Professional Documents
Culture Documents
04
Shop no:
Password:
Software version:
Engineering Manual
UNISAB II Control
Computerized Control System
for refrigerating compressors
Version 2.04
Preface
This engineering manual covers reciprocating as This document is produced by:
well as screw compressors, unless otherwise stat- Sabroe Refrigeration
ed. This manual offers a detailed description of Chr. X’s Vej 201
the UNISAB II control system including function, DK-8270 Højbjerg
application, service and trouble shooting. Danmark
In version 2.04, the title of this manual has been Copyright © 2004 Sabroe Refrigeration
changed from Instruction manual to Engineering
manual.
In the space below you can enter the name and address of your local Sabroe representative:
This document must not be copied without the Be aware of the version number of this manual.
written permission of Sabroe Refrigeration and The version number is printed at the bottom of the
the contents must not be imparted to a third party preceeding page. It is important that this number
nor be used for any unauthorised purpose. Con- is identical to the UNISAB II version number ap-
travention will be prosecuted. pearing for a few seconds in the second line of the
This manual is intended for operating and service display when turning on power. It is, however,
personnel. possible to use a manual with higher version
number than UNISAB II. In such cases use the
Please read this manual carefully so that you fully section List of Versions to view the differences.
understand the UNISAB II control system and Never use a manual with lower version number
know how to operate it correctly. Damage occur- than UNISAB II.
ring as a result of incorrect operation is not cov-
ered by Sabroe Refrigeration‘s guarantee.
WWarning!
If it is necessary to service UNISAB II control system, the power supply to the compressor motor must
be switched off at the main switch to prevent the compressor from starting up accidentally.
The UNISAB II box contains live parts, which makes it absolutely necessary to comply with the safety
regulations on site.
Failure to do so may cause damage to equipment and affect personal safety. Even though the power
supply to UNISAB II is switched off, some of the terminals may still be live.
Only authorized personnel is permitted to service UNISAB II. If UNISAB II is connected on a network,
always be aware that the compressor can be started from REMOTE. This cannot be avoided solely
by making choices on the UNISAB II display.
Emergency stop
Activate the emergency stop by a light pressure and deactivate it by turning it clockwise. The emer-
gency stop cuts right into the power circuit of the compressor motor guard. Activation of the emergency
stop during operation will lead to immediate unloading of the motor guard while there is still power on
UNISAB II. In this way it will always be possible to read the state of the compressor.
Whenever the emergency stop is activated during operation, the alarm text COMPR. MOTOR ERROR
will be read on the display. Before compressor restart is possible, deactivate the alarm by means of
the R key and release the emergency stop. PLEASE OBSERVE: If UNISAB II is set on REMOTE or
AUTO, the compressor will restart automatically.
Technical Data
24 +10/-15% 45 - 65
115 +10/-15% 45 - 65
230 +10/-15% 45 - 65
Consumption: 50 VA
Ambient temperature: 0-55° C (during operation)
Humidity: 20-90% relative humidity (not condensing)
Tightness: IP 54
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Emergency stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SETUP I CONFIG I CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COMPRESSOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I OIL SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I ECONOMIZER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MULTISAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUPI CONFIG I DIG. IN VIA PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
SETUP I CONFIG I MEASURING UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SETUP I CONFIG I UNIT/PLANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
SETUP I CONFIG I FACTORY RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
No starting permission . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Compressor motor error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Compressor motor overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Discharge pressure, overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
High motor temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Oil pump error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Oil pump error (SAB 80) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Full flow pump error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Cooling fan error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Oil rectifier error (screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Wrong starting number in sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Error in diagnosis - EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting suction pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting discharge pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting hot water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Limiting discharge temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
No communication to Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Chiller, alarm from Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Watch the oil pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Vi position error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evolution, alarm from PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evolution, warning from PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evolution, no communication to PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Low lubricating pressure monitoring (screw compressor) . . . . . . . . . . . . . . . . . . . . . . . . . . 58
High oil differential pressure
(SMC Mk4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
1. TIMERS - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
2. TIMER SETUP - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
3. SERVICE COUNTER - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
4. DATE - TIME - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5. OIL CHARGING - I
(screw compressor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6. MOTOR FAN I (Frequency controlled screw compressor) . . . . . . . . . . . . . . . . . . . . . . 64
Timer description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Screw compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7. P BAND FACTOR - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Stop delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Special timers in connection with MULTISAB
Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
8. TRANSFER - I Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
9. TAKE-OVER - I Reciprocating compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
MULTISAB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
1. MULTISAB STATE - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
2. ALL COMPRESSORS - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
3. PARALLEL CONTR. - I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Compressor regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Control mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
PID regulation (outer loop) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
P regulation (inner loop) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Regulation of Vi slide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Setting the regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Set points on regulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Universal regulator (Ext. input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Set point control with current input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Suction pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Disch. pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Hotwater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Capacity control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Climatic Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Adjusting slide speed (screw compressors with hydraulic slides) . . . . . . . . . . . . . . . . . . . 100
Capacity slide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Volume ratio slide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Variable Zero position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Corrected capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Automatic setting of new zero point (SAB 202) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Manual setting of new zero point (all types of screw compressors) . . . . . . . . . . . . . . . . . . 102
Built-in spacer block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
The alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Zero pos. picture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Electrical slide control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Part load and full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Calculated Vi position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Change to full load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Change to part load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Position indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Slide brake control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Capacity alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Pressure transducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Brine temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Calibration of motor frequency signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Motor current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Hydraulic slide systems
(certain screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Adjusting capacity measuring system with turning transmitter . . . . . . . . . . . . . . . . . . . . . . 131
Adjusting long-stroke capacity rod for SAB 110, SAB 128, SAB 163, SAB 202, SAB 81, SAB 83,
SAB 85, SAB 87, SAB 89 and SAB 330 (capacity and Vi) . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Adjusting long-stroke capacity rod for SAB 283 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Adjusting short-stroke capacity rod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Electrical slide systems
(certain screw compressors) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Factory setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Replacement of door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Replacement of CPU print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Replacement of CPU print and EEPROM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Replacement of relay print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Replacement of EPROM (program) UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Replacement of serial EEPROM (diagnosis) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Replacement of battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Installation of data communication cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
UNISAB II is programmed according to the type of a PLC, the configuration by the name EVO-
compressor it is going to controls. See section LUTION
Configuration. one or more Quantum compressor control-
UNISAB II contains different ways of control- lers also manufactured by
ling/regulating compressor capacity according to Sabroe Refrigeration.
pressure levels or temperatures. Compressor ca- The above points are described in separate man-
pacity can be regulated both manually and auto- uals, only the configuration is included in this man-
matically. ual.
Furthermore, a number of limiting functions have UNISAB II is operated by means of a front panel
been incorporated. In periods of overloading as shown in the following drawing. The front panel
these limiting functions will intervene and limit is well-arranged with only a few keys and a distinct
compressor capacity until the situation has re- display.
turned to normal. Consequently, the number of The subsequent description refers to the numbers
undesirable operational stops will be reduced as in the drawing. On delivery UNISAB II is preset
well as the need for supervision. with a number of factory values and is thus ready
Compressors fitted with UNISAB II CONTROL for operation. Therefore, only a few adjustments
can be linked via the built-in communication sys- are necessary to adapt the UNISAB II system to
tem, MULTISAB. In this way compressors can its actual use. For this purpose, use the enclosed
work in a common refrigerating system, thus opti- leaflet Quick Reference.
mizing the operation of the entire compressor UNISAB II is constructed not to lose its preset or
plant. changed values in case of a temporary power fail-
The communication system makes it possible ure. UNISAB II is fitted with a battery, which is
also to connect UNISAB II with a PLC or PC cen- used by the built-in timer so that time and date are
tral monitoring, control and data logging system. always correct even though current has been dis-
UNISAB II can be linked to and communicate with connected. The hour counter and any stored
old SABROE control units such as PROSAB II alarm values will thus maintain the correct time.
and UNISAB S/R/RT/RTH.
10 9 8 7 3 4 2 5 6 1 11 13 12 14 15
Suct.temp. -25°C
I Disch.temp. 38°C Set
Oil press. 4.3 bar
Ready 0%
R O
UNISAB II
Operating UNISAB II control Fig. 1.3 Drawing of fuses and their positions
Start-up
On delivery all electrical components in the com-
pressor are connected to UNISAB II. On site it is 1 2 3
only necessary to add the correct supply voltage 3A
Note in particular
a. that no outside voltage must be applied to the
digital inputs of UNISAB II.
STOPPED 0%
points is carried out via the display. The display Front panel
contains a number of different pictures.
The UNISAB II front panel is divided into two sec-
The control panel is usually closed and locked tions:
with a screw at each end of the panel. The control section, pos. 2 to 10, by means of
By turning the screws half a turn the control panel which the compressor is controlled.
is loosened and can be lifted to an open position, The recording section, pos. 11 to 15, by means
Here, it is fastened to the cabinet. See Fig. 1.4. of which menu pictures are selected and values
Fig. 1.4 Opening the cabinet changed.
Control section:
Pos. 2 Green lamp indicating whether the
compressor is running. At start-up
UNISAB II this lamp will flash until UNISAB II
has received feedback from the mo-
tor starter. At the same time the text
"STARTING" (lamp flashes) and
"OPERATING" (lamp light steady)
UNISAB II
can be seen in the bottom line of an
operating picture.
