

The COMPANY/CONTRACTOR will consider all deviations and concession requests; approval
may be granted at the discretion of the COMPANY/CONTRACTOR. No deviation or concession
shall be implemented prior to approval being granted. Any deviations or concession implemented
prior to approval shall be subject to rejection.

11. DESIGN REQUIREMENTS FOR GAS INSULATED SWITCHGEAR

11.1 General

The design shall be based on the specific requirements stated in this specification, Project Data
Sheet(s) and other applicable documents inclusive of the applicable editions of codes and
standards listed under Section 2.

Any deviations shall be submitted by the SUPPLIER together with the Bid in the format specified in
the Material Requisition//Bid document. In the absence of this, it shall be construed that the
SUPPLIER fully complies with this specification.

11.2 Configuration

Reference should be made to the relevant Single Line Diagram and data sheet.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 20/45
Ref. FEED DOC. No. :

11.3 Operating Requirements

Operation of circuit breakers will normally be from a remote location. In this context, ‘remote
location’ means ‘not from in front of the switchgear’ and may be manual control from a separate
Gas Insulated switchgear control panel located in the same room or by digital commands from an
external control and monitoring system via digital data communication interfaces (see section 6.2).

GIS Switchgear shall be designed to minimize risk of an internal short circuit. It shall also provide
for personnel and operating safety during all operating conditions, inspections, maintenance, the
connection of main, control and auxiliary cables whilst the Switchgear is energized and in operation.

Under extreme conditions of major short circuits or mal-operation, there shall be no danger to
persons in the vicinity of the Gas Insulated Switchgear. Interlocks and covers shall be provided to
prevent incorrect or unsafe operation and to prevent access to live parts.

The maximum difference in time between the circuit breaker phase contacts touching during
closing shall not exceed one half cycle. The maximum difference between the instant of contacts
separating during opening shall not exceed one half cycle.

Provision shall be made to padlock the following:

Grounding switches in the closed position

Bus bar in closed.

Circuit breakers in test and isolated.

Voltage transformers in the engaged and disengaged positions.

Labels shall be provided to clearly indicate the above positions.

11.4 General Design Requirements

Gas Insulated Switchgear (GIS) Enclosures shall be designed in accordance with the requirements
of IEC 62271 – 203 for 132kV. The arrangement for bolting together and the method of ensuring
electrical conductivity between enclosures shall be to approval of the CONTRACTOR. The live
parts of the switchgear and busbars shall be supported on barriers of insulating material with
proven long-term compatibility with SF6 gas and its arc degradation products.

Insulating barriers shall be discharge free at all working voltages. The design of the enclosure shall
be such as to keep loss of SF6 gas to a minimum. It is expected that replenishment of gas shall not

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 21/45
Ref. FEED DOC. No. :

be necessary for at least 10 years. The switchgear gas enclosures must be sectionalized into gas
zones with gas tight barriers between sections or compartments. The sections shall be arranged to
minimize the extent of plant rendered inoperative when gas pressure is reduced, either by
excessive leakage or for maintenance purposes, and to minimize the quantity of gas that has to be
evacuated and then recharged before and after maintaining any item of equipment. In order to
minimize the extent of equipment outage in the event of gas loss when gaining access inside
equipment for maintenance or when an item of equipment needs to be removed, the overall
equipment shall be divided into discrete gas zones isolated from each other by gas-tight bulkheads.
The gas-tight support insulating barriers shall be capable of withstanding a pressure differential of
a vacuum on one side and on the other a pressure equal to the design gas pressure or the
maximum gas pressure under conditions of an internal fault if this is greater. The design of the
enclosure assemblies shall be such that in the event of a fault, the damaged items can be replaced
with minimum disturbance to the adjacent compartments.

The basic equipment design shall be the responsibility of the SUPPLIER. Hybrid type Gas
Insulated Switchgear can be applied.

The SUPPLIER shall submit full technical details of his standard equipment with the Bid proposal,
which most nearly meets the requirements detailed herein. Aspects of the requirements which
cannot be met, or for which the SUPPLIER proposes new or alternative technology, shall be
identified and the variances explained.

Unless otherwise specified, all equipment shall be designed for continuous working under the
service conditions stated in the relevant documents and the Project Data Sheet.

Gas Insulated Switchgear shall be metal enclosed, vermin proof, dead front and floor mounted.
Outgoing transformer feeders shall be provided with SF6 circuit breakers.

Continuous current rating of incomers and bus tie feeders of HV Switchgear shall be maximum
2000A. Transformer outgoing feeders shall be maximum 1250A.

The electrical apparatus shall be located in such a manner as to enable the apparatus to be easily
maintained when in service. The location and installation shall also satisfy all relevant statutory and
regulatory requirements applicable at the installation site.

All electrical equipment supplied shall be adequate for the short circuit levels specified in the data
sheets.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 22/45
Ref. FEED DOC. No. :

Interlocks, bus bar shutters, covers, etc. shall be provided to prevent incorrect or unsafe operation,
and to prevent access to live parts. Mechanical interlocking should be provided on the GIS to
prevent operation of isolators or grounding devices until necessary GIS conditions are satisfied.

GIS Switchgear ratings and configuration shall be as per Project Data Sheets/ Project drawings.

Electrical running loads shall be uniformly distributed across each bus and it shall be ensured that
running and stand by loads for a given service are fed from two different bus sections.

All control, indication and protection equipment associated with a circuit breaker feeder shall be
accommodated in the segregated control compartment.

The GIS will be provided with separate power supplies from an external source to each bus section.

11.5 Bus Bars

The Gas Insulated Switchgear will house a double bus arrangement.

