62.3:4200
D200357X012
April 2009 4200 Series Transmitter
W9274
W966/IL
W4271−1/IL
Figure 1. FisherR 4200 Series Transmitter Figure 2. FisherR 4200 Series Transmitter on a Control Valve
D200357X012
www.Fisher.com
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
Specifications
Available Configurations Power Supply: Output signal changes less than
See table 1 ±0.1% when operating terminal voltage varies
between 11 and 30 volts DC
Input Signal Source
Electromagnetic Compatibility for 4211 and 4221
J Standard single potentiometer, or optional
J dual potentiometer is the source for the
Meets EN 61326-1 (First Edition)
transmitter and travel limit alarm circuit inputs. Immunity—Industrial locations per Table 2 of
Refer to table 2 for zero and span limits. the EN 61326-1 standard. Performance is
shown in table 4 below.
Emissions—Class A
Transmitter Output Signal
ISM equipment rating: Group 1, Class A
Range: 4-20 mA DC transmitter output
Load Impedance: See figure 3. Travel Limit Alarm Relays
Output Current Limit: 30 mA DC maximum
Type: Two single-pole, double-throw relays
Contacts: 1 Form C, silver-nickel alloy with gold
Travel Limit Alarms
overlay
Number of Possible Alarms: Two or none. Each Service Rating: The relay rating is 5 amperes at
SPDT relay indicates limit and fault conditions as either 30 volts DC or 120 volts AC (resistive load).
follows: Life Expectancy: 100,000 operations at rated
load, or 50,000 operations at a typical in-rush
Operating Relay Coil NC Contact NO Contact
Condition State State State current of 10 amperes with a 120 volt AC lamp or
Travel within
motor load
energized open closed
limits
Travel beyond Operating Conditions
de-energized closed open
limits
Transportation
Power loss de-energized closed open Normal and Normal
Condition and Storage
NC—Normally closed. Contacts are closed when relay is de-energized
Operative Limits Reference
Limits
NO—Normally open. Contacts are open when relay is de-energized.
Ambient −40 to 71_C −50 to 80_C 25_C
Temperature (−40 to 160_F) (−60 to 180_F) (77_F)
Power Supply Requirements Ambient
Relative 10 to 95% 10 to 95% 40%
See table 3 Humidity
2
Product Bulletin
62.3:4200
April 2009 4200 Series Transmitters
Specifications (continued)
Electrical Classification Housing
Intrinsic Safety, Explosion proof, NEMA 4X; CSA Enclosure 4X; IP66
Dust-Ignition proof,
3
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
4
Product Bulletin
62.3:4200
April 2009 4200 Series Transmitters
PRINTED RELAY
WIRING FIELD PRINTED
NUMBER 1 WIRING BOARD
BOARD
TERMINAL TERMINAL
BLOCK BLOCK
NUMBER 1 NUMBER 3
TERMINAL
BLOCK TERMINAL RELAY
NUMBER 1 BLOCK NUMBER 2
NUMBER 2
W9275
W4675-1/il
D Easy Maintenance—The simple design of the motion to rotational. To reduce the possibility of
transmitter and alarms allows easy maintenance. physical damage if the linkage should slip, the
The high reliability of the instrument requires potentiometer has no physical stops. Zero and span
minimum spare parts inventory. can be adjusted as follows:
D Zero—Between 0 and 51 mm (2 inches) of
D Moisture Resistant—The field wiring travel, or between 0 and 105 mm (4.125 inches) of
compartment is isolated from the electronic travel.
compartment. This protects the electronic circuits
from any moisture brought into the housing via the D Span—Between 9 mm (0.3 inch) minimum
field wiring ports. span and 51 mm (2 inches) maximum span, or
between 17 mm (0.6 inch) minimum span and 105
mm (4.125 inches) maximum span.
