Professional Documents
Culture Documents
Reciprocating Compressor
0178-915-EN Rev. 00.02 Christian X´s Vej 201, P.O. Box 1810, DK-8270 Højbjerg, Denmark
Phone +45 86 27 12 66 . Fax +45 86 27 44 08
00.01
Specifications for
SMC 104Ć106Ć108 Mk3 and TSMC 108 Mk3, SĆLĆE
The SMC/TSMC-type piston compressor can instruction manual, even if they are not fea-
be fitted with a range of equipment, depend- tured on your particular unit.
ing on the function and requirements it is ex-
pected to meet. The variants featured on the unit are marked
with an ’x’ in the following diagram, with the
Some of these variants are discussed in this serial number stated below.
Compressor type
Designation
Serial number
Refrigerant R717 ❑ R22 ❏ R134a ❏ R404A ❏ R507 ❏ _____ ❏
UNISAB II Control- and regulating system
Control
Analogue Control System
Thermopump
Water cooled top and side covers
Compressor
cooling Air cooled top and side covers
Oil cooling (water-cooled side covers)
Oil cooling OSSI/HE8S
Coupling
Drive type
V-belts
Explosion-proof electrical design
Pinion drive
Oil pump drive
Chain drive
Equipment for parallel operation
SABROE OVUR-type oil separator
0178-910-EN 1
Preface
The aim of this instruction manual is to this instruction manual to ensure reliable and
provide the operators with a thorough efficient operation of the plant as SABROE is
knowledge of the compressor and the unit, at unable to provide a guarantee against
the same time providing information about: damage occurring during the warranty period
where this is attributable to incorrect
S the function and maintenance of the
operation.
individual components;
96.06
to typical sources of errors which may occur
The contents of this instruction manual must
during operations. It states their cause and
not be copied or passed on to any
explains what should be done to rectify them.
0171-500-EN
unauthorized person without Sabroe’s
It is imperative that the operators familiarize permission.
themselves thoroughly with the contents of
In the space below you can enter the name and address of your local SABROE
REPRESENTATIVE :
2 0171-702-EN
List of Contents
Specifications for SMC 104-106-108 Mk3 and TSMC 108 Mk3, S-L-E . . . . . . . . . . . . . . . 1
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
List of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
First Aid for accidents with Ammonia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
First Aid for accidents with HFC/HCFC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Protecting the environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Description of compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Handling of the compressor, areas of application, safety equipment etc. . . . . . . . . . . . . . 16
Sound data for reciprocating and screw sompressor units - all types of compressors. . 17
Vibration data for compressors - all types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Compressor data for reciprocating compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operating limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
R717 - Operating limits single stage compressors CMO, SMC 100 S-L, SMC 180 . . 23
R717 - Operating limits single stage compressors SMC 100 E . . . . . . . . . . . . . . . . . . . 24
R717 - Operating limits two-stage compressors TCMO, TSMC 100 S-L-E, TSMC 180 . 25
R22- Operating limits single stage compressors CMO, SMC 100 S-L, SMC 180 . . . . 26
R22 - Operating limits two-stage compressors TCMO, TSMC 100 S-L, TSMC 180 . 27
R134a - Operating limits single stage compressors CMO, SMC 100 S-L . . . . . . . . . . 28
R134a - Operating limits two-stage compressors TCMO, TSMC 100 S-L . . . . . . . . . . 29
R404A - Operating limits single stage compressors CMO, SMC 100 S-L . . . . . . . . . . 30
R404A - Operating limits two-stage compressors, TCMO, TSMC 100 S-L . . . . . . . . . 31
R507 - Operating limits single stage compressors CMO, SMC 100 S-L . . . . . . . . . . . 32
R507 - Operating limits two-stage compressors TCMO, TSMC 100 S-L . . . . . . . . . . . 33
R407 - Operating limits one-stage compressors CMO & SMC . . . . . . . . . . . . . . . . . . . 34
General operating instructions for CMO/TCMO, SMC/TSMC piston compressors . . . . . 35
Starting up compressor and plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Stopping and starting-up compressor during a short period of standstill . . . . . . . . . . . 36
Stopping plant for brief periods (until 2-3 days) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Stopping plant for lengthy periods (more than 2-3 days) . . . . . . . . . . . . . . . . . . . . . . . . 37
Automatic plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Pressure testing refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Pumping down refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Operating log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Servicing the piston compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Pressure drop test: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Removing refrigerant from compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Lubricating oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Lubricating oil requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
General rules for use of lubricating oil in refrigeration compressors . . . . . . . . . . . . . . . 46
Instructions for choosing lubricating oil for refrigeration compressors . . . . . . . . . . . . . 46
Charging refrigeration compressor with lubricating oil . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Changing oil in refrigeration compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Charging the compressor with oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
0178-910-EN 3
Assessing the oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Visual assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Analytical evaluation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
The analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Expected discharge gas temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Servicing the refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Maintenance of reciprocating compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
1. If the compressor is operational . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
2. If the compressor is inoperative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Top covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Mounting top and water covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Discharge valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Tightness testing of discharge valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Cylinder lining with suction valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Connecting rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Piston . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Shaft seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Crankshaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Main bearings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Compressor lubricating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Oil pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Chain-driven oil pump with inverse direction of rotation . . . . . . . . . . . . . . . . . . . . . . . . . 72
Oil pressure valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
By-pass valve pos. 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Oil filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Suction filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Stop valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Unloaded start and capacity regulation on SMC and TSMC 100 and 180 compressors 81
Description of unloader mechanism and capacity regulation . . . . . . . . . . . . . . . . . . . . . 81
Pilot solenoid valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Schematic outlines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Standard unloaded start and capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Schematic drawings 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Totally unloaded start and capacity regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Schematic drawings 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Relief cylinders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Heating rods for heating the oil in reciprocating and screw compressors . . . . . . . . . . . . . 88
Stop valves pos. 23 and 42 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Monitoring cylinder lining insertion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
1. Checking clearance volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Adjustment is made as follows: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
2. Checking lifting reserve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Check lifting reserve: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Pressure gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Undersize Bearing Diameters for Crankshaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Sundry clearances and check dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
4 0178-910-EN
Torque moments for screws and bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Refrigeration Plant Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Operational reliability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Pumping down the refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Dismantling plant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Tightness testing and pump-down of refrigeration plant . . . . . . . . . . . . . . . . . . . . . . . . . 100
Trouble-shooting on the Reciprocating Compressor Plant . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Remedying malfunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Selecting lubricating oil for SABROE compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Data sheet for listed Sabroe oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
List of major oil companies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Alignment of unit, AMR coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Fitting and alignment of AMR-type coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Boring of motor flange for AMR coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
V-belt drive for piston compressor types (T)CMO and (T)SMC . . . . . . . . . . . . . . . . . . . . . . 150
Oil Separator OVUR for SMC/TSMC 100 HPC - SMC/TSMC 180 . . . . . . . . . . . . . . . . . . . 152
Connections on SMC 104-106-108 Mk3, HPC 104S-106S-108S . . . . . . . . . . . . . . . . . . . . 156
Connections on TSMC 108 Mk3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Oil return in parallel operation for reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . 158
Reciprocating compressors used for air conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Water-cooling of reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Pressure loss in water cooling on SMC/TSMC/HPC compressors . . . . . . . . . . . . . . . . 165
Thermo pump cooling of R717 reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . 166
Principle drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Oil cooling with an OSSI or HE8S oil cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
HFC and HCFC compressors: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Cooling of the intermediate gas on TCMO and TSMC 100 and 180 . . . . . . . . . . . . . . . . . 176
Ordering Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Spare parts sets for compressors and units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Compressor block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Spare part set for Basic Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
List of parts for SMC/TSMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0661-680
Tools for compressor SMC/TSMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0661-684
Spare Parts drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0661-521/0661-522
Spare Parts drawings (in detail) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0661-520
Piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Dimension sketch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Cooling water diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
Positioning of vibration dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . order specific
0178-910-EN 5
First Aid for accidents with Ammonia
(Chemical formula: NH3 - refrigerant no.: R717)
General Inhalation
Ammonia is not a cumulative poison. It has a 1. Move affected personnel into fresh air im-
distinctive, pungent odour that even at very mediately, and loosen clothing restricting
low, harmless concentrations is detectable by breathing.
most persons. Since ammonia is self-alarm-
ing, it serves at its own warning agent, so 2. Call a doctor/ambulance with oxygen
that no person will voluntarily remain in con- equipment immediately
centrations which are hazardous. Since am-
monia is lighter than air, adequate ventilation 3. Keep the patient still and warmly wrapped
is the best means of preventing an accu- in blankets.
mulation.
4. If mouth and throat are burnt (freeze or
Experience has shown that ammonia is ex-
96.01
acid burn), let the conscious patient drink
tremely hard to ignite and under normal water, taking small mouthfuls.
conditions is a very stable compound. Under
extremely high, though limited concentra- 5. If conscious and the mouth is not burnt,
0170-008-EN
tions, ammonia can form ignitable mixtures give hot, sweet tea or coffee (never feed
with air and oxygen, and should be treated an unconscious person).
with respect.
6. Oxygen may be administered, but only
Basic rules for first aid when authorized by a doctor.
1. Call a doctor immediately.
7. If breathing fails, apply artificial respira-
2. Be prepared: Keep an irrigation bottle tion.
available, containing a sterile isotonic
(0.9%) NaCl-solution (salt water).
Eye injuries from liquid splashes or
3. A shower bath or water tank should be concentrated vapour
available near all bulk installations with
ammonia. 1. Force the eyelids open and rinse eyes im-
mediately for at least 30 minutes with the
4. When applying first aid, the persons as- salt water solution just mentioned
sisting should be duly protected to avoid
further injury. 2. Call a doctor immediately.
6 0178-910-EN
Skin burns from liquid splashes or 2. Call a doctor immediately.
concentrated vapour
1. Wash immediately with large quantities of 3. After washing, apply wet compresses
water and continue for at least 15 minutes, (wetted with a sterile isotonic (0.9%)
removing contaminated clothing carefully NaCl-solution (salt water)) to affected
while washing. areas until medical advice is available.
0178-910-EN 7
First aid for accidents with HFC/HCFC
Refrigerant no.: R134a – R404A - R410A - R505A - R507 - R22, etc
General Inhalation
HFC/HCFC form colourless and invisible 1. Move affected person into fresh air im-
gasses which are heavier than air and smell mediately. Keep the patient still and warm
faintly of chloroform at high concentrations and loosen clothing restricting breathing.
only. They are non-toxic, non-inflammable, 2. If unconscious, call a doctor/ambulance
non-explosive and non-corrosive under nor- with oxygen equipment immediately.
mal operating conditions. When heated to
above approx. 300°C they break down into 3. Give artificial respiration until a doctor au-
toxic, acid gas components, which are thorizes other treatment.
strongly irritating and aggessive to nose,
eyes and skin and generally corrosive. Be- Eye injuries
sides the obvious risk of unnoticeable, heavy 1. Force eyelids open and rinse with a sterile
gases displacing the atmospheric oxygen, isotonic (0.9%) NaCl-solution (salt water)
inhalation of larger concentrations may have or pure running water continuously for 30
an accumulating, anaesthetic effect which minutes.
may not be immediately apparent. 24 hours
2. Contact a doctor, or get the patient to a
medical observation is, therefore, recom-
hospital immediately for medical advice.
mended.
Skin injuries – Freeze burns
Basic rules for first aid 1. Wash immediately with large quantities of
luke warm water to reheat the skin.
1. When moving affected persons from low- Continue for at least 15 minutes, removing
lying or poorly ventilated rooms where contaminated clothing carefully while
high gas concentrations are suspected, washing.
the rescuer must be wearing a lifeline, and
be under continuous observation from an 2. Treat exactly like heat burns and seek
assistant outside the room. medical advice.
8 0178-910-EN
Protecting the environment
Increasing industrialisation threatens our en- concentrations of refrigerant vapours are in-
vironment. It is therefore absolutely impera- haled they attack the human nerve system.
tive that we protect nature against pollution.
When halogenated gasses come into contact
with open flame or hot surfaces (over approx.
To this end, many countries have passed le-
300°C) they decompose to produce poiso-
gislation in an effort to reduce pollution and
nous chemicals, which have a very pungent
preserve the environment. These laws apply
odour, warning you of their presence.
to all fields of industry, including refrigeration,
and must be complied with. In high concentrations, R717 causes respira-
tory problems, and when ammonia vapour
Be especially careful with the following sub- and air mix 15 to 28 vol. %, the combination
stances: is explosive and can be ignited by an electric
96.01
HFC HCFC
Unit
TWA
Time weighted ave- vol.% 0,1 0,1 0,1 0,1 0,1 0,1 0,005
rage during a week
0178-910-EN 9
Further comments on refrigerants: Halogenated refrigerants must never be
S If released to the atmosphere, haloge- mixed. Nor must R717 ever be mixed with
nated refrigerants of the type HCFC halogenated refrigerants.
(e.g. R22) may cause a depletion of the
ozone layer in the stratosphere. The Purging a refrigeration plant
ozone layer protects the earth from the If it is necessary to purge air from a refrige-
ultraviolet rays of the sun. Refrigerants of ration plant, make sure you observe the follo-
the types HFC and HCFC are greenhouse wing:
gases with contribute to an intensification
of the greenhouse effect. They must, S Refrigerants must not be released to the
therefore, never be released to the atmo- atmosphere.
sphere. Use a separate compressor to
draw the refrigerant into the plant con- S When purging an R717 plant, use an ap-
denser/receiver or into separate refriger- proved air purger. The purged air must
ant cylinders. pass through an open container of water
so that any R717 refrigerant remaining
S Most halogenated refrigerants are mis- can be absorbed. The water mixture must
cible with oil. Oil drained from a refrigera- be sent to an authorized incinerating plant.
tion plant will often contain significant
amounts of refrigerant. Therefore, reduce S Halogenated refrigerants can not be ab-
the pressure in the vessel or compressor sorbed by water. An approved air purger
as much as possible before draining the must be fitted to the plant. This must be
oil. checked regularly using a leak detector.
S Even small amounts of ammonia in water In recent years alcohol, glycol and halogena-
(2-5 mg per litre) are enough to wreak ted compounds have been used in the brine
havoc with marine life if allowed to pollute production.
waterways and lakes.
In general, all brines must be considered as
S As ammonia is alkaline it will damage
harmful to nature and must be used with
plant life if released to the atmosphere in
caution. Be very careful when charging or
large quantities.
purging a refrigeration plant.
Refrigerant evacuated from a refrigerant
plant shall be charged into refrigerant cylin- Never empty brines down a sewer or into
ders intended for this specific refrigerant. the environment.
If the refrigerant is not to be reused, return it The brine must be collected in suitable con-
to the supplier or to an authorized incinerat- tainers, clearly marked with the contents, and
ing plant. sent to an approved incinerating plant.
10 0178-910-EN
Lubricating oils – alkyl benzene-based synthetic oil
Note
This instruction provides only general information. The owner of the refrigeration
plant is responsible for ensuring that all by-laws are complied with.
0178-910-EN 11
Description of compressor
SMC 104Ć106Ć108 Mk &
TSMC 108 Mk 3, SĆLĆE
96.12
by the first digit in the type designation. The SABROE
number of cylinders in the compressor block AARHUS DENMARK
0171-481-EN
is indicated by the following two digits, Type Refrigerant
where, for example, SMC 108 is an 8-cylin- Shop no Year
der compressor. SMC 100 is a one-stage Max. speed r.p.m.
compressor which compresses the gas in a
Swept volume m3/h
Working pressure bar
single stage.
Test pressure bar
12 0178-910-EN
der linings and are kept in position by a pow- At the axle end, the crankshaft is fitted with a
erful safety spring. The safety spring allows balanced slide-ringtype seal consisting of a
the discharge valve unit to rise, providing a cast iron ring with an O-ring which rotates
greater throughflow aperture in the event of with the crankshaft, and a stationary
liquid strokes in the cylinder. This prevents spring-loaded carbon ring.
any overloading of the connecting rod bear-
ings. All compressors can be capacity-regulated
by connecting or disconnecting the cylinders
The crankshaft is supported in slide bearings in pairs. The following diagram shows the
able to assimilate both radial and axial capacity stages at which the compressors
forces. The oil pressure for the bearings and can operate.
the capacity regulating system is supplied
from the gearwheel oil pump incorporated in Capacity regulation is controlled by means of
the compressor. solenoid valves mounted on the compressor.
SMC 104 x x
SMC 106 x x x
SMC 108 x x x x
TSMC 108 x x x
0178-910-EN 13
Handling of the compressor, areas of application,
safety equipment etc.
97.12
TSMC is indicated by an arrow cast into the SMC 100-TSMC 100 Mk3, S, L, E
compressor cover, near the shaft seal. SMC 180-TSMC 180,
On the BFO compressors the direction of HPO-HPC
0170-119-EN
rotation is not indicated by an arrow but is In view of preventing an unintended applica-
standard as illustrated by the following tion of the compressor, which could cause
sketch: injuries to the operating staff or lead to tech-
nical damage, the compressors may only be
applied for the following purposes:
Note: sors:
SMC-TSMC 100 E (only R717)
The compressor block alone may be lifted HPO and HPC (only R717 and R410A))
in the lifting eye. The same applies to the All other types of gas may only be
motor. used following a written approval from
SABROE.
The unit is lifted by catching the lifting eyes
welded onto the unit frame. These have been S As a heat pump:
14 0178-910-EN
– BFO 3-4-5 manual handle, to which there is free ac-
cess.
CMO - TCMO and SMC - TSMC may
be used with a max. discharge pressure S It must be able to stop any dangerous si-
of 25 bar. tuation, which may occur, as quickly as
possible without this leading to any further
– HPO – HPC may be used with a max.
danger.
discharge pressure of 40 bar.
S In an explosion-prone environment, pro- Combustion motors
vided the compressor is fitted with ap- If combustion motors are installed in rooms
proved explosion-proof equipment. containing refrigeration machinery or rooms
The compressor must NOT be used: where there are pipes and components con-
S For evacuating the refrigeration plant of air taining refrigerant, you must make sure that
and moisture, the combustion air for the motor is derived
from an area in which there is no refrigerant
S For putting the refrigeration plant under air
gas, in case of leakage.
pressure in view of a pressure testing,
S As an air compressor. Failure to do so will involve a risk of the lubri-
Emergency device cating oil from the combustion motor mixing
with the refrigerant; at worst, this may give
The compressor control system must be
rise to corrosion and damage the motor.
equipped with an emergency device.
In case the compressor is delivered with a Explosion-proof electrical execution
SABROE-control system this emergency de-
If the compressor is delivered in an explo-
vice is found as an integrated part of the con-
sion-proof electrical execution, this is stated
trol.
in the table on page 1 of this instruction
The emergency device must be executed in manual.
a way to make it stay in its stopped position,
following a stop instruction, until it is deliber- Likewise, the compressor will, besides the
ately set back again. It must not be possible SABROE name plate, be equipped with an
to block the emergency stop without a stop Ex-name plate like the one illustrated below.
instruction being released.
It should only be possible to set back the
emergency device by a deliberate act, and
this set back must not cause the compressor
to start operating. It should only make it pos-
sible to restart it.
0178-910-EN 15
The temperature of tangible surfaces close to the warning signs during operation
When a compressor is working, the surfaces are so hot that your skin may be burnt from 1
that are in contact with the warm discharge second’s touch or longer.
gas also get warm. However, the temperatu-
re depends on which refrigerants and under
which operating conditions the compressor
is working. Often, it exceeds 70°C which for
metal surfaces may cause your skin to be
burnt even at a light touch.
16 0178-910-EN
Sound data for reciprocating and screw
compressor units - all types of compressors
In the following tables the noise data of the S SAB 81-83-85-87-89, SAB 128, Mk3,
compressors is stated in: SAB 163 Mk3, SAB 202, SAB 330, SV
and FV:
– A-weighted sound power level LW
Compressor block + IP23 special motor +
(Sound Power Level)
oil separator.
– A-weighted sound pressure level LP
S SAB 128 HR and SAB 163 HR:
(Sound Pressure level)
Compressor block at max. number of
The values for LW constitute an average of a revolutions + IP23 special motor + oil
large number of measurings on various units. separator
The measurings have been carried out in ac-
cordance with ISO 9614-2. S SAB 110:
Compressor block + IP23 standard motor
The values are further stated as average + oil separator
99.06
pressors
Normally, the immediate sound pressure
±5 dB for VMY screw compressors
lies between the LW and LP values and can
be calculated provided that the acoustic data As to the reciprocating compressors the
of the machine room is known. values are stated for the compressor block
only.