To minimize the extent of dismantling necessary to remove a part of a main busbar, it is required
that discrete lengths of busbar shall be able to be withdrawn without disturbing adjacent busbar
lengths; this may be achieved by the use of compressible bellows or other approved means. The
equipment shall be arranged to avoid excessive dismantling in the event of a main busbar fault.
Information shall be provided with the Tender to indicate the facilities incorporated in the equipment
to allow removal of busbars and the consequential maximum extent of dismantling that may be
involved in the event of such a fault.

The bus bar system shall be fully gas insulated, 3 phase and rated to withstand all dynamic
thermal and dielectric stresses for the full length of the Gas Insulated Switchgear. Bus bars and
connections shall be adequately sized, braced and supported to withstand the mechanical forces
and thermal effects resulting from the GIS rated short circuit current and carry certification from a
recognized testing authority.

Bus bar joints and connections shall be designed to be maintenance free for the life of the
equipment without the need for tightening of bolted connections. The SUPPLIER shall provide
details on the proposed method of bus bar jointing in their Bid.

Main bus bar sections shall be rated as specified on Project Data Sheets and shall be of the same
current rating throughout their length.

No wiring shall be contained within bus bar compartments.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 23/45
Ref. FEED DOC. No. :

The main bus for the end section cubicles shall be pre-drilled and insulated to facilitate future
extension on either end of the board. For connecting new sections of bus bar it shall not be
necessary to remove, cut, drill, or bend the existing conductors.

11.6 Grounding

A common copper earth bus bar having the same fault withstand capability as the main bus bars
shall be provided continuous through the bottom of the GIS for grounding of cable screens, armors
and gland plates. The earth bar shall be positioned and prepared so as to receive bonding straps
from the incoming and outgoing cables.

All metallic non-current carrying conductive parts of the GIS including hinged doors shall be
bonded to the earth bus bar.

Provision shall be made, adjacent to the cable termination, for grounding cable armor to the earth
bus bar.

All GIS units shall be supplied with two (2) grounding bosses for external grounding connections

All gland plates and doors shall be provided with flexible grounding connections connected to the
earth bar.

The earth bar extension shall be used to earth each end of the GIS Section system earth.
Grounding cables and extensions shall not restrict the removal of panels or access to cable
termination compartments.

Joints in the main earth bus bar shall be tinned and fixed with galvanized steel bolts, washers and
lock nuts.

Internal grounding and bonding wiring shall be identified by green/yellow outer sheath.

11.7 Circuit Breakers

11.7.1 General

SF6 gas insulated circuit breakers shall be single-pressure puffer or Self-blast or Self-
blast/Rotating Arc type, suitable for indoor installations. Circuit breakers shall be designed
to IEC 62271 - 203 and fully tested in accordance with IEC 62271 and with the
requirements of this Specification and shall be capable of carrying the specified rated
current continuously under the Site conditions.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 24/45
Ref. FEED DOC. No. :

The design of the circuit breaker shall be such that inspection and replacement of
contacts, nozzles and any worn or damaged component can be carried out quickly and
easily. The circuit breaker shall be fitted with the open/closed position indicators easily
visible from ground level. The inherent design of the circuit breakers shall be such that
one set of contacts and nozzle (or nozzles as the case may be) shall be able to
successfully interrupt at least twenty 100% fault currents without excessive erosion. The
over-voltages produced on any switching duty must be less (<<) than 2.5 pu. The sound
pressure levels of the breaker during the mechanical operations shall comply with the
local and national health and safety regulations. A suitably sized molecular sieve shall be
used in the circuit breaker tank to absorb any moisture and contaminants for at least ten
years in service.

The circuit breakers shall be suitable for 10,000 satisfactory open and close mechanical
operations in accordance with IEC 62271. A low gas pressure alarm and lockout system
with local and remote indications shall be provided on each circuit breaker. The low
pressure/density alarm switches shall instantly provide an instruction to the operator and
subsequently inhibit their further operation until suitable remedial action has been taken.

The continuous rating of the circuit breakers shall be equal to or greater than the specified
values on the Project data sheets.

HV power circuits shall be disconnected and remote control circuits shall be inoperable
when the circuit breaker is in test .

Power driven mechanisms which do not require manual assistance shall be used.

The rated short time withstand current and the rated making and breaking current for the
circuit breakers shall not be less than the ratings for the main bus bars of the Gas
Insulated Switchgear.

Circuit breakers shall be provided with trip circuit supervision to monitor trip circuit
continuity and trip circuit supply.

The operating mechanism shall be a stored-energy system for tripping and closing. It shall
consist of a motor-charged, spring operated type mechanism as specified in the
datasheet, complete with all associated devices and accessories for efficient and reliable
operation.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 25/45
Ref. FEED DOC. No. :

A local manual operating facility shall be provided.

Two trip coils shall be provided, one actuated by the main protection, and the other by
back -up protection circuit.

A graphic on the bay controller, which depicts the single line diagram of the feeder and all
devices status, shall be provided.

11.7.2 Spring Operation

The circuit breakers shall be fitted with power-spring mechanism. Other types of reliable
mechanisms such as leak-free Hydraulic, Spring/Hydraulic, and Spring/SF6 gas will also
be considered, provided they comply with the above circuit breaker mechanical
operations requirement.

