Structural Description
-dimension of the tank = 20*28 m
-clear height =5.5 m
-water height =5 m
-the roof is flat slab with column head
-thickness of slab = 23 cm
-Spacing between the column:-
In longitudinal direction = 5.6 m
In transverse direction =5m
-column = 40*40 cm
-column head =1.25*1.25 m
- Column head height = 37 cm
-the wall variable thickness
At the bottom = 95 cm
At 2m from the bottom =50 cm
At the top = 30 cm
-The wall condition fixed - hinged
- Thickness of raft = 95 cm
- The raft rested on the plain concrete
- The raft rested on the pile
-Diameter of the pile = 50 cm
- The pile capacity = 70 t
Depth = 20 cm ts = 23cm
As = 14cm2 take 8 Ø 16 /m
M=3.5t.m/m
As =6.7cm2 take 8 Ø 12 /m
Field strip
y- direction
Reinforcement in y direction as X direction
Column strip
M-ve As = 14cm2 take 8 Ø 16 /m
M+ve As = 6.7cm2 take 8 Ø 12 /m
Field strip
2-design column
Ac =365.25cm2
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ
4-design wall
From sap :-
y- direction
Load on wall D.L+L.L+water
Assume the tank fill of water
The wall condition fixed - hinged
Maximum Moment at the bottom = 11.1t.m/m
Normal force (compression) = -12.11t.m
Take Bcr =0.75
Take factor =0.28
Category three
Design section subjected to B.M & N.F
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ
From equation:-
Inside the tank:-
Water section:-
= 0.127 n/mm2
=0.766 n/mm2
Ft =0.645n/mm2
=1
=3n/mm2
=3n/mm2
Safe
e=M/N = 0.917m
e/t =0.966>0.5 design as tension failure us es
es=e+0.5t-cov = 1.34m
Mu=Nu*es =24.32t.m
From equation:-
e=M/N = 0.41m
e/t =0.43<0.5 design as compression failure us interaction diagrams
Calculate the equation:-
= 0.0509
=0.021
From diagrams
=1.9
q= 0.2t/m
ɣ=1.8t/m3
Ka=0.33
Hwall= 5.5m
E1=Ka*q = 0.1t/m
E2=Ka*hw*ɣd =3.4t/m
5-design Raft
From sap :-
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ
X-direction
Load on raft D.L+L.L+water+ load from column +(moment &normal)
force from wall
Assume the tank fill of water
The raft rested on the pile
Take Bcr =0.85
Take factor =0.28
Category three
Design section subjected to B.M & N.F
M-ve = 17.52 t.m/m M+ve = 12.2t.m/m
N= +12.1t/m
From M- ve =17.52t.m/m
T(mm)=831mm
*check stress
From equation:-
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ
=0.811 n/mm2
Ft =0.93/mm2
= 1.7
=3n/mm2
=1.76n/mm2
Safe
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ
e=M/N = 1m
e/t =1.05>0.5 design as tension failure us es
es=e+0.5t-cov = 1.425m
Mu=Nu*es =25.86t.m
From equation:-
e=M/N = 1.44m
e/t =1.5>0.5 design as tension failure us es
es=e+0.5t-cov = 1.865m
Mu=Nu*es =33.84t.m
From equation:-
y- Direction
Reinforcement in y direction as X direction
Water section take As= 7 Ø 20/m
6-pile capacity
From sap :-
pile capacity
c118 -6.82E-07 c27 8.097086 c87 3.27E-07 c103 27.30554
c109 -6.53E-07 c51 9.790114 c75 3.56E-07 c100 27.3056
c107 -6.24E-07 c94 9.79018 c66 3.85E-07 c39 27.3067
c95 -5.95E-07 c45 9.790311 c53 4.15E-07 c36 27.30676
c119 -5.70E-07 c88 9.790378 c20 4.19E-07 c72 29.74005
c86 -5.66E-07 c73 10.82026 c44 4.44E-07 c68 29.74017
c74 -5.37E-07 c67 10.82038 c32 4.73E-07 c102 29.8546
c65 -5.07E-07 c113 11.12298 c30 5.02E-07 c101 29.85463
c52 -4.78E-07 c115 11.12303 c21 5.31E-07 c38 29.85579
c120 -4.59E-07 c24 11.12321 c111 3.232452 c37 29.85582
c43 -4.49E-07 c26 11.12326 c117 3.23247 c62 33.65326
c31 -4.20E-07 c114 12.12072 c22 3.232525 c83 33.65328
c29 -3.91E-07 c25 12.12098 c28 3.232544 c57 33.65338
c13 -3.62E-07 c105 16.21605 c106 5.714983 c78 33.6534
c121 -3.47E-07 c98 16.2162 c97 5.715165 c49 37.65176
c14 -2.51E-07 c41 16.2166 c42 5.715268 c47 37.65185
c122 -2.35E-07 c34 16.21676 c33 5.71545 c92 37.65187
c15 -1.39E-07 c104 22.25293 c64 8.012966 c90 37.65196
c123 -1.24E-07 c99 22.25302 c85 8.012975 c48 41.54199
c16 -2.73E-08 c40 22.25374 c55 8.013107 c91 41.54211
c124 -1.21E-08 c35 22.25384 c76 8.013116 c61 42.11433
c17 8.43E-08 c63 23.94942 c112 8.096894 c82 42.11434
c125 9.95E-08 c84 23.94945 c116 8.096944 c58 42.1144
c18 1.96E-07 c56 23.94958 c23 8.097036 c79 42.11441
ﺷﺮﻛﺔ ﻣﯿﺎه اﻟﺸﺮب ﺑﺎﻻﺳﻜﻨﺪرﯾﺔ
ﻗﻄﺎع اﻟﺪﻋﻢ اﻟﻔﻨﻲ
إدارة اﻟﺘﺼﻤﯿﻤﺎت اﻟﻤﺪﻧﯿﺔ واﻟﻤﻌﻤﺎرﯾﺔ
اﻻدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻋﻢ اﻟﻔﻨﻲ