Pos. 3 Yellow lamp indicating whether the
state of operation is automatic or
In this way it is still easy to operate the control manual. Yellow light = manual op-
panel. At the same time easy access to the cabi- eration.
net interior is obtained. Pos. 4 Red lamp indicating warning or
When UNISAB II is open, it is still fully opera- alarm.
tional. Slow flashes = warning;
Quick flashes = alarm.
Fig. 1.5
UNISAB II I PARAMETER SETTING
- Ver. 2.02/2.03/2.04 HIGH ALARM
HIGH WARN.
°C/R
°C/R
Menu Tree Suction LOW WARN. °C/R
SUCT.PRES. °C/R LOW ALARM °C/R
Screw Compressor SUCT.TEMP. °C ACTUAL SP. °C/R
SUCT.SUPERH. °C SETPOINT 1 °C/R
RUNNING 100% SETPOINT 2 °C/R
NEUTRALZONE °C/R
PROP.BAND °C/R
T.INT. SEC
T.DIFF. SEC
Discharge P.PART %
I.PART %
DISCH.PRES. °C/R D.PART %
DISCH.TEMP.DI °C REG.OUTPUT %
SCH.SUPERH. °C
RUNNING 100%
Oil
Multisab state
OIL PRES. BAR
DIFF.PRES. BAR START NO.
OIL TEMP. °C SYSTEM NO.
RUNNING 100% SYS.CONTROLLER
Motor
MOTOR CURR 0A All compressors
MOTOR POWER 0 kW
MOTOR FREQ 0 RPM COMPR. # 01 MANUAL
Main picture Main menu READY 0% SYSTEM # 01
START # 01 J
RUNNING 100%
SUCT.PRES. °C/R SUCTION BRINE
DISCH.PRES. °C/R DISCHARGE ALARM Brine
MOTOR CURR A OIL WARNING
RUNNING 100% MOTOR SETUP BRINE TEMP. °C
Timers
SUCT.BRINE °C/R START START SEC
EXT.INPUT STOP START SEC
RUNNING 100% START DELAY SEC
STOP DELAY SEC
Alarms Control
NO ALARMS Service-timers
COMPRESSOR CTRL.
ON TIME HOUR
SINCE START
MANUAL
CAPACITY SETPOINT
Config.
CONFIG Auxiliary output
CONTROL
COMPRESSOR AUXILIARY OUTPUT
OIL SYSTEM ACTIVE WHEN
AT MAX.CAP
Language
CONTRAST
LANGUSGE GB
H
Fig. 1.6
I PARAMETER SETTING
Suction HIGH ALARM °C/R
HIGH WARN. °C/R
SUCT.PRES. °C/R LOW WARN. °C/R
SUCT. TEMP. °C LOW ALARM °C/R
SUCT.SUPERH. °C ACTUAL SP. °C/R
RUNNING 100%
UNISAB II - Ver. 2.02/2.03/2.04 SETPOINT 1
SETPOINT 2
°C/R
°C/R
NEUTRALZONE °C/R
Menu Tree PROP.BANDD °C/R
Single-stage Discharge
Reciprocating Compressor DISCH.PRES. °C/R
°C
DISCH. TEMP.
DISC.SUPERH. °C
RUNNING 100% Multisab state
START NO.
SYSTEM NO.
Oil SYS. CONTROLLER
SUCT.PRES. BAR
OIL PRES. BAR
OIL TEMP. °C All compressors
RUNNING 100%
COMPR. # 01 MANUAL
Motor SYSTEM # 01
MOTOR CURR 0A START # 01
MOTOR POWER 0 kW RUNNING 100%
MOTOR FREQ 0 RPM
Language
CONTRAST
H LANGUAGE GB
Fig. 1.7
I PARAMETER SETTING
Suction
-
UNISAB II Ver. 2.02/2.03/2.04 SUCT.PRES.
SUCT.TEMP.
°C/R
°C
HIGH ALARM
HIGH WARN.
°C/R
°C/R
LOW WARN. °C/R
Menu Tree SUCT.SUPERH. °C LOW ALARM °C/R
RUNNING 100% ACTUAL SP.
Two-stage reciprocating SETPOINT 1
°C/R
°C/R
compressor SETPOINT 2
NEUTRALZONE
°C/R
°C/R
Discharge PROP.BAND °C/R
DISCH.PRES. °C/R
DISCH.TEMP. °C
DISCH.SUPERH. °C
RUNNING 100%
Multisab state
Oil
START NO.
SUCT.PRES. BAR SYSTEM NO.
OIL PRES. BAR SYS. CONTROLLER
OIL TEMP. °C
RUNNING 100%
J
Motor All compressors
MOTOR CURR 0A COMPR. # 01 MANUAL
MOTOR POWER 0 kW SYSTEM # 01
MOTOR FREQ 0 RPM START # 01
READY 0% RUNNING 100%
Main picture Main menu
SUCH.PRES. °C/R SUCTION INTERMED Timers
DISCH.PRES. °C/R DISCHARGE ALARM Intermed.
MOTOR CURR A OIL WARNING START START SEC
RUNNING 100% MOTOR SETUP INTERM.PRES. °C/R STOP START SEC
INTERM.TEMP. °C/R START DELAY SEC
EXT.INPUT STOP DELAY SEC
RUNNING 100%
Service timers
Alarms Control ON TIME HOUR
NO ALARMS
COMPR.CTRL MODE
SINCE START
K
MANUAL Date-time
HOUR
MIN
Warnings Multisab SEC
DAY
NO WARNINGS MULTISAB
ALL COMPRESSORS
PARALLEL CONTRS Dig. input
D.INPUT
D.INPUT
Setup Timers D.INPUT
D.INPUT
CONTROL CALIBRATE TIMERS
MULTISAB CAPACITY TIMERS
TIMERS CONFIG. TIMER SETUP Dig. output
DIAGNOSIS LANGUAGE SERVICE TIMERS
D.OUTPUT
D.OUTPUT
D.OUTPUT
Capacity Diagnosis D.OUTPUT
DIAGNOSIS
CAPACITY 0% 4-20 MA input
NOT USED 0% INSPECT OLD ARLAMS
NOT USED 0% MISC. FUNCTIONS PRES. INP 1
READY 0% SOFTWARE VERSION PT 100 INR 1
EXT.
Calibrate
CALIBRATE 4-20 MA input
PRES. TRANSDUCER 4 MA
BRINE TEMP. 20 MA
CAPACITY
SUCT. PRES.
Config. Auxiliary output
CONFIG. AUXILIARY OUTPUT
CONTROL ACTIVATE WHWN
COMPRESSOR AT MAX. CAP
OIL SYSTEM
Language
CONTRAST
H LANGUAGE GB
Press I POS.NO
OIL CHARGING
This example applies to screw compressors.
MOTOR FAN
Press K until the cursor is at the desired timer
P.BAND FACTOR
TRANSFER
START-DELAY.
TAKE-OVER Press H until the Main picture appears.
Press H until the Main picture appears. Press I and again I until
SUCT.PRESS 0,0 BAR SUCT.PRESS XX
DISCH.PRES 0,0 BAR SUCT.TEMP XX
MOTOR CURR 0A SUCT.SUPERH XX
BLOCKED 0% BLOCKED X
Press I and next K until the cursor reaches OIL. By a quick pressure on G it is possible to switch
SUCTION BRINE between Bar and °C/R.
DISCHARGE ALARM
Press G , until the cursor covers the entire line.
OIL WARNING
SUCT. PRESS and value are moved to line 3 in
MOTOR SETUP
the main picture and DISCH.PRES in line 1 has
Press I disappeared from the picture:
OIL PRESS XX MOTOR CURR XX
READY X READY X
Procedure for changing of set values • Using the arrow keys H I K J, enter the
There are two types of changes: new value, eg - 0.5 BAR.
Changing a value
• It is now possible to change other values
To change the alarm value for
during the 60 minutes the password is open.
LOW SUCTION PRESSURE, do as follows:
• From the main picture, press I until this pic- Changing a function
ture appears:
Example 1
SUCT.PRESS XX
SUCT.TEMP XX
To change the state of operation from AUTO to
SUCT.SUPERH XX REMOTE, proceed as follows:
READY X • From the Main picture, press I once.
• Select Bar or °C/R by a quick pressure on • With the K key, move the cursor to
G. SETUP.
SUCTION
• Press I until the following picture appear:
HIGH ALARM XX
HIGH WARNING XX
SETUP
LOW WARNING XX
LOW ALARM X • Press I once.
ACTUAL SP XX CONTROL
ETC
• Using the K J keys, change between • Press G to confirm. In the same way other
STOPPED-MANUAL-AUTO-REMOTE. functions may be changed by using the cur-
• Press G to confirm. sor to point them out.
Example 2
Factory settings
If required to change the regulating function to
BRINE regulation, do as follows: On delivery UNISAB II is programmed with facto-
• From the Main picture, press I once. ry settings for all values such as: Alarms, Warn-
ings, Timers, Set points. These values are stated
• With K, move the cursor to SETUP.
in tables for reciprocating and screw compressors
• Press I once more respectively.
CONTROL
See tables 1, 2, 3, 4 and 5 in section Alarms and
warnings, tables 7 and 8 in section Timers and ta-
CONFIG
bles 9A, 9B and 9C in section Compressor regu-
• With K, move the cursor to CONFIG. lation.
• Press I once more Although other values may have been entered af-
CONFIG
ter delivery, it is always possible to return to the
CONTROL factory settings in the following way:
COMPRESSOR For safety reasons, first make sure the compres-
OIL SYSTEM sor is stopped.