A positively driven open/closed, mechanical indication device to show the position of the
main contacts and with local manual operated features for tripping, closing and spring
charging, visible without the necessity to open the mechanism door, shall be provided.
The drive for the device shall be positive in both directions. The mechanism shall fully
close the circuit breaker and sustain it in the closed position against the forces of the
rated making current and shall fully open the circuit breaker without undue contact bounce
at a speed commensurate with that shown by tests to be necessary to achieve the rated
breaking capacity in accordance with IEC 62271. The mechanism shall be capable of
being locked in the open position. When an auto-reclose facility is specified, the
mechanism shall be capable of fully closing and opening again after the auto-reclose time
interval specified i.e: performing a complete O-0.3 sec-CO-3 min-CO duty. Mechanical
counters, to record the number of closing operations, shall be provided for each circuit
breaker mechanism. The mechanism and the connected interrupters shall satisfy the
mechanical endurance requirements of IEC 62271 and all additional requirements
specified herein.

Motorized spring charging shall be automatic. When fully charged, the spring set shall
store sufficient energy to perform a trip-close-trip sequence without assistance from an
external power source.

It shall have provision for local and remote indication of the spring charged condition and
the spring failed condition.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 26/45
Ref. FEED DOC. No. :

It shall be possible to hand charge the operating springs with the circuit breaker in either
the open or closed positions. In normal operation, recharging of the operating springs
shall commence immediately and automatically upon completion of the closing operation
and shall be completed within 30 seconds. Closure whilst a spring charging operation is in
progress shall be prevented, and release of the springs shall not be possible until they are
fully charged. The state of charge of the operating springs shall be indicated by a
mechanical device which shows `SPRING CHARGED' when operation is permissible and
`SPRING FREE' when operation is not possible. A local manual spring release device
shall be provided and so arranged as to prevent inadvertent operations.

11.7.3 Local control

The following facilities shall be provided at each circuit breaker local control point:

a) LOCAL/REMOTE selector switch. The selection of `local' operation shall inhibit the
operation of the breaker from any remote source with the exception of the protection
scheme.

b) OPEN/NEUTRAL/CLOSE control switch or open and close push buttons.

c) EMERGENCY TRIP DEVICE, suitable for manual operation in event of failure of


electrical supplies. The device shall be accessible without opening any access doors
and distinctively labeled and protected against inadvertent operation.

A local point of control shall be provided which is local to the substation but remote from
the switchboard in the from a remote control box located within the vicinity of the
switchboard. A test facility shall also be provided on all circuit breakers when in test with
the primary contacts isolated but secondary contacts maintained to include all external
interlocks.

The selector switch shall be lockable in both positions and the control switch shall be
lockable in the neutral position. For maintenance purposes, means shall be provided for
manual operation including the slow closing and opening of those circuit breakers whose
moving contacts are mechanically coupled to the direct linkage mechanism. A suitable
interlock shall be provided between slow closing and the fast normal operation. Such
operation shall be possible without the necessity of gaining access to the interior of the
power unit, and shall not require excessive physical effort.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 27/45
Ref. FEED DOC. No. :

The breaker shunt-operating mechanism shall be capable of closing with the control
supply energized at 110%, 100% and 85% of the rated supply and opening with the
supply at 110%, 100% and 75% of the rated supply voltage.

The circuit breaker shall be driven by a single mechanism coupled to the three phases.
The circuit breaker shall be mechanically and electrically trip-free.

Alarm and indication facilities shall be provided for each circuit breaker and a volt free
group contact provided via internal bus wiring for remote common alarm.

11.7.4 Disconnect Switches

The GIS disconnect switches shall be constructed and fully tested in accordance with the
requirements of IEC 62271 and this Specification. The design shall incorporate features,
which shall reduce or eliminate very high frequency voltage transients during disconnect
switch operation.

The disconnect switches shall be provided with power and manually operated
mechanisms. The power operation of the disconnect switches shall be capable of being
controlled from a local or remote point. Each power-operated disconnect switch shall be
complete with a lockable LOCAL/REMOTE selector switch and OPEN/NEUTRAL/CLOSE
control switch or push buttons.

Where any particular scheme requires special timing of auxiliary contacts, these shall be
provided.

11.7.5 Earth Switches

GIS Earth Switches shall comply with IEC 62271 and the requirements of this
Specification. They shall be provided with power and manually operated mechanisms and
shall be provided on one or both sides of the disconnect switches dependent upon the
locations. The electrical operation shall be performed from their control cubicles. The
position indicators shall be clearly visible from the permanent working platform level.

Fully rated integral and mechanically interlocked grounding by means of dedicated


grounding switch shall be provided at the following places:

On all feeder circuit breakers : For cable grounding

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 28/45
Ref. FEED DOC. No. :

On incoming circuit breakers : For bus bars

All incomer grounding switches shall have a key interlock to eliminate the risk of closing
the grounding switch onto a live cable or bus bar. All feeder, incomer and bus bar
grounding switches shall have provisions for locking the switch in the closed position.

Operation of grounding switches shall be manual and only possible with the security door
closed.

All grounding switches shall be rated for the asymmetrical peak making current and the
rated short circuit current of the HV Switchgear. The design shall include appropriate
measures to protect an Operator from any harm if the grounding switch is closed onto a
live cable or bus bar.

11.8 Interlocks

Interlocks shall be provided for both general operation of GIS Switchgear and for specific switching
functions required for safe operation of the facility.

11.8.1 General Interlocks

It shall only be possible to open or close circuit breakers when the doors are closed and
secured. Mechanical interlocks shall be provided to ensure the following:

The operation of a circuit breaker shall not be possible unless it is in the service
or disconnected/test position or it is removed

It shall not be possible to electrically close a circuit breaker in the service unless
the 110Vdc tripping supply and all auxiliary and protective circuits are connected
and operable

A functional unit is prevented from being energized unless the door is closed and
secured

Simultaneous closure of devices is prevented where this may cause a fault (e.g.
forward and reverse contactors)

Inserting a circuit breaker into the service position is prevented unless the
grounding switch is open

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 29/45
Ref. FEED DOC. No. :

All locking shall be arranged such that it can be achieved by the use of padlocks. Barrel
type locks shall not be used. The following provisions for padlocking shall be provided:

Doors closed

Grounding switches closed

It shall not be possible to padlock any switching device, except grounding switches, in the
closed position.

