DESIGN & BUILT OF 66/11KV SUBSTATIONS FOR LUSAIL WEST, LUSAIL WADI, LUSAIL NORTH, LUSAIL
CONTRACT:
MARINA AND LUSAIL QETAIFAN SOUTH SUBSTATION CONTRACT CODE: CP24
QATARI DIAR REAL ESTATE
INVESTMENT COMPANY & LUSAIL CONSULTANT
CLIENT: REAL ESTATE DEVELOPMENT :
CO,DOHA
SUBSTATION 66/11kV LUSAIL MARINA-04 DOCUMENT NO:
LUS-CP24-5495-10-33-R747
NAME: SUBSTATION
BAY NO: B31.LCC NAME: 66/11KV TX-1 66KV SIDE VOLTAGE
66kV PAGE : 1 of 18
LEVEL:
EQUIPEMEN 66 kV ALSTOM BAY CONTROL UNIT– C264 CHAPTER NO: REVISIO
- 0
T: N:
List of Content
1 BCU Details 2
2 CT Details 2
3 VT Details 2
4 Visual Check 2
6.1. CT Measurement 3
6
6.2. VT Measurement 4
6.3. Power Measurement 5
9 Functional Checks 14
11 Instruments Used 15
12 Remarks 15
Signature
1. BCU DETAILS:
Make : ALSTOM BCU Designation : C264
Cortec code : C264MB1I691002280300A060000N10 Firmware Version : 5.1.9.6
Nominal Current : 1.0 Amp Database Set Version : 0.1
BCU Sl.No. : 33890384/11/16 Auxiliary Volt. : 110V DC
IP Address : 10.22.91.66 Rated Frequency : 50 Hz
2. CT DETAILS:
Rated Primary Current : 400 A
Rated Secondary Current : 1A
Ignd-CT Rated Primary current : 400 A
Ignd-CT Rated Secondary current : 1A
3. VT DETAILS:
Rated Primary Voltage : 66 kV
Rated Secondary Voltage (L-L) : 110 V
Confirm that only ring type Lugs are used for all CT / VT. :
Signature
6.1. CT Measurement: Inject current in the BCU as per the table below and observe the reading on the BCU display, in
primary and secondary values.
Acceptance Norm
Primary current value should be as per CT primary ratio.
Tolerance ±0.5%
Current Injected at terminals X630 -(1,8,15,26) with Test Block TT1-BCU in service position.
Signature
6.2 VT Measurement: Inject Voltage in the BCU as per the table below. Observe the reading on the BCU display,
in primary values.
Acceptance Norm
Primary Voltage value should be as per VT primary ratio.
Tolerance ±0.5%
Voltage injected in terminals X16-(64,65,66,67) with Test Block TT1 in service position.
Signature
6.2. Power Measurement: Inject Current and Voltage in the BCU as per the table below. Observe the Power, PF and
Frequency readings on the BCU display.
Apparent Power = Tolerance ±0.5%
Active Power = Tolerance <1.5%
Reactive Power = Tolerance <3.0%
Frequency = Tolerance ±0.01Hz
6.2.1. Apply 3-phase, 63.5 V & 3-phase 1 A @ 0° phase shift.
Signature
7 BINARY INPUT:
Binary Input check: Threshold Check (V)
P Slot – 5 SPARE OK
P Slot – 6 SPARE OK
Signature
BI No. BI Assigned to as per approved Schematic drawings Pick up Drop out Tested( ) Remarks
47.50 44.20
O Slot - 1 CB LOSS OF SF6 STAGE-1 OK
Signature
N Slot – 3 SPARE OK
N Slot – 6 SPARE OK
N Slot – 7 CONTROL & I/L MCB TRIP/OFF OK
Signature
N Slot – 9 SPARE OK
N Slot - 15 SPARE OK
N Slot - 16 SPARE OK
Signature
47.50 44.90
L Slot - 1 F87 –B11 LINK-2 FAIL OK
Signature
L Slot – 5 SPARE OK
L Slot - 6 SPARE OK
L Slot - 14 SPARE OK
L Slot - 16 SPARE OK
Signature
K Slot - 9 SPARE OK
K Slot - 10 SPARE OK
K Slot - 11 SPARE OK
K Slot - 12 SPARE OK
K Slot - 13 SPARE OK
K Slot - 14 SPARE OK
K Slot - 15 SPARE OK
K Slot - 16 SPARE OK
Signature
J Slot - 1 SPARE OK
J Slot - 2 SPARE OK
J Slot - 3 SPARE OK
J Slot - 4 SPARE OK
J Slot – 5 SPARE OK
J Slot - 6 SPARE OK
J Slot - 7 SPARE OK
J Slot - 8 SPARE OK
46.80 43.80
J Slot - 9 SPARE OK
J Slot - 10 SPARE OK
J Slot - 11 SPARE OK
J Slot - 12 SPARE OK
J Slot - 13 SPARE OK
J Slot - 14 SPARE OK
J Slot - 15 SPARE OK
J Slot - 16 SPARE OK
Signature
I Slot - 2 SPARE OK
I Slot - 3 SPARE OK
I Slot - 4 SPARE OK
I Slot – 5 SPARE OK
I Slot - 6 SPARE OK
I Slot - 7 SPARE OK
I Slot - 8 SPARE OK
I Slot - 9 SPARE OK
I Slot - 10 SPARE OK
I Slot - 11 SPARE OK
I Slot - 12 SPARE OK
I Slot - 13 SPARE OK
I Slot - 14 SPARE OK
I Slot - 15 NO RELAY ANOMALY OK
Signature
9. BINARY OUTPUT:
Acceptance Norm:
Value of Binary Output should vary from Low to High during activation of BO
Resistance Value ≤0.2 Ohms
Signature
Signature
Signature
Signature
Signature
NOTE : BINARY INPUT EACH CARD FIRST INPUT CHECKED FOR THRESHOLD PICK UP & DROP OUT VOILTAGE
Signature