2. Configuration
UNISAB II can be configured to a number of differ- Changes in the points that will lead to the above
ent functions depending on compressor type, re- situation are marked with ** in the following con-
frigerant, etc. Some of the settings have already figuration table.
been made by the factory, but it will always be The configuration points are common for 1) recip-
necessary to make some final settings before rocating and 2) screw compressors and their use
start-up. is marked in the list.
The immediate configuration can always be The configuration points have been divided into
checked during operation, BUT if one or more sub-menus available from the menu SETUP I
configuration points have to be changed, always CONFIG.
STOP the compressor and activate the emergen-
CONFIG
cy stop while making the changes. CONTROL
COMPRESSOR
After changing the configuration, the first pressure OIL SYSTEM
on H will in some cases display the following pic- ECONOMIZER
MOTOR
ture: MULTISAB
COP
CONFIGURATION COMMUNICATIONS
CHANGED DIG.IN VIA PROFIBUS
RESTARTING MEASURING UNIT
- PLEASE WAIT UNIT/PLANT
FACTORY RESET
Wait a few seconds - the main picture will appear
and UNISAB II will be reconfigured. At this stage In case of a screw compressor, the sub-menus
the picture may be dark as the contrast is being are composed as follows:
adjusted. This is quite normal. RELEASE the
emergency stop.
SETUP I CONFIG I MEASURING • Select the picture SETUP, move the cursor
UNIT to CONFIG. and press I once.
26 PRESS/TEMP BAR/C • Move the cursor with K and J to the rele-
45 PRESS -1/9-1/25 vant sub-menu and press I.
44 MOTOR SIGNAL kW
53 MOTOR INPUT 4-20 mA
• Move the cursor with K to the function that
54 CAP/FREQ CAP.POS is going to be changed.
56 LOW SUCTION PRESS. YES/NO • Press G and enter password if not already
open.
SETUP I CONFIG I UNIT/PLANT • Use the H I and J K keys to enter the
2 REFRIGERANT R22 new configuration.
32 CHILLER NO
• Press G to confirm.
• With J or K move the cursor to the next
value to be changed.
SETUP I CONFIG I FACTORY RESET • When finished changing the values, use H
33 FACTORY RESET NO to quit the sub-menu and thereby to activate
the possible changes, which will make
UNISAB II restart.
The following table gives a description of each
Carry out configuration as follows: configuration point as well as possible choices
with reference to the position numbers in the pre-
vious pictures.
CONFIGURATION
7 PRELUB. 2) Yes; No
9 BOOSTER 2) Yes; No
12 ECONOMIZER 2) Yes; No
CONFIGURATION
32 CHILLER 1) 2) Yes; No
50 PROFIBUS Yes; No
51 NODE NO 1 to 254
55 PID Yes; No
GSV 84 H R407C
GSV 111 H R744
GSV 147 H R 1270
GSV 185 H R 290
GSV 224 H R000
RWF 270 H For R407C (and all other refrigerants) the convert-
GSV 263 H ed pressure is always shown as dew point values.
GSV 331 H
GSV 339 H Before the user-defined refrigerant R000 is cho-
RWF 480 H sen, the refrigerant curve must be entered in pic-
GSV 412 H → 0153 L ture SETUP I CALIBRATION I DEF. REFRIG-
GSV 412 H → 0154 L ERANT R000. See also section Compressor con-
GSV 562 H → 0222 K trol and surveillance, Define refrigerant R000.
GSV 562 H 0222 K → Pos. 3: CONTROL ON:
GSV 715 H → 0109 XL SUCTION
GSV 715 H 0110 XL → BRINE
GSV 900 H DISCHARGE
GSB 84 - GSB 465 HOT WATER
SAB 283 L EXT. COOL
SAB 283 E EXT. HEAT
SAB 355 L
SUCTION: Pressure is measured by the built-in
SAB 110 SR/LR
pressure transducer on the compres-
Note: Please note that the screw compressors sor suction side.
SV 17/19 and GSB 84 - GSB 465 are not yet sup- Set point is set in the picture
ported. SUCT.PRESS I PARAMETER.
Note: Choose GVS/RWF L for compressors with BRINE: Temperature is measured by an ex-
“low volume range” (1.7 - 3.0) and GSV/RWF H tra Pt 100 sensor in the water output
for compressors with “high volume range” (2.2 - of the evaporator.
5.0). See compressor name plate for indication of Set point is set in the picture BRINE
volume range. TEMP. I PARAMETER.
Pos. 2: REFRIGERANT DISCHARGE:
NOT-DEF. Pressure is measured by the built-in
R717 pressure transducer on the compres-
R22 sor discharge side.
R502 Set point is set in the picture
R23 DISCH.PRES I PARAMETER.
R404A HOT WATER:
R134A Temperature is measured by an ex-
R507 tra Pt 100 sensor in the water output
R410A of the condenser. Set point is set in
Use pump for prelubrication before start-up and to regulator in a MULTISAB system, independent of
maintain minimum oil pressure during operation. the starting sequence.
At the same time remember to set set points 1 and START#: If START# is selected, the compressor
2, which determine at which pressure levels the which has the lowest starting number and which is
pump is going to start and stop. Select picture OIL in REMOTE (MULTISAB) will be the regulator.
PRESS I PARAMETER.
Pos. 12: ECONOMIZER (screw compr.)
NO
XX YES
LOW WARNING XX
If the compressor is connected to an economizer,
SET POINT 1 XX
this function must be selected. Thus the econo-
SET POINT 1 XX
mizer is connected/disconnected according to the
SET POINT 1 is the pressure at which the pump compressor operation. The connection is impor-
will start; SELECT 5.5 Bar. tant as regards the regulation of the compressor
SET POINT 2 is the pressure at which the pump volume ratio.
will stop; SELECT 7.0 Bar. Pos. 13: ECO LO CAP (screw compr.)
For more details, see Compressor control and
0 to 100%
surveillance.
If the immediate slide position is higher than the
Pos. 9: BOOSTER (screw compr.) set value, connect the economizer. If the slide po-
NO sition is 20% below this value, disconnect the
YES economizer again.
YES means that the oil pump will run continuously Pos. 14: ECO HI SUCT (screw compr.)
during compressor operation. The capacity slide -100 to +100°C/R
can thus be moved at low pressure conditions.
With ECO operation it is possible to enter a suc-
Note: Both SAB Mk3, SAB HR, SAB 202, VMY
tion pressure value in °C/R. If the suction pressure
Mk3, SV/FV and GSV/SGC compressors are fit-
of the economizer is above this value, the sole-
ted with differential pressure controlled oil pumps noid valves connected in the economizer system
(see table 1) and consequently do not use this
will be closed. Hysteresis of 2°C/R.
configuration point.
By a combined ECO and HLI operation the set
Pos.10: COMPR. NO. 1 to 14 value must not be above -20°C/R.
This no must be entered into UNISAB II. The com-
Pos. 15: COMMON EVAP/COND
pressor has now been "named".
Two compressors must under no circum- N/N
stances have the same number. N/Y
Y/N
Pos. 11: PREF. MASTER Y/Y
START#
This point can be configured to the following four
COMPR#
values:
COMPR#: If COMPR# is selected, the compres-
sor with the lowest no (pos 10) will always be the
N/N - separate evaporator and condenser for Pos. 17: WATER COOLED (recip.compr.)
each compressor. NO
N/Y - separate evaporator for each compressor, YES
but common condenser.
Water cooling output is activated by a rising dis-
Y/N - common evaporator, but separate condens-
charge pipe temperature. The set point for this
er for each compressor.
value is set in picture DISCH. TEMP I PARAM-
Y/Y - common evaporator and condenser for each
ETER, SET POINT 1. The set point has fixed hys-
plant (ie compressors with a MULTISAB system
teresis of 5K.
no).
Ex.: Sp 1 = 100°C:
On plants with a common evaporator the suction
Cooling starts at 100°C and stops at (100-5) =
pressure limiter cannot start the next compressor
95°C.
in the sequence. This is only possible if a separate
evaporator has been configured. Water cooling output is closed at compressor stop
according to adjustable time delay. In picture TIM-
On plants with a common condenser the dis-
ERS I TIMER SETUP adjust time delay OIL
charge limiter cannot start the next compressor in
COOL ON.
the sequence. This is only possible on plants with
separate condensers. Intermediate pressure liquid injection (two-
stage reciprocating compressors)
Pos. 16: HP ON TWO STAGE
The intermediate pressure liquid injection for
NO TSMC/TCMO compressors is active whenever
YES the compressor is configured to TCMO or TSMC.
Usually NO is chosen The solenoid valve for intermediate pressure liq-
In special cases on a two-stage plant YES can be uid injection is activated when the compressor has
selected for HP compressors. The compressors started and the discharge pipe temperature gets
can thus be forced to start by means of the input too high.
"External starting permission". The set point for this value is entered in picture:
Please note that the compressor does not stop DISCH.TEMP I PARAMETER, SET POINT 2.
before the starting permission has been removed The set point has fixed hysteresis of 5°K.
even though there is no cooling requirement. See Ex.: Sp2 = 90°C. Cooling starts at 90°C and stops
detailed description in section Compressor control at (90-5) = 85°C.
and surveillance, HP on TWO-STAGE
Adjusting range: -20°C-+150°C.
Factory value: 100°C.
The regulator controls the solenoid valve through
the liquid injection digital output.