11.8.2 Specific Interlocks

Where specified on the Project drawings, interlocking shall be provided by a mechanical


key operated interlock system for specific operations of 132kV Gas Insulated Switchgear.

12. GAS INSULATED SWITCHGEAR PROTECTION, CONTROL, METERING AND


AUXILIARIES

12.1 General

Tripping, closing, control and indication supplies for Gas Insulated Switchgear shall be as shown
on the Project drawings/data sheets and be complete with monitoring devices to detect
undervoltage or loss of supply.

All protection, monitoring and control functions shall be implemented using multi-function,
microprocessor based numerical relays and/or intelligent electronic devices (IED). All protection
relays and other IEDs shall have digital data communication ports internally wired in the switchgear
so that monitoring and control of the circuit breakers can be done remotely via external data
communication links if required.

Normal control and status monitoring of circuit breakers shall be from a separate local control
panel included as part of the SUPPLIER’s scope. The local control panel shall include Close/Open
manual controls and Closed/Open indication for all circuit breakers and fused contactors, arranged
on the front of the panel in the form of a synoptic diagram representing the physical arrangement of
the switchgear. All controls and indicating devices on the local panel shall be wired out to terminals
for hardwire connection (by others) between the local panel and the switchgear.

All stored data and configurable parameters of protection relays and IEDs shall be available for

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 30/45
Ref. FEED DOC. No. :

viewing/setting from a graphical user interface on the front of the device and shall also be available
via the internally wired data communication ports for use by remote monitoring and control systems
(by others). Facilities shall also be provided on the front of the device to permit the use of a hand
held digital device or laptop computer for downloading/viewing stored data and configuration
settings or to upload new configuration settings.

It is preferable that all protection functions should be combined into a single numerical relay. The
SUPPLIER shall offer a scheme that best suits this application.

Protection relays shall be of the draw out type. When drawn out the relay shall short-circuit all
connected CT circuits.

Test facilities shall be provided to allow secondary injection of current and voltage into the
protection relay, while isolating the instrument transformers.

All CT terminals on the protection relays and other IEDs shall be a bolted stud type and utilize ring
type compression lugs.

The control circuits of incomer circuit breakers and outgoing transformer feeders shall include
provision for implementation of inter-tripping and close permissive electrical interlocking schemes
such that the downstream incomer circuit breaker cannot be closed unless the upstream circuit
breaker is closed and will be tripped if the upstream circuit breaker is tripped or otherwise opened.
Furthermore, any earth fault protection trip of the incomer circuit breaker shall result in a trip of the
corresponding upstream circuit breaker via the inter-tripping circuit.

In some cases, as indicated in project data sheets/drawings, inter-tripping/permissive schemes or


pilot wire differential protection may have to be implemented via the use of fibre-optic interfaces
between protection and control relays in the upstream and downstream switchgear. In such cases,
the SUPPLIER shall include in the Gas Insulated Switchgear all necessary devices required for the
fibre optic interfaces.

12.2 Gas Insulated Switchgear Control

12.2.1 Local Panel

All panels shall be fitted with a 230 Volt single-phase receptacle and an interior light
controlled by a door-operated switch located inside the panel.

The panels shall be bolted to the floor. Any cable entering to the panels shall be tight and

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 31/45
Ref. FEED DOC. No. :

dustproof through suitable cable glands.

12.2.2 Gas Insulated Switchgear Modes of Operation

All of the following control modes are applicable only when the respective circuit breaker
is in service and otherwise will be inhibited. Refer to other relevant sections of this
specification for applicable control modes when a unit is in test.

Mode of control for the main circuit breakers shall be by manual operation of Open-0-
Close pistol grip control switches mounted on the front of the Gas Insulated switchgear
local control panel.

Alternative mode of control for the main circuit breakers shall be by digital commands
from an external monitoring and control system via the data communication interface with
the unit control and protection relay or IED. All main circuit breakers shall be capable of
this mode of operation irrespective of whether or not a digital monitoring and control
system is used.

As a general rule each feeder shall be tripped, regardless of the control mode, by the
following:

Electrical protection relays

A manual trip on the Gas Insulated Switchgear

A loss of power supply to a bus shall not result in a trip of any Gas Insulated Switchgear
unit other than protection inter-tripping of incomer circuit breaker.

12.3 Gas Insulated Switchgear Metering

The metering for each circuit shall be as shown on Project data sheets/drawings.

Unless otherwise specified, all metering shall be a part of the microprocessor based numerical
protection relay or other IED. However, analogue type voltmeter and ammeter shall be separately
provided wherever required in Project Data Sheets/drawings.

Analogue indicating meters, where specified, shall be flush mounted and comply with IEC 60051,
class index 2.5 and shall have an external zero adjustment.

The overall accuracy of the metering provided by numerical relays, IEDs and associated CTs shall
be 2% or better.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 32/45
Ref. FEED DOC. No. :

Minimum metering requirements for various feeders shall be as indicated in the Project Data

Sheets/drawings and the table below:


MWH Hours MVAH
Feeder Type A V Hz MW MVAR MVA
a) Run a)

X
Incomer X X X X - X X X
b)

Bus Tie X - - - - - - - -
Transformer
X - - - X - - - -
Feeder
Bus VT - X - - - - - - -

Notes:

d) MWh and MVAh, only when specified on project data sheets or where inherently
available in standard equipment.

e) VT connected on cable side of incomer circuit breaker.

f) 1 amp secondary CT wired to outgoing terminals for ammeter located at motor.

