You are on page 1of 2

TN CR 0016

Isolation Transformers and Surge Protection

There is often confusion between the roles of Surge The main benefit offered by Isolation Transformers is
Protection Devices and Isolation Transformers. This the input-to-output isolation, where the output circuit
Technical Note attempts to clarify the applications that can be re-grounded and isolated from input or other
each is best suited to. ground noise sources. This isolation can also useful
where Ground Potential Rise protection can not be
Surge Protection Devices: afforded by normal bonding procedures.
Surge Protection Devices (SPDs), also known as
Transient Voltage Surge Suppressors (TVSSs) are Transformer Operation:
non-linear voltage clamping devices. They are The two winding Isolation Transformer is a useful
installed across the lines to be protected (in parallel building block for power conditioning applications. It is
with the equipment) and thus do not need to be rated not a power conditioner in its own right, but is one of
to the line current. The SPD is normally in a high the most effective devices available for rejecting
impedance state under nominal supply voltage common mode noise. Isolation Transformers have
conditions. Under transient conditions the line voltage very little effect on attenuating differential mode noise,
is increased by the transient voltage to a point where particularly at lower frequencies as they are designed
the SPD clamping threshold is reached. The SPD then as a “pass”device at power frequencies. When
rapidly moves into a lower impedance state, diverting coupled with a suitably grounded or shield, Isolation
the excess transient energy (current) to ground/source Transformers can present an effective barrier to high
and thus limiting the transient voltage to a safe level. frequency common mode noise and prevent
The SPD automatically resets after the transient. propagation of this noise to the down stream
equipment via the power supply or ground system
Series Filtering SPD:
A Series Filtering SPD is an improvement on the As shown below, a shielded Isolation Transformer
standard SPD where a low pass and RFI/EMI filter is provides a path for high frequency common mode
added. This secondary filtering stage reduces the rapid noise to flow via capacitive coupling to the grounded
rate of pre clamped voltage raise, plus provides further screen and thus back along the ground. For this
attenuation to the clamped voltage as well as small screening to be effective, the screen, transformer core
signal noise that may be below the SPD clamping and grounded conductors should be bonded together
voltage. The Surge Filter is series connected devices at a single point as shown.
and must be rated to the maximum circuit current.
COMMON
MODE NOISE SHIELD TRANSFORMER
CORE
Isolation Transformers: PHASE

Isolation Transformers are generally composed of two


separate windings with a magnetic shield between
LINE PRIMARY EQUIPMENT
these windings to offer noise control. The transformer SIDE
SECONDARY
SIDE

carries the full load current, and thus must be suitably


sized. Rather than employing non-linear clamping NEUTRAL

devices, the transformer operates by attenuation.


Attenuation is normally quoted in dB (decibels) for EARTH EARTH

small signal noise conditions (not large transient COMMON


conditions to which the Transformer may offer "SINGLE POINT"
EARTH

considerably less attenuation). Each quoted 20dB of


attenuation equates to a reduction in noise voltage by FIGURE 1. SHIELDED ISOLATION TRANSFORMER
a factor of 10. Hence 60dB attenuation is a 1000% The shielded Isolation Transformer can thus be seen to
reduction in the noise voltage between input and be effective against common mode noise and low
output. level transients but effectively provide no
attenuation of differential mode noise and

Phone 800-248-9353 Fax 800-677-8131 www.erico.com


transients. Isolation Transformers have other power flashover and potential damage to the down stream
conditioning qualities such as dampening three phase equipment.
harmonics, “capturing”triplen harmonics in the Delta of
a Delta - Wye transformer and enabling a stable Suitability:
ground reference to be established via a Neutral - The most common causes of industry power quality
Ground bond on the secondary side. equipment reliability problems is generally differential
Differential Mode* Common Mode** mode voltage transients. Electronic equipment is far
more susceptible to differential mode impulses than
LINE 1
VT TRANSIENT
LINE 1
common mode. Note that although most lightning
VOLTAGE
LINE 2 EQUIPMENT LINE 2 EQUIPMENT impulses are common mode at the point of coupling,
VT VT TRANSIENT

EARTH EARTH
VOLTAGES
these will be converted to a differential mode at the
service entrance by the presence of the neutral-ground
*Also known as Transverse,
**Also known as Longitudinal Mode bond. Thus Isolation Transformers are ineffective at
Normal or Metalic Modes
rejecting the most predominate type of transient. A
more effective transient protection device for sensitive
Consider now a high voltage, high current transient equipment is a SPD with low pass Series Filter. This
introduced onto a power line by the direct and indirect offers both effective common and differential mode
(induced) effects of lightning activity or a switching transient and noise protection.
surge. If these transients are differential mode (i.e.
induced onto a line with respect to neutral) then the In conclusion, there is an overlap in the protection
Isolation Transformer will effectively pass these provided by Isolation Transformers and SPDs
transients with little or no attenuation. This occurs combined with Low Pass Filters, but due to overall
because the Isolation Transformer is designed to performance, size, weight and cost the SPD is better
“pass”power frequencies in the differential mode, and for most industry protection applications. The smaller
the frequency make up of a lightning transient is such and lighter SPD provides superior protection against
that most of the energy content is in frequency differential mode transients and adequate protection
components below a few tens of kilohertz (i.e. well for an estimated 85 to 90% of industries noise
within the pass band of most Isolation Transformers). problems. This makes it the low cost first choice for
If, on the other hand, these signals are common mode, most installers in the protection of sensitive electronic
then a suitable shielded Isolation Transformer will industrial equipment such as PLCs.
provide effective protection against such surges
provided the peak voltage does not exceed the Isolation Transformers are still the best solution for the
insulation rating of the transformer. In some cases, small number of sites that have electrically noisy
the peak voltage magnitude resulting from a direct grounds or where isolation is required. However a SPD
strike to overhead, low voltage power feeds near the Filter may also need to be added to give effective
point of entry to a facility can exceed the insulation differential mode transient protection.
rating of a 1:1 Isolation Transformer, resulting in a

PROBLEMS SOLUTIONS
ISOLATION SPD WITH LOW PASS
TRANSFORMERS FILTER
Solution Cost $$$ $
Ground Potential Rise üüü û
Noise üü ü
Common Mode Transients üü üüü
Differential Mode Transients û üüü
[ û- no protection, ü- Good, üü- Better, üüü- Best,]

Phone 800-248-9353 Fax 800-677-8131 www.erico.com

You might also like