For screw compressors the average values
are indicated in the tables for the following The dimensional values are stated for 100%
components. capacity.
Fig. 1
Fictional frame
Dimensional plane
0178-910-EN 17
Note the following, however: S the acoustics is another factor that can
change the sound level in a room. Please
S at part load or if the compressor works
note that the sound conditions of the site
with a wrongly set Vi the sound level can
have not been included in the stated
sometimes be a little higher than the one
dimensional values.
indicated in the tables.
S additional equipment such as heat ex- S by contacting SABROE you can have
changers, pipes, valves etc. as well as the sound data calculated for other operating
choice of a different motor type can in- conditions.
crease the noise level in the machine
room.
The tables have been divided into reciprocat-
S as already mentioned, the stated sound ing and screw compressors, respectively.
pressures are only average values above The reciprocating compressors are further
a fictional frame around the noise source. divided into one- and two-stage compressors
Thus, it is sometimes possible to measure as well as in a heat pump. In each table the
higher values in local areas than the ones operating conditions of the compressor dur-
stated – for inst. near the compressor and ing noise measuring have been stated, just
motor. as the refrigerant used has been mentioned.
18 0178-910-EN
RECIPROCATING COMPRESSORS Two-stage
One-stage Evaporating temperature = –35°C
Evaporating temperature = –15°C Condensing temperature = +35°C
Condensing temperature =+35°C Refrigerant = R22/R717
Refrigerant = R22/R717 Number of revolutions =1450 rpm.
Number of revolutions =1450 rpm.
Compressor block LW LP
SMC 112 S 99 82
SMC 116 S 100 83
Evaporating temperature = –35°C
Condensing temperature = +35°C
SMC 104 L 96 80
Refrigerant = R22/R717
SMC 106 L 97 81
Number of revolutions = 900 rpm.
SMC 108 L 98 82
SMC 112 L 100 83 Compressor block LW LP
SMC 116 L 101 84
TSMC 188 100 82
SMC 104 E 96 80
SMC 106 E 97 81
SMC 108 E 98 82 Heat pump
SMC 112 E 100 83 Evaporating temperature = +20°C
SMC 116 E 101 84 Condensing temperature = +70°C
Refrigerant = R22/R717
Number of revolutions =1450 rpm.
Evaporating temperature = –15°C
Condensing temperature = +35°C
Compressor block LW LP
Refrigerant = R22/R717
Number of revolutions = 900 rpm. HPO 24 91 76
HPO 26 93 78
0178-910-EN 19
SCREW COMPRESSORS
Evaporating temperature = –15°C Evaporating temperature = –35°C
Condensing temperature = +35°C Condensing temperature = –5°C
Refrigerant = R22/R717 Refrigerant = R22/R717
Number of revolutions = 2950 rpm.
Number of revolutions = 2950 rpm.
*Number of revolutions = 6000 rpm.
Compressor block LW LP
20 0178-910-EN
Vibration data for compressors Ć all types
Vibration data for SABROE screw compres- sor unit can - under normal circumstances -
sors comply with the following norm: be classified in Class III or IV according to
ISO 2372 group C the following table from ISO 2372. Recip.
compressor units can be classified in class
Depending on the laying of the foundation
IV, likewise under normal conditions.
and the size of the motor a screw compres-
Vibration severity ranges and examples of their application to small machines (Class I) medium size ma-
chines (Class II), large machines (Class III) and turbo machines (Class IV)
0.28
0.28
0.45
0.45 A
0170-115-EN
0.71
0.71 A
1.12
1.8
1.12 B A
1.8 B A
2.8
2.8 C B
4.5
4.5 C B
7.1
7.1 D C
11.2
11.2 D C
18 18
28
D
28 D
45
45
71
SABROE screw compressor unit: – Motor and compressor have not been
Group C, class III or IV aligned as described in the Instruction
SABROE recip. compressor unit: Manual.
Group C, class IV. – For screw compressors, if the compres-
sor runs at a wrong Vi ratio.
Pay attention to the following, however:
– The pipe connections have been
S On placing the unit on the vibration executed in a way that makes them force
dampers delivered by SABROE pull or push powers on the compressor
(additional) the vibrations against the unit or they may transfer vibrations to the
foundation are reduced by: unit, caused by natural vibrations or con-
nected machinery.
– 85-95% for screw compressor units
– The vibrations dampers have not been
– 80 % for recip. compressor units
fitted or loaded correctly as indicated on
S However, a higher vibration level may oc- the foundation drawing delivered
cur if: together with the order.
0178-910-EN 21
Compressor data for reciprocating compressor
CMO 4, CMO 24-28, TCMO 28, SMC 104-116,
TSMC 108-116, SMC 186-188, TSMC 188
Operating limits
SABROE prescribes operating limits within which the compressor and any additional equipment
must operate. These limits for R717, R22, R134a, R404A, R507 and R407C are shown in the
following tables, together with the main data for the compressor.
Bore Stroke Max/min Swept Weight
Compressor Number of Speed volume (max.)
type cylinders max RPM* compr. block
mm mm RPM m3/h kg
CMO 4 4 65 65 1800/900 93,2 200
CMO 24 4 70 70 1800/900 116 340
CMO 26 6 70 70 1800/900 175 380
CMO 28 8 70 70 1800/900 233 410
TCMO 28 2+6 70 70 1800/900 175 410
99.04
SMC 104S 4 100 80 1500/700 226 580
SMC 106S 6 100 80 1500/700 339 675
SMC 108S 8 100 80 1500/700 452 740
0171-476-EN
SMC 112S 12 100 80 1500/700 679 1250
SMC 116S 16 100 80 1500/700 905 1350
TSMC 108S 2+6 ♦ 100 80 1500/700 339 775
TSMC 116S 4+12 ♦ 100 80 1500/700 679 1400
SMC 104L 4 100 100 1500/700 283 580
SMC 106L 6 100 100 1500/700 424 675
SMC 108L 8 100 100 1500/700 565 740
SMC 112L 12 100 100 1500/700 848 1250
SMC 116L 16 100 100 1500/700 1131 1350
TSMC 108L 2+6♦ 100 100 1500/700 424 775
TSMC 116L 4+12♦ 100 100 1500/700 757 1400
SMC 104E 4 100 120 1500/700 339 600
SMC 106E 6 100 120 1500/700 509 700
SMC 108E 8 100 120 1500/700 679 770
SMC 112E 12 100 120 1500/700 1018 1300
SMC 116E 16 100 120 1500/700 1357 1400
TSMC 108E 2+6♦ 100 120 1500/700 509 800
TSMC 116E 4+12♦ 100 120 1500/700 1018 1450
SMC 186 6 180 140 1000/450 1283 2560
SMC 188 8 180 140 1000/450 1710 2840
TSMC 188 2+6♦ 180 140 1000/450 1283 2900
✶ The maximum speed permitted can be lower than stated here depending on operating
conditions and refrigerant; please see the following diagrams.
♦ Two - stage compressors (High Stage cylinders and Low Stage cylinders)
22 0178-910-EN
TC
°F °C R717
158 70 Operating limits
140 60 single stage
122 50 compressors
1 CMO
104 40 4
Condensing temperature
50 10
32 0 3
14 –10
–4 –20
–22 –30
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 40 °C
T245400_0/2
TE
–94 –76 –58 –40 –22 –4 14 32 50 68 86 104 °F
Evaporating temperature
NB: At part load the discharge gas temp. must not exceed 150°C/302°F
0178-910-EN 23
°F
TC
°C 1a R717
158 70 Operating limits
140 60 single stage
122 50 compressors
SMC 100 E
104 40 2
Condensing temperature
86 30
68 20 1
50 10
32 0
14 –10
–4 –20
–22 –30
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 40 °C
TE
104 °F
T245400_0/2
Evaporating temperature
Thermopump: Water-cooled:
Top- and side covers are cooled Top- and side covers.
by refrigerant injection. Oil cooling included in the system.
Oil cooling included in the system
NB: At part load the discharge gas temp. must not exceed 150°C/302°F
1a: In this area the compressor is not allowed to run at a capacity below 50%.
24 0178-910-EN
TC
°F °C R717
158 70
Operating limits
140 60
two-stage
122 50
compressors
104 40 1 TCMO
Condensing temperature
32 0
14 –10
–4 –20
–22 –30
0177128_0 VIEW 3,1
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 40 °C
TE
–94 –76 –58 –40 –22 –4 14 32 50 68 86 104 °F
Evaporating temperature
0178-910-EN 25
TC
°F
158
°C
70
R22
Operating limits
140 60
single stage
122 50
1
4 2 compressors
104 40
CMO
Condensing temperature
32 0
14 –10
–4 –20
–22 –30
0177128_0 VIEW 4,1
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 40 °C
TE
–94 –76 –58 –40 –22 –4 14 32 50 68 86 104 °F
Evaporating temperature
Type Area rpm Oil-cooling Note
max min required 1)
1 no
1500
2 no
CMO 900
3 At less than 50% capacity
1800
4 yes
1 1000 no
2 1200 no
SMC 100 S 700
3 1500 At less than 50% capacity
4 1200 yes
1 Not applicable
2 1000 no
SMC 100 L
3 1200 700 At less than 50% capacity
4 1000 yes
1-2 Not applicable
SMC 180 3 At less than 50% capacity
750 450
4 yes
26 0178-910-EN
°F
TC
°C R22
158 70
Operating limits
140 60
two-stage
122 50 compressors
3 1
104 40 2 TCMO
Condensing temperature
86 30
TSMC 100 S-L
4
68 20
TSMC 180
50 10
32 0
14 –10
–4 –20
–22 –30
–40 –40
40 °C
0177128_0 VIEW 5,1
Evaporating temperature
0178-910-EN 27
TC
°F °C R134a
176 80 Operating limits
158 70
1
single stage
140 60
2 compressors
122 50
CMO
SMC 100 S-L
104 40
3
Condensing temperature
86 30
68 20
50 10
32 0
14 –10
–4 –20
–22 –30
–40 –40
40 °C
T0177128_ V8,1
1200 no
1-2
1500 At less than 50% capacity
CMO 900
1500 no
3
1800 At less than 50% capacity
1 1000 no
2 1200 no
SMC 100 S 700
1200 no
3
1500 At less than 50% capacity
1 Not applicable
2 1000 no
SMC 100 L
1000 700 no
3
1200 At less than 50% capacity
28 0178-910-EN
TC
°F
158
°C
70
R134a
Operating limits
140 60 1
2 two-stage
122 50 compressors
104 40 3 TCMO
Condensing temperature
50 10
32 0
14 –10
–4 –20
–22 –30
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 40 °C
TE
T0177128_0 V8,1
Evaporating temperature
0178-910-EN 29
TC
°F °C R404A
140 60 Operating limits
122 50 single stage
1
compressors
104 40
CMO
Condensing temperature
32 0
14 –10
–4 –20
–22 –30
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 °C
TE
274263.1 Rev. 0
Evaporating temperature
30 0178-910-EN
TC
°F °C
R404A
140 60 Operating limits
two-stage
122 50
compressors
TCMO
Condensing temperature
104 40
1 TSMC 100 S-L
86 30
2
68 20
50 10
32 0
14 –10
–70 –60 –50 –40 –30 –20 –10 0 °C
TE
32 °F
274263.3 Rev. 0
Evaporating temperature
0178-910-EN 31
TC
°F °C R507
140 60 Operating limits
122 50 single stage
1
104 40
compressors
CMO
Condensing temperature
86 30
SMC 100 S-L
68 20
2
50 10
32 0
14 –10
–4 –20
–22 –30
–40 –40
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 °C
TE
–94 –76 –58 –40 –22 –4 14 32 50 68 86 °F
74263.2 Rev. 0
Evaporating temperature
32 0178-910-EN
TC
°F °C
R507
140 60 Operating limits
two-stage
122 50
compressors
TCMO
Condensing temperature
104 40
1 TSMC 100 S-L
86 30
2
68 20
50 10
32 0
14 –10
–70 –60 –50 –40 –30 –20 –10 0 °C
TE
32 °F
274263.4 Rev. 0
Evaporating temperature
0178-910-EN 33
TC
R407C
°F °C Operating Limits
140 60
one-Stage
122 50
Compressor type
104 40 1 CMO & SMC
Condensing temperature
86 30
2
68 20
3
50 10
32 0
14 –10
–4 –20
–22 –30
–70 –60 –50 –40 –30 –20 –10 0 10 20 30 °C
TE
–94 –76 –58 –40 –22 –4 14 32 50 68 86 °F
Evaporating temperature
T245411_0 view 2
34 0178-910-EN
General operating instructions
for CMO/TCMO, SMC/TSMC piston compressors
Starting up compressor and plant For pre-lubrication use a clean new refriger-
ant machine oil of the same type as the
S Before the initial start-up of the compres-
one found in the compressor, and pump as
sor following a lengthy stand-still period of
follows:
several months, the compressor must be
prelubricated. Hereby, the bearings are Pump strokes w. Estimated
lubricated and the oil system filled up Compressor SABROEs oil quantity
type hand-operated
with oil before the compressor is set run- oil pump Liters
ning.
CMO
Carry out the prelubrication by connect- TCMO appr. 25 2.5
ing the oil pump to the prelubricating HPO
SMC 104
valve which in the more recent SMC- 106-108 appr. 35 3.5
TSMC-HPC compressors is connected to TSMC 108
96.06
HPC
the shaft seal housing pos. 6A and on the
CMO-TCMO-HPO to the cover pos. 86H SMC 112-116
appr. 45 4.5
TSMC 116
0171-461-EN
0178-910-EN 35
S In order to avoid excessive pressure re- Stopping and starting-up com-
duction in the compressor on start–up, the pressor during a short period of
suction stop valve must be opened a few
standstill
turns, as there is otherwise a risk of oil
foaming in the crankcase. Before stopping the compressor, its capacity
must be reduced to the lowest capacity stage
S Open all other stop valves except for the for a few minutes, before it stops.
main valve in the liquid line and possible
During short periods of standstill, it is not
by-pass valves serving other purposes.
necessary to shut off the suction stop valve
and the discharge stop valve. The heating
S Check that the time relay 3K13 keeps the
rod must be energized.
solenoid valve in the oil return line closed
for 20-30 mins. after start-up of the com- If the compressor is cooled by means of cool-
pressor. ing water, the water flow must always be
stopped during periods of standstill.
S Start compressor motor and check suction This is normally done by means of a solenoid
and oil pressures. valve in the water inlet line to the compres-
sor.
S Carefully continue opening suction stop Connect the solenoid valve to the start/stop
valve to its full open position. relay of the compressor motor.
S Open main valve in liquid line. Compressor start-up must always take place
at the lowest capacity stage, after which ca-
S If the oil in the crankcase foams, or knock- pacity is increased stepwise at suitable inter-
ing noises are heard from the compressor vals, in order to avoid that a sudden exces-
because droplets of liquid are being fed in sive pressure reduction in the evaporation
with the suction gas, throttle suction stop system causes liquid hammering in the com-
valve immediately. pressor and oil foaming in the crankcase.
S Do not leave plant for first 15 minutes after S Cut off power supply to both master and
start-up and never before it has stabilized. control currents.
36 0178-910-EN
Stopping plant for lengthy periods – correct setting of safety automatics.
(more than 2-3 days)
S Shut off main valve after receiver and Pressure testing refrigeration plant
pump down evaporators. If necessary, ad- Before charging the plant with refrigerant, it
just low-pressure cut-out on unit to a lower must be pressure tested and pumped down.
pressure during evacuation.
Pressure test the plant with one of the follow-
S Allow temperature in evaporators to rise, ing:
then repeat evacuation.
S dry air - pressurized cylinders containing
S When suction pressure has been reduced dry atmospheric air may be used - but
to slightly over atmospheric, stop com- never oxygen cylinders;
pressor. Shut off suction and discharge
S air compressor for high pressure;
stop valves and close off stop valve in oil
return. S nitrogen.
0178-910-EN 37
S The entire unit must be pressure tested in atmospheric air and moisture. Evacuation
accordance with the local regulations for must be carried out on all types of refrigera-
pressure testing. tion plant, regardless of the type of refriger-
ant with which the plant is to be charged.
S The test pressure must never exceed the
disign pressure.
Observe that HCFC and HFC refrigerants
S If it is required that the compressor should mix only minimally with water, and it is there-
be pressure tested together with the unit fore necessary to effect evacuation of such
or with the plant, the testing pressure must systems with particular care.
not exceed:
For reciprocating compressors: The boiling point of a fluid is defined as the
HP side: 24 bar temperature at which the steam pressure
LP side: 17.5 bar equals atmospheric pressure. For water, the
boiling point is 100°C. Lowering the pressure
S Please observe that manometers, pres- also lowers the boiling point of the water.
sure controls, pressure transmitters and
other control equipment are not exposed The table sets out the boiling point of water
to testing pressure. at very low pressures:
S Afterwards, reduce pressure to 10 bar for
a period of 24 hours - as an initial tight-
Boiling point of At pressure
ness test - as a tightly sealed plant will water °C mm HG
maintain this pressure throughout the peri-
od. 5 6,63
10 9,14
During the tightness test, it is permitted to
15 12,73
enter the room and approach the plant.
20 17,80
S By way of a second tightness test, ex-
amine all welds, flange joints etc. for leak-
age by applying soapy water, while main- For evacuation, use a vacuum pump which
taining the 10 bar pressure. bleeds the plant of air and steam.
When pressure testing, compile a pressure The vacuum pump must be able to lower the
test report containing the following: pressure to approx. 0.1 mm Hg (mercury col-
S date of pressure testing, umn) and must be fitted with a gas ballast
valve. This valve should be used wherever
S person carrying out the test, possible to prevent water vapours condens-
ing in the vacuum pump.
S comments.
Important
Pumping down refrigeration plant
Never use the refrigeration compressor
Following pressure testing, the refrigeration to evacuate the plant.
plant must be evacuated in order to eliminate
38 0178-910-EN
For a satisfactorily performed evacuation, the S Blow dry air or nitrogen into system to a
final pressure must be lower than 5 mm Hg. pressure corresponding to atmospheric.
Attention is drawn to the fact that there may Never use OXYGEN cylinders.
be a risk of any water left in the refrigeration
S Repeat evacuation to reduce pressure to
plant freezing if ambient temperatures are
less than 5 mm Hg.
lower than 10°C. In such instances, it will be
necessary to supply heat to the component S Shut the vacuum pump off from refrigera-
surroundings, as ice evaporates with difficul- tion plant and check that the pressure
ty. does not rise for the next couple of hours.
If the system still contains water, this will
It is recommended to carry out evacuation as
evaporate and cause the pressure to rise,
follows:
thereby indicating unsatisfactory evacua-
S Evacuate to a pressure lower than 5 mm tion and necessitating a repetition of the
Hg. procedure.
0178-910-EN 39
Operating log This operating log should be kept at regular
intervals, thus providing important informa-
In order to keep tabs on the operating state tion about the cause of any undesired
of the refrigeration plant, it is recommended changes in the operating state.
that an operating log be kept. (See following page)
40 0178-910-EN
Servicing the piston compressor
0178-910-EN 41
1. Run compressor at lowest capacity stage
and throttle suction stop valve slowly until
completely closed.
42
Note:
The following instructions apply to the
compressor only. Servicing of the refrig-
42 eration plant is described in a separate
section. Service the compressor motor ac-
cording to your own instructions. For the
various scheduled services, SABROE can
Evacuating pump supply ready-made spare-part sets, which
it would be an advantage to have before
R22
carrying out the scheduled service.
42 0178-910-EN
Scheduled services
0178-910-EN 43
Operating Operating
No. hours hours Activity
< 1200 rpm > 1200 rpm
44 0178-910-EN
Operating Operating
No. Hours Hours Activity
< 1200 rpm > 1200 rpm
0178-910-EN 45
Lubricating oil
46 0178-910-EN
the crankcase, refrigeration oil may be therefore, it is necessary to refill with re-
topped up while the compressor is in opera- frigeration oil after starting up for the first
tion. time and after charging with fresh refriger-
ant.
For this purpose, use a manual oil pump or
adopt the following procedure: For a while after the plant is started for the
first time, keep an extra sharp eye on the oil
Note: level in the compressor, therefore.
When charging for the first time, use the
oil pump; it goes without saying that the
Changing oil in refrigeration com-
compressor must not be started unless
already charged with oil. pressor
S Cut off power to heating rod.
S Reduce pressure in crankcase, e.g. by
throttling suction stop valve, until suction S Close compressor stop valves and valve
pressure gauge shows pressure slightly in oil return line from oil separator.
below atmospheric.