12.4 Current Transformers

Current transformers shall comply with IEC 60044-1. Current transformers shall be dry type. The
SUPPLIER shall supply all metering and protection CTs, including any neutral and restricted earth
fault CTs for installation by others, as shown on Project Data Sheets/drawings.

The selection of appropriate class of protection CT shall remain the responsibility of the SUPPLIER.
The SUPPLIER shall size the CT to ensure correct operation of the protection equipment. The
SUPPLIER shall provide calculations to justify the selection.

The rated accuracy limit factor for protection CTs shall be selected such that the accuracy limit
primary current is greater than the prospective rms fault level of the Gas Insulated Switchgear
(based on GIS rating).

Measurement CTs shall preferably be selected such that the nominal current is not less than 25%
of the CT rated current.

In general, the transformation ratios of measurement CTs shall be as shown on Project data
sheets/drawings.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 33/45
Ref. FEED DOC. No. :

CTs shall have a rated short-time current capability equal to that of the GIS bus bar short circuit
rating.

CTs shall be designed to prevent damage to instruments and protection relays when their primary
circuits are passing the rated short circuit current of the GIS.

CTs shall have a minimum accuracy designation as per relay manufacturer recommendations,
subject to a minimum as follows:

Measuring Class 1

Differential Class PX

Other Protection Class 5P

12.5 Voltage Transformers

Voltage transformers shall comply with IEC 60044-2. Voltage transformer shall be dry type.

Where not defined on Project Drawings, voltage transformers shall have a minimum accuracy
class as per the following:

Measuring Class 1.0

Protective Class 3P

The SUPPLIER shall be responsible for the selection of the VT burden and shall provide
calculations to justify the selection.

The VT primary windings shall be protected by removable HRC fuses. VTs and their associated
primary fuses shall be withdrawable.

All VTs shall have a secondary voltage of 110 V AC between phases. VT secondary windings shall
be protected by fuses and wired to terminals. Over current protection of VT secondary shall be
coordinated with VT rating / burden.

Protection and metering VTs shall be double wound with an earth shield between windings.
Secondary windings of VTs shall be earthed at one point through a removable link. Provisions shall
be made for attaching test links.

12.6 Electrical Protection Relays

Protection relays shall be multi-function, microprocessor based numerical type suitable for

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 34/45
Ref. FEED DOC. No. :

communication with external monitoring and control systems via data communications interfaces
using high speed industry standard open protocols. The communication protocol of the protection
relays shall be subject to COMPANY / CONTRACTOR’s approval.

Where applicable, lock out relays shall be electromagnetic type with hand reset facility. Lockout
relays or lockout circuits shall be arranged to ensure circuit breakers cannot be reclosed without
manual resetting.

The amount and type of protection functions, metering, and transducers to be incorporated into the
relay shall be as specified in the Project Data Sheets.

It is preferable that all protection functions for a given unit can be combined into a single numerical
relay. The SUPPLIER shall offer a scheme that best suits this application.

All stored data and configurable parameters of protection relays and other IEDs shall be available
for viewing/setting from a graphical user interface on the front of the device and shall also be
available via the internally wired data communication ports for use by remote monitoring and
control systems (by others). Facilities shall also be provided on the front of the device to permit the
use of a hand held digital device or laptop computer for downloading/viewing stored data and
configuration settings or to upload new configuration settings.

12.7 Control and Monitoring Interfaces

12.7.1 General

All gas zones shall be filled to the design pressure with pure SF6 gas (to IEC 60376/BS
5207) and shall be monitored individually by temperature compensated pressure switches
and pressure gauges. An alarm system shall be provided for each gas section, including
all relays, fascias, etc, these shall be accommodated adjacent to the switchgear.
Additional repeat alarms to announce remotely each alarm stage for the group alarms of
each switch bay shall be provided. The local control cubicle shall be adequately labeled to
allow easy identification of signals from each gas section. The low pressure/density alarm
switches shall be arranged to provide an instruction for the operation, either automatically
or manually of the circuit breakers and disconnectors adjacent to a faulted gas zone and
to subsequently inhibit their further operation until suitable remedial action has been taken.

Facilities shall be provided to constantly monitor the gas density. A low gas pressure
alarm and lock out system with local and remote indications shall be provided on each

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 35/45
Ref. FEED DOC. No. :

circuit breaker.

This specification shall be used for the bid and purchasing of the Gas Insulated
Switchgear. Configuration of data communications interfaces and details of data/control
functions shall be in accordance with project data sheets and drawings forming part of the
inquiry. Final configuration of data communications interfaces data/control command
function requirements shall be determined during bid evaluation and agreed with the
SUPPLIER before any purchase award.

The SUPPLIER shall be responsible for the supply of all application software and device
configuration tools, software licenses, OPC server software, configuration and
programming, factory acceptance testing and commissioning required for the interface of
protection relays and other IEDs with external monitoring and control systems.

The Gas Insulated Switchgear shall be designed to be capable of standalone operation


on failure of the communications with the external monitoring and control systems.

12.7.2 Power Distribution Monitoring and Control

All protection relays and other IEDs associated with non-motor circuit breaker and fused
contactor units shall have their communication ports wired to outgoing terminations in
such a way that they can be incorporated into external communication interfaces forming
part of a power distribution control and monitoring system provided by others.