RECIPROCATING COMPRESSORS
SCREW COMPRESSORS
This only applies to UNISAB II versions manufac- Pos. 28: MANUAL ZERO
tured from May 1998 supplied with revision G re- 0 to 40%
lay prints (relay no 7 will in such cases be mount-
For screw compressors without automatic zero
ed in the socket).
point setting, it is possible manually to set a "zero
For older UNISAB II units, the maximum is 9600 point" below which the compressor capacity slide
baud. is not allowed to fall while the compressor is oper-
Usually always select the highest baud rate that ating.
all units on the network can use. In case the compressor has a built-in spacer
If UNISAB II is connected with UNISAB I and/or block as well as automatic Vi regulation, MAN-
PROSAB II, adjust speed to 1200 baud. UAL ZERO is used for reducing the travel of the
capacity slide by the entered percentage. Thus
Pos. 25: OIL RECTIFIER corrected capacity is calculated and shown cor-
NO rectly.
YES
The value [0-40%] to be entered in MANUAL
The oil rectifying function is used on brine plants ZERO must be of the following size:
in marine execution. In case this function is select-
ed, check also the timers Oil Rectifying Start, Oil Length of spacer block 4 x 100
Manual zero [%]
Max. movement of capacity slide 2
Rectifying Delay and Oil Rectifying Blocked.
Pos. 26: PRESS/TEMP
See the following table.
BAR/°C
PSI/°F For SAB 202, which has automatic zero point set-
KPA/°C ting, the value 0% must be kept in FACT. setting.
Pressure levels and temperatures can be dis- See also pos. 27 MECHANICAL ZERO.
played in either SI units: Bar, kPa and °C or US Pos. 29: PORT 1
units: PSI and °F. Note that the use of PORT 1 requires UNISAB II
Pos. 27: MECHANICAL ZERO to be fitted with the add-on printed circuit board
NO UNICOM IF.
YES NONE
Only in case the compressor has a built-in spacer EVOLUTION A1S
block as well as automatic Vi regulation, ME- EVOLUTION FX2N
CHANICAL ZERO must be set for YES. In this Select EVOLUTION A1S or EVOLUTION FX2N if
way the travel of the capacity slide is automatically UNISAB II is to be used as an EVOLUTION con-
reduced by the percentage (0-40%) entered in trol, ie an extended (PLCY) control in which
MANUAL ZERO. Thus corrected capacity is cal- UNISAB II is integrated with a PLC control.
culated and shown correctly - see the following ta-
Select NONE if UNISAB II is to be used as an EV-
ble.
OLUTION control.
Select NO if UNISAB II is not used for COP meas- This point is only relevant for screw compressors
uring. with electrical slide control. See section Electrical
slide control.
Pos. 31: TAKE OVER (reciprocating
compressors) Pos. 35: MOTOR SIZE
NO 0 to 2500 kW or Amp
YES This selection is identical to MOTOR SIZE found
Select YES if UNISAB II is configured as a recip- in menu CALIBRATE I CALIBRATE COP. See
rocating compressor, operates in a combined section COP setting.
plant of reciprocating and screw compressors and Pos. 36: FLOW FACTOR
the function MULTISAB TAKE OVER/TRANS- 0.01 to 10 l/pls
FER is required.
This selection is identical to FLOW FACTOR
Pos. 32: CHILLER found in menu CALIBRATE I CALIBRATE COP.
NO See section COP setting.
YES1) Chiller
Pos. 37: LIQ. SUBCOOL
2) Evolution
0 to 99.9 °C
Select YES if UNISAB II is used as part of a chiller
This selection is identical to LIQ. SUBCOOL found
unit control, ie UNISAB II and a UNISAB II chiller
in menu CALIBRATE I CALIBRATE COP. See
control are connected via a communication cable.
section COP setting.
See UNISAB II-Chiller Manual.
Pos. 38: DANBUSS
Always select NO if UNISAB II is not connected to
YES (not changeable)
a UNISAB II chiller
Functions as header of the menu Communication.
Shows that the succeeding COMPR. NO and
BAUD RATE refer to the main communication
port, which always runs the Danbuss protocol.
UNISAB II as the motor power. Enter the motor scribes the use of frequency converters together
nominal power in the picture MOTOR I MOTOR with UNISAB II.
SIZE I PARAMETER. For SAB HR compressors, enter the value in rpm
Pos. 48: MINIMUM FREQUENCY corresponding to maximum frequency in the fre-
700 to 2000 revolutions quency converter.
Table 2.1
Screw compressor Max. movement Evaporating Length of Mechanical Manual
type of capacity slide temp. spacer block zero zero
1 2 R717/R22 4 5 6
mm 3 mm (pos 27) (pos 28)
SAB 110SM
84.5 < -20°C 22 NO 0%
SAB 110SF
SAB 110 LM
96 > -20°C NONE NO FACT 0%
SAB 110 LF
SAB 128 HM Mk2
< -20°C 31.5 NO 0%
SAB 128 HF Mk2
126
SAB 128 HM Mk3
> -20°C NONE NO FACT 0%
SAB 128 HF Mk3
SAB 163 M Mk1, Man Vi
SAB 163 F Mk1, Man Vi < -20°C 38.5 NO 0%
SAB 163 HM Mk2, Man Vi
160
SAB 163 HF Mk2, Man Vi
SAB 163 HM Mk3, Man Vi > -20°C NONE NO FACT 0%
SAB 163 HF Mk3, Man Vi
SAB 163 HM Mk2, Aut Vi
< -20°C 38.5 YES 24 %
SAB 163 HF Mk2, Aut Vi
160
SAB 163 HM Mk3, Aut Vi
> -20°C NONE NO FACT 0%
SAB 163 HF Mk3, Aut Vi
SAB 202 SM, Man Vi
SAB 202 SF, Man Vi ** *
245 ALL NONE
SAB 202 SM, Aut Vi NO FACT 0%
SAB 202 SF, Aut Vi
SAB 202 LM, Man Vi
SAB 202 LF, Man Vi ** *
317 ALL NONE
SAB 202 LM, Aut Vi NO FACT 0%
SAB 202 LF, Aut Vi
SAB 283 L 314
Not Not Not Not
SAB 283 E 391
relevant relevant relevant relevant
SAB 355 L 350
SAB 330 S 262
Not Not Not Not
SAB 330 L 371
relevant relevant relevant relevant
SAB 330 E 480
* If another value than the factory set value of 0% is inserted, the automatic zero setting is eliminated.
Therefore, only insert a value different from 0% after having contacted Sabroe Refrigeration.
** If another value than NO is inserted, the automatic zero setting is eliminated.
Therefore, only insert a value different from No after having contacted Sabroe Refrigeration.
Analog alarms and warnings In case an alarm limit is exceeded, the compres-
ALARM and WARNING limits can be set sepa- sor will stop immediately. The red light diode
rately as described in section Changing the set above the D key will start to flash quickly. In the
values. picture ALARM the reason for the alarm can be
read, and at the same time the alarm relay will
UNISAB II does not check whether ALARM and change its position.
WARNING limits have been interchanged by a
mistake (eg if warning limit for high discharge The alarm relay works by connecting the
pressure is set higher than the alarm limit). Con- alarm/common switch during alarm and by dis-
sequently, during adjustments check that the connecting it once the alarm is reset.
settings are correct. The picture ALARM also shows the exact time of
If a warning limit is exceeded, the red light diode the alarm. See also under Diagnosis.
above the D key will begin to flash slowly, and The alarm is reset by pressing the D key, and the
the warning relay will be activated. The reason for warning and alarm relays will return to their nor-
the warning can be seen in the picture WARNING, mal position. However, if the alarm value is still
which also shows whether there are several si- outside the limit, the red light diode will continue to
multaneous warnings. flash. When the situation has returned to normal,
Note that in case of warning, a limiter might be ac- the D key must be pressed once more,
tive as described in section Limiting functions. The set values for high and low alarms as well as
When the warning disappears, it is automatically the factory values are stated in the following ta-
removed from the picture WARNING and the re- bles 1-5. These are followed by explanatory
lay returns to its normal position. notes.
Table 1
Screw compressors
Measured and calculated pressure levels
Measuring Min. Max. Factory Note
Table 2
Screw compressors
Measured and calculated temperatures
Table 3
Reciprocating compressors
Measured and calculated pressure levels
Measuring Min. Max. Factory Note
Table 4
Reciprocating compressors
Measured and calculated temperatures
Measuring Min. Max. Factory Note
Discharge temp. High alarm 60.0 155.0 125.0 1+6
(°C) High warning 50.0 155.0 120.0 1+6
Low warning -65.0 -65.0 -65.0
Low alarm - - -
Oil temperature High alarm 40.0 105.0 80.0 2
(°C) High warning 30.0 105.0 75.0 2
Low warning 0.0 50.0 30.0 2+7
Low alarm 0.0 40.0 25.0 2+7
Brine temperature High alarm -60.0 100.0 60.0 1+6
(°C) High warning -60.0 100.0 50.0 1+6
Low warning -100.0 100.0 4.0 1+6
Low alarm -100.0 100.0 2.0 1+6
Intermediate gas High alarm 50.0 155.0 100.0 2+7
temperature (°C) High warning 50.0 120.0 95.0 2+7
For two-stage Low warning -20.0 50.0 4.0 2+7
compressors only Low alarm -20.0 50.0 2.0 2+7
Suction gas superheat High alarm 6.0 120.0 110.0 2+7
(°C) High warning 5.0 120.0 100.0 2+7
Low warning 0.0 40.0 4.0 2+7+13
Calculated value Low alarm 0.0 40.0 2.0 2+7+13
Disch. gas superheat Low warning 5.0 40.0 10.0 2+7+10
(°C) Low alarm 0.0 40.0 0.0 2+7+10
Calculated value
Table 5
Reciprocating compressors HPO/HPC
Measured and calculated pressure levels and temperatures
Measuring Min. Max. Factory Note
Notes:
Note 1 The alarm cannot be switched off un- Note 17 For VMY Mk 2-2.5, calculate the fol-
til the problem has been solved. lowing (see Fig. 3.1): Oil pressure =
Note 2 The alarm can be switched off imme- Oil pressure 3 (after oil filter) - Dis-
diately (RESET key). charge pressure 2. For all other
compressor types (except for SAB
Note 3 The alarm is switched off automati- 80, see Note 20), calculate the fol-
cally. lowing: Oil pressure = Oil pressure 3
Note 4 The safety limits can be entered in (after oil filter) - Suction pressure 1 .
bar or °C/R. Note 18 The limits are not active until AUX.