S Reduce pressure in compressor crank-
S Fill pipe connected to oil charging valve case to slightly above atmospheric by
with refrigerator oil and insert free end of throttling suction stop valve while com-
pipe down into a receptacle containing pressor is running at its lowest capacity
fresh refrigerator oil. stage. Alternatively, raise to slightly above
atmospheric pressure by stopping com-
S Open oil charging valve carefully, thereby pressor and closing suction stop valve.
causing external air pressure to force oil Pressure in crankcase will then rise gradu-
into crankcase. ally.
S Avoid getting air or other impurities S Oil in the crankcase can then be forced
sucked into compressor. out through drain valve Pos. 23 when
compressor is at a standstill.
Note:
In order to achieve pressure below atmo- S Equalize pressure in compressor to atmo-
spheric, it will sometimes be necessary to spheric through purge valve pos. 42. See
reset the low-pressure cut-out so that the section on Environmental protection.
compressor can aspirate down to this
S Dismantle side covers.
pressure. Remember to reset the pressure
cut-out to its normal setting after charging S Replace oil filter cartridge with a new one.
with oil.
S Clean crankcase thoroughly, wiping with a
When in operation, the compressor may be clean, dry linen cloth (not cotton waste).
refilled with oil using the manual oil pump.
S Reassemble side covers.
Note:
S Charge to correct level with fresh, clean
Since halocarbon refrigerants such as
refrigerator oil according to SABROE’s oil
R22 mix with refrigeration oils, there will
recommendations.
always be a good portion of oil blended
with the refrigerant in the plant. Often, S Connect heating cartridge.
0178-910-EN 47
S Connect vacuum pump to compressor and 42 is open. See section on Environmental
pump down to 5-7 mm Hg; close off con- protection, however. When smelling R717,
nection. close purge valve.
48 0178-910-EN
Charging the compressor with oil
Compressor Volume of oil The oil level must be checked with extreme
in crankcase care, particularly when starting and charging
Type Size
Litres with refrigerant.
3 1,5 The oil level must always be visible in the
BFO 4 4
oil level sight glass. The below diagram
5 5
illustrates, how many litres of oil a drop in
24 14 the oil level of 10 mm is approximately
CMO 26 16 equal to.
TCMO 28 18
4 13
104 26
SMC 100 106 28
TSMC 100 108 30
Mk 3 112 47
S-L-E
116 50
0178-910-EN 49
We would, therefore, advise that the oil anal- As a special offer to our customers
yses be carried out at the intervals prescri- SABROE has developed an analytical con-
bed. cept, in cooperation with Mobil Oil, which is
able to analyse all oil makes. This will mean
An oil sample must be drawn off while the
a uniform reporting of the results.
compressor is in operation, which gives a
representative sample. Before taking the
The analysis allows the following to be deter-
sample, clean the drain valve and tap a little
mined:
oil off, to prevent any impurities which may
have accumulated in the valve or the piping S Whether or not the oil is still usable, if nec-
from mixing with the sample. essary after filtering.
If you don’t feel that you can approve the oil S A form set with a plastic sampling bottle
by visual assessment, charge with new oil or and a dispatching envelope can be re-
send a sample to a laboratory for analysis. quested from the local Sabroe Refrigera-
tion representation.
Warning
If the oil sample is poured into a glass bottle, S The oil sample must be drained from the
this must not be hermetically sealed until all cleaned oil drain valve into the sample
the refrigerant in the oil sample has evapora-
bottle. Screw the lid loosely on and let the
ted. Refrigerant in the oil may produce ex-
cess pressure in the bottle with subsequent bottle stand for a few hours to enable re-
risks of explosion. Never fill a bottle up com- frigerant contained in the oil sample to
pletely. Do not send glass bottles through evaporate before sending it to the labora-
the postal service – use purpose-made plas-
tic bottles. Please see below. tory.
50 0178-910-EN
The analysis Wear particles expressed im ppm, are mea-
sured for:
The following section states some average
values that can be applied in practice. How- Lead max. 10
ever, you should be on the alert whenever Copper max. 10
the results of the analyses approach these Silicon max. 25
values. In some cases the water content of Iron max. 100
Chrome max. 5
100 ppm in HCFC plants may be too much
Nickel max. 5
and thus lead to Cu–plating in the shaft seal. Aluminium max. 10
Similarly, a rise in the oil viscosity of max. Tin max. 10
65% normally does not cause any operating
A report is drawn up for every sample re-
problems as the refrigerant reduces the oil
ceived. This report indicates:
viscosity in the plant.
Whether the oil can still be used – without
Kinematic viscocity at +40°C.
taking any further action.
Max. indication from the specified value
at +40°C stated in the tables of Selecting Whether the oil can be used after it has
lubricating oil for SABROE compressors been filtered through a very fine filter.
–15% specified value +65%
If this is necessary, the oil must be
S Acid number (TAN). max.0.1
pumped directly from the compressor unit
S Oxidation. max.7 through a 3 micron filter and back to the
unit. The system must be completely
S Water content (ppm). max.100 (HCFC)
closed, to prevent the oil being affected by
S Water content (ppm). max.600 (R717) moisture in the air.
S pH value. min.4 (HCFC) Whether the oil is no longer fit for use.
S pH value. min.5 (R717) The report will always be sent to the address
stated on the sample label included in the
S Strong acids (SAN). max.0
form set. A copy will be sent to SABROE Re-
S The oil is filtered through two filters frigeration, so that we are in a position to ad-
(1,2 micron and 5 micron). vise you, if required.
0178-910-EN 51
Pressure and temperature settings for SABROE
compressor types SMCĆTSMC and CMOĆTCMO
Refrigerant
R404A
R134a
R507
R717
R22
24 bar (standard)
HP x x x x x
Safety valve 22 bar (special)
on the compressor
IP x x x x x 12 bar
96.04
(KP15) x x x x x 5° C lower than the lowest evaporating
cut-out
temperature.
1)
Oil pressure cut-out MP 55 x x x x x 3,5 bar
0170-012-EN
Discharge pipe x x x x * 120 ° C
KP 98
thermostat x * 150 ° C
Oil thermostat KP 98 x x x x x 80 ° C
Thermostat for KP 77 x x x x x 55 ° C
compressor cooling
Thermo valve for T(E) X Normally set at 4 ° C superheat.
compressor cooling T(E) Y x x x x Change to min. 10° C superheat
T(E) F
Control equipment
PMC + x x x -25 ° C
By-pass valve CVC x -15 ° C
Oil pressure x x x x x 4.5 bar 2)
regulating valve
* Factory setting - can be adjusted, if required, to a breaking point 20°C higher than the
highest normal discharge pipe temperature.
** For TCMO, R717 TEAT 20-2 spec., the factory setting is 85°C.
Adjust the TEAT valves so that the expected discharge pipe temperature (-5°C/+10°C) is achie-
ved at 100% compressor capacity.
Increase the opening temperature 10°C by turning the spindle 5 turns clockwise.
NB: Factory setting must always be increased by min. 10°C.
Adjustment of the TEAT valve must be carried out with the thermopump
out of operation
1) SMC - TSMC - CMO2 - TCMO2 3.5 bar 2) SMC - TSMC - CMO2 - TCMO2 4.5 bar
CMO4 0.8-1.2 bar CMO4 1.3 bar
52 0178-910-EN
0170-105-EN 96.02
0178-910-EN
20 5.7 38 41 43 48 55 8
8.2 37 48 61 76 91 11.0 40 42 46 53 62 7.6 53 71 91 110 131
25 6.6 44 45 48 52 59 9
9.5 47 57 69 84 101 12.5 44 47 51 58 67 9.1 65 83 102 121 142
30 7.7 49 50 53 58 11. 55
66 11.1 65 77 92 108 14.3 49 52 56 63 71 10.7 77 95 113 133 151
10 35 8.8 53 54 58 64 74 12.7 68 74 85 99 115 16.2 54 57 61 67 75 12.6 89 106 123 141 160
40 10.1 57 59 63 69 14
79 14.5 72 82 94 106 120 18.2 59 62 66 72 79 14.6 101 117 133 151 170
45 11.5 61 63 67 74 82 16.5 81 90 100 112 126 20.5 65 67 71 77 83 16.9 110 126 143 161 –
20 5.7 48 51 53 58 65 8
8.2 48 59 72 88 103 11.0 50 52 56 63 72 7.6 65 83 103 122 143
25 6.6 54 55 58 62 69 9
9.5 57 68 80 95 110 12.5 54 57 61 68 77 9.1 77 95 114 132 153
20 30 7.7 59 60 63 68 11
76 11.1 65 76 88 102 117 14.3 59 62 66 73 81 10.7 89 106 125 142 162
35 8.8 63 64 68 74 12
84 12.7 73 84 96 109 123 16.2 64 67 71 77 85 12.6 100 116 134 152 –
40 10.1 67 69 73 79 14
89 14.5 82 92 103 115 128 18.2 69 72 76 82 89 14.6 111 127 144 162 –
45 11.5 71 73 77 84 16
92 16.5 90 98 109 121 133 20.5 75 77 81 87 93 16.9 121 136 154 171 –
20 5.7 58 61 63 68 75 8
8.2 59 70 83 97 113 11.0 60 62 66 73 82 7.6 78 96 115 134 153
25 6.6 64 65 68 72 79 9
9.5 69 78 91 105 120 12.5 64 67 71 78 87 9.1 90 106 126 144 163
30 7.7 69 70 73 78 11
86 11.1 75 86 98 111 125 14.3 69 72 76 83 91 10.7 102 118 136 154 –
30
35 8.8 73 74 78 84 12
94 12.7 84 95 106 118 131 16.2 74 76 81 87 95 12.6 112 128 146 163 –
40 10.1 77 79 83 89 14
99 14.5 92 101 111 123 135 18.2 79 82 86 92 99 14.6 123 138 155 – –
45 11.5 81 83 87 94 102 16.5
16 99 108 117 128 139 20.5 85 87 91 97 103 16.9 132 148 165 – –
Discharge gas temp.° C Discharge gas temp.° C Discharge gas temp.° C Discharge gas temp.° C
53
Servicing the refrigeration plant
During both start-up and operation it must be S the condenser pressure is not excessively
made sure that the plant is working correctly. high, and
97.07
Check Interval Activity
0171-470-EN
Condensing pressure Excessively high pressure may be
due to:
• reduced cooling effect
Pressure • air in the condenser.
and temp. Too low condenser pressure im-
Daily
plies a risk of restricting the refri-
gerant supply to the evaporator.
54 0178-910-EN
Check Interval Activity
0178-910-EN 55
Maintenance of reciprocating compressor
SMC 104-106-108 Mk3, TSMC 108 Mk3 - S, L and E
SMC 112-116 and TSMC 116 Mk3 - S, L and E
00.01
All seals and gaskets used are resistant to
S Draw off last remains of refrigerant gas
oil, HFC/HCFC and ammonia. All O-rings are
through purge valve Pos. 42.
made of neoprene rubber.
0171-468–EN
S Having ensured that power to compressor
Pump-down motor cannot be inadvertently connected,
Before opening up the compressor for in- the compressor is ready for opening.
spection, the pressure inside must be low- S Remove all fuses, if any.
ered to slightly above atmospheric. This can
be done in the following way, depending on
2. If the compressor is inoperative
whether the compressor is operational or de-
fective. S Leave heating rod in crankcase connected
for a couple of hours before compressor
is due to be opened in order to heat up oil.
1. If the compressor is operational Warm oil does not contain as much refrig-
Run the compressor at minimum capacity at erant.
normal operating temperature.
S Suction stop valve must be open while
Adjust the low-pressure cut-out so that the heating rod is connected.
compressor stops at a suction pressure of
approx. 0.1 bar. S Keep discharge stop valve closed.
Throttle the suction stop valve very slowly. S Close suction stop valve and disconnect
Keep an eye on the suction pressure gauge. heating rod.
The suction pressure must be lowered slowly S Equalize pressure in compressor through
enough to give the refrigerant dissolved in purge valve Pos. 42.
56 0178-910-EN
S Once pressure has been equalized to at- de from a soft hammer while keeping the
mospheric, compressor is ready for two screws fitted. This must be done be-
opening. Remember to make sure that cause of the powerful spring pressure bene-
power cannot be inadvertently connected, ath the top cover. After dismantling the
thereby starting the motor. two bolts - unscrewing them alternately - the
top cover can be removed.
S Remove all fuses, if any.
Fitting top cover
Dismantling and assembly
Before fitting the top cover, the long plug
The following sections describe the individual must be fitted into the relief cylinder. Check,
components. When dismantling and assem- in addition, that the gasket Pos. 2C is intact
bling, parts should generally be fitted in the and, if necessary, check that the clearance
same position from which they were taken, volume and lifting reserve have been ad-
and should therefore be marked as they are justed as described later on in these instruc-
removed. Further they should be thoroughly tions.
cleaned, checked and lubricated prior to be-
ing reassembled. If the gasket Pos. 2C needs to be replaced at
all, the graphitized side must face the com-
Top covers pressor frame. After placing the top cover
loosely on top of the springs Pos. 21, it is
Dismantling top cover recommended that all screws be mounted by
Before dismantling the top cover, the relief hand, as they will jointly guide the top cover
mechanism must be deactivated; this is into position. Now tighten the top cover firmly
done by dismantling the short plug Pos. 12D with the two screws mentioned above, then
and mounting the long plug from the tool kit with the remaining ones.
instead. This moves the piston Pos. 12B to
the opposite end of the relief cylinder. Finally, cross-tighten all the screws to the
prescribed torque in the following sequence:
Loosen and remove screws Pos. 2E, except
for the two screws shown on the drawing.
7 1 3 5 9
11
15 13
16 14
12 10
8 4 2 6
These screws should be loosened approx. 1 Once the top cover has been fitted, remove
mm, then checking that the cover lifts off the the long plug and insert the short plug. The
gasket. If, to the contrary, it remains fastened top covers must be mounted as shown on
to the gasket, loosen it with a blow on the si- the following chart.
0178-910-EN 57
Mounting top and water covers
Shaft end
Shaft end
Shaft end
SABROE SABROE SABROE SABROE SABROE SABROE
Control end
SMC 104 SMC 106 SMC 108 TSMC 108
Shaft end
SABROE SABROE
Water covers
Right top covers
Shaft end
SABROE
SABROE SABROE SABROE SABROE
Side covers
T0177092_0
58 0178-910-EN
Discharge valve
21
20E
20F
20D
Pos. 20
0178-910-EN 59
Refrigerants HFC/HCFC : S Tighten bottom nut Pos. 20E to torque of
All discharge valves are marked with two 10.2 Kpm ≅ 100 Nm. If need be, exert
grooves. counterpressure with 5 mm Allen key on
bolt head.
60 0178-910-EN
Cylinder lining with suction valve Dismantling suction valve
Marking of suction valve stop: Dismantling the screws Pos. 19N makes it
possible for the guide ring Pos. 19J, suction
valve stop Pos. 19H and ring plate Pos. 19F
to be removed from the cylinder lining. The
Marking of
suction valve paper gasket Pos. 19T can be expected to
disintegrate during dismantling and require
replacement.
0178-910-EN 61
interior will catch the piston rings and S Remove nuts Pos. 17D; following this, the
squeeze them to the diameter of the cylin- bottom part of the connecting rod can be
der. If possible, fit cylinder in same place taken out by hand.
from which it was taken.
S Piston and connecting rod can then be
S Press cylinder lining down manually, and lifted out through the top cover opening on
with no rotary movements, until it makes the frame.
contact with gasket Pos. 19K. The connecting rod Pos. 17 is equipped with
independent bearings at both ends. The big
S Check clearance volume, which is de- end is fitted with two bearing half bushes
scribed in section Control measurements Pos. 17A, consisting of a half-cylindrical steel
for insertion of new cylinder lining. plate internally coated with white metal.
These bearing half bushes are secured in the
S Discharge valve Pos. 20 and safety head
connecting rod, partly through their fit in the
spring Pos. 21 can then be fitted.
connecting rod bore and partly by a spring
S Fit gasket and top cover. which fits into a milled groove in the connect-
ing rod. The opposite end of the connecting
S Once top cover is in position - see Top rod is fitted with the gudgeon pin bearing
covers section - remove long threaded Pos. 17B, of which the following two types
plug and screw in short plug, having first are found: See spare-parts drawing.
checked aluminium gasket Pos. 12E and S The bearing bushing Pos. 17B-1 is made
found it fit for use. of special bronze and is also used in
R717 compressors.
The bearing bushing is used in all SMC
Connecting rod
compressors and in the low pressure
The connecting rod pos. 17 is made of two stage on TSMC compressors.
parts carefully adapted to each other.
The two parts are held together by means of S The needle bearing Pos. 17B-2 is 2 mm
two bolts secured with lock nuts. greater in outside diameter than the above
bearing bush and must therefore be fitted
in a piston rod bored to the diameter of
Procedure for removing piston and
this bearing. The needle bearing has no
connecting rod inner ring but fits the diameter of the gud-
S Bleed compressor of oil and refrigerant geon pin directly.
and safeguard against any unintended
S If the bearings in the connecting rod are
start-up.
worn so that the clearance is greater than
that prescribed in the table entitled Vari-
S Disconnect any water hoses and other
ous clearances and adjustment measure-
piping connections to top and side covers.
ments, they must be replaced with new
S Dismantle top and side covers. bearings. In this connection, note that un-
dersized half sections of bearing can be
S Remove spring Pos. 21, discharge valve supplied for use in the crankshaft where
and cylinder liner. the journals have been ground to a corre-
62 0178-910-EN
sponding undersize. See table in section S Introduce connecting rod down through
on Diameters for undersized bearings. top cover opening in frame and guide into
position on crankshaft manually. Take care
Fitting bearings so that connecting rod bolts do not leave
S The bearing bushing or needle bearing marks in crankshaft journals.
can be squeezed into or out of the con- S Position connecting rod interior through
necting rod in a vice or hydraulic press. lateral opening on frame, and fit nuts.
Use softjaws in the vice and use tools
which do not damage any components. Note:
The bearing bushing must be fitted as The two parts of the connecting rod are
shown on the sketch, with the lubricating numbered with the same number; this is
ducts facing sideways. only of importance when assembling.
Parts with different numbers must not be
Fig. 1 assembled and it is important that the
Note:
numbers are fitted in the same direction
Sleeve to be
fitted with lubri- as shown in Fig. 2.
cating ducts
positioned as Fig. 2
shown on dra-
Note:
wing. Stamped number on
the same side on as-
sembly
T0177131_0 v2,a
0178-910-EN 63
Piston For compressors with:
The piston is made of aluminium and fitted 80mm stroke lengths, type S,
with two piston rings, nearest the piston top, 100mm stroke lengths, type L, and with
and an oil scraper ring. 120mm stroke lengths, type E.
The difference is clearly seen from fig. 3.
The piston comes in three versions:
Fig. 3
70 60 60
120 110 100
50 50 40
T0177131_0 v1
The same piston and piston pin are used, S Fit one of the circlips pos. 18D into bore
irrespective of whether the connecting rod reserved for piston pin.
contains a sleeve or a needle bearing.
S Heat piston to 70°C in oil or on hotplate.
64 0178-910-EN
Shaft seal
5.5 mm
8C
8H
2 mm
8A
8F
10F
10D
10E
10H
10J
10A
10G
10B
8G
8B
The carbon slide ring Pos. 10F is pressed When the shaft seal is operating, a tiny
against the flat-machined, lapped slide ring at amount of oil drifts out between the slide
the end of Pos. 10E by a series of springs faces to lubricate them. An oil throw ring Pos.
Pos. 10B. The carbon slide ring is prevented 8F has therefore been fitted to prevent this oil
from rotating by means of the retention pin migrating along the axle to the transmission
Pos. 8H. linkage.
The spring pressure, combined with the The thrower ejects the oil into the groove in
flat-lapped faces of the two slide rings, ensur- the shaft seal cover Pos. 8A and the oil is
es an optimal seal between the faces, either piped via the plastic hose to a plastic bottle
when rotating or stationary. positioned under the compressor.
0178-910-EN 65
1. Dismantling and stripping down shaft Fig. 3
seal
8G 10F 10G 8A 8C
1.1. Once the gas pressure in the compres-
sor has been eliminated and the motor
• •
safeguarded against inadvertent start-up,
dismantle coupling or V-belt disk.
Note: •
•
On units featuring coupling, there is no •
A
need to move the motor, as the coupling
and the shaft seal can be taken out be- •
tween the two shaft ends.