12.7.3 Communication Protocol

Communication systems for Gas Insulation Switchgear with ECS shall conform to Modbus
TCP/IP.

12.8 Control Relays

Control relays shall be rated for their application and shall have a minimum rating as follows:

1 A at 500 V AC and 0.3 power factor (AC-15)

1 A at 250 V DC inductive (DC-13)

2 A at 60 V DC inductive (DC-13)

Control relays shall operate correctly between 85% and 110% supply voltage, measured at the bus
bars.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 36/45
Ref. FEED DOC. No. :

Control relays shall remain energized without chatter at 75% supply voltage, measured at the bus
bars. The dropout voltage shall not be lower than 10% supply voltage.

12.9 Control Switches/Push Buttons

The functional requirements of Control switches/Push-buttons shall be as specified in the Project


data sheets/drawings.

Control switches shall comply with IEC 60947-5-1.

Control switches/Push-buttons shall be rated for their application or, as a minimum, 1A at 500V AC
or 250V DC.

Circuit breaker shall be of rotary type, provided with suitable nameplate engraved with switch
operating positions. Breaker control switches shall be of pistol grip type, spring return with position
indicator, sequence interlock and normal after closing (NAC) contact (when specifically called for).
Selector switches shall have stay put positions with oval handle. The number of contacts and their
operation in each switch shall be as per the requirement specified in Project drawings/data sheets.

Push buttons shall be provided on the front door.

Stop Push Button - with stay put feature, (preferably lockable) with
mushroom head.

Reset Push Button - for hand-reset.

Colors of the push buttons:

Stop – red

Reset- black or yellow

For all feeder modules which include the contactor, the module shall be fitted with a ‘Local’ / ‘Off’ /
‘Remote’ rotary switch to control the operation of the modules, and ‘start’ and ‘stop’ push buttons
which are active only when the module is selected to ‘remote’.

12.10 Indication Lamps

Indicating lamps shall be provided on various feeders as indicated on the Project data
sheets/drawings.

Wherever required, indication lamps shall be clustered LED type. Color of the lamps shall be as

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 37/45
Ref. FEED DOC. No. :

follows:

On / Running : Red

Off / Ready : Green

Trip : Yellow

Trip Circuit healthy : Blue

Indicating lamps shall be flush mounted. Lamps operating at the same voltage shall be
interchangeable and the lamp holders and lenses shall be designed to dissipate continuously the
heat produced by the largest lamp that may be fitted, without deterioration and discoloration.

Indicating lamps shall be provided on the front of each Gas Insulated Switchgear module for each
outgoing module.

Each main switch and outgoing module shall be provided with a common ‘Lamp Test’ pushbutton
or similar function to enable the proving of all indication elements.

In general, indicating lamps shall be rated for the same voltage as the control circuits of the
respective module or circuit breaker. The lamps shall be able to be replaced from the front of the
panel.

12.11 Auxiliary Contracts

Auxiliary contacts on circuit breakers and contactors shall be rated AC -15, suitable for a nominal
control circuit voltage of 230 V AC and a current of 2 A.

Auxiliary contacts shall also be appropriate for a rating of DC-13, suitable for a nominal control
circuit voltage of 110 V DC and a current of 2 A.

Each contactor shall have a minimum of one open and one closed spare voltage free auxiliary
contacts wired to outgoing terminals, in addition to those required for the normal functioning of the
module.

Each circuit breaker shall be provided with a minimum of one open and one closed spare voltage
free auxiliary contacts, wired to outgoing terminals, in addition to those required for the normal
functioning of the module, subject to a minimum of six normally open and six normally closed
contacts. If spare auxiliary contacts are not available, an auxiliary relay shall be used to provide
this facility.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 38/45
Ref. FEED DOC. No. :

Each module shall be provided with a voltage free contact, wired to outgoing terminals, to indicate
fault status of the module.

Auxiliary contacts shall be wired to terminals via two isolating contacts per circuit, including the
spare contacts required as above.

12.12 Wiring

All panel and cubicle wiring shall have approved 600 V stranded copper, with heat, moisture and
flame resistant insulation, conforming to IEC 60227. The insulation shall have a glossy finish and
shall be incapable of supporting combustion. All wiring, other than that for light current (telephone
type) apparatus, shall be of 3/1 mm or, preferably, of 7/0.75 mm tinned copper. Single strand
copper wire, if proposed, shall be approved by the CONTRACTOR.

All cubicle wiring shall be neatly run and securely fixed in such a manner that, wherever practicable,
wiring can be easily checked against diagrams. Wiring passing out of the cubicles shall be run in
non-rustable flexible tubes or galvanized steel tubes. Wherever practicable, wiring shall be
accommodated on the sides of the cubicles and the wires for each circuit shall be separately
grouped.

Back-of-panel wiring shall be so arranged that access to the connecting stems of relays and other
apparatus and to contacts of control and other switches is not impeded. Where provision is made
for addition of equipment not required initially, means shall be adopted for supporting and
terminating wiring during the interim period. All wiring shall be taken to terminal boards and the
wires shall not be jointed or thread between terminal points.

12.13 Terminals

All connections for control circuit or power circuits loaded less than 16A shall be made by readily
accessible tunnel type terminal blocks, for all external wiring connections for controls, relays,
meters, interlocks, alarms etc. The terminals shall incorporate captive pressure screws which do
not bear directly on the wire.

Terminal blocks shall be arranged and positioned to afford ready access for carrying out external
cable termination, testing, inspection and maintenance. There shall be ample clear space allowed
between the terminals and the gland plate for the spreading and termination of external conductors.
Terminal blocks shall be mounted in a single deck arrangement.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 39/45
Ref. FEED DOC. No. :

For all power circuits exceeding 16A load, terminals shall be of the moulded stud type. All terminals
shall be rated minimum 600V.