D Field Reversible Action—The output is easily
reversed in the field simply by switching two Rotary-Shaft Valve—In typical valve applications,
potentiometer leads on the printed wiring board. the transmitter is mounted on the actuator as shown
in figure 2. A coupling connects the hub of the
D Electromagnetic Interference (EMI) actuator to the potentiometer shaft. To reduce the
Filters—Filters between the electronic compartment possibility of physical damage if the coupling should
and the field wiring compartment of the housing help slip, the potentiometer has no physical stops. Zero
provide protection against electromagnetic and span can be adjusted as follows:
interference.
D Zero—Between 0 and 90 degrees of shaft
rotation.
Applications
D Span—Between 15 and 90 degrees of shaft
Standard Position Transmitter
rotation.
Sliding-Stem Valve—In typical valve applications,
the transmitter is mounted on the actuator as shown Other Devices—The transmitter is mounted such
in figure 1. Two linkage configurations sense up to that the potentiometer shaft or linkage aligns with the
51 mm (2 inches) or up to 105 mm (4.125 inches) of motion of the device. The motion of the device
stem travel. The linkages incorporate mechanical should not exceed the zero and span input signal
gearing to linearize the transformation from linear limits in degrees of rotation.
5
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
PORT
1/2 NPT
(2 PLACES) TRANSMITTER FIELD WIRING
COMPARTMENT COMPARTMENT
102
(4.00)
159
(6.25)
102
(4.00)
CAP
(2 PLACES)
6 (0.25)
DIA.
35
(1.38)
67 75
(2.62) 21
(3.00) POTENTIOMETER
(0.81)
SHAFT
67
(2.62)
END VIEW
ALLOW 254 mm (10 INCHES)
FOR MAINTENANCE (2 PLACES)
SIDE VIEW
51
(2.00)
5/16-18UNC
13 DEEP
(0.53)
51
(2.00)
19A7968−E
B1910−3*A / IL
mm
BOTTOM VIEW (INCH)
Figure 5. Dimensions
6
Product Bulletin
62.3:4200
April 2009 4200 Series Transmitters
Other Devices—The transmitter is mounted such 3. Valve body design.
that the travel transducer aligns with the motion of
the device to allow straight retraction of the cable to
the transducer. The motion of the device should not
exceed the zero and span limits in mm (inches). 4. Other applications
Installation
Field wiring is inserted into one of the ports and
connected to the terminal blocks mounted on the Note
printed wiring board in the field wiring compartment.
The instrument with transmitter circuits and travel
limit alarms, and the instrument with alarms only (no Contact your Emerson Process
transmitter circuits), use terminal blocks numbered Management sales office for
1, 2, and 3 (see figure 4) on the printed wiring board. assistance in determining the type and
These terminal blocks are accessible when the field style of linkage and mounting
wiring compartment cover is removed. The hardware required for the application.
instrument with transmitter circuits only (no alarms)
uses a barrier strip mounted in the field wiring
compartment without the printed wiring board.
Dimensions of the transmitter housing are shown in
figure 5. Mounting dimensions are shown in figure 6.
Note
7
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
48 108
(1.88) (4.25)
86
(3.40)
271 ACTUATOR
(10.69) HOUSING
204
(8.00)
51
(2.00)
CONNECTION CONNECTION
NUMBER 1 NUMBER 2
204 1
(8)
10
(0.38)
111
(4.38)
GE16563-A / IL
NOTE:
1 FOR OTHER SIZES OF 585CLS ACTUATORS, THE MOUNTING PLATE
LENGTH WILL CHANGE DEPENDING ON THE CHANNEL WIDTH.
