DATA PENGAMATAN

Spesifikasi AC Split Ruangan


Arus (A) 4.1 Panjang (m) 5.3
Daya input (W) 840 Lebar (m) 3.6
Refrigerant R22 Tinggi (m) 3.2
Cooling capacity (Btu/hr) 900
Luas Penampang (m2) 0.0476
Panjang (m) 0.7
Lebar (m) 0.07

Kompresor Evaporator
V P
I total cos Rh Rh Setting Keterangan
Waktu V I cos P total total v in v out Tin Tout
(ampere) phi in out Suhu Cuaca
(volt) (ampere) phi (kW) (volt) (kW) (m/s) (m/s) (˚C) (˚C)
(%) (%) (˚C)
16:10 225.8 3.45 0.966 0.754 228.7 3.62 0.966 0.777 1.6 3 22.6 14.5 58.2 71 16 Cerah
16:15 225.9 3.46 0.968 0.758 229.7 3.63 0.968 0.781 1.7 3.6 22.6 14.6 61.7 70.9 16 Cerah
16:20 226.3 3.46 0.965 0.755 229.8 3.63 0.965 0.778 1.7 3.3 22.8 14.9 62.5 70.9 16 Cerah
16:25 226.5 3.48 0.968 0.762 229.8 3.65 0.968 0.785 1.6 3.3 22 14.3 67.2 76.2 16 Berawan
16:47 229.7 3.43 0.96 0.75 230.1 3.6 0.96 0.774 1.4 2.9 24.7 25.2 73.8 79.5 27 Berawan
16:52 229.5 3.4 0.96 0.75 231.2 3.57 0.96 0.774 1.8 3.2 25.9 25 70.4 74.3 27 Berawan
16:57 229.7 3.4 0.967 0.755 231.7 3.57 0.967 0.778 1.6 3.5 26.2 25.5 70.5 73.3 27 Cerah
17:02 229.9 3.46 0.969 0.758 232.1 3.63 0.969 0.782 1.5 3.5 26.7 26 69.8 72.7 27 Cerah
VII. PROFIL SISTEM HVAC

TEGANGAN
235

230
Tegangan (V)

225

Setting 16˚C
220
Setting 27˚C
215

210
0 5 10 15 20 25
Waktu (Menit ke-)

ARUS
3.7

3.6

3.5
Arus (A)

3.4

3.3 Setting 16˚C

3.2 Setting 27˚C

3.1

3
0 5 10 15 20 25
Waktu (Menit ke-)

COS PHI (FAKTOR DAYA)


0.99

0.97

0.95
Cos Phi

0.93

0.91 Setting 16˚C

0.89 Setting 27˚C

0.87

0.85
0 5 10 15 20 25
Waktu (Menit ke-)
KONSUMSI DAYA
0.79
0.78
Daya Total (kW) 0.77
0.76
0.75
0.74 Setting 16˚C
0.73 Setting 27˚C
0.72
0.71
0.7
0 5 10 15 20 25
Waktu (Menit ke-)

SUHU
30

25

20
Suhu (˚C)

T in (Setting 16˚C)
15
T out (Setting 16˚C)
10 T in (Setting 27˚C)

5 T out (Setting 27˚C)

0
0 5 10 15 20 25
Waktu (Menit ke-)

KELEMBABAN
90
80
70
Kelembaban (%)

60
50 Rh in (Setting 16˚C)
40 Rh out (Setting 16˚C)
30 Rh in (Setting 27˚C)
20
Rh out (Setting 27˚C)
10
0
0 5 10 15 20 25
Waktu (Menit ke-)
ENTALPI
70
65
60
55
H (kJ/kg)

Hin (16˚C)
50
Hout (16˚C)
45
Hin (27˚C)
40
Hout (27˚C)
35
30
0 5 10 15 20 25
Waktu (Menit ke-)

ENERGI DI EVAPORATOR
1200

1000

800
Energi (kJ)

600
Setting 16˚C
400 Setting 27˚C

200

0
0 5 10 15 20 25
Waktu (Menit ke-)

KERJA KOMPRESOR
0.067

0.065

0.063
Kerja (kWh)

0.061
Setting 16˚C
0.059 Setting 27˚C

0.057

0.055
0 5 10 15 20 25
Waktu (Menit ke-)
KINERJA SISTEM
6

4
COP

3
Setting 16˚C
2 Setting 27˚C

0
0 5 10 15 20 25
Waktu (Menit ke-)