Terminal blocks shall have separate terminals for incoming and outgoing wires.

Terminals shall be numbered in accordance with the approved wiring diagrams. Each strip of
terminals shall be identified with a group label. In addition, each terminal in the strip shall be
labeled with its individual number.

Terminals for different voltage grades shall be separated by partitions.

Positioning of cable termination facilities shall avoid obstruction of other cable terminations,
removable covers, etc., and provide easy access for terminating cables. Cable supports shall be
provided (where practicable) by the SUPPLIER to avoid undue strain on the cable termination.

Minimum 25% spare terminals shall be provided.

Termination of single core cables shall be through a non-magnetic metal panel or gland plate and
provision shall be made for bonding and grounding any armor and/or concentric ground conductors.
Separate cable facilities shall be provided for each HV Switchboard cubicle and for power and
control cables.

12.14 Accessories

Illumination, controlled by toggle or door switches, shall be provided in equipment compartments of


Gas Insulated Switchgear. Lighting fixture switches shall be identified with engraved nameplates.

Power for lights and receptacles shall be rated for 220V AC supply. An appropriate circuit breaker
shall be provided at the point where the incoming power cable is terminated.

A data connection socket shall be provided at each HMI for connection of the Engineering
Workstation laptop. A standard three pin power socket and withdrawable support tray shall be
provided at each HMI for the Engineering Workstation laptop.

Handles for moving the breaker into the CONNECTED, TEST, or DISCONNECTED
position.

Device for manually charging the operating mechanism.

Necessary test plugs for draw out relays.

Mounting channels including foundation bolts.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 40/45
Ref. FEED DOC. No. :

Standard accessories and special tools

13. NOISE
Unless specification otherwise noise level shall be in accordance with the Specification “Equipment Noise
Control Specification” (2342-AA00-JSD-6000-01)

14. NAME PLATES AND LABELS


Name plates and label shall be of stainless steel and be permanently fixed and if specified shall be
engraved on plastic laminate and secured with non corrodible screws.

The lettering on name plates and labels shall be engraved, embossed or otherwise formed so as to
permanent.

All labels shall have black characters on white background except warning labels shall have white
characters on a red background.

Handwritten stickers or dymo-type or self tapping screws are unacceptable.

15. INSPECTION & TESTING


For the activities listed below, the SUPPLIER shall comply with the requirements specified in relevant
clauses of the Material Requisition/ Bid Document, in addition to the following:

15.1 Inspection

The COMPANY / CONTRACTOR or its authorized representatives shall be permitted at all times
free access to all parts of the SUPPLIER’s workshops that concern the construction and testing of
the Gas Insulated Switchgear.

15.2 Testing

All testing shall be carried out at the SUPPLIER’s test facility (except for type tests to be done in
other premises). Test equipment shall be supplied by the SUPPLIER and shall be calibrated within
six months of the test date. The minimum scope of testing is summarized below. The SUPPLIER
shall supply an ITP with the bid.

The SUPPLIER shall provide the COMPANY / CONTRACTOR with advance notice as per the
provisions of the Material Requisition, to witness tests performed in either the SUPPLIER’s shop or

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 41/45
Ref. FEED DOC. No. :

his sub- SUPPLIER’s shops.

15.2.1 Type Tests

Type Tests shall be carried out with supervision and certification by a recognized testing
authority. Where previous type testing has been completed on equipment of identical
design, type test documentation may be submitted in lieu of performing each of the listed
type tests. The tests for HV Switchgear shall comply with the requirements of IEC 62271.

On completion of tests and before dispatch of HV Switchgear from the SUPPLIER's works,
the SUPPLIER shall supply a full set of test documents to the COMPANY /
CONTRACTOR. The test documents shall include, but not be limited to, all of the test
data for the following Type Tests:

Dielectric type tests

Temperature rise test

Radio interference voltage (RIV) tests

Short-time and peak withstand tests

Switchboard making and breaking capacity tests

Protection of persons against dangerous electrical effects

Arc fault containment test

Lightning Impulse test

Tests to verify the degrees of protection of enclosures

15.2.2 Routine Test

Prior to delivery, each HV Switchboard/MCC unit shall undergo the following routine tests
and checks. Tests shall comply with the requirements of IEC 62271. Instrument
transformer routine tests to verify its class, ratio and rating shall comply with IEC 60044.

All tests may be witnessed by the COMPANY / CONTRACTOR.

Full written test reports shall be submitted to the COMPANY / CONTRACTOR on


completion of the tests:

Power-frequency voltage test on the bus bar

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 42/45
Ref. FEED DOC. No. :

Dielectric tests on auxiliary and control circuits

Measurement of bus bar resistance

Mechanical operation checks

Protection operation checks by primary injection of current as required.

Numerical relay functionality and calibration checks

Visual inspection of overall finish

Check of the HV Switchgear auxiliaries and accessories against specification


requirements

Check of the rating plate, nameplate and any additional markings and labels
required

Full functional testing of control and indication circuits and devices

Inter-changeability tests

15.2.3 Field Test

The following field tests shall be carried out and reported:

Gas leakage test

Operational test

Gas moisture measurement

Resistance test of conductor

Current transformer test

High voltage tests

15.3 Inspection and Test Plan(ITP)

The SUPPLIER shall submit an Inspection and Test Plan, in accordance with the Material
Requisition, along with the Bid documents. The ITP shall list all inspections and tests proposed for
the equipment by the SUPPLIER, between the date of ordering and the date of delivery.