Circlip pos. 8G is now easily extracted by 1.6. O-ring Pos. 10D can now be removed.
means of a screw driver without damag-
ing the slide surface of the carbon slide Assembling and mounting shaft seal
ring. After thoroughly cleaning the crankshaft,
check that its sealing faces are smooth and
After removing tool no. 2, the carbon free of scratches, blows and wear marks.
slide ring pos. 10F, O-ring pos. 10G and Then oil the crankshaft and the shaft seal
springs pos. 10B (see fig. 2) can now be components thoroughly with the same type of
dismantled. oil as used in the compressor.
66 0178-910-EN
2. Unit with slide ring, Pos. 10E measure distance from gasket Pos. 8B to
2.1. Before fitting slide ring Pos. 10E, tighten sealing face of shaft seal cover.
screws Pos. 10J until there is approx. 2 This distance must be about 3 mm.
mm spacing and parallelism between the Make sure the hose branch Pos. 8D fa-
two flanges. Check also that locking ring ces down.
Pos. 10H is mounted as shown in the 3.5. Mount screws Pos. 8C and tighten even-
drawing and that O-ring Pos. 10D is in ly, crosswise. This will avoid damaging
position. the carbon slide ring. Tighten screws
2.2. Position slide ring Pos. 10E on shaft and Pos. 8C to prescribed torque according
ensure tightening flange makes contact to table in instruction manual.
with shaft shoulder. 3.6. Mount oil throw ring, as shown in
2.3. Crosswise, tighten screws Pos. 10J alter- drawing.
nately with Allen wrench from tool kit. 3.7. After mounting coupling half or V-belt
The torque is specified in the instruction disk, it must be possible to turn the
manual. crankshaft easily by hand.
2.4. Check axial position of shaft seal by
measuring distance from frame sealing Crankshaft
face to slide face on Pos. 10E. This must
The crankshaft is made of heat-treated SG
measure approx. 5.5 mm, as shown in
cast iron with fine strength and glide proper-
the drawing.
ties. The bearing journals are superfinished
and oil channels are bored for all lubricating
3. Unit with shaft seal cover Pos. 8A
points.
3.1. Mount O-ring Pos. 10G and the ten spiral
springs 10B in shaft seal cover Pos. 8A, At the centre and end of the crankshaft, the
then position carbon slide ring Pos. 10F oil channels are blanked off with 3 blind plugs
carefully. Rotate carbon slide ring so slot on the SMC 104 - 106 - 108, and 6 plugs on
fits in over retention pin Pos. 8H. the SMC 112 and 116.
3.2. With tool no. 2 fitted as shown in fig. 3
press carbon slide ring pos. 10F against When fitting the crankshaft, it should be
spring pos. 10B. Locking ring Pos. 8G checked that the plugs are mounted and
can now be fitted. Observe closely that tightened. By way of bores in the counter-
the carbon slide ring is not overloaded by weights, the crankshaft is dynamically bal-
misbalanced pressure and that its slide anced with regard to 1st and 2nd order
face is not damaged. forces.
3.3. Give complete shaft seal cover an extra
oiling on slide face of carbon slide ring The crankshaft is available in three versions:
and guide it in over shaft together with an S type for compressors with short strokes
gasket Pos. 8B. (80mm), an L type for longer stroke (100mm)
3.4. Gently pressing shaft seal cover and car- and an E type for the longest strokes
bon ring in against slide ring Pos. 10E (120mm). The crankshafts have an S, L or E
without compressing springs Pos. 10B, stamped into the connecting end.
0178-910-EN 67
Dismantling crankshaft Inspection
Dismantle the crankshaft through the pump Check bearing journals on connecting rods
end of the frame in the following way: for wear and tear and, if necessary, measure
diameter of journals. The maximum wear on
S Bleed compressor of oil and refrigerant the bearings is shown in the section Various
and safeguard against inadvertent clearances and adjustment measurements.
start-up. In most instances, the permissible play in the
S Dismantle top and side covers. bearing can be obtained by replacing the
bearing half bushes. The bearing journals on
S Dismantle all cylinder linings. the main bearings are normally subject to
very little wear, but should be check mea-
S Extract all pistons and connecting rods.
sured during main overhauls. If wear and tear
S Pull off V-belt pulley or coupling half . exceeds the play stated, the crankshaft can
normally be ground to 0.5 mm undersize. For
S Dismantle shaft seal cover and shaft seal. the ground crankshaft, main bearings and
connecting rod bearings with an undersize of
S Dismantle cut-outs and pipes to manome-
0.5 mm can be supplied as stated in the
ters, or piping connections to UNISAB.
parts list.
S Dismantle end cover, Pos. 4A.
The drawing for grinding the crankshaft to
S Dismantle oil filter. undersize is found in this instruction manual.
68 0178-910-EN
The permissible end play is indicated in Fig. 1
Mounting of bearing bushing pos. 6C
the section Various clearances and adjust-
ment measurements.
12 o’clock
The gasket can be supplied in the follow-
ing thicknesses, see the spare parts list:
0.25mm 0.50mm 0.75mm 1.0mm
4 o’clock
Main bearings
The main bearings pos. 5C and 6C are
mounted on the main bearing covers and
Cover pos. 6A seen from the inside T0177167_0
their purpose is to guide the crankshaft both of the compressor
radially and axially.
The bearing bushings can be delivered with
crankshafts ground to undersize. See Spare
They consist of a steel bushing with collar.
Parts List.
The collar and the inside of the bushing are
provided with a thin white metal coating. The crankshaft for the SMC 112 and 116, and
for the TSMC 116, is fitted with a centre bear-
ing. This is fitted with four sets of bearing half
The bushing can be pressed out and re-
bushes of the same type as used in the con-
placed by new ones and need no further
necting rods. The centre bearing housing is
machining after mounting.
made up of two half parts which must be
clamped around the crankshaft before this is
On mounting the bushings it is recommended inserted into the compressor stand.
to secure them with Loctite 601.
The half parts are assembled by means of
four screws and guided together with the aid
When a new bearing bushing pos. 6C at the of cylindrical guide pins. The bearing housing
shaft seal end is put into place in cover pos. is prevented from rotating by two screws
6A the in- and outlets of the lubricating chan- Pos. 49F. These screws are accessible only
nels must be positioned in a four o’clock when the threaded plug Pos. 49H has been
position as illustrated on fig. 1 below. removed. The screws can be removed using
The bearing bushing pos. 5C is positioned a box wrench NV 17 and crank from the tool
with in- and outlets in a 12 o’clock position. set.
0178-910-EN 69
Compressor lubricating system
19D
15D
19B
15A
15B 12
13
22
11 38A
33A
33
33J/K
T0177131_0 V10
The oil pump pos. 11 sucks oil from the Excess oil is returned through a bored chan-
crankcase, through the filter element Pos. 33, nel to the crankcase.
where the oil passes the filter element pos.
33A and past the magnetic filter pos. 33J/K, From the shaft seal housing, the oil is distrib-
as shown on the spare parts drawing. The uted as follows:
pump forces the oil through an internal pipe,
S Through the bored channels in the crank-
pos. 38A, until it reaches the shaft seal hous-
shaft to lubricate main and connecting rod
ing.
bearings. Lubrication of piston pin bear-
The filter element Pos. 33A is a disposable ings is done by splash lubrication through
filter which cannot be cleaned. See descrip- a countersunk hole in the top of the con-
tion of oil filter. necting rod.
The shaft seal housing forms a distribution S To the differential oil pressure cut-out and
chamber for the oil. The oil pressure in the the pressure gauge. The effective oil pres-
shaft seal housing is adjusted by means of sure can be read straight off the manome-
the oil pressure regulating valve Pos. 22, ter (the suction pressure gauge of the
which is mounted in the shaft seal housing. compressor).
The regulating valve can be adjusted from
the outside by means of a screwdriver. S Through external oil pipes, on to the regu-
Clockwise rotation increases the pressure; lating cylinders Pos. 12 for unloaded start
anticlockwise rotation lowers the pressure. and capacity regulation.
70 0178-910-EN
Oil pump
•
4A
11H
11Q
11R
11G
11M 11T •
••
11J •
11L
•
11N
• 11P
11S
The oil pump is a gearwheel pump driven by S When the four M6 screws pos. 11M secur-
the crankshaft via a pinion drive. ing the oil pump to the bearing cover have
been removed, it can be taken out by
It is therefore important to ensure that the
hand.
direction of rotation of the crankshaft is as
indicated by the arrow on the bearing cover Note:
Pos. 6A. The oil pump normally has a very long
service life. Therefore, it is not worthwhile
If the crankshaft is to turn in the opposite di-
repairing it. Rather replace it with a new
rection of rotation, the oil pump can be fitted
one.
with a chain drive. See next section.
S Dismantle end cover Pos. 4A and side The play between the two teeth when en-
covers Pos. 3. gaged must be 0.05-0.08mm measured with
a feeler gauge. Repeat the measurement six
S Dismantle internal oil pipes and nipples
times, turning the crankshaft 60° between
screwed into pump.
each measurement, and adjust until the
S Dismantle nut Pos. 11J and extract gear- smallest play is measured to be as started
wheel pos. 11G. above.
0178-910-EN 71
Chain-driven oil pump with inverse stores no. 3141-127. This set contains a chain,
direction of rotation a chain wheel (springs for old shaft seals only)
and a baffle for lubricating oil, as well as all
If the SMC 100 compressor is to run in the screws needed.
opposite direction of rotation to that shown by
the arrow on the bearing cover Pos. 6A, the In case the compressor is driven by an elec-
gearwheel drive on the oil pump must be re- tric motor, attention should be paid to the pre-
placed with a chain drive. scribed direction of rotation of the motor.
See section: Direction of rotation of the com-
To this end, use a set of replacement parts, pressor.
5
3
1
6
7
8
4
2
72 0178-910-EN
holes are oval-cast to give scope for ad- Adjusting the chain drive:
justment, and there are no guide pins.
S Tighten chain by shifting oil pump. The
S Mount lubricating oil baffle as shown on
correct tension of the chain is shown on
drawing. Drill two M6 threaded holes and
the sketch.
tap, using baffle as template; position so
that the baffle is at a tangent to the exter-
nal diameter of the bearing bush D = 92
mm.
D92
3.5 – 5.5mm
T0177085_0
Thread depth: 5 mm
Drilling depth: 20 mm
Core drill: 5 mm
Finally, when the proper centre distance
Secure screws with spring washers.
has been established, secure oil pump
S Slightly tighten four screws securing oil tightly.
pump to bearing cover.
S Place chain wheel with hub Pos. 4 and 2 S Tighten chain wheel on oil pump.
on pump shaft. The retainer nut can be
tightened once the entire chain drive has
been mounted. Marking direction of rotation
S Place the assembled chain, hub and chain The arrow on the end cover of the compres-
wheel, Pos. 5, 1 and 3, in position; tighten sor should be cancelled out and replaced by
wheel firmly with screws Pos. 11Q from one painted on the indicate the new direction
gearwheel drive. of rotation.
0178-910-EN 73
Oil pressure valve Adjustment
The oil pressure valve pos. 22 regulates the Oil pressure: 4.5 bar.
oil pressure in the compressor. Mounted in
The oil pressure can be read off the suction
the cover Pos. 6A, it connects directly with
pressure gauge or on UNISAB II.
the oil pressure chamber in the shaft seal
housing. On more recent compressor models the
The oil pressure is regulated by a spring adjusting screw may be locked by means
loaded cone, the spring pressure being ad- of an M6 pointed screw, fig. 1, which must
justed by turning an adjusting screw at the be loosened before adjustment can take
valve end. Use a screwdriver for this pur- place.
pose.
Service
Turning to the right (clockwise) raises the oil
Since the oil pressure valve is not subject to
pressure; turning to the left (anticlockwise)
any appreciable wear or soiling, it should not
lowers the pressure.
be disassembled during routine services.
22B
T0177083_0
74 0178-910-EN
By-pass valve pos. 24 Thus, watch out that hole pos. B does not
get covered or clogged.
The compressor is equipped with a built-in
mechanical by-pass valve, fig. 1, which safe- In case the pressure on the discharge side
guards it against any inadvertent excess exceeds the set pressure so that the by-pass
pressure if the electrical safety equipment valve opens, the valve will remain open until
fails. The by-pass valve safeguards against the pressure on the discharge side has fallen
any excess pressure between the discharge to approx. half the set pressure. The valve
and suction sides of the compressor. then closes automatically. However, at great
differential pressures across the compressor
If the by-pass valve goes into action, the the valve may remain open. In that case,
compressor must be immediately stopped stop the compressor and close the discharge
and the cause established. stop valve entirely. The equalization of pres-
sure in the compressor will then close the
The by-pass valve is supplied ready-set and safety valve and the compressor can be re-
sealed in accordance with the adjustment started.
pressures indicated in the table Pressure and
temperature settings. The actual set pressure The by-pass valve is supplied factory-set and
is stamped on the rating plate, pos. A. sealed and need normally not be disassem-
bled and readjusted.
The by-pass valve is of the high-lift type
If necessary, control of function and set pres-
which makes it very sturdy and durable.
sure must be made in accordance with local
regulations for safety valves.
Further, the by-pass valve is independent of
the pressure on the compressor suction side. On the outside the by-pass valve is sealed
Consequently, it only opens when the pres- with two O-rings, pos. 24B and 24C. Fasten
sure on the discharge side exceeds the set it to the compressor housing by means of
pressure in relation to atmospheric. screws pos. 24D and washers pos. 24E.
•
•
A B T3137T02I_1
0178-910-EN 75
Oil filter The filter cartridge is fastened to bracket pos.
33F by means of a lock nut pos. 33M and a
All oil to the lubricating system of the com-
washer pos. 33L. The gasket pos. 33B seals
pressor is filtered through a oil filter installed
off the filter cartridge and the bracket pos.
in the crankcase. The filtration element is a
33F.
filter cartridge (Pos. 33A on the drawing)
which is non-cleanable and must be replaced Changing filter cartridge
with a new one when the filter capacity is
The filter cartridge should be replaced at reg-
used up.
ular intervals. See the section entitled Servic-
It is important, therefore, always to have ing compressors on this point. In particular, it
an extra filter cartridge available. should be remembered that the filter car-
tridge must often be replaced after a relative-
Filter cartridge
ly short operation time following initial start-
As shown in fig. 1 the filter cartridge pos. 33A up.
is a single unit consisting of a 60 m primary
filter, a magnetic filter and a shield which co- This is due to small particles of dirt origina-
vers half of the filter. ting from the plant during the initial operating
period.
Fig. 1
33B 33A
33L
33F 33M
Before changing the oil filter cartridge all pre- filter cartridge pos. 33A and the gasket
parations in connection with the opening of pos. 33B.
the compressor must be carried out in accor-
dance with the instruction manual. Proceed as follows:
S Dismount the lock nut pos. 33M and S Let the bracket pos. 33F stay mounted in
washer pos. 33L and remove manually the the compressor.
76 0178-910-EN
S When mounting the new oil filter cartridge the closed shield on the filter faces up-
as illustrated in Fig. 1, first place the gas- wards.
ket pos. 33B on the bracket pos. 33F. Then fasten the filter by means of the lock
nut pos. 33M and the washer pos. 33L.
S Then place the oil filter cartridge pos. 33A S Tighten the nut pos. 33M to a torque of
on the bracket pos. 3Fand turn it so that 4.5 Nm.
0178-910-EN 77
Suction filters Note:
Do not forget to remove the filter cartridge
The purpose of the filters is to collect impuri-
after 50 operating hours, as a blocked fil-
ties conveyed from the plant to the compres-
ter bag may cause the suction filter to
sor with the suction gas and thus prevent
burst and thus contaminate the compres-
them from penetrating into the compressor.
sor to an extreme degree.
The suction filters therefore have a very fine
mesh and as an additional precaution have a There are always two suction filters in the
filter bag insert, which should normally be compressor and these are removed through
used for 50 operating hours from the initial the flanged opening in the bottom end of the
start-up of the compressor. The filter bag is filter housing. Attention is drawn to the fact
then removed and disposed of. that there are two types of suction filter, as
If the filter bag is badly soiled after the 50 op- detailed below:
erating hours mentioned, it is recommended
that a new bag be fitted for an additional 50 On SMC compressors, the two suction fil-
operating hours. Similarly, a filter bag ought ters are identical and should only be fitted
to be fitted for a period of 50 operating hours with an O-ring in the end facing up towards
after any major repair work to the refrigera- the suction stop valve. The filters are open at
tion plant. both ends.
LP HP
LP HP
On TSMC compressors, the suction filter The suction filter fitted on the righthand side
located on the lefthand side opposite the low- opposite the high-pressure cylinders has a
pressure cylinders (see drawing) is the same closed end-bottom which must face upwards
type as on SMC compressors, i.e. open at and close towards the suction stop valve.
both ends and having an O-ring in the end This suction filter must be fitted with O-rings
facing up towards the suction stop valve. at both ends.
78 0178-910-EN
Stop valves
AK AC A AJ L P K R
AD
E S
F T
D U
C M
H B
Y J
POS. 25
Z AG Q G N T0177131_0 V14
The suction and discharge stop valves are S Mount threaded piece Pos. 25G in a
used to isolate the compressor from the re- soft-jawed vice and dismantle screw Pos.
frigeration plant. 25E.
0178-910-EN 79
Reassembly of valve: Pos. 25M to be serviced even when there
Reassembly is done in the reverse order to is excess pressure in the valve housing.
that above. Note the following, however:
Adopt the following procedure:
S Before mounting the complete valve in-
sert, the valve cone with threaded piece S Using handwheel, open valve completely
Pos. 25G must be screwed right into the to achieve a seal between valve cone and
valve neck Pos. 25B. valve throat. The gasket Pos. 25Q acts as
a sealing element.
S The O-ring Pos. 25J may have expanded
under the influence of the oil in the plant
S The packing screw joint Pos. 25M can
and will normally have to be replaced with
then be screwed out for inspection or re-
a new one.
placement of the O-ring Pos. 25R and
The stop valve has a so-called retroseal, 25P. Thoroughly lubricate all parts with oil
which enables the packing screw joint before reassembling.
80 0178-910-EN
Unloaded start and capacity regulation on SMC
and TSMC 100 and 180 compressors
SMC and TSMC compressors are equipped The unloader system is also used to regulate
with an automatic unloader system to provide the capacity of the compressor.
full relief to the compressor during the
start-up phase. This reduces the starting The following schematic outline shows the
torque of the compressor considerably. lubrication and hydraulics system on the
compressors together with unloader me-
chanism.
Fig. 1 12
2
12J
50
20 13 2
19D
96.02
15D
19B 2
15A
15B
0171-907-EN
1
3
22
11
38
33
T0177131_0 V10
Description of unloader mechanism See the blue spare parts drawing of the cylin-
and capacity regulation der linings at the end of this manual.
0178-910-EN 81
When the regulating piston is unaffected by the ate freely and close during the compression
oil pressure - i.e. when the connected solenoid phase.
valve is de-energized or when the compressor
During operation, the unloader system can
is at standstill - the regulating piston and the en-
therefore regulate the capacity of the com-
tire frame are shifted to the right by the pres-
pressor by causing the solenoid valve - which
sure from the springs Pos. 12J (see fig. 1) .
is linked to the relief cylinder - to open or
The tension springs Pos. 15D will thus raise close for oil pressure to the relief cylinders,
the rocker arms Pos. 15A into the vertical po- controlled by an electrical regulation system.
sition, as these rotate in the ball sockets Pos.
On TSMC compressors, attention is drawn to
15B.
the two types of relief cylinder - for the LP
This movement lifts the relief ring and the and HP stage, respectively, as shown on the
pins Pos. 19B, opening the suction valve by spare parts drawing.
force.
Note:
If oil pressure is placed on the relief cylinder Adjust the oil pressure on the regulating
during operation, the unloader system is valve Pos. 22 to 4.5 bar. At an oil pressure
shifted to the left (see sketch). This lowers lower than 3.5 bar (the breaking pressure
the rocker arms Pos. 15A, and the relief ring for the safety automatices), there is a risk
with pins Pos. 19B is moved away from the of the unloader system not being moved
suction valve ring plate, allowing this to oper- effectively and thus being damaged.