Note 5 Alarm monitoring active when digital INPUT SIGNAL has been selected in
output "compressor starting signal" the menu CALIBRATION 4-20 mA.
has been selected. Note 19 For SAB 80 the differential pressure
Note 6 Alarm monitoring always active - ex- across the oil filter is calculated as
cept when "BLOCKED" has been se- follows (see Fig. 3.1): Oil filter diff.
lected in picture COMPRESSOR pressure = Discharge pressure 2 -
CTRL MODE. Oil pressure 4 (after oil filter).
Note 7 Alarm monitoring 300 sec delayed The shown oil filter pressure will thus
after compressor start. be 0.1 to 0.7 bar higher than the ac-
Note 8 Alarm monitoring 180 sec delayed tual pressure loss across the filter
after compressor start. due to the pressure loss across the
oil separator and the oil cooler.
Note 9 Alarm monitoring 45 sec delayed af-
ter compressor start. The maximum allowed pressure
drop across the oil filter is 1.2 bar.
Note 10 A setting of 0.0 impedes monitoring.
Consequently, the warning limit
Note 11 Delay of 300 sec, regardless of when should be set between 0.8 and 1.4
limits are exceeded. bar or lower. The alarm limit should
Note 12 The compressor must have been be set between 1.1 and 1.7 bar or
above 5% capacity. Below 5% ca- lower.
pacity monitoring is impeded. Note 20: Set points 1 and 2 are used for alarm
Note 13 Alarm monitoring 15 sec delayed af- monitoring of the mechanical oil
ter compressor start. pump, cf description of the alarm un-
der "Oil pump error" in section Other
Note 14 Delay of 60 sec, regardless of when
Alarms. For SAB 80, the oil pressure
limits are exceeded.
is calculated as follows (see
Note 15 Only applies to HPO and HPC com- Fig. 3.1): Oil pressure = Oil pressure
pressors. 3 (after pump) - Suction pressure 1.
Note 16 Alarm monitoring 20 sec delayed af-
ter compressor start.
Note 21: The set points are used for control- Note 22: The set points are used for control-
ling the oil pump. When the pressure ling the full flow pump. When the
falls below set point 1, the oil pump pressure falls below set point 1, the
will start. When the pressure ex- full flow pump will start. When the
ceeds set point 2 for 60 seconds, the pressure exceeds set point 2 for 60
oil pump will stop. seconds, the full flow pump will stop.
Fig. 3.1
SAB 80
Oil
Oil filter separator
Oil cooler
Others
Oil
Oil filter separator
Oil pump
Compressor
Oil cooler
Suction gas superheat, alarm 20%; or that the slide - in connection with auto-
The superheat alarm is an alarm which in many matic setting of variable zero point - cannot reach
cases will protect the compressor against liquid the position corresponding to calculated or adjust-
strokes. However, there are many aspects which ed zero point (ie positive read capacity) before the
may affect superheating for which reason this expiry of the timer "cap.negative".
alarm must not be considered as full protection 1) If the compressor is set on "MAN" or "AU-
against liquid strokes. TO" and in operation, and the slide does not
If the superheat falls below the set value, the com- react to the regulating signal within 30 mins,
pressor will stop on the relay. However, on R717 a warning will be issued. The compressor
pump circulation plants with a short distance be- does not stop.
tween liquid separator and compressor, the suc- 2) If the compressor is set on "REMOTE" and
tion gas superheat may drop below 0 K during in operation, and the slide does not react to
normal operation. the regulating signal within 30 mins, an
In such cases adjust LOW ALARM to 0, thus alarm will be issued. The compressor will
making it inactive. stop.
3) If the compressor is REMOTE CONTROL-
Auxiliary input signal (4-20 mA) LED by a PC/PLC-system, a warning will
be issued as well. The monitoring is possi-
The alarm and warning limits are activated when
ble by means of a 4-20 mA signal in the aux.
AUX. INPUT SIGNAL has been selected under
input or via communication.
CALIBRATION 4-20 mA.
The reason for the difference between situ-
ation 1) and 2) is: If the system runs in se-
Other alarms and warnings
quence - REMOTE (MULTISAB), the com-
pressor must be stopped to start any subse-
Oil system error (screw compressors) quent compressors in the sequence.
The reason for the alarm is that the oil float switch
When a compressor is remote controlled (3)
is not activated within the time set in the timer OIL
it is not a part of the sequence - REMOTE
FLOW during prelubrication; or that there is a
(MULTISAB) system - thus stopping this
drop-out on the oil float switch for a longer period
compressor will not start up subsequent
than the one set in the timer NO OIL during oper-
compressors.
ation.
PMS error
Capacity error (screw compressors)
If the control is to start the compressor and conse-
The reason for the alarm is that the capacity slide
quently adjusts the output START REQUEST
is not below 5% within the time set in the timer
(PMS) to ON, the input START REQUEST OK
SLIDE MAX at compressor stop; or that the slide
must be set on ON within the time set in the timer
- during operation - has not moved within 30 mins,
PMS FEEDBACK - or the alarm will be activated.
although the regulator is to regulate up or down
and the output signal from the regulator is above
Full flow pump error (screw (EEPROM) fitted on the CPU card, ie the serial
compressors) EPROM is either missing or defective.
The reason for the alarm is that feedback of the
full flow pump motor is not set/does not disappear Limiting suction pressure
within the time set in the timer FULL FLOW M, The warning indicates that the suction pressure
when the motor starts/stops (ie the output full flow limiter is active, ie the suction pressure is within
pumps start is activated/deactivated), or that the limiter neutral zone or below the warning limit.
feedback from the motor disappears even briefly
during operation.
Limiting discharge pressure
The alarm functions as a warning during opera- The warning indicates that the discharge pressure
tion, ie after the prelubrication sequence has been limiter is active, ie the discharge pressure is within
completed. the limiter neutral zone or above the warning limit.
Chiller, alarm from Chiller The alarm will be activated if the alarm of the con-
The alarm will only be activated if UNISAB II is nected PLC goes off.
configured as part of a Chiller control, ie as
SETUP I CONFIG I CHILLER = YES. Evolution, no communication to PLC
The alarm will be activated if the alarm of the con- The alarm will only appear if UNISAB II is config-
nected Chiller goes off. ured as part of an Evolution control, ie as SETUP
I CONFIG. I COMMUNICATIONS I PORT 1 =
EVOLUTION XXX
Watch the oil pressure
The warning will appear if the oil pump for oil The alarm will only be activated if there is no com-
charging is started by means of the picture munication between UNISAB II and the connect-
TIMERS I OIL CHARGING ed PLC.
and the compressor is in operation at the same
time. Low lubricating pressure monitoring
(screw compressor)
Vi position error The reason for this alarm is that the differential
pressure across the compressor and thus the ef-
The alarm will only be activated if UNISAB II is
fective lubricating pressure is too low. The differ-
configured for automatic Vi regulation, ie
ential pressure is calculated in the following way:
SETUP I CONFIG I VOLUME RATIO = AUTO
measured oil pressure - 1.1 x suction pressure.
The alarm indicates that the display of capacity in The differential pressure must be higher than the
connection with automatic Vi regulation is incor- set alarm limit for low oil pressure, see the draw-
rect. The real capacity of the compressor is lower ing below. A warning will be issued after 25 sec-
than the one shown in the display. onds and an alarm after 145 seconds.
Fig. 3.2
No
t1 = 145 sec fixed
Table 6
Identification numbers for alarms / warnings
This is a list of alarms and warnings with identification numbers for both screw and reciprocating compres-
sors.
Screw compr. Recipr. compr. Id
High oil filter differential pressure Warn + Alarm Warn only (Mk4) 43
63
Low auxiliary input signal (univ. reg.) Warn + Alarm Warn + Alarm 67
High auxiliary input signal (univ. reg) Warn + Alarm Warn + Alarm 68
4. Timers
UNISAB II includes a number of timer functions the compressor, the counter will stay on the value
under the menu SETUP I TIMERS I . reached at that particular moment. In this way it is
possible to know for how long the compressor has
been running since the last operating period.
TIMERS
1 TIMERS
When the compressor is restarted, the counter be-
2 TIMER SETUP gins from 0.
3 SERVICE TIMERS
4 DATE-TIMER 4. DATE - TIME - I
5 OIL CHARGING
This picture shows:
6 MOTOR FAN
7 P BAND FACTOR TIME The time in hours
8 TRANSFER MIN The time in minutes
9 TAKE - OVER SEC The time in seconds
DAY Date
1. TIMERS - I MONTH Month
YEAR Year
This picture includes all the timers and shows
which timers are activated (they are counting Must be set correctly in order for the alarms to be
down). stored with the correct time. This function is pro-
vided with a battery back-up.