The SUPPLIER shall be responsible for the planning and execution of all inspections and tests, but
the COMPANY / CONTRACTOR’s representative shall have the right to witness any or all of the

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 43/45
Ref. FEED DOC. No. :

manufacturing, inspection or tests.

The COMPANY / CONTRACTOR and the SUPPLIER shall sign off the final version of the ITP,
which, thereafter, shall form part of the contract documents.

The SUPPLIER shall provide the COMPANY / CONTRACTOR with advance notice as per the
provisions of the Material Requisition of the date on which any of the inspections or tests
nominated as Hold or Witness Points on the ITP are due to be carried out.

Certificates of Test shall be provided for each item of equipment to prove it has been satisfactorily
tested to meet all requirements of its appropriate manufacturing standards, whether or not
witnessed by the COMPANY / CONTRACTOR.

Where appropriate, test certificates shall state values for all test results. Tests for which the results
are indicated as pass or fail shall be qualified by the relevant acceptance criteria.

15.4 Commissioning and Start-Up

The SUPPLIER, in their Bid, shall identify any special requirements or recommendations for
SUPPLIER support during commissioning and start-up of the equipment supplied. The COMPANY
/ CONTRACTOR's final acceptance of the equipment will be subject to a performance test once
the equipment has been installed and commissioned.

15.5 Training and After Sales Support

The SUPPLIER shall comply with the relevant provisions of the Material Requisition / Bid
document for training and other activities.

The SUPPLIER, in their Bid, shall provide details of their after sales support capability.
SUPPLIER’s shall advise their nearest service representative and nearest service facility to the
project fabrication yard and the facility location

16. PAINTING
Unless specification otherwise painting shall be in accordance with the specification “Job design
specification for external surface painting” (IONE-AA00-SP-PR-2300)

17. SPARE PARTS AND SPECIAL TOOLS


Unless specification otherwise spare part and special tools shall be in accordance with the Specification

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 44/45
Ref. FEED DOC. No. :

“Spare parts requirement” (2342-AA00-JSM-603)

The Vendor shall submit with his proposal the following:

Construction and pre-commissioning spare part priced list.

Commissioning and start-up spare part priced list.

Two years spare parts priced list.

Capital spare priced list.

Priced list of special wrenches, tools and gauges required for the routine operation and
maintenance of the supplied equipment.

18. GUARANTEE AND WARRANTY


All equipment and component parts shall be warranted by the vendor against defective materials, design
and/or workmanship as required by the purchase order.

Length of warranty period shall be stipulated in the purchase order.

19. PREPARATION SHIPMENT

19.1 Packaging and Shipping

After inspection and test, equipment shall be completely free of water and dry before start of
preparation for shipment.

Preparation for shipment shall be in accordance with the VENDORS standards and as noted
herein. VENDOR shall be solely responsible for the adequacy of the preparation for shipment
provisions with respect to materials and application, and to provide equipment at the destination in
ex-works condition when handled by commercial carriers.

Adequate protection shall be provided to prevent mechanical damage and atmospheric corrosion
in transit and at the jobsite.

Preparation for shipment and packing will be subject to inspection and rejection by
COMPANY’S/CONTRACTOR’S inspectors. All costs occasioned by such rejection shall be to the
account of the VENDOR.

After inspection and test, equipment shall be completely free of water and dry before start of

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea


PROJECT SPECIFICATION

132kV GIS

DOC. NO. : IONE-AA00-SP-EL-1002


KARBALA REFINERY PROJECT Rev. 2 Page 45/45
Ref. FEED DOC. No. :

preparation for shipment.

Equipment shall be packed, securely anchored, and skid mounted when required. Bracing,
supports, and rigging connections shall be provided to prevent damage during transit, lifting, or
unloading. All temporary bracing/supports shall be marked "REMOVE BEFORE EQUIPMENT
COMMISSIONING AND STARTUP."

Flanged openings shall be protected with metal cover plates to prevent damage during shipment.
Covers shall be a minimum of 6 mm thick and shall be installed with a full-size gasket using a
minimum of 4 full diameter bolts. Large diameter flanges will require enough full diameter bolts to
seat the cover all around. The cover and flange shall be taped for waterproof protection.

Open ends of tubes and pipes shall be capped for protection. Female threaded connections shall
be plugged with solid metal pipe plugs, and male threaded connections shall be protected with full
metal pipe caps.

Separate, loose, and spare parts shall be completely boxed. Pieces of equipment and spare parts
shall be identified by item number and service and marked with CONTRACTOR’S order number,
tag number, and weight, both inside and outside of each individual package or container. A bill of
material shall be enclosed in each package or container of parts.

Exposed finished and machined surfaces, including bolting, shall be given a coating of rust
inhibiting compound. Internal metal surfaces shall be sprayed or coated with a suitable rust
preventative prior to shipment. Openings shall be suitably tagged to indicate the rust preventative
applied.

Mechanical seal assemblies shall be fully protected from rusting and entry of moisture and dirt.

One complete set of the installation, operation, and maintenance instructions shall be packed in
the boxes or crates with equipment. This is in addition to the number called for in the Purchase
Order.

19.2 Preservation and Storage

Equipment and materials shall be protected to withstand ocean transit and extended period of
storage at the jobsite for a minimum period of 12 months. Equipment shall be protected to
safeguard against all adverse environments, such as: humidity, moisture, rain, dust, dirt, sand, mud,
salt air, salt spray, and seawater.

HDGSK JV Gran Seoul Tower 1, 33, Jong-ro, Jongno-gu, Seoul, Korea

You might also like