82 0178-910-EN
Pilot solenoid valves The solenoid valves are integrated in blocks
The pilot solenoid valve is an electromagnet- (fig. 2) with 1,2,3, or 4 solenoid valves in
ic three-way valve which with a dead coil each block. In these blocks the solenoid
connects the unloading cylinder to the crank- valves have a collective supply of pressure
case (the path for the oil flow from pipe 2 to oil (pipe 1) and a collective connection to the
pipe 3 is open). See fig. 1. If the coil is ener- crankcase (pipe 3). Each individual solenoid
gized, the valve switches so that the path for valve has its own oil connection to the rele-
the oil flow from pipe 1 to pipe 2 is open and vant unloading cylinder (pipe 2).
the connection to pipe 3 is closed off.
Fig. 2
Danfoss 034F9034_1
0178-910-EN 83
Schematic outlines The S-valve is connected to the regulating
cylinder(s) not involved in capacity regula-
The following schematic outlines shows the
tion.
oil pipe connections and the wiring diagram
with cut-out functions.
The valve is designed to prevent fast rising
The schematic outlines also indicate the per- oil pressure actuating the compressor cylin-
centual capacity at which the compressor op- ders before the motor starter has changed
erates at the various capacity stages. over to the delta position, or a gas or diesel
motor has reached full rotation speed.
The lowest capacity percentage indicated on
schematic outlines 1 corresponds to the low- TSMC compressors are always equipped
est permissible capacity step at which the with S-valves and thus feature totally un-
compressor may work by continous opera- loaded start as standard.
tion.
Note:
In special instances, e.g. where the start-up Please note that the solenoid valve S
phase is lengthy, it may prove necessary to must not be wired so as to form part of
relieve the compressor altogether until the the capacity regulation.
motor has achieved a sufficient torque. In The compressor may operate totally un-
such cases, an extra solenoid valve marked loaded for no more than 5 minutes, as its
’S’ can be mounted as shown on schematic operating temperature will otherwise be-
outlines 2. come too high.
84 0178-910-EN
Standard unloaded start and capacity regulation
The SMC and TSMC compressors always Regulating sequence
start totally unloaded and in their standard
The unloading is effected for two cylinders at
design will activate a number of cylinders
a time by cutting off the voltage to the ac-
corresponding to the lowest capacity stage
companying solenoid valve.
once the oil pump has built up the necessary
oil pressure. The unloading must be effected in numerical
order (1 - 2 - 3 - 4), while loading should be
done in reverse order (4 - 3 - 2 - 1).
See discussion of the ’S’ solenoid valve in
the Totally unloaded start and capacity regu- Note:
lation section, however. TSMC 116 must always have valves 3
and 4 connected simultaneously, as this
capacity stage includes both low- and
It is recommended that solenoid valves be
high-pressure cylinders.
wired so as not to receive the opening
signal until the drive motor has achieved The regulating sequence may be seen from the
full torque. schematic drawings.
Schematic drawings 1
SMC/HPC 106 50
2
4
SMC 186 33
N
3 L
1 2
%
100 1
67 2
33 SMC 116 TSMC 116
N
L %
% 3 7 100 1
2 S
1 5 1 5
100 1 83 2
3 5
87 S
SMC/HPC 108 5
67
SMC 188 75
HP
% 4 1
2 3 63 4 6 S 4
100 1 50
75 2 8 3 S
2 50 2 S
50 3 3
4
25 37 6 33 4
N
L 25
N 0
L L N
T1534070_1 rev.3
0178-910-EN 85
Totally unloaded start and capacity regulation
Futher to the standard equipment, as shown pacity. The ’S’ solenoid valve may therefore
on the previous page, the compressor may be used only as follows:
feature an extra solenoid valve marked S.
S Where total unloading is required until the
TSMC compressors, however, are invariably
motor has achieved max. torque.
equipped with this S-valve.
S Where a refrigeration plant is occasionally
The ’S’ solenoid valve makes total unloading
subject to brief operating stops and com-
of the compressor possible, i.e. 0% capacity
pressor stop is not desirable. The com-
over a shorter period during operation. How-
pressor may then be allowed to run for a
ever, the ’S’ solenoid valve must never be
maximum of 5 minutes at 0% capacity.
involved in normal capacity regulation, as
there is a risk of the compressor overheating The regulating sequence may be seen from
if operated for some length of time at 0% ca- the schematic drawings:
Schematic drawings 2
1
Oil pressure
SMC/HPC 106
SMC 186
S SMC 112 SMC 116
1 2
% S
100 1
67 2 % S
33 S 3 S
1 3 100 1
0 N 1 5
L
% S 3
100 1 87 5
3
75
83
SMC/HPC 108
63
67 4 4 6
% 1 2 S 50 2
S 2 S
100 1 50 S 4
2 3
75 2 2 37 6
50 3 33 4 25 S
25 S S 0 0
N
L L N
0
N
L
T1534070_2 rev.3
86 0178-910-EN
Service rent to the number of solenoid valves needed
to supply the compressor with the capacity
It will normally not be necessary to service
required.
the solenoid valves, and it is therefore re-
commended not to strip them down. Should it
be considered necessary to replace the sole- Note:
noid valve, however, unscrew it from the When starting a compressor this must be
block and replace by a new one. See the done at the lowest capacity stage and it
spare parts list. should be allowed to run for a few minutes
(e.g. 3 to 5 minutes) before its capacity is in-
Regulating sequence creased. This will prevent the oil in the com-
pressor from heavy foaming and the refriger-
The schematic outlines show that disconnec- ant from being sucked into the compressor
tion of a cylinder pair is done by cutting off from the evaporating system; something
the current to the relevant magnetic coil. Dis- which can lead to liquid strokes. For the
connection must be done by numerically as- same reasons the compressor should al-
cending sequence, while connection should ways, when a new stage has been loaded,
be done by numerically descending se- be allowed to run for 3 to 5 minutes at this
quence. stage before the next higher capacity stage is
The automatic gear which controls the sol- loaded. Unloading of capacity on the com-
enoid valves must cut off or connect the cur- pressor can usually take place more quickly.
0178-910-EN 87
Heating rods, pos. 30
In order to keep the lubricating oil in the com- As illustrated on the drawing the heating rod
pressor warm during a period of standstill, consists of an electric heating element, incor-
the oil reservoir has one or two heating rods porated in a dia. 30 mm pipe. The entire hea-
built in. Before start-up, the heating rod (s) ting cartridge is screwed on tight at the
must have been activated for 6-8 hours in G 1 1/4” thread.
order to ensure that there is only a minimum
of refrigerant in the oil. When containing Note:
much refrigerant, the oil will lose its lubricat- The heating rod must not be energized if
ing property and the following operational in- the oil level in the reservoir is below the
terruptions may occur: minimum mark in the sight glass, and it
should generally be switched off during
In reciprocating compressors there is a
compressor operation. Remember to turn
serious danger of vigorous oil foaming when
off the heating rod whenever the crank-
the compressor starts as a result of a falling
98.05
case of the reciprocating compressor is
suction pressure.
opened for inspection.
For screw compressors starting with much
0170-017-EN
refrigerant dissolved in the oil, there is a risk The following table indicates which heating
of the compressor being stopped by the Flow rods are used for the various compressor
Switch as the oil will be foaming owing to the types. In the spare parts lists for compressor
fall in pressure through oil pipe and oil filter. or unit you will find the current part numbers.
Marking: Prod. nr.
NV 50 Watt
G 1 1/4” Volt
Manu. date
Ø 30
30
50
L1
80 L2
Heating rods
Power Voltage L1 L2 Used for:
Watt V mm mm
270 250
270 230 CMO - TCMO - SMC 100 - TSMC 100
270 115*
158 175
460 250 HPO - HPC, SMC 180 - TSMC 180
460 230 VMY 347 /447 – 536
460 115* SAB 110 – 128 – 163 – 202 – 330
* Can be delivered with a UL approval.
All heating rods are executed in Degree of Protection IP54.
88 0178-910-EN
Stop valves pos. 23 and 42
23G
Fig. 1
Danv
42A 42H
Fig. 2
95.03
0171-463-EN
42G
42D 42B
T0177156_0
The compressor is fitted with stop valves trating the valves whenever they are not
pos. 23 for charging of oil and pos. 42 for used.
draining of oil. They are service-free valves
and should as a rule not be dismantled. S If the valve is used as an oil charging
valve it is fitted with a nut pos. 23C and
The valves are safeguarded against inadver- threaded nipple pos. 23B as shown by
tent opening by means of a red cap. fig. 1.
The red cap can further be used for opening S If the valve is used as a purge valve it is
or closing the valve by unscrewing it and fitted with a screwed connection as illus-
turning it upside down. The square hole in trated by fig. 2.
the top of the cap fits the square in the valve
spindle. The purge valve is fitted either directly on
the top cover or by means of an intermedi-
The valves are equipped with a blank nut ate connection in the cast pressure chan-
pos. 23G/42H that prevents dirt from pene- nels in the frame.
0178-910-EN 89
Monitoring cylinder lining insertion
When reassembling the slide linings, it is im- no. 1 from the tools kit.
portant to check the clearance volume as Fit the locking devices diagonally as
described in section 1 below. shown in fig. 1.
When mounting new cylinder linings, both
the clearance volume and the so called lift- Fig. 1
ing reserve must be checked in the order S-L for SMC 100 type S
• E for SMC 100 type E
mentioned and as described in sections 1
and 2. It is recommended that the cylinder
linings be marked so that they can be reas-
sembled in the same place as before.
98.01
checked. pos. 19K
0171-467-EN
by means of gasket pos. 19K which, in addi-
tion to its sealing function, is also used as an
adjusting element. Consequently, the gaskets
come in two sizes and may sometimes be
used at the same time under the same cylin-
der lining. S Turn crankshaft until piston is in top posi-
tion.
Gasket HPC SMC 180
thickness SMC 100 S Using a depth or slide gauge, measure ”X”
19K part no. part no. as shown in fig. 2
0.5mm 2356-111 2356-116
Fig. 2 Cylinder lining
0.8mm 2356-233 2356-249
X
90 0178-910-EN
Clearance The rocker arms must be in their vertical
min. max.
volume position i.e. with the short screw pos. 12D
”X” mm mm
HPC and gasket 12E fitted. The measured dis-
SMC 100
0.6 1.0 tances ”Y1 and Y2” may not vary more
Mk1, Mk 2, Mk 3
SMC 180 than max. 0.25mm.
0.9 1.5
Mk1, Mk 2
S Adjustment of the lifting reserve can now In case this difference is greater, a shim
be performed if necessary. See point 2. Pos. 15E must be placed under the lowest
rocker arm bearing pos. 15B or a shim re-
2. Checking lifting reserve moved from the highest bearing. Normally,
When fitting a new cylinder, or if the com- there is no shim or max. 2 shims under
pressor is to be changed from running on the rocker arm bearing.
R717 to some other refrigerant, or vice versa,
or in the event of any major overhaul to the
compressor, the lifting reserve must be
checked.
Check lifting reserve:
Note:
The lifting reserve must not be checked S The lifting reserve of the rocker arm is im-
until the clearance volume has been ad- portant in order to make sure that the
justed. Start by checking that the mutual rocker arm in its upright position can keep
height of the rocker arms is the same as the suction valve ring plate open while the
described in the following: cylinder is unloaded. However, it must not
Having removed the cylinder lining, mea- be possible for them to be so upright that
sure distance ”Y” from the contact face of there is a risk of their jamming, this mak-
the cylinder lining in the frame to the top of ing them unable to be lowered again
the two rocker arms which interact on ei- when the cylinder is put into service. Per-
ther side of the cylinder lining. See fig. 3. form the adjustment as follows:
Fig. 3
S Position cylinder lining incl. the correct
Block
gasket pos. 19K in the compressor block
and press down against rocker arms by
hand.
Y1 Y2
S The rocker arms are in their upright posi-
Rocker arms tion as the normal plug pos. 12D as well
as gasket pos. 12E have been mounted in
T0177131_0 v4
the unloading cylinder.
0178-910-EN 91
S The difference in the two measurements
Fig. 4
of ”Z” must be within the limits stipulated
in the following table.
Z
T0177131_0 v5
92 0178-910-EN
Pressure gauges
The analog instrumentation on the compres- temperature under which the instrument will
sor includes two pressure gauges: one that be functioning.
measures the discharge pressure on the
compressor and one combined suction and Example:
oil pressure gauge. These pressure gauges If the mid–compensation range is to be
are filled with glycerine, which both attenu- moved from 20°C to 10°C, equalization must
ates the deflections of the indicators and lu- be performed at 10°C. When the screw is
bricates the gauge works. then retightened, the middle of the com-
pensation range will have been moved down
However, a fluctuating ambient temperature to 10°C. The total stretch of the compensa-
has an influence on the volume of the glycer- tion range remains unchanged.
ine (warm glycerine takes up more space
The middle of the compensation range.
than cold glycerine), which can affect the Tighten the balancing screw at this temperature
measuring accuracy of the gauge.
10°C
Furthermore, it is essential that no excess -10°C 50°C
95.06
of the housing.
30°C
+10°C 70°C
Both these considerations have been effec-
tively solved in the gauges by a combination T0177086_0
0178-910-EN 93
Note: Compensator
Glycerine should be refilled at a room tem-
perature of 20°C; when mounted, and the +20°C
94 0178-910-EN
Undersize Bearing Diameters for Crankshaft
Reciprocating Compressors with 4 to 8 Cylinders
B
A A
B C
R=2.5 R=2.5
R=d
a
b
°
96.05
45
c
T0177137_0
0171-904-EN
A B C a b c d
Main bearing Connecting rod bearing
Compressor First Super First Super
type grinding finish grinding finish
or or
Final Final
grinding grinding
mm mm mm mm mm mm mm mm mm
–0.060 –0.060 –0.030 –0.035 0.0 0.0
HPO 59.5 59.5 54.5 54.5 35 0.2 1.0 2.5 2.5
–0.070 –0.090 –0.049 –0.050 –0.1 –0.3
CMO 2
Ra=0,20 Ra=0,20
HPC, 0.0
40
SMC/TSMC –0.1
100 S
–0.070 –0.070 0.000 0.000
79.5 79.5 79.5 79.5 0.0
SMC/TSMC –0.080 –0.090 –0.010 –0.020 50 0.2 1 3 3.5
100 L Ra=0.35 Ra=0.35 –0.1
SMC/TSMC 0.0
60
100 E –0.1
0178-910-EN 95
Sundry clearances and check dimensions
– – – – – –
91.04
At right angles manufactured 0.11 0.11 0.11 0.15 0.15 0.35
to piston pin max. 0.30 0.30 0.30 0.40 0.40 0.90
0171-901-EN
If the maximum value has been exceeded, replace the parts.
Crankshaft end-play
min. 0.30 0.30 0.30 0.40 0.75 0.95
max. 0.55 0.55 0.55 0.64 1.00 1.20
The end–play can be adjusted by means of the gasket under the bearing cover.
The gasket is available in the following thicknesses: 0.3, 0.5, 0.75 and 1.0 mm.
Bushing and bearing halves can be supplied for all above journals.
96 0178-910-EN
Torque moments for screws and bolts
ft.lbf. 2.1 3.9 6.8 16 30 50 80 110 170 220 270 370 490
Nm 2.7 5.2 9.2 22 40 69 108 147 225 295 375 510 670
94.12
ft.lbf. 3.0 5.7 10 23 44 75 120 160 240 320 400 550 720
T0177082_0
0178-910-EN 97
Bolt on discharge valve
HPO/CMO HPC/SMC 100 SMC 180
depending
VMY on the 312 7/16” 5.6 40 55
motor size
350 1/2” 13 95 128
98 0178-910-EN
Refrigeration Plant Maintenance
1. Incorrect control of liquid supply to the 3. Start up the compressor. Adjust regulat-
evaporator. ing system to lower suction pressure.
dirt.
If the receiver has an extra stop valve in
6. Congestion due to iron oxides. the feed line, this can be closed; practical-
0171-464-EN
0178-910-EN 99
3. Note: Tightness testing and pump-down
If the piping system is colder than the sur- of refrigeration plant
roundings, there is a considerable risk of
Before charging refrigerant into that part of
damp precipitation (condensation) on cold
the refrigeration plant which has been
plant parts. Plant components to be dis-
opened, this should be pressure-tested as
mantled must be warmer than the ambi-
described in the section entitled Pressure
ent temperature.
testing.
4. No two points in the system should be Afterwards, pump down in order to eliminate
opened at the same time. air and moisture. In this regard, consult the
section on Evacuation.
5. Plug, close or at least cover opening with
Otherwise, follow the instructions given in the
oiled paper or suchlike.
separate instruction manual on plant compo-
6. Be aware of the possibility of filters nents.
being very moist. Note:
If the oil in the crankcase of the piston
compressor or the oil separator of the
screw compressor has been in contact
with the atmospheric air for any length of
time, it must be replaced with fresh oil of
the same grade and make.
100 0178-910-EN
TroubleĆshooting on the Reciprocating Compressor
Plant
In the following chart, each individual error Any explanatory comments will be stated in
option is indicated by a code number in the the section that follows.
0178-910-EN 101
Error
code Observed error Cause code
1 Compressor fails to start 1, 2, 3, 4, 5, 6, 7, 9, 10, 12, 14.
2 Compressor starts and stops too often 9, 10, 11, 13, 21, 22, 23, 24, 32, 34, 35, 36, 37,
40, 41, 43, 44, 51, 52, 54, 56, 59.
3 Compressor starts but stops again immediately 3, 5, 6, 9, 10, 11, 12, 13, 14, 15, 17, 18, 41,
42, 49, 50, 55, 61.
4 Compressor operates continuously 8, 21, 22, 24, 41, 46, 52, 53, 56, 60.
5 Abnormal noise from compressor 16, 17, 18, 19, 26, 48, 49, 50, 51, 52, 53, 54, 56,
57, 58.
6 Insufficient capacity on compressor 13, 15, 17, 18, 20, 21, 22, 23, 24, 32, 34, 35, 36,
37, 40, 41, 44, 45, 46, 49, 50, 51, 52, 53, 56, 60.
7 Liquid stroke in compressor during start up 16, 18, 26, 37, 38, 39, 44, 56, 61.
8 Liquid stroke in compressor during operation 21, 23, 26, 37, 39.
14 Excessive discharge pipe temperature 11, 21, 22, 23, 28, 29, 30, 31, 33, 34, 35, 36, 37,
40, 41, 46, 52, 54.
15 Too low discharge pipe temperature 26, 32, 39.
16 Excessive oil temperature 33, 34, 35, 36, 37, 40, 50, 52.
17 Oil level in crankcase falling 16, 18, 20, 26, 51, 57, 58.
18 Oil foaming vigorously in crankcase 16, 26, 39, 61.
19 Crankcase sweating or frosting up 16, 18, 26, 37, 39.
20 Capacity regulating oscillating 13, 15, 16, 17, 18, 49, 55, 56.
21 Impossible to bleed plant 10, 43, 51, 52, 53, 54, 60.
102 0178-910-EN
Code Case Code Case
0178-910-EN 103
Remedying malfunctions
1. Compressor fails to start
1.6 Control current circuit open owing Pinpoint open switch and
to activated: remedy cause of
pressure cut-outs interruption.
thermostats
motor protection device
defrosting timer
1.9 High-pressure cut-out has cut Reset pressure cut-out and investigate cause
of high condenser pressure.
1.10 Low-pressure cut-out has cut Compressor cannot start before suction pres-
sure has risen above set point for pressure
cut-out restarting.
2.10 Low-pressure cut-out cuts at too Low suction pressure - see section 12.
low suction pressure.
If low-pressure cut-out is set too high, adjust
pressure cut-out.
2.11 Low-pressure cut-out differential is Increase differential pressure - see also special
too small between stopping and instructions.
starting
2.13 Compressor capacity too high Check operating conditions and, if need be,
reduce capacity.
104 0178-910-EN
3. Compressor starts but stops again immediately
3.10 Low-pressure cut-out has cut Open any suction stop valve which is closed.
3.15 Oil charge insufficient Top up with oil and investigate cause of oil
shortage.
3.18 Oil pressure failing owing to for- Reduce capacity. See sections 17 and 18.
mation of foam in oil.
4.21 Restricted supply of refrigerant to Remove dirt in filters and check function of ex-
evaporator. Compressor working pansion device as per special instructions.
at too low suction pressure.
0178-910-EN 105
5. Abnormal noise from compressor
5.26 Liquid refrigerant in suction line Liquid stroke. See points 7 and 8.
Adjust expansion or float valves.
5.48 Incorrect alignment of motor and Check alignment as per special instructions.
compressor
Loose bolts in coupling Tighten with torque wrench
5.56 Capacity regulation oscillating Low oil pressure - see section 13.
owing to failing oil pressure
6.15 Insufficient oil charge Top up with fresh oil of same type and make.
106 0178-910-EN
7. Liquid stroke in compressor during start-up
Liquid stroke in the compressor should not occur, as in the worst instance this can
cause rupture to the valve ring plates and damage to the inbuilt relief devices. Fur-
thermore, it can result in damage to the connecting rod bearings and cylinders if the
coolant degreases the faces and impairs the lubricating capacity of the oil.