2. TIMER SETUP - I
In this picture the set values of the timers can be 5. OIL CHARGING - I
changed. The timers and their functions appear (screw compressor)
from the following tables for screw compressors Provided that the compressor is fitted with a pump
and reciprocating compressors respectively. for oil charging, this can be started in the picture
Some of these timers can be changed using the OIL CHARGING. This picture shows:
keyboard whereas others are fixed. The tables START OIL PUMP NO
also include the factory set values. TIMER 0 sec
6. MOTOR FAN I (Frequency To start the cooling fan manually, carry out the fol-
controlled screw compressor) lowing:
If the compressor is fitted with an electrical cooling Place the cursor on TIMER SP with K and press
fan for cooling the compressor motor, this can be G to change the parameter. Set the fan running
started manually in the picture COOLING FAN. time and place the cursor on START COOLING
The function is only available on frequency con- FAN. Select YES with G,and J . Enter setting
trolled compressors. with G .
The picture shows the following: The cooling fan will now start and operate for the
START COOLING FAN NO set running time.
TIMER SP 10 sec
To stop the cooling fan before the end of the
TIMER 0 sec
running time, select NO in the upper line. The fan
will now stop and the time be reset to 0.
29 No Chiller 10 - - Sec No
34 Vi-pause 60 - - Sec No
12 Not used -- -- -- -- --
29 No Chiller 10 - - Sec No
30 Not used - - - - -
31 Not used - - - - -
33 Not used - - - - -
34 Not used
Timer description
18. Superheating high been reached, the solenoid valve to the oil rectifier
During start the alarm for high superheating is de- will be activated.
layed for the stated time. No delay during nor- 26. Oil rectifier delay
mal operation.
If suction gas superheating drops below set point
19. Disch. pressure, overload 1 for superheating, the solenoid valve will close.
If the discharge pressure is higher than the warn- Once the superheating rises above this limit
ing limit in the time stated, the compressor will again, the timer must expire before the solenoid
stop and an error message will appear. valve opens.
See also Limiters. 27. Oil rectifier disable
20. Current overload If suction gas superheating drops below set point
1 for superheating, the timer will start counting
If the motor current is higher than the set point in
down. Provided the superheating still remains be-
the time stated, the compressor will stop and an
low the limit once the timer has reached 0, a warn-
error message will appear.
ing will be issued to a superior computer.
See also Limiters.
28. Start high pressure
21. Motor start On two-stage plants the HP compressors can be
When the compressor starts, the motor guard started by force by activating the input
must issue a feedback before the timer expires; if External starting permission, normal stop.
not, an error message will appear.
The start will be delayed for the set number of sec-
The green light diode above the starting key A will onds.
flash until feedback has been received whereup-
With the compressors in sequence, number 1 in
on the light will be steady.
the sequence will start and the system will now
22. PMS (Starting request) feedback operate normally.
After the control has issued a starting request, it
29. No Chiller
must receive a feedback within the stated time; if
When UNISAB II is configured as part of a Chiller
not, an error message will appear.
control, the timer will ensure that communication
23. F. F. Pump start between UNISAB II and the connected Chiller
In case the motor guard of the full flow pump has does not disappear for a period longer period than
failed to issue a feedback within the stated time af- the set time. If this happens, both UNISAB II and
ter the starting signal, an error message will ap- UNISAB II-Chiller will be stopped by the alarm.
pear.
30. Cap. negative
24. Oil pump start When the compressor is started, the slide must
In case the motor guard of the oil pump has failed move to the position corresponding to the set zero
to issue a feedback within the stated time after the point (ie positive read capacity) as quickly as pos-
starting signal, an error message will appear. sible before the expiry of the cap. negative timer.
25. Oil rectifier start Otherwise an error message will be issued. The
Whenever the compressor starts, this timer will be cap. negative timer counts down each second by
activated and start counting down. When 0 has the value: (corrected capacity)2/5, where corrected
capacity may be negative values between -0 and 32. Low suction pressure
-30%, ie the timer will count down each second by During start-up and operation the alarm for low
a factor between 1 and 180. suction pressure is delayed for the indicated peri-
Each time the slide moves above 0% capacity, the od of time.
timer will stop. 33. Lubricating pressure
The timer is reset and restarted, as soon as the During start-up and operation the alarm for low
slide moves below -2% corrected capacity. suction pressure is delayed for the indicated peri-
od of time. A warning is issued after 25 seconds.
31. Unloaded start
The timer is used in connection with the compres- 34. Vi-pause
sors FV 17/19. When the compressor motor is The timer is used in connection with GST com-
started, a by-pass solenoid valve for oil discharge pressors, which have a three-stage automatic
will open for the time set. regulation of the volume ratio, 2.2-3.5-5.0. Before
switching from one Vi-step to another, the actual
The timer is used in connection with the compres-
Vi ratio for the compressor must have been
sors FV 24/26. When the compressor motor is
present for at least the indicated time other wise
started and stopped, the slide capacity down sole-
the change of the Vi step will be cancelled.
noid valve will open for the time set.
operation. If the measured suction pressure is a Basically, starting and stopping as well as engag-
little lower than -18°C and the capacity slide is be- ing and disengaging are delayed by the timers
low 5%, the STOP DELAY timer will start to count START DELAY, STOP DELAY, DELAY UP and
and the compressor will stop after 60 seconds. DELAY DOWN. See section Timer description.
In case of a reciprocating compressor, the fol- The relevant timers start as soon as the regulated
lowing picture will appear: input (eg suction pressure) is just outside the neu-
tral zone.
DELAY UP 1
DELAY DOWN 1 There is one P BAND FACTOR for each of these
START DELAY 1 timers.
STOP DELAY 1 If the P BAND FACTOR is 1, the time delay will be
the same no matter if the regulated input is just
Each of these factors can be selected in the range outside the neutral zone or far outside the neutral
1-10. zone.
In AUTO and REMOTE mode, the various By selecting a P BAND FACTOR higher than 1
P BAND FACTORs are influencing the decision of (up to 10), it is possible to have the timer run slow-
when to start or stop the compressor or, for recip- er when the regulated input is close to the neutral
rocating compressors, when to engage or disen- zone as illustrated in the drawing.
gage another capacity stage.
Fig. 4.1
PBF
1
Diff
-NZ 0 NZ PB
-PB
When the measured suction pressure exceeds If the pressure is still moving upwards and ex-
-9°C/R, the START DELAY timer will begin to ceeds 36°C/R (the Pb limit), the timer will count in
count with an interval of 5 sec (P BAND FACTOR) seconds.
each time the value in the display counts one The resulting total delay will range between 30
down. If the pressure steadies, the timer will run and 90 seconds, after which the compressor will
for 5 x 60 = 300 seconds. disengage one capacity stage.
Should the measuring value reach -6.5°C/R, the
counting interval will be 3 sec. Special timers in connection with
If the pressure is still moving upwards and ex- MULTISAB
ceeds -4°C/R (the Pb limit), the timer will count in Reciprocating compressors
seconds. In the MULTISAB system which regulates and op-
The resulting total delay will range between 60 timizes more than one compressor, there are a
and 300 seconds, after which the compressor will number of factors attached to a TRANS-
start. FER/TAKE-OVER function between reciprocating
and screw compressors. These factors are de-
Example 2:
scribed in detail in section MULTISAB regulation.
Discharge pressure regulation has been selected
on a reciprocating compressor. The measured The factors are found in the pictures:
discharge pressure equals the set point. The com-
pressor is running at 100% capacity. 8. TRANSFER - I Reciprocating
Set point Sp = 30°C/R compressors
Nz = 2°C/R FACTOR DOWN 1
Pb = 5°C/R ZONE 15%
DELAY DOWN = 30 sec
P BAND FACTOR DELAY DOWN = 3.
9. TAKE-OVER - I Reciprocating
When the measured discharge pressure exceeds compressors
31°C/R, the timer DELAY DOWN will begin to
FACTOR UP 1
count with an interval of 3 sec (P BAND FACTOR)
FACTOR START 1
each time the value in the display counts one
ZONE 15%
down. If the pressure steadies, the timer will run
for 3 x 30 = 90 seconds.
Should the measuring value reach 33.5°C/R, the
counting interval will be 2 sec.
5. MULTISAB
MULTISAB is a distributed compressor control If MULTISAB is to function optimally, it is of vital
system, which is very useful when more compres- importance that certain key parameters are se-
sors are working together (eg connection to the lected correctly by the user as explained in section
same suction line). With MULTISAB it is possible MULTISAB regulation. To understand the con-
to start, stop and capacity regulate compressors tents of the MULTISAB pictures, the following key
according to the varying cooling requirements. parameters are described here: COMPR. NO,
MULTISAB is a standard function in UNISAB II. SYSTEM NO, PREF. MASTER, START NO and
MULTISAB is described in detail in section MUL- CONTROL MODE.
TISAB regulation. Always make sure that all UNISAB II units on a
MULTISAB is only able to work if all UNISAB II network have different COMPR. NOs, ie two units
units which are to participate in the distributed are not allowed to have the same COMPR. NO.
control are physically connected via the Danbuss See section Configuration.
communication network. The section Installation SYSTEM NO informs MULTISAB which com-
of data communication cable describes how to pressors are to work together. The drawing below
connect the units. shows two examples.
