Professional Documents
Culture Documents
Air-Air Bushings PDF
Air-Air Bushings PDF
Additional custom designs and new custom designs available upon request.
Cantilever Testing
Cantilever loading test.
Applied Voltage
Testing
60 Hz WET applied volt-
age test, up to 150 kV.
Electrical Test
HV Bushing Reference Impulse BIL Chopped Wave Impulse Applied-Voltage Applied Voltage
Full Wave 2 ms 3 ms (60 Hz) Dry (60 Hz) Wet
15kV - 1200 Amps 125kV BIL - Pass 142kV - Pass 126kV - Pass 1 Min. 50kV - Pass 10 Sec. 45kV - Pass
15kV - 2000 Amps 125kV BIL - Pass 142kV - Pass 126kV - Pass 1 Min. 50kV - Pass 10 Sec. 45kV - Pass
27kV - 1200 Amps 150kV BIL - Pass 194kV - Pass 175kV - Pass 1 Min. 60kV - Pass 10 Sec. 50kV - Pass
27kV - 2000 Amps 150kV BIL - Pass 194kV - Pass 175kV - Pass 1 Min. 60kV - Pass 10 Sec. 50kV - Pass
38kV - 1200 Amps 200kV BIL - Pass 258kV - Pass 230kV - Pass 1 Min. 80kV - Pass 10 Sec. 75kV - Pass
38kV - 2000 Amps 200kV BIL - Pass 258kV - Pass 230kV - Pass 1 Min. 80kV - Pass 10 Sec. 75kV - Pass
38kV - 1200 Amps 250kV BIL - Pass 322kV - Pass 290kV - Pass 1 Min. 105kV - Pass 10 Sec. 95kV - Pass
38kV - 2000 Amps 250kV BIL - Pass 322kV - Pass 290kV - Pass 1 Min. 105kV - Pass 10 Sec. 95kV - Pass
Cantilever Test
HV Bushing Reference Top Transverse Force Bottom Transverse Force
Static Values (Ibf) Static Values (Ibf)
15kV, 125kV BIL - 1200 A 200 - Pass 200 - Pass
H-J Enterprises, Inc. • 3010 High Ridge Blvd. • High Ridge, Mo. 63049 USA • Phone: (636)-677-3421 • Fax: (636)-376-1624 • www.h-jenterprises.com