7.26 Refrigerant has condensed in suc- Heating element in crankcase should be con-
tion line or crankcase nected for 6-8 hours before starting, so that
refrigerant dissolved in oil can be boiled out
before starting compressor up.
Suction line has free fall towards Start with throttled suction stop valve - stop
compressor when hammering is heard.
Liquid separator should be mounted in suction
pipe.
0178-910-EN 107
9. Excessive condenser pressure
In the event of abnormally high pressures in the refrigeration system, there is a risk of
damage to the compressor. At very high pressures (see pressure testing), the risk of
the components in the refrigeration plant exploding can constitute a threat to life.
Abnormally high pressures can occur in the case of:
- extreme heating of plant parts (fire, solar radiation or other abnormal heating);
- volumetric expansion of fluids in sealed-off premises.
9.25 Overfilling with refrigerant Refrigerant fills condenser and reduces its ef-
fective area.
Draw off coolant.
10.51 Defective piston rings or worn cy- Replace worn parts. See compressor instruc-
linders tions.
10.52 Discharge valves are defective or See compressor instructions. Check valve ring
leaky plates and piston rings.
10.54 Bypass between high-pressure Check compressor for internal leakage by per-
side and suction side of compres- forming pressure-drop test.
sor
See compressor instructions.
108 0178-910-EN
11. Excessive suction pressure
11.54 Open by-pass between suction si- Check system for any by-pass detectable as a
de and high-pressure side of com- warm connection.
pressor. Safety valve leaky, or
opens prematurely. Adjust or repair leaky valves.
12.35 Freezing-up of expansion valve Thaw out expansion valve with hot, wet cloths.
(HFC/HCFC plant)
Replace dessicant in drying filter.
12.36 Thermostatic expansion valve has Valve fails to open - change valve.
lost charge
0178-910-EN 109
12.41 Filter in liquid line clogged Check and clean filter in liquid line.
12.42 Solenoid valve in liquid line fails to Coil may have blown. Control signal lacking.
open
13.15 Too little oil in compressor Top up compressor with oil and investigate
cause of oil consumption.
If, after approx. 1 hour’s operation, the discharge pipe temperature is more than
10°C higher than indicated in the table, the error may be due i.a. to:
14.52 Leaky discharge valves Leaking in discharge valves gives rise to gen-
eration of heat.
Change defective valves.
14.54 Open by-pass between high and Localize by-pass and remedy any leakages.
low-pressure side of compressor,
e.g. leaky safety valve
110 0178-910-EN
15. Too low discharge pipe temperature
15.26 Low suction temperature as result Adjust liquid regulating valve. Increase super-
of overflow of liquid refrigerant heating.
from evaporator
During operation, the heat of the compressor crankcase must be 40-70°C. When
working with R717 and R22, it may be necessary to supply the compressor with oil
cooling.
See point 14.
Where HFC/HCFC refrigerants are used, there will be some blending of refrigerant
and oil during the initial operating period. It may therefore prove necessary to top up
the oil after initial start-up of the plant.
Note:
The oil level must always be visible in the oil level sight glass on the compressor.
17.20 Filter in solenoid valve or jet in oil Oil return pipe must be warm during opera-
return line clogged tions. Clean filter.
17.26 Liquid in suction line and crank- Examine evaporator system and check super
case may cause foaming in oil heating of suction gas.
and thus increase oil consumption
17.51 Worn-out piston rings or cylinders Renew piston rings and, if need be, renew pis-
tons and cylinder linings.
17.57 Solenoid valve in oil return line de- Coil in solenoid valve defective.
fective - Replace coil.
- Electrical control signal lacking.
0178-910-EN 111
18. Heavy oil foaming in crankcase
18.61 Too much refrigerant dissolved in - Before starting compressor, heating element
oil must have been on for at least 8 hours in
order to boil refrigerant out of oil. During
start-up phase, capacity should be con-
nected at a slow rate to prevent sudden drop
in pressure on suction side with resultant
foaming.
- Under normal operating conditions, com-
pressor should operate under as stable
pressure conditions as possible.
19.37 Expansion valve sensor misplaced Check positioning of expansion valve sensor -
cf. instructions for expansion valve.
19.39 Liquid regulating valve or float val- Increase superheating on thermostatic expan-
ve producing too much liquid sion valve.
21.43 Solenoid valve leaky Pinpoint and seal leak, or change leaky com-
ponent.
21.51 Defective piston rings Check and replace any defective parts.
21.52 Defective discharge valves Check and replace any defective parts.
21.53 Defective suction valves Check and replace any defective parts.
112 0178-910-EN
Selecting lubricating oil for SABROE compressors
During the past few years YORK Lubricating oils with relatively high viscosities
Refrigeration has experienced a number of must be used to ensure satisfactory lubrica-
problems with mineral oils, particularly in tion of refrigeration compressors.
R717 plants. The problems can be divided
To obtain the best lubrication, the oil must:
into two groups:
S Provide the required fluidity at the lowest
a: The oil changes viscosity evaporating temperature encountered in
b: The oil decomposes (becomes very black) the plant and at the highest permissible
temperatures in the compressors.
The problems have been seen with several
S Provide acceptable fluidity at start-up.
mineral oil brands, often occuring within a
few operating hours and resulting in severe S Provide sufficient oxidation stability (the oil
consequences for both compressor and must be moisture-free when added to the
system).
plants.
S Provide sufficient chemical stability when
99.02
Following the careful investigation undertak- used together with the particular refriger-
en by YORK Refrigeration during the past ant.
few years, it has been decided to introduce a In addition, the extent to which different re-
0170-151-EN
range of synthetic oils which can fulfil the de- frigerants dissolve in the oil must be deter-
mands of modern refrigeration plants. mined, so that the oil return systems, etc. can
be designed to function properly.
Mineral oils may continue to be used in re-
frigeration plants, providing the lubricating Stratification
quality is carefully monitored. For modern, It should be noted that in certain plants, par-
high capacity refrigeration plants, where long ticularly with HFC and HCFC refrigerants, the
lifetime for both lubricants and moving parts oil may stratify into layers in the refrigerant
is expected, YORK Refrigeration recom- receivers and evaporators at certain operat-
mends the choice of synthetic lubricating oils. ing conditions and at particular oil concentra-
tions.
The application areas and specifications for
these synthetic oils can be found in the fol- The Oil recommendation diagrams for
lowing pages. Installers and/or users are at SABROE compressors for HFC and HCFC
liberty to choose either YORK Refrigeration’s will indicate the limits for Sabroe oils at which
own or alternative oil brands which fulfil the this stratification occurs. The oil concentra-
necessary specifications. tions stated in these diagrams must not be
exceeded. This will enable suitable oil rectifi-
General cation/return systems to be designed to bal-
This recommendation only deals with the lu- ance with the compressor oil ”carry-over” so
brication of the compressor. The perfor- that the maximum concentration is not ex-
mance of the lubricant in the plant (receiver, ceeded.
evaporator, etc.) must, however, also be tak- For area A in the diagrams, the max oil con-
en into consideration. centration in liquid phase must not exceed
0178-910-EN 113
2%. For the other area, the max. oil con- In the oil recommendation diagrams for each
centration must not exceed 5%. For area B: refrigerant and compressor type, it is pos-
please contact YORK Refrigeration. sible to determine the code number for the
oil best suited to the operating conditions.
Plants with several different compressor With this code number, it is possible to se-
types/makes lect the correct Sabroe oil for the application.
In plants comprising several different inter- The marked area on each side of the sepa-
connected compressor types and makes, it is rating line in the diagram shows the zone
strongly recommended that all compressors where both oils are useable.
should use the same type of oil. This is es-
sential where automatic oil return systems Oil types and oil companies
are employed. As a result of the large number of oil compa-
nies world-wide that deals in oil for refrigera-
If it is intended to change the oil from one tion plants, it is impossible for YORK
type to another, please refer to the Oil chang- Refrigeration to test the many different
ing on SABROE compressors later in this brands of oil on the market. It is our experi-
publication. ence, however, that some oil brands during
use can change character and thus no longer
Selecting the lubricating oil fit the specifications given by the companies
There are a number of operating diagrams at delivery. We have thus experienced
for the selection of lubricating oils for Sabroe changes in the specifications as well as in
compressors operating with various refriger- the formula and performance without having
ants. Once the general conditions concern- had any information about this from the oil
ing the lubrication of the compressor and oil company. This makes it very difficult for
type in the plant have been considered, the YORK Refrigeration to give a general ap-
specific plant conditions must be taken proval of the various oil brands.
into consideration.
Use the Oil recommendation diagrams to se- For this reason YORK Refrigeration has, in
lect the appropriate oil code number. cooperation with a large recognised oil com-
pany, developed a series of three oils which
The oil code number consists of letters de- cover most purposes. YORK Refrigeration
signating the oil type together with the has however, also listed a limited number of
Sabroe viscosity grade number. oils which can be supplied through YORK
Refrigeration. The typical data of these oils
Code can be found in the Data Sheet for Sabroe
Oil types
design Oils. We suggest you to use these Sabroe
M Mineral oil oils, which are delivered in 20 litre pails and
Synthetic oil based on 208 litre drums and can be ordered using the
A
Alkylbenzene
parts no. listed in the List of Oils.
Synthetic oils based on
PAO
Polyalphaolefin
AP Mixture of A and PAO-oils It is of course possible to use similar oils from
E Synthetic ester-based lubricants other oil companies, and in this connection,
114 0178-910-EN
the Data Sheet for Sabroe Oils may be help- Screw compressors:
ful. The oil temperature before injection in
the compressor, but after the oil cooler
Please note, however, that YORK
Refrigeration has not tested any other oils Max. permitted oil temperature = set-
than our own brand, and hence we cannot ting point for alarm
answer for the quality, the stability or the suit- Min. permitted oil temperature = set-
ability of other oils for any purposes. The oil ting point for alarm
company in question is thus solely responsi- • Condensing pressure
ble for the quality and suitability of the oil de- • Evaporating pressure
livered, and if any problems are experienced
S Oil viscosity in the compressor during
with these oils in the compressors or in the
operation and under the influence of:
refrigeration plant, the oil supplier should be
contacted directly. • Refrigerant type and solubility of refrig-
erant in the oil
When choosing oils from other oil compa-
• Operating temperatures
nies, please pay particular attention to the
oil’s effectiveness in the compressor and the • Vapour pressure in the oil reservoir
refrigeration plant as a whole. Reciprocating compressor: Suction
pressure and oil temperature in the
Pay particular attention to the following as- crankcase.
pects:
Screw compressor: Discharge pressure
S Oil type and gas temperature.
Reciprocating compressors:
For this reason it is not recommended to
Normal oil temp. in the crankcase change oil type from M oil to PAO oil as a
50-60 °C leakage may occur if the O-rings are not
Max. permitted oil temperature = Set- changed. YORK Refrigeration therefore
ting point for alarm recommends using the Sabroe AP68 oil
Min. permitted oil temperatures = set- as it reduces the risk of leaks considerably
ting point for alarm - if fitted in this case.
0178-910-EN 115
YORK Refrigeration can supply a calculation YORK Refrigeration is aware, however, that
showing the operating data on request. several customers have been using mineral
oils for many years without problems. Those
Attention is drawn to the following viscosity customers who wish to continue using mine-
limits during operation: ral oils in existing, as well as new, compres-
sors can do so, providing the compressor
S Optimum viscosity range
type and operating conditions are similar to
(to be designed for) = 20 to 50 cSt
the existing ones (excepting the HPC and
S Max. permissible viscosity =100 cSt HPO series compressors).
S Min. permissible viscosity =10 cSt
(only applicable to HCFC and HFC under YORK Refrigeration has therefore decided to
cartain operating conditions: 7cSt)
market a brand of mineral oil which has been
S Max. permissible viscosity during the tested and found to be suitable for most ge-
starting of the compressor = 500 cSt neral refrigerating purposes.
Maximum refrigerant concentration in the oil
at running condition: 25% - also if viscosity If another brand of mineral oil is chosen, the
requirements are met. specifications in the data sheet in this recom-
mendation should be followed as a guideline.
Use of mineral oil
Lately we have experienced a number of
Mineral oil can be used in refrigerating
problems with mineral oil, particularly in R717
plants, providing the lubricating quality is
plants. The problems can be divided into two
carefully monitored. For modern, high capac-
groups:
ity refrigeration plants, in which a long life-
a: The oil changes viscosity within a few time for both lubricant and moving parts is
operating hours. expected, YORK Refrigeration recommends
b: The oil decomposes (becomes very using synthetic lubricating oils.
black) within a few operating hours.
A benefit of using the synthetic lubricant oil is
The problems have been seen with several
a much lower oil carry-over to the plant and
oil brands and have resulted in severe con-
longer intervals between oil changes.
sequences for both compressors and plants.
A better fluidity at lower temperatures also
gives an easier drainage at the cold parts of
When using mineral oil, it is thus important
the plant.
that the plant is monitored very closely, that
oil samples are taken regularly (every
1-2,000 hours) and that the condition/colour
How to use the oil recommendation dia-
of the oil is checked on a weekly basis.
grams:
YORK Refrigeration therefore recom- To determine the code number, first refer to
mends only to use M oil at moderate oper- the Oil recommendation diagram for the re-
ating conditions - cf. the attached oil rec- frigerant and compressor type and then plot
ommendation diagrams. the proposed operating conditions.
116 0178-910-EN
Example (recip. compressors): the example above, a oil code number E5
Refrigerant: R134a can be selected.
Condensing temp. TC +35°C
Evaporating temp. TE –3°C Code no Area no
1 2
Please observe !
E5 Y
Plants may operate at different conditions
from time to time, for example at different E9 Y
evaporating temperatures due to plant
In plants which incorporate both screw and
variations or at different condensing tem-
reciprocating compressors and where the
peratures due to seasonal changes.
recommendations indicate the use of differ-
By plotting TC and TE in the oil recom-
ent oil types, please contact YORK
mendation diagram, this example would
Refrigeration for advice.
require a No 1 oil. If, however, TE
changes at certain times, e.g. from –3 to Changing oil on Sabroe compressors
+7°C, a No 2 oil should be utilised. But, as
The oil should never be changed to another
+7°C is inside the marked area, the No 1
type without consulting the oil supplier. Nor is
oil can be utilised also at this TE.
it advisable to ”top up” compressors with an
R134a other oil than the one already used for the
ÎÎ
TC
particular plant and compressor.
°F °C
158 70
140 60 ÎÎ
ÎÎ 2
Mixing different oils may result in operating
problems in the refrigerant plant and damage
122 50
ÎÎ
ÎÎ
to the compressors. Incompatibility between
Condensing temperature
• •
104 40
the different oil types may degrade the lubri-
86 30
68 20 1 ÎÎ
ÎÎ
cating properties or may cause oil residues to
form in the compressor or oil separator or in
50 10
the plant. These oil residues can block filters
32 0
and damage the moving parts in the com-
14 -10
pressor.
-4 -20
0178-910-EN 117
It is imperative that oil is only used from the Oil drums should, ideally, be ”racked” and
original container and that both the make and mounted with a proper barrel tap to ensure
type complies with the specification for the an effective airtight seal.
plant.
Oil changing intervals
Ensure that the original container is sealed A list of the recommended intervals for
during storage to prevent moisture from the changing the oil can be found in the com-
air being absorbed into the oil - many oils, pressor instruction manual. These are pro-
particulary the polyolester oils, are extremely vided for guidance only. The actual interval
hygroscopic. Consequently, it is recom- between oil changes will often be determined
mended that the oil is only purchased in con- by a variety of operating parameters within
tainers corresponding to the amount to be the plant.
used on each occasion.
It is strongly recommended to monitor the
If the oil is only partially used, make sure that quality of the oil by carrying out oil analyses
it is effectively re-sealed in the original con- with regular intervals. This will also give a
tainer and that it is stored in a warm, dry good indication of the condition of the plant.
place. Ideally with nitrogen blanking of the oil The service can be supplied by YORK
to keep the water content below 50 ppm. Refrigeration or the oil suppliers.
ÑÑ
ÜÜ
SH : Suction gas superheat, K (Kelvin)
ÜÜ
: Zone in which both oils are useable
: Calculation must be performed using COMP1
118 0178-910-EN
Data sheet for listed Sabroe oils
Typical data for lubricating oils for Sabroe compressors
The listed data are typical values and are intended as a guideline only when selecting a similar
oil from a different oil company. Data equivalence alone does not necessarily qualify the oil for
use in YORK Refrigeration’s Sabroe compressors.
0178-910-EN 119
List of part numbers for available Sabroe oils
Part no.
Oil brand Oil code no.
20 litre pail 208 litre pail
Mobil Gargoyle Arctic 300 M 1 (M68) 1231-264 1231-296
Sabroe Oil A100 A 3 (A100) 1231-263 1231-262
Sabroe Oil AP68 AP 1 (AP68) 1231-257 1231-260
Sabroe Oil PAO68 PAO 3 (P68) 1231-256 1231-259
Mobil Gargoyle Arctic SHC 228 PAO 5 (P100) 1231-282 1231-283
Mobil Gargoyle Arctic SHC 230 PAO 9 (P220) 1231-284 1231-285
Mobil EAL Arctic 68 E 3 (E68) 1231-272 1231-273
Mobil EAL Arctic 100 E 5 (E100) 1231-274 1231-275
Mobil EAL Arctic 220 E 9 (E220) 1231-279
Sabroe H oil E11 (E370) 3914 1512 954 1) 9415 0008 000
1) 18.9 litre pail (5 US gallons)
The oils recommended by the former Stal Refrigeration correspond to the following oils:
120 0178-910-EN
R717 TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
68 20 1
50 10
32 0
-22 -30
AP 1 l/Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil
0178-910-EN 121
R717 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20
50 10
32 0
-22 -30
AP 1 l/Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
Y : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil
122 0178-910-EN
R717 TC
HPO and HPC
°F °C
reciprocating
176 80
compressors
158 70
Condensing temperature
140 60
1
122 50
104 40
86 30
68 20
50 10
Code no Area no
1 32 0
PAO 5 Y -30 -20 -10 0 10 20 30 40 50 °C
TE
-22 -4 14 32 50 68 86 104 122 °F
Evaporating temperature
Please observe: PAO 5 oil is the only oil which can be used in the HPO and HPC compressors.
Y : In case of a new plant. Very suitable.
0178-910-EN 123
R22 TC Contact YORK Refrigeration
one-stage
°F °C
reciprocating 2
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20
50 10
32 0
14 -10 A
Code no Area no -4 -20
1
-22 -30
A3 Y
-60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 ° F
C Evaporating temperature
124 0178-910-EN
R22 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30 1
A
68 20
50 10
32 0
14 -10
0178-910-EN 125
R134a
TC
ÑÑ
°F °C
one-stage
ÑÑ
158 70
reciprocating
ÑÑ
140 60 2
compressors
Condensing temperature
122 50
ÑÑ
ÑÑ
ÑÑ
104 40
86
68
30
20 1
ÑÑ
ÑÑ
50 10
32 0
14 -10
Code no Area no
-4 -20
1 2
-22 -30
E5 Y
E9 Y
-60 -50 -40 -30 -20 -10 0 10 20 30 ° C
TE
-76 -58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature
ÑÑ
YĂ:
ÑÑ :
In case of a new plant. Very suitable.
Zone in which both oils are useable
126 0178-910-EN
R134a TC
two-stage °F °C
reciprocating 158 70
compressors 140 60
122 50
1
Condensing temperature 104 40
86 30
68 20
50 10
32 0
14 -10
-4 -20
Code no Area no
-22 -30
1
-40 -40
E5 Y
-70 -60 -50 -40 -30 -20 -10 0 10 20 30 °C
TE
-94 -76 -58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature
0178-910-EN 127
R407C TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
68 20
1
50 10
32 0
14 -10
B
Code no Area no -4 -20
1
-22 -30
E3 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature
128 0178-910-EN
R407C TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30 1
68 20 B
50 10
32 0
14 -10
0178-910-EN 129
R404A TC
one-stage
°F °C
reciprocating
compressors
122 50 ÑÑÑ
ÑÑÑ
104 40
ÑÑÑ
ÑÑÑ
2
ÑÑÑ
Condensing temperature
86 30
68 20 ÑÑÑ
ÑÑÑ
50 10 1
ÑÑÑ
32 0
1 2
-4 -20
E3 Y
-22 -30
E5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature
ÑÑ
YĂ: In case of a new plant. Very suitable.