Fig. 5.1
SYSTEM NO
= 1 or 2
Compr. 1 Compr. 1
Common Multisab
Multisab network Suction main line 1
network
SYSTEM NO SYSTEM NO = 1
= 1 or 2
Suction main line 2
SYSTEM NO = 2
Compr. 3
Compr. 3
In the example to the left, two separate compres- • UNISAB No 1 has the same SYSTEMNO as
sor plants are connected on a common Danbuss UNISAB No 2
network. Here it is of vital importance that • UNISAB No 3 has the same SYSTEM NO
as UNISAB No 4
• SYSTEM NO of UNISAB 1 and 2 differs ble if it is shut off, not communicating, not in RE-
from SYSTEM NO of UNISAB 3 and 4. MOTE mode or in shutdown alarm condition. An
In the example to the right, each of the four com- alarm condition may be due to a sensor error, re-
pressors can be connected independently to any sulting in a change of SYS CONTROLLER and
of the two suction main lines. In this example is is thus of sensor.
also important that SYSTEM NO is correct. How- In order for a compressor to become part of a
ever, it is particularly important that when chang- MULTISAB system, the above key parameters
ing the valve settings, the SYSTEM NO in the must be set up. CONTROL MODE must be set for
UNISAB II units in question is changed according- REMOTE. In other words, by changing the CON-
ly as this does not take place automatically. TROL MODE, the user is able to include and ex-
START NO defines the priority of the compres- clude the compressor from the MULTISAB sys-
sors with common SYSTEM NO. The unit with the tem. See section Compressor regulation.
lowest START NO will be the first to start. The MULTISAB functions are found in the menu
PREF. MASTER must be identical for all units SETUP I MULTISAB I
with the same SYSTEM NO. See section Config- MULTISAB
uration. PREF. MASTER specifies whether it is MULTISAB STATE
COMPR. NO or START NO which is to define ALL COMPRESSORS
which UNISAB II is to be SYS CONTROLLER. PARALLEL CONTR.
State Explanation
BLOCKED The compressor cannot (and is not going to) start MULTISAB now.
NOT MY TURN Another compressor must start before this one / there is no cooling requirement.
MAY START Starts when START DELAY expires as there is now a cooling requirement.
STOP RAMP DOWN Stops parallel operation, as slave - only screw compr.
State Explanation
READY UNISAB II is ready to start.
RUNNING Compressor in operation.
STARTING Compressor motor start-up.
SHUTDOWN In a state of alarm.
PAUSE Waiting for a timer to expire / compressor stopped and in limitation mode.
PRELUB Working on the prelubrication sequence.
CAP SLIDE DOWN Runs the slide down after stop.
RUNS AT OVERL. Motor current too high.
DISCHARGE LIM. Discharge pressure too high.
SUCTION LIM. Suction pressure too low.
STOPPED Compressor cannot start.
6. Compressor regulation
between the desired value (Sp) and the actual val- as the regulating impulse will be very long if the
ue. measured value is outside the P Band. The P
In case the measured value is just outside the Nz, Band is positioned symmetrically around Sp out-
the regulating impulses will be very short, where- side the Nz. See Fig. 6.1.
Fig. 6.1
rapidly up
Very slowly up
SP
P.Band P.Band
Error signal
NZ
rapidly down
Screw compressors
Screw compressors are capacity regulated (hy- matically by the outer loop. As long as this set
draulically or electrically) by moving the capacity point is constant, the inner loop will ensure that
slide. This takes place via two digital outputs the capacity slide remains in this position, inde-
which are controlled by UNISAB II, so that the pendent of any other outside influences.
slide moves towards max. or min. capacity ac- The outer loop, which is a PID regulator, adjusts
cording to demand. The setting is stepless from 0 the capacity set point according to the selected
to 100%. UNISAB II will usually pulse the digital control set point and measured value, eg the suc-
outputs with a pulse/delay ratio. Consequently, a tion pressure set point and measured value. In
constant up or down signal will rarely be given. MANUAL mode, the outer loop is not active. In
The capacity control must be seen as two PID AUTO and REMOTE, the outer loop is active ac-
control loops (an inner and an outer loop). cording to the CONTROL ON setting. See section
The inner loop, which is a proportional regulator, Regulators.
adjusts the slide position continuously according The inner loop set point can also be controlled via
to the capacity set point. In MANUAL mode the the external input (see section Set point control
capacity set point is selected with the E F keys with current input) or via the communication net-
and in AUTO/REMOTE mode it is selected auto- work.
PID regulation (outer loop) TRAL ZONE and PROP. BAND are accessible.
On screw compressors a PID regulator is used for The actual parameters are found in the relevant
the outer loop of capacity regulation. In the picture picture, eg SUCT SIDE I SUCT PRESS. Each
SET UP I CONFIG I REGULATE I PID it is parameter is briefly described below. The theory
now possible to select PID = YES or NO. If PID = behind PID regulation is described in innumerable
YES is selected all the parameters stated below books about automatic regulation. These books
are accessible. If PID = NO is selected only pa- also describe methods for optimizing the parame-
rameters ACTUAL SP, SET POINT 1 and 2, NEU- ters
Name Description
ACTUAL SP. The set point which the PID controller works with at the moment.
NEUTRAL ZONE The neutral zone is a symmetrical area around ACTUAL SP. When the controlled val-
ue is inside the area, the controller will be passive. The purpose is to increase service
life of the output hardware (relays, valves, spindle motor, etc). However, this is also
partly ensured by the parameter MIN PULSE, see section P regulation (inner loop)
below, which is why the NEUTRAL ZONE can be set at 0. A larger NEUTRAL ZONE
makes the regulation less accurate.
PROP. BAND This parameter decides the total gain in the control loop. Increasing PROP. BAND
will give a slower response. Thus changing PROP. BAND does not only affect the
proportional term, but also the integral and differential terms.
T. INT. Integral Time decides the gain of the integral term. A smaller T. INT means a larger
gain, ie the controller will try to reach the set point faster.
T. DIFF. Differential Time decides the gain of the differential term. A larger T. DIFF means a
larger gain. Normally select T. DIFF = 0 which deactivates the differential term and
thus the regulator will be working as a PI controller.
P. PART This field shows the actual Proportional term calculated by the PID controller.
I. PART This field shows the actual Integral term calculated by the PID controller.
D. PART This field shows the actual Differential term calculated by the PID controller
REG. OUTPUT The actual Regulator Output is the sum of P. PART, I. PART and D. PART.
P regulation (inner loop) point generated by the outer loop. Additionally the
The parameters for the inner loop, which is only a following parameters can be selected:
proportional regulation (P regulator), are set in the • MIN PULSE is the shortest pulse that
picture SET UP I CAPACITY I CAPACITY. The UNISAB II will give on the relay output, eg it
P regulator parameters include ACTUAL SET takes time for a hydraulic valve to open and
POINT, NEUTRAL ZONE, PROP.BAND and close, and for the hydraulic oil to move, so a
P.PART. ACTUAL SET POINT is the capacity set pulse shorter than about half a second
would have no effect and would only short-
en the service life of the valve and the relay. neutral zone is too high, the regulator may fluctu-
A longer MIN PULSE increases the service ate too much.
life of the hardware, but it also makes the If PID = NO is selected, the outer loop is working
regulation less accurate. more moderately than when PID = YES is select-
• RUN TIME is the approximate time it takes ed. A P band of less than 10°C may therefore be
for the capacity slide to move from minimum used. Requirements for the neutral zone are the
position to maximum position and vice versa same as when PID = YES. As already mentioned,
at constant signal. Please note that RUN T.INT. and T.DIFF. are not accessible when PID =
TIME for the capacity slide may be reduced NO.
by variable slide end stop etc where this is
Inner loop
relevant.
As regards the inner loop it is not recommended
to use any other values than the default values for
Regulation of Vi slide Neutral zone (Nz = 0.0) and Proportional band (P
If there is automatic Vi slide control, it works the band = 200%).
same way as the inner loop with the one exception The parameter MIN PULSE determines the pulse
that UNISAB II calculates the position set point duration up or down every time the solenoid valve
according to the actual suction and discharge is activated. If the value is high, a correspondingly
pressure. The parameters are available in the pic- large capacity change is required before the regu-
ture SET UP I CAPACITY I Vi POSITION. lator reacts with an up or down signal. This is a
kind of neutral zone. Default value is 0.5 seconds
Setting the regulator and should not be higher than 2 seconds.
With version 2.01, the PID regulator was intro- The parameter RUN TIME defines how long it will
duced to replace the previous “three-point I regu- take to run the slide from 0-100% at constant up
lator”. As from version 2.03.2 it is possible to se- signal or from 100-0% at constant down signal.
lect PID = YES or NO. If PID = NO is selected the Usually slide speed is always adjusted on the oil
regulator works approximately like the former I needle valves positioned on the capacity regulat-
regulator. Irrespective of whether PID = YES or ing block so that the slide speed is approx. 60 sec-
NO is selected, it is recommended to begin with onds when the oil is warm from operation. This ad-
the factory values and then, if necessary, adjust justment is usually carried out by the service engi-
the values to the conditions of the actual plant. neer who starts up the compressor unit.
Outer loop If the slide speed for some reason cannot be ad-
If PID = YES is selected, it is not recommended to justed for 60 seconds, the RUN TIME parameter
adjust the P band further down than 10°C and must be changed so that run time corresponds to
T.INT. further down than 30 seconds. Higher val- the actual operating conditions. If this is not done,
ues may very well occur. it will appear as if the PID regulator is out of control
T.DIFF. is usually always 0. and it may cause hunting.
The neutral zone can be set for 0.4°C or higher if Example 1
it is not required that the suction pressure is kept A screw compressor with a combination of slide
as narrow as possible around the set point. If the regulation and frequency regulation has a slide
velocity at 60 seconds from 0-100% slide move- Usually it will never be necessary to change the T.
ment. Depending on min. and max. frequency this DIFF. to a value different than 0 sec. However, in
is shown as eg 0-42% capacity on the UNISAB II special cases where the compressor is part of a
display. When the slide has reached 100%, the process plant, eg. in petrochemical plants, it may
frequency converter will start to increase the fre- be necessary to use another value than 0 sec.
quency to the max. frequency set. This will take 60 This will only be necessary if the process requires
seconds and be shown as 42-100% in the a very fast regulation upwards or downwards to
UNISAB II display. Thus the RUN TIME parame- avoid that the suction pressure removes itself too
ter must be set for 60+60=120 seconds for correct far from the set point.
regulation.