8
Product Bulletin
62.3:4200
April 2009 4200 Series Transmitters
Table 4. FisherR 4211 and 4221 Electronic Position Transmitter EMC Summary Results—Immunity
BASIC PERFORMANCE
PORT PHENOMENON TEST LEVEL
STANDARD CRITERIA(1)
4 kV contact
Electrostatic Discharge (ESD) IEC 61000-4-2 A
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
Enclosure Radiated EM field IEC 61000-4-3 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% A
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Rated power frequency magnetic
IEC 61000-4-8 60 A/m at 50 Hz A
field
Burst (fast transients) IEC 61000-4-4 1 kV A
Surge IEC 61000-4-5 1 kV (line to ground only, each) B
I/O signal/control
150 kHz to 80 MHz at 3 Vrms
Conducted RF IEC 61000-4-6 A
1 kHz AM at 80%
Specification limit = ±1% of span
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Table 5. FisherR 4200 Series Electronic Position Transmitter Hazardous Area Classifications—CSA (Canada)
CERTIFICATION TEMPERATURE ENCLOSURE
TYPE CERTIFICATION OBTAINED ENTITY RATING
BODY CODE RATING
Ui = 30 VDC
(Intrinsic Safety)
Ii = 150 mA
Class/Division
4211, 4221
Class I,II,III Division 1 GP A,B,C,D,E,F,G
Pi = 1.0 W T4(Tamb 71°C) 4X
Ci = 5 nF
per drawing GE16020
Li = 0 mH
(Explosion Proof)
4210, 4211,
Zone
CSA 4212, 4215,
Ex d IIC T5 −−− T5 (Tamb 71°C) 4X
4220, 4221,
Class/Division
4222
Class I, Division 1 GP B,C,D T5
4210, 4211,
4212, 4215,
Class II Division 1 GP E,F,G T5 −−− T5 (Tamb 71°C) 4X
4220, 4221,
4222
Table 6. FisherR 4200 Series Electronic Position Transmitter Hazardous Area Classifications—FM (United States)
CERTIFICATION TEMPERATURE ENCLOSURE
TYPE CERTIFICATION OBTAINED ENTITY RATING
BODY CODE RATING
(Intrinsic Safety) Vmax = 30 VDC
Class/Division Imax = 150 mA
4211, 4221
Class I,II,III Division 1 GP A,B,C,D,E,F,G
Pi =1.0 W T4 (Tamb 71°C) 4X
Ci = 5 nF
per drawing GE16019 Li = 0 mH
(Explosion Proof)
4210, 4211,
Zone
4212, 4215,
Class I Zone 1 AEx d IIC T5 −−− T5 (Tamb 71°C) 4X
FM 4220, 4221,
Class/Division
4222
Class I, Division 1 GP A,B,C,D T5
Class I Division 2 GP A,B,C,D T5
4211, 4221 −−− T5 (Tamb 71°C) 4X
Class II Division 2 GP F,G T5
4210, 4211,
4212, 4215,
Class II Division 1 GP E,F,G T5 −−− T5 (Tamb 71°C) 4X
4220, 4221,
4222
9
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
Table 7. FisherR 4211 and 4221 Electronic Position Transmitter Hazardous Area Classifications—ATEX
TEMPERATURE ENCLOSURE
CERTIFICATE TYPE CERTIFICATION OBTAINED ENTITY RATING
CODE RATING
II 1 GD
Gas T4 (Tamb 71°C)
Ui = 30 VDC
Ex ia IIC T4/T5—Intrinsic Safety T5 (Tamb 40°C)
4211, 4221 Ii = 150 mA
Dust Pi = 1.0 W IP66
Ex tD A20 IP66 T81°C (Tamb 71°C) Ci = 5 nF −−−
ATEX Li = 0 mH
Ex tD A20 IP66 T50°C (Tamb 40°C)
II 3 GD
Gas
Ex nL IIC T4—Type n T4 (Tamb 71°C)
4211, 4221
−−− IP66
Dust
−−−
Ex tD A22 IP66 T81°C (Tamb 71°C)
10
Product Bulletin
62.3:4200
April 2009 4200 Series Transmitters
11
Product Bulletin
62.3:4200
4200 Series Transmitters April 2009
Fisher is a mark owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson
Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property
of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end-user.