ÑÑ
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
: Zone in which both oils are useble
130 0178-910-EN
R404A TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20
50 10
32 0
14 -10
0178-910-EN 131
R410A TC
HPO og HPC
°F °C
reciprocating
122 60
compressors
50
104
40
86
Condensing temperature
30
68 20
10 1
50
0
32
A
-10
14
-20
Code no Area no -4
-30
1
-22 -40
E5 Y
132 0178-910-EN
R507 TC
one-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature 86 30
68 20
1
50 10
32 0
14 -10
0178-910-EN 133
R507 TC
two-stage
°F °C
reciprocating
122 50
compressors
104 40
Condensing temperature
86 30
1
68 20
50 10
32 0
14 -10
134 0178-910-EN
R717 TC
Screw compressors °F
ÜÜÜÜÜÜÜÜ
°C
122 50
ÜÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜÜ
Condensing temperature
104 40
ÜÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜÜ
86 30
68 20
ÜÜÜÜÜÜÜÜ
ÜÜÜÜÜÜÜÜ
1
50
32
10
0
ÜÜÜÜÜÜÜÜ
14 -10
Code no Area no
1 -4 -20
PAO 3 Y
-22 -30
AP 1 l/Y 20 °C
-60 -50 -40 -30 -20 -10 0 10
TE
M1 See note -76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature
Note: YORK Refrigeration recommends that the use of M oils is restricted to moderately loaded compressors and
that the oil quality is monitored carefully via regular oil analyses.
HLI: Calculation must be performed using COMP1
YĂ : In case of a new plant. Very suitable.
lĂ : In case you wish to change from mineral oil
ÜÜ
C :
ÜÜ :
Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
Calculation must be performed using COMP1.
0178-910-EN 135
R22 TC
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ÔÔÔÔÔÔÔÔÔÔÔ
ÒÒÒÒÒÒÒÒÒÒÒ
ÔÔÔÔÔÔÔÔÔÔ
SH25
Screw compressors °F °C
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ÔÔÔÔÔÔÔÔÔÔÔ
ÒÒÒÒÒÒÒÒÒÒÒ
ÔÔÔÔÔÔÔÔÔÔ
ŠŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ÒÒÒÒÒÒÒÒÒÒÒ
ŠŠŠŠŠŠŠŠŠŠ
122 50
2
104 40
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ÒÒÒÒÒÒÒÒÒÒÒ
ŠŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ÒÒÒÒÒÒÒÒÒÒÒ
ŠŠŠŠŠŠŠŠŠŠ
Condensing temperature SH20
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠŠ
86 30 SH5
68 20
ÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜ 1
SH10
50 10
ÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒ
32 0 ÒÒÒÒÒÒÒÒ
A
ÒÒÒÒÒÒÒÒ
Code no Area no
14 -10
ÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒÒ
1 2* SH20
-4 -20
A3 Y
-22 -30
PAO 5 Y -60 -50 -40 -30 -20 -10 0 10 20 °C
TE
-76 -58 -40 -22 -4 14 32 50 68 °F
C Evaporating temperature
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development of
lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
Ü
SH : Suction gas superheat, K (Kelvin)
: Calculation must be performed using COMP1
136 0178-910-EN
R134a TC
Screw compressors °F °C
ÜÜÜÜÜÜÜÜÜ
ÏÏÏÏÏÏÏÏ
ÒÒÒÒÒÒÒÒÒÒÒ SH30
158 70
ÜÜÜÜÜÜÜÜÜ
ÏÏÏÏÏÏÏÏ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚ
ÜÜÜÜÜÜÜÜÜ
ÒÒÒÒÒÒÒÒÒÒÒ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
140 60 SH20
122 50
ÜÜÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑ
ÜÜÜÜÜÜÜÜÜ
Condensing temperature 104 40 ÚÚÚÚÚÚÚÚÚÚ
ŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑ
ÜÜÜÜÜÜÜÜÜ
ŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑ
2 SH10
ÜÜÜÜÜÜÜÜÜ
ŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑ
ŠŠŠŠŠŠŠŠ
ÑÑÑÑÑÑ
86 30
SH5
68 20
ÑÑÑÑÑÑ
ÒÒÒÒÒÒÒ
ÑÑÑÑÑÑ
ÒÒÒÒÒÒÒ1
ÒÒÒÒÒÒÒ
50 10
Code no Area no
32 0
ÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒ
ÒÒÒÒÒÒÒ
(See note) 14 -10
1 2 SH20
E5 Y -4 -20
E9 Y -50 -40 -30 -20 -10 0 10 20 30 °C
TE
-58 -40 -22 -4 14 32 50 68 86 ° F
Evaporating temperature
Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
YĂ : In case of a new plant. Very suitable.
ÑÑ
SH : Suction gas superheat, K (Kelvin)
ÜÜ
: Zone in which both oils are useable
: Calculation must be performed using COMP1
0178-910-EN 137
R404A TC
Screw compressors
ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÖÖÖÖÖÖ
°F °C
ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÖÖÖÖÖÖ
SH15
104 40
ÜÜÜÜÜÜÜ
ÚÚÚÚÚÚÚÚÚÚ
ÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ ÖÖÖÖÖÖ
Condensing temperature
86 30
ÚÚÚÚÚÚÚÚÚÚ
ÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑ 3 SH10
2 (3)
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑ
68 20
50 10
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖ
ÜÜÜÜÜÜÜ ÖÖÖ
32 0 ÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖÖÖ
ÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖ 1
(2)
14 -10
ÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖ
ÖÖÖÖÖÖÖ
B
ÖÖÖÖÖÖÖ
Code no Area no
(See note) -4 -20
ÖÖÖÖÖÖÖ
1 2 3 SH15
E3 Y -22 -30
E5 Y -70 -60 -50 -40 -30 -20 -10 0 10 °C
E9 Y TE
-94 -76 -58 -40 -22 -4 14 32 50 °F
C Evaporating temperature
Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
ÑÑ
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
ÑÑ
ÜÜ
SH : Suction gas superheat, K (Kelvin)
: Zone in which both oils are useable
138 0178-910-EN
R407C TC
Screw compressors
°F
122
°C
50 ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚ
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ ÚÚÚÚÚ
SH10
ŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ
104 40
SH5
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
Condensing temperature 2
86 30
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
68 20
50 10
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ÑÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ 1
32 0
B
14 -10
ŠŠŠŠŠ
ŠŠŠŠŠ
ŠŠŠŠŠ
Code no Area no -4 -20
(See note) SH5
1 2
-22 -30
E3 Y -70 -60 -50 -40 -30 -20 -10 0 10 20 °C
E9 Y TE
-94 -76 -58 -40 -22 -4 14 32 50 68 ° F
C Evaporating temperature
Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
YĂ : In case of a new plant. Very suitable.
B : Max oil concentration in liquid phase: contact YORK Refrigeration
C : Min suction temperature –50°C: at TE< –50°C superheating must be introduced.
ÑÑ
SH : Suction gas superheat, K (Kelvin)
ÜÜ
: Zone in which both oils are useable
: Calculation must be performed using COMP1
0178-910-EN 139
R507 TC
Screw compressors
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ
°F °C
104 40
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ÜÜÜÜÜÜÜ ŠŠŠŠŠ
ÑÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ 2
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ŠŠŠŠŠ
86 30 SH5
Condensing temperature
ÜÜÜÜÜÜÜ
ÑÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖÖÖ
ÜÜÜÜÜÜÜ ŠŠŠŠŠ
ÑÑÑÑÑÑÑÑÑ
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
68 20
50 10
ÜÜÜÜÜÜÜ
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÜÜÜÜÜÜÜ
1 SH5
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏ
32 0
SH15
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏ
ÖÖÖÖÖÖÖÖÖÖ
ŠŠŠŠŠŠŠŠŠŠŠ
ÏÏÏÏÏÏ
14 -10
Note: For the compressors type ”S”, ”Rotatune”, ”SAB 81”, ”SAB 83”, and ”SAB 85” only Sabroe oil H is approved.
Using the calculating programme COMP1 it is possible to optimize the requirement for suction superheat values
(SH) as stated in the diagram. See Oil types and oil companies in this section. Due to the ongoing development
of lubrication oils, please contact YORK Refrigeration for an update on the requirement for superheat.
HLI: Calculation must be performed using COMP1.
Ñ
SH : Suction gas superheat, K (Kelvin)
Ü
: Zone in which both oils are useable
: Calculation must be performed using COMP1
140 0178-910-EN
List of major oil companies
The oil from the companies listed below are NOT tested by YORK Refrigeration and are there-
fore NOT approved by YORK Refrigeration either. The following list reflects the information pro-
vided by the companies themselves. The assessment of durability and suitability of specific oils
for specific purposes are entirely at the companies’ own discretion. Oils tested and approved by
YORK Refrigeration can be found in the ”List of part numbers for available Sabroe oils”.
0178-910-EN 141
Notes:
142 0178-910-EN
Alignment of unit, AMR coupling
Where the compressor and motor are directly manufacturer prior to delivery. The following
interlinked, an AMR coupling is used; this is a sections will deal with the individual points
torsionally rigid coupling with enough radial concerning the fitter.
and axial flexibility to assimilate small move-
ments between the two machines. Alignment of unit with foundation
Whenever installing a unit directly onto the
In order to ensure compressor and motor a
foundation or machine floor, it should stand
long life as well as noise- and vibration-free
free of stresses and press down evenly on all
operation, compressor unit and coupling
supports.
need to be aligned with care. Misalignment of
the compressor unit or coupling may The unit can be installed in the following
produce stresses and vibrations which can ways:
be transmitted to the compressor and motor
S on vibration dampers
bearings and thus cause major damage.
S straight onto a foundation, using founda-
95.03
0178-910-EN 143
Installation on vibration dampers
1
A1
A2
H Hmax
A1
A2
T0177040_0
144 0178-910-EN
Installing directly on foundation Perform this check with the bolts loosened. If
slip occurs at one or more resting surfaces,
When installing a unit directly on a concrete
shim up before tightening. If unaligned, there
foundation, the foundation should be cast in
is a risk of stresses occurring in the compres-
accordance with the foundation drawings dis-
sor frame, which will damage the bearings.
patched.
When the foundation has been cast - with the Alignment of motor with base frame
holes shown for foundation bolts - and has Check the contact faces of the motor against
set, place the unit in position, allowing it to the base frame in the same way as for the
rest on beams levelled at a suitable height so compressor.
that the foundation plates are recessed
slightly into the foundation. Stresses from piping connections
In order to prevent stress being transmitted
Check that the foundation plates are right
from piping connections between unit and
next to the base frame. This can be achieved
plant, pipes must be laid so as not to gener-
by binding them to the resting surfaces of the
ate compressive stresses or tensile strains in
base frame with steel flex.
the event of expansions or contractions due
The concrete cast down around the founda- to temperature changes. Steel piping ex-
tion bolts should contain only a small amount pands approx. 1 mm per metre per 100°C.
of water, so that it can be well tamped around We recommend that piping be laid as shown
the bolts. Low water content produces no in example 2 of the sketch. Example 1 dem-
contraction of the setting concrete. onstrates too rigid pipe laying.
Check that the entire footing of the compres- Final alignment of compressor and motor can
sor makes full contact against the milled-off be performed once all piping has been con-
faces of the base frame. nected to the unit.
0178-910-EN 145
Fitting and alignment of AMR-type coupling
Installation and alignment Important
Before any work on the coupling, ensure
In principle, alignment involves manoeuvring
that the compressor motor cannot be
the motor so as to make the shaft form an
started inadvertenly.
extension of the crankshaft.
Fig. 1
1
Compressor Motor
Z
2
X
a
A
B
C
T0177120_0/V2
HPC/SMC
312 S 103,5 147 55 0,2 0,1/0,3 0,2
104-108
SMC
350 S 114,5 147 128 0,2 0,1/0,3 0,2
112-116
SMC
450 S 149,0 295 275 0,3 0,1/0,4 0,3
180
* See Final mounting, pt. 4
146 0178-910-EN
Preliminary installation Alignment
S Check tightening of coupling flange on Check that the motor with loose bolts stands
compressor. with all four feet on the base frame. Insert
any liner plates needed where there is an air
S Tighten 8 coupling bolts securing lamellar gap beneath the feet. Tauten the bolts slight-
segments to intermediate piece to pre- ly.
scribed moment stated in table. It is worth-
while doing this before placing the inter- Achieving parallel shafts in
mediate piece in position.
horizontal plane
S Mount retaining plate from coupling S Turn coupling so that alignment gauge is
screen onto compressor and insert sup- in upper position. See fig. 1.
port ring for coupling screen over motor S Guide measuring pin (Pos. 2) towards
flange. coupling flange, using a 1.0 mm feeler
gauge, and fix pin. Remove feeler gauge.
S Insert coupling intermediate piece. Create
space between flanges either by shifting S Rotate coupling 180° and measure
entire motor or just motor coupling flange. change in distance from measuring pin to
The intermediate piece should only be flange, using feeler gauges. This change
secured to the compressor flange. Do is called ”x”.
not insert the last four bolts in the mo- S Insert shims of thickness ”y” either under
tor flange until the coupling has been both front feet or both rear feet, thereby
aligned. tilting motor in direction required. Shim
As the compressor shaft rotates during the thickness ”y” is calculated using the fol-
alignment procedure, the motor must turn lowing formula (see drawings):
with it, as the bolts in the intermediate
b
piece engage in the free holes in the mo- y = X •
2xa
tor coupling flange.
0178-910-EN 147
Achieving correct centre height S Turn coupling 180° and, using feeler
gauges, measure deviations from one mil-
S Turn coupling so that alignment gauge
limetre at both pins.
faces vertically down.
S Guide measuring pin (pos. 1) towards S Moving and turning motor and repeating
coupling flange, using a 1.0 mm feeler this measurement, align motor in accord-
gauge, and fix pin. Remove feeler gauge. ance with pos. 1 horizontal and pos. 2 in
S Rotate coupling 180° and measure in- table. Remember that the motor must be
crease in distance ”z” from one millimetre firmly secured during any measurements.
using feeler gauges.
Final installation
S Then lift motor by placing shims of thick-
ness equal to half value of ”z” under all S Tighten foundation bolts on motor (see
four feet. torque table).
S After securing motor, repeat measurement S Fit four bolts into motor coupling flange so
and compare result with table values in that thin shims are placed between flange
pos. 1 vertical. Remember that the centre- and lamellae, with rounded side facing la-
line of the motor shaft must be at least mella. There are no thin shims on cou-
0.05 mm higher than the centreline of the plings for CMO and HPO.
compressor, corresponding to a minimum
S Tighten bolts to torque specified in table.
of 0.1 mm distance less at the top position
of the alignment gauge. S Readjust flange distance ”C” so that la-
mellae are aligned, by moving motor
Achieving parallel shafts in vertical flange on shaft and fastening motor
plane flange.
S The motor is now positioned at its correct S Check alignment of coupling in horizontal
height. What now remains is to push and and vertical planes for pos. 1 and pos. 2.
turn the motor at the level on which it is
already lined up. S Dismantle measuring pin and tighten
screw to prescribed torque.
S Turn coupling so that alignment gauge
faces out to one side horizontally. S Fit coupling guard.
S Guide both measuring pins towards coup- S Once normal operating temperature has
ling with a 1.0 mm feeler gauge in be- been achieved, double-check coupling
tween. alignment.
148 0178-910-EN
Boring of motor flange for AMR coupling
A MAX. 0.02 mm
B
92.03
MAX. 0.02 mm
T0177131_0 V12
Unless the necessary data for the motor are S The bore should then be made to the rele-
010-502-EN
known prior to dispatch, the motor flange for vant dimensions and to the following toler-
the AMR coupling will not be supplied in ances:
ready bored form.
H8 for AMR 312, 350 and 450,
In such case, the motor flange is supplied H7 for AMR 225.
prebored and balanced.
S Cut keyways.
Finish-boring is done as follows:
For reasons of balance, coupling AMR
S Secure flange in lathe or jig-boring ma- 312, 350 and 450 must be executed with
chine. Observe following tolerances for the two keyways shown.
alignment purposes:
S Make the width of the keyway to a toler-
Max. axial eccentricity ance of H7.
measured at point A 0.02 mm
S The keyway must be deep enough to al-
Max. axial eccentricity 0.02 mm low a clearance between parallel keys
measured at point B
and hub of 0.2-0.3 mm.
Max. boring diameter:
Compressor CMO - TCMO - HPO SMC - TSMC 100 - HPC SMC - TSMC 180
Boring tolerance H7 H8 H8
0178-910-EN 149
VĆbelt drive for piston compressor types
(T)CMO and (T)SMC
If your SABROE compressor is belt driven, V-belts are used with profiles specified in the
table below.
95.06
SMC - TSMC 186 - 188 SPC (21 x 18) 1230 9,00 6,50
0171-469-EN
Fig. 1 Fig. 2
C
C/2
15 mm
T0177084_0
150 0178-910-EN
question, as stated in the table. Tighten S When changing worn V-belts, the whole
belt drive so that sag is approx. 15 mm for set should be replaced.
all V-belts.
S A new belt drive always has to be tight- S A set of V-belts must always be within the
ened to the max. value. same tolerance group.
S Run transmission for a few minutes and S Never use belt lubricant.
then check tension.
0178-910-EN 151
Oil Separator OVUR for SMC/TSMC 100
HPC Ć SMC/TSMC 180
97.01
the discharge gas temperature. Rising tem- nor does it get worn. Consequently, the filters
peratures often lead to an increased oil con- cannot be removed from the oil separator.
0171-475-EN
Fig. 1 A
L
A: Discharge gas inlet B: Discharge gas outlet L: Oil return to the compressor
152 0178-910-EN
Oil return to the compressor a: Solenoid valve controlled oil return
As illustrated in fig. 2 the oil is conveyed from
The separated oil leaves the oil separator
the oil separator through the screwed con-
through the pipes pos. L, and can be regu-
nections pos. 80A and 80B. Fig. 2 pos. also
lated by the following systems:
shows that pos. 80A is of such a length that it
pierces the base plate by approx. 10mm. In
a: Solenoid valve controlled oil return this way any dirt particles may be collected
on the bottom of the oil separator instead of
b: Float valve controlled oil return being returned with the oil to the compressor.
80M
Oil separator
Solenoid valve
80M 80C
stop
valve 80M
Filter
80A
At point A the oil flows into the valve block 80E, which can be removed by dismounting
pos. 80 and from point B is led to the com- cover pos. 80F. The filter can be cleaned in a
pressor as illustrated in fig. 3. cleansing fluid and blown clean with com-
pressed air.
The valve block consists of a stop valve pos.
80D, which is closed and opened by turning On remounting of the cover tighten it with a
of the spindle. This valve may be dismantled 60 Nm torque. Remember gasket pos. 80G.
by unscrewing the big union nut from the val-
Before removing the oil filter, close stop valve
ve block. On mounting, tighten it once more
pos. 80D and evacuate the compressor to
with a 60 Nm torque.
atmospheric pressure as described earlier on
From the stop valve the oil passes filter pos. in this manual.
0178-910-EN 153
Fig. 3 During start-up of the compressor, the sole-
1.4 Nm
80N noid valve can be kept closed for 20 to 30
80K mins. by means of a time relay, available as
80H
an additional equipment. This prevents any
80J
A
refrigerant from entering the compressor
80M
80P
during start-up.
60 Nm 80L
50 Nm The seat of the solenoid valve pos. 80I also
10 Nm
80Q acts as a nozzle that regulates the oil flow
80I back to the compressor.
80
80D
Select the nozzle size on the basis of table 4.
We recommend not to use a bigger nozzle
size than prescribed. In order to replace the
nozzle the compressor must first be depres-
B
80E
surized. Next, dismantle coil pos. 80J and
80G armature tube pos. 80P.
60 Nm 80F
The nozzle is screwed into the valve block
and, on remounting, use gasket pos. 80Q
for the nozzle and gasket pos. 80L for the
armature tube. Tighten with the prescribed
moments of 10 and 50 Nm – see fig. 3.
After the oil has been cleaned, it flows to the On mounting the coil keep it in place by
solenoid valve, which is always closed at using hand screw pos. 80N and O-ring pos.
compressor standstill. 80K and 80M.
Fig. 4
Two stage compressor
R717 One stage compr. Booster compr. TCMO TSMC TSMC
Mk 2 100 180
CMO SMC SMC CMO SMC SMC
Mk 2 100 180 Mk 2 100 180 LP HP LP HP LP HP
Number of cylinders
154 0178-910-EN
b: Float valve controlled oil return
Fig. 5
To the compressor
A D
As shown in fig. 5, the separated oil is The filter pos. D and the float valve can be
drained to the float valve pos. C while valves cleaned by dismantling the threaded nipple
pos. A and B are open. At a rising oil level on the stop valve housing and removing the
the float valve will open and lead the oil back cover on the float housing after the valves
to the compressor crankcase. pos. A and B are closed and the pressure in
the compressor equalized to atmospheric.
0178-910-EN 155
Connections on SMC 104Ć106Ć108 Mk3,
HPC 104SĆ106SĆ108S
X 1 AF, S
1
•
Z
2 • S
• •
2
AC
L • •• • H, Q
• F
• S
•
S
• •
•
• ••
K
• •
• •
• J
• •
P
•• •
O
• T
• •
AM U
V
AB G N
E C D B A T0177087_0/V1
97.10
Air- Air-
Thread Oil, cooled cooled Ther- Booster
Pos. RG Pressure gas or Water- w/built-in mo- with Normal application
0171-414-EN
(Inch) liquid cooled oil cooler pump oil cooler
A 1 1/4 suction oil + + + + Heating rod
B 3/4 suction oil + + + + Oil charging valve
C 1/2 suction oil + + + + Oil temperature
D 1/2 suction oil plugged + plugged + Oil temperature
E 1/4 suction gas plugged plugged plugged plugged Available
F 1/4 oil oil + + + + Oil pressure to unloading cylinder
G 1/2-1/4 suction gas plugged + + + Return from built-in oil cooler *
H 1/4 discharge gas + + + + High pressure connection (HP)
J 1/4 suction gas + + + + Oil return from solenoid valves
K 1/4 oil oil + + + + Oil pressure to solenoid valves
L 1/4 suction gas + + + + Low pressure connection (LP)
N 1/4 suction gas + + + + Oil return from oil separator
O 1/2-1/4 oil oil + + + + Oil pressure connection
P 1/4 suction gas plugged + + plugged Return from built-in oil cooler/
equalization from thermopump *
Q 1/4 discharge gas plugged plugged + plugged Return from oil cooler
(thermopump cooled)*
S 1/4 discharge gas plugged plugged + plugged Refrigerant cooling to top covers *
T 1/4 discharge gas – – + – Equalization to suction pressure end from
thermopump
U 1/4 discharge liquid – – + – Liquid inlet to thermopump*
V 1/2-1/4 suction liquid plugged + + + Supply to built-in oil cooler*
X 1/2 discharge gas + + + + Discharge gas temperature
Z 3/4 discharge gas + + + + Purge valve
AB 1/4 oil oil + + + + Prelubrication of bearings
AF 1/4 discharge gas plugged + + + Return from oil cooler (booster) *
AC 1/2 suction gas Used in connection with UNISAB II Suction temperature (superheat temp.)
AM 1/4 oil oil plugged plugged plugged plugged Available
1 Suction stop valve * These connections are not applied on HPC compressors
2 Discharge stop valve
156 0178-910-EN
Connections on TSMC 108 Mk3
1 AC Y 1 S
AF
• Z 2 • Q
H M
• S
• ••
• L X •
• • •
AL
• S
• 4
• •
•
• • • • •
• • •
F
O K • •
• • • • P
•• •
J
•
T
3
AM U
E C D B A
R AB G N
0178-910-EN 157
Oil return in parallel operation for
reciprocating compressors
95.06
on compressor
0171Ć474ĆEN
T0177089_0/2
158 0178-910-EN
Schematic diagram
Standard
Oil separator with
solenoid valve controlled oil return
Parallel system,
fitted on unit Alternative
Oil separator with
float valve controlled oil return
Compressor 1 Compressor 2
5 5
1 1 5
2 2
3 7 3 7 8 12
4 6 4 6 11 13
9
10
Oil charging
Heating cartridge 9 Liquid level glass
Oil receiver
0178-910-EN 159
Unscrew the cap on the vent valve and acti- connected to the discharge side of the plant,
vate the spring-loaded valve in the branch by as shown in the schematic diagram.
pressing it down with a screwdriver or similar.
In the pipe connection to the discharge side,
mount a 0.4 mm diameter nozzle Pos. 12
If the float-valve controlled oil return Pos. and a solenoid valve Pos. 11, which must be
8 is used, the oil tank must - in order to main- open also when only one compressor is op-
tain the driving pressure at 1 bar - also be erating.
160 0178-910-EN
Reciprocating compressors used for air conditioning
CMO 24Ć26Ć28 and SMC 104Ć106Ć108
When the CMO or SMC compressor is used connected to any of the above pressure
for air conditioning, you can choose to control cut-outs.
the compressor capacity by means of one or
Pressure cut-out A must be set to a close at
two KP1 pressure cut-outs.
a pressure approx. 0.5 bar higher than the
CMO compressors are all controlled by three setpoint for cut-out B.
solenoid valves. When these are to be con-
A third cut-out, the low-pressure cut-out,
trolled with pressure cut-outs, cut-out A must
must be set to break at a pressure equal to
be connected in parallel with solenoid valves
the lowest evaporator temperature that can
nos. 1 and 2. Cut-out B must be connected
occur, however, never lower than started in
with solenoid valve no. 3.
section Pressure and temperature settings.
The SMC 108 must be connected in the At this temperature, the compressor must
91.06
same way as CMO. stop. This control form provides the following
capacity stages:
The SMC 106 is controlled by two solenoid
0171-348-EN
3 4 1
2 1 1 2 3
2
1
A A 1 A 2
1 2 3
1 B 2 B 3
A B
0178-910-EN 161
WaterĆcooling of reciprocating compressors
SMC 104Ć106Ć108 and TSMC 108
SMC 186Ć188 and TSMC 188
HPC 104ĂSĆ106ĂS and 108ĂS
The reciporcating compressor can be cooled sket. This will prevent water flowing into the
with water on the top and side covers, the compressor block.
cooling requirement being dependent on the
operating conditions and the refrigerant on Salt water-cooling
which the compressor operates. If it is expedient not to use fresh water for the
See page 1 for details. cooling of the top and side covers, salt water
dan be used to cool the side covers. The top
Water cooling is obtained by mounting an ex- covers must never be cooled with salt water
tra cover (water cover) Pos. 2B on the outsi- as the high temperature combined with the
de of top and side covers with an intervening salt water will corrode the covers in a short
seal Pos. 2D. period of time. For R717 compressors the top
99.11
covers may in some cases be cooled by me-
Tighten top and water covers with the bolts
ans of a thermal pump, see the diagram of
Pos. 2E, which are longer than the bolts for
0171-411-EN99
the operating range of the compressor in
the air-cooled version. See the Spare-parts
quistion.
list at the back of this instruction manual for
details. Fitting cooling water hoses
S When supplied, the compressor is not
For water cooling of the side covers, a spe-
fitted with cooling water hoses or any rele-
cial finned side cover Pos. 3A is used toget-
vant assembling parts. These are pro-
her with a water cover Pos. 3B and a seal
vided loose. This avoids damage to the
Pos. 3D. These are also listed in the spare-
parts in transit. Fit the cooling water hoses
parts list.
as shown in the following drawing, corre-
The water cover, together with the cover on sponding to the specification enclosed
which it is mounted, forms a channel system with the delivery.
in which the water is channelled back and
forth and effectively cools the top or side co- Please note:
ver. By virtue of their large surface area, the S The direction of water throughflow is
cooling fins on the interior of the side cover shown by arrows on the drawing.
Pos. 3A provide excellent cooling of the oil in
S The hose length is indicated opposite the
the crankcase.
respective Pos. nos. on the drawing.
When dismantling top or side covers with wa- S The hoses must not be in contact with the
ter covers, it is a good idea first to dismantle frame, covers, discharge pipe or similar
the topmost covers on the compressor. In components.
addition, you should ensure that the two co-
vers are kept tight against the intervening ga-
162 0178-910-EN
In the supply pipe to the water system a solenoid valve must be fitted which shuts off the water flow in
the refrigeration system at compressor standstill.
However, we do recommend to continue the water cooling for approx. 10 mins after the compressor has
been stopped as this protects the cooling water hoses against excessive temperatures
SMC 108
1
TSMC 108 SMC 188
1
HPC 108 TSMC 188
Pos Length Length
2 Nr. (mm) (mm)
1 300 325
3 *)2 790 1300
3
4 3 400 470
5 4 160 300
5 700 1100
SMC 106
HPC 106 SMC 186
1
6 Pos Length Length
Nr. (mm) (mm)
1 500 760
2
*)2 820 1300
3 3 325 525
3
4 4 150 300
5 5 670 1100
6 380 550
1 SMC 104
HPC 104
Pos Length
2 Nr. (mm)
3
1 610
3 *)2 750
4
3 370
5 4 160
5 670
*) To be secured to the vertical oil pipe using two pieces of plastic tape. T0177088_0/1
0178-910-EN 163
Necessary water consumption Max. permissible inlet temperature:
+40°C
To achieve satisfactory distribution of cooling
water and hence good compressor cooling, Min. permissible inlet temperature:
the following limit values should not be ex- +10°C
ceeded:
Max. permissible outlet temperature:
+55°C
Min. water through flow:
5.5 litres per hour per Kw motor output. Max. permissible temperature rise from
On water circulation plants, greater water inlet to outlet on the compressor:
throughflow is recommended. 15°C
164 0178-910-EN
Pressure loss in water cooling
on SMC/TSMC/HPC compressors
TSMC 108
Pressure loss SMC 108
p(mVS) HPC 108
SMC 106/HPC 106 SMC 104/HPC 104
4
SMC
112
T/SMC
116
3
2
SMC
186
T/SMC
1 188
T0177130_0
0178-910-EN 165
Structure of the thermo pump control the solenoid valves, pos. 98G and
Together with the cooling cover, pos. 98Q, pos. 98H, so that they are open and shut si-
the side cover, pos. 98A, forms a pump ves- multaneously. The thermo pump is safe-
sel, pos. 98, which is supplied with heat from guarded by the following systems:
the oil bath in the crankcase. The cooling (See principle drawing)
cover is equipped with cooling fins in order to a: A thermostat built into the control box pos.
provide a satisfactory thermal contact with 98B with sensors pos. 98X fitted on the
the oil. compressor discharge pipe.
As illustrated in the principle drawings, the
Fasten the sensor to the discharge pipe
pump vessel has the following three pipe
right next to the discharge stop valve by
connections:
means of two clips. Ensure a proper
S Connection pos. A which is linked to the thermal contact.
compressor suction side and which can be
blocked by means of solenoid valve pos. The thermostat is factory set to start up
98G. Used to lower the pressure in pump the thermo pump once the discharge gas
vessel pos. 98. Part of the pumping cycle. temperature is above 80°C.
S Connection pos. B emerges from the re- b: An evacuation system emptying the pump
ceiver or the priority tank and goes right to vessel through solenoid valve pos. 98V
the valve block pos. 80 which is of the sa- whenever the thermo pump stops.
me type as the one described in the sec- Please, notice that the pipe connection
tion on: Solenoid valve controlled oil
pos. D to the plant evaporating side must
return in this instruction manual.
be made at a spot where there is no risk
Please, note that the size of orifice
of the liquid flowing back to the compres-
pos. 80I must be 3.3 mm.
sor. Connection should, f.inst., be made to
S Connection pos. C is connected to the top the liquid separator or the evaporator.
covers and the oil cooler pos. 98T through c: A safety circuit with a non-return valve
a number of nozzles pos. 98M. pos. 98Z that opens for the flow at a pres-
Filling and evacuation of the pump vessel is sure 3 bar higher in the pump vessel than
controlled by two level sensors, pos. 98C, the one in the compressor discharge gas
which by means of the control box, pos. 98B, line.
98G 80 B 98B 98A
98Q
A
98C
98D 98E
98F
98L
C
98H 98X
T3185085_5
166 0178-910-EN
Description of pumping cycle Capacity regulation of thermo pump
On reducing the compressor capacity it be-
Filling of pump vessel comes necessary also to reduce the cooling
As soon as the liquid leaves the bottom level effect of the thermo pump. This is done as
sensor, the control box will activate the sole- follows:
noid valves pos. 98H in valve block pos. 80
SMC 104-106-108, TSMC 116
and pos. 98G.
CMO 24-26-28
Hereby, solenoid valve pos. 98G opens in the The pipe connection from the pump vessel to
pipe connection to the compressor suction the top covers is on its way divided into two
side and the pressure in the pump vessel de- pipe lines. In one of these pipe lines a sole-
creases slightly. At the same time solenoid noid valve, pos. 98U, is fitted.
valve pos. 98H opens and refrigerant liquid This solenoid valve is connected to the the
starts flowing to the pump vessel through capacity regulating system of the compressor
pipe connection B. and closes when the compressor capacity
has been reduced, as indicated in the follow-
Evacuation of pump vessel ing table:
The pressure in the pump vessel now rises SMC 104 100% 50%
as a consequence of the heat impact from
the compressor oil and - when exceeding the SMC 106 100-67% 33%
pressure on the compressor discharge side -
will make the refrigerant flow through the SMC 108 100-75% 50-25%
pipe connections to the top covers and the oil
TSMC 116 100-83-67% 50-33%
cooler.
CMO 24 100-75% 50-25%
At the top covers the refrigerant expands
through the nozzles pos. 98M directly into the CMO 26 100-67% 50-33%
hot discharge gas, with immediate cooling of
the discharge gas. CMO 28 100-75% 50-25%
0178-910-EN 167
positioned at the compressor shaft end and Similarly, the other green diode for the bot-
marked X on the principle drawing. tom sensor will only be switched off from the
moment the bottom level has been registered
The disconnection is achieved through the
and until the liquid rises once more on filling
connection of the thermo pump via terminals
of the vessel.
5 and 6/7 or 8 to the capacity regulating sys-
tem of the compressor. The supply voltage to At the bottom level a time lag of a few se-
the thermo pump must be switched off once conds has been built in order to prevent the
the compressor capacity has been reduced solenoid valves from clattering in the event of
to the values indicated in the table below. any lapping in the vessel.
168 0178-910-EN
Possible sources of error Both diodes are constantly lit
In case the above tests should reveal that If one or both diodes are constantly lit, even
one or both of the diodes do not light up with no liquid on the sensor, this may be due
when touched, this may be due to: to a conductive connection between the inner
and the outer part of the level sensor rod.
1. No voltage to the control box.
Outside the side cover the level sensor rod is
2. Loose power connection. protected by O-rings and a protective cap
preventing water and moisture from making
3. Defective control box. contact.
(To be replaced by a new one)
An oil drop may have slipped inside the side
In case both diodes switch on and off correct- cover. In this case it is recommended to strip
ly but the built-in relay is not working, replace down the sensor rod and clean the parts. On
the control box. mounting make sure that the sensor rod cen-
ters in the sensor tube.
If the diodes light up and the relay is working,
the error may be found in the solenoid If, after remounting, the error persists, the
valves: control box must be replaced.
1. Loose connections to the solenoid valves.
Ensuring liquid to the thermo pump
2. Burnt coils in the solenoid valves. The thermo pump must always be ensured
liquid from the plant, no matter whether the
3. Some other malfunction in the solenoid plant lacks liquid or some other factor pre-
valves. vails.
If the above-mentioned sources of error are Thus, the thermo pump must also be en-
not present and the thermo pump still fails, sured liquid during a possible pump down by
the reason may be: means of the compressor.
1. Closed stop valve in the liquid line. In other words: During operation the com-
pressor must never be short of cooling.
2. Clogged filter in the liquid line.
This safety is achieved by either taking the
3. Dirt in the solenoid valves. liquid directly from the receiver, pipe connec-
tion B or by building a priority tank into the
4. Flash-gas in the liquid supply pipe or liquid liquid line of the plant (see drawing).
shortage. The liquid volume A of the priority vessel
must be minimum 10 litres per thermo pump.
5. A very low differential temperature be-
tween oil and condensing temperature. The liquid tube from the priority vessel to the
thermo pump must be dimensioned to pre-
6. Clogged nozzles pos. 98M. vent the formation of flash gas along the way.
0178-910-EN 169
1 1
3
Receiver
Priority tank
3
B
B
2
170 0178-910-EN
Oil cooling of SMC and TSMCĆtype reciprocating
compressors with an OSSI or HE8S oil cooler
Oil separator
that the oil cooling system is not activated
until the oil temperature in the crankcase ex- CT
MT HT
ceeds +55°C. LT MT
0178-910-EN 171
Cooling of the intermediate gas on
TCMO and TSMC 100 and 180
97.03
quid stroke in the HP cylinders and result in
wear to the moving parts. It is important, Fig. 2
TCMO, TSMC 100/180 compressor
therefore, to check the systems as indicated
0171-359-EN
below. Oil separator Oil separator
CT
LP IP HP
LPIP
Intermediate cooling system with Suction filter
intermediate cooler type DVEA,
R717 Equalizing pipe
172 0178-910-EN
In the liquid subcooling spiral, the refrigerant liquid refrigerant into the intermediate pipe.
flowing from the receiver to the evaporator This is achieved with the following systems 1
side of the refrigeration plant is cooled. The and 2:
intermediate cooler is dimensioned so that
1: Intermediate cooling with thermostatic
the cooled gas is free of liquid refrigerant be-
expansion valve type:
fore leaving the top of the intermediate cool-
TEA (R717) or TEX (R22)
er. It is important to check that the float valve
TCMO and TSMC 100/180
is functioning correctly and keeping the liquid
level constant. Frosting of the liquid level Fig. 3
pipe on the intermediate cooler indicates the TCMO and TSMC
liquid level. Oil separator
• CT
In order to avoid violent foaming of the liquid
in the intermediate cooler, the compressor IP HP Suction filter (opt.)
LP LP IP •
should run for a few minutes after start-up at
the lowest capacity stage to stabilize plant LP
Make sure that the equalizing pipe on the in- TEA or TEX 80
0178-910-EN 173
It is essential to make sure that the inter- before the HP-stage suction filter. The sensor
mediate cooling system functions correctly in must be fitted on the side of the pipe and in-
order to prevent too much liquid refrigerant sulated as shown in fig. 5
from being injected into the IP gas.
Position the sensor of the expansion valve on S SABROE has adjusted the valve to 10 K
the intermediate pressure pipe immediately superheat.
174 0178-910-EN
2: Intermediate cooling with thermostatic Fig. 7
injection valve type:
TEAT (R22) 83A
TCMO and TSMC 100/180
B: TSMC 100/180
HP
IP Fig. 8
LP
KP 77
80
T
Oil separator
Liquid subcooler CT
To evaporator IP HP
TEAT LP LP IP Mixing chamber
LP
From receiver Liquid tank 4L
A
TEAT
Liquid supply
From receiver To evaporator
HESI
As illustrated in fig. 6 the intermediate gas is On TSMC 100 and 180 plants, the intermedi-
cooled by injecting refrigerant into the low ate cooling system can be designed as illus-
pressure stage pressure chamber in the trated in fig. 8, in which the intermediate cool-
compressor. The liquid is thoroughly mixed ing is carried out by a thermostatic injection
with the hot discharge gas by means of the valve of the TEAT type, and in which the sub-
distributor pos. 83A as may be seen from cooling takes place in a HESI heat exchang-
fig. 7. er.
0178-910-EN 175
Adjusting the TEAT valve: Adjustments are made by rotating the regu-
For both systems, A and B, the following lating spindle clockwise, 5 turns for every
applies: 10K of temperature increase.
The sensor of the TEAT valve is placed in a
Example:
sensor pocket at the discharge branch of the
compressor, and a proper thermal contact is Refrigerant R22
obtained by means of the heat conducting Regulating temperature
compound. factory setting 75°C
Before using the valve, the regulating tem- At reduced compressor capacity, the dis-
perature must be changed to the same value charge gas temperature may rise somewhat;
as the discharge gas temperature indicated under these circumstances it should be
in the table Anticipated discharge gas tem- checked that the discharge gas temperature
peratures in this instruction manual. does not exceed the Set point for the KP98.
176 0178-910-EN
Ordering Spare Parts
When placing an order for spare parts, ber. If you are in any doubt, add the spare
please state the following: part no. too.
0178-910-EN 177
Spare parts sets for compressors and units
CMO/TCMO Ć SMC/TSMC 100 Ć SMC/TSMC 180
97.03
part sets recommended by SABROE.
0171-941-EN
S Standard spare part set
S Standard spare part set
This is a set consisting mainly of O-rings
Contains a suitable selection of O-rings
and gaskets for some of the components
as well as valve ring plates and valve
included in the unit.
springs.
178 0178-910-EN