Reciprocating compressors
For screw compressors connected to frequency
Reciprocating compressors are capacity regulat-
converters see also the separate UNISAB II Rota-
ed in stages by connection/disconnection of cylin-
tune appendix.
ders, typically in pairs, through solenoid valves
Example 2 controlled by UNISAB II.
PID = YES
How fast the compressor loads/unloads stages is
Values for outer loop:
determined by the timers DELAY UP and DELAY
Nz = 0.0
DOWN, which will start counting as soon as the
P band = 10.0
value is outside the neutral zone.
T. INT. = 60.0
T. DIFF. = 0.0 The regulator is allowed to have a P Band of 0,
which means that the stages are loaded in sec-
If the compressor is running very unsteadily dur-
onds as set.
ing regulation or two compressors cannot find one
another in parallel operation, raise the P band to If the P Band is above 0, the delay times can be
eg. 50°C. prolonged as long as the value is within the P
Band.
If the running of the compressor has steadied, but
the regulator seems slow to reach its set point, re- The P Band is only relevant if the P Band factors
duce the P band a little at a time until the running DELAY UP and/or DELAY DOWN are set in the
of the compressor becomes unsteady again. Now picture P BAND FACTOR at a value above 1. See
raise the P band to the last applicable value. If the P BAND FACTOR in section Timers.
suction pressure still does not reach its set point If the value is just outside the neutral zone and the
(depending on the setting of Nz) a reduction in the P Band factor DELAY UP is eg 10, counting will be
integral-time can be necessary to fine-tune the slow: "1 sec." becomes 10 sec.
regulator.
If the value is just outside the P Band, counting will
If the regulator during a long period of time seems be speeded up, "1 sec" becomes 1 sec.
to hunt, increase the T. INT. to eg. 100-200 sec. If
For reciprocating compressors connected to fre-
the hunting stops, reduce the T. INT. until the sys-
quency converters see also the separate UNISAB
tem starts hunting again. Now increase the T. INT.
II Rotatune appendix.
to the last applicable value.
Input signal
0 5 10 15 Time
Output signal
P-part B
A: Proportional band=10°C A
B: Proportional band=5°C
0 5 10 15 Time
Output signal
I-part C
D
C: Integral time=30 sec
D: Integral time=60 sec
0 5 10 15 Time
Output signal
D-part
F
E: Differential time=10 sec E
F: Differential time=20 sec
0 5 10 15 Time
Output signal
PID-part
0 5 10 15 Time
Sp 2 -1 +9 +1 BAR
(-90) (+ 24.8)1* (-19.4) °C/R717
Nz 0 100 4 °C
Pb 0 100 10 °C
Sp 2 - 60 + 100 20 °C
Nz 0 100 4 °C
Pb 0 100 5 °C
Sp 2 -1 + 24 +8 BAR
(-90) (+ 58)2* (+ 21.4) °C/R717
Nz 0 100 4 °C
Pb 0 100 10 °C
Sp 2 - 60 + 100 20 °C
Nz 0 100 4 °C
Pb 0 100 5 °C
Sp 2 - 999 + 999 0 -
Nz 0 + 999 0 -
Pb 0 + 999 0 -
Sp 2 - 999 + 999 0 -
Nz 0 + 999 0 -
Pb 0 + 999 0 -
Sp 2 -1 +9 +1 BAR
(-90) (+24.8) (-19.4) °C/R717
Sp 2 -60 100 20 °C
Nz 0.0 100 0 °C
Pb 0.1 999.9 50 °C
Sp 2 -1 +24 +8 BAR
(90) (+58) (+21.4) °C/R717
Sp 2 -60 100 20 °C
Nz 0.0 100 0 °C
Pb 0.1 999.9 50 °C
Nz 0 999.9 0
Pb 0 999.9 100
Nz 0 999.9 0
Pb 0 999.9 100
Vi Run Time 19 24 31 60
The picture will now look like this: Ex.: The set point is to vary from -50 to -10°C/R
4 mA -30 corresponding to a change of the current signal
20 mA 20 from 4 - 20 mA.
EXTERNAL INPUT SIGNAL
The cursor is positioned on 4 mA. Press G until
Each measuring signal can be scaled in accord- the cursor moves to the right, and change the val-
ance with the transducer measuring range. ue to -50 with K, then press G again.
In the menu CONFIG, select in line CONTROL Move the cursor to 20 mA, Press G until the cur-
ON one of the following: sor moves to the left, and change the value -10,
press G again.
Ext. cool
If selecting this function, the compressor will reg-
ulate the capacity upwards in case of increasing
measuring value.
Move the cursor to third line, press G until the The picture will now look like this:
cursor moves to the right, and select 4 mA -10
SUCT.PRESSURE SETPOINT with J or K. Fin- 20 mA 20
ish by pressing G. BRINE TEMP. SETPOINT
The picture will now look like this: The set point of the brine regulator is now going to
4 mA -50 change from -10 to +20°C corresponding to a
20 mA -10
change of the current from 4-20 mA.
SUCTION PRESS. SETPOINT
It is possible to follow the set point value by select-
The set point of the suction pressure regulator is ing BRINE I BRINE TEMP I PARAMETERS
to vary from -50 to -10°C/R corresponding to a and press downwards to ACTUAL SP with K.
change in the current from 4-20 mA.
It is possible to follow the set point value by select- Disch. pressure
ing SUCTION SIDE I SUCTION PRESSURE I In the menu CONFIG DISCH.SIDE must be se-
PARAMETERS and press downwards to ACTU- lected in the line CONTROL ON. Select 4-20 mA
AL SP with K. INPUT I in the menu CALIB, and the following
picture will appear:
Brine temperature 4 mA 0
20 mA 0
In the menu CONFIG BRINE must be selected in
NOT USED
the line CONTROL ON. Select 4-20 mA INPUT I
in the menu CALIB, and the following picture will Ex.: The setpoint is to vary from +10 to +35°C/R
appear: corresponding to a change of the current signal
4 mA 0 from 4-20 mA.
20 mA 0
NOT USED
The cursor is positioned on 4 mA. Press G until
the cursor moves to the right. Change the value to
Ex.: The set point is to vary from -10 to +20°C cor- +10 with J, then press G again.
responding to a change of the current signal from Move the cursor down to 20 mA. Press G until
4 - 20 mA. the cursor moves to the right. Change the value to
The cursor is positioned on 4 mA. Press G until +35, and press G.
the cursor moves to the right. Change the value to Move the cursor down to third line. Press G until
-10 with K, then press G again. the cursor moves to the right, and select DISCH.
Move the cursor down to 20 mA. Press G until PRESSURE SET POINT with J or K. Finish by
the cursor moves to the right. Change the value to pressing G.
+20, and press G. The picture will now look like this:
Move the cursor down to CONTROL ON. Press 4 mA 10
G until the cursor moves to the right, and select 20 mA 35
BRINE TEMP SET POINT with J or K . Finish by DISCH. PRESS. SETPOINT
pressing G.
The set point of the discharge pressure regulator It is possible to follow the setpoint value by select-
is now going to change from +10 to +35°C/R cor- ing BRINE I BRINE TEMP I PARAMETERS
responding to a change of the current from 4-20 and press downwards to ACTUAL SP with K .
mA.
It is possible to follow the set point value by select- Capacity control
ing DISCH.SIDE I DISCH.PRESS I PARAME- UNISAB II must be set in REMOTE mode in the
TERS and press downwards to ACTUAL SP with picture CONTROL.
K.
In the menu CALIB, select 4-20 mA INPUT I, and
the following picture will appear:
Hotwater 4 mA 0
In the menu CONFIG, HOTWATER must be se- 20 mA 0
lected in the line CONTROL ON. Select 4-20 mA NOT USED
the signal is above or below the percentage corre- timer STOP DELAY will be activated when the sig-
sponding to the capacity stage in question. The nal is below 0%. When the STOP DELAY timer
timers DELAY UP and DELAY DOWN, which are has finished counting down, the compressor will
used during the loading/unloading of capacity stop.
stages, are now active when capacity regulation In case the current signal drops to -10% (2.4 mA),
takes place with an external 4-20 mA signal (ap- there will be a change to the chosen form of regu-
plies to version 1.08 and later versions). This lation (eg suction pressure regulation, brine regu-
means that for an SMC 108 without total unload- lation, etc). If the signal exceeds -10% once more,
ing the following changes apply: there will be a change to capacity remote control.
0% ≤ Signal < 25% = 0% capacity, When UNISAB II is configured to "capacity set
25% ≤ Signal < 50% = 25% capacity, point", the starting number is changed to 0. The
50% ≤ Signal < 75% = 50% capacity, "old" starting number is stored and reinserted in
75% ≤ Signal < 100% = 75% capacity, case UNISAB II is configured differently from "ca-
100% ≤ Signal = 100% capacity. pacity set point".
This works as follows:
Start Climatic Control
When the signal is above 5% (4.8 mA) and AUTO This function can be used for both reciprocating
START = YES has been configured, the timer and screw compressors without automatic Vi reg-
START DELAY will begin to count down (in case ulation. The function is included in the menu CON-
of screw compressors). FIG and is further described in section Configura-
For reciprocating compressors, the timer START tion.
DELAY will start once the signal is above the low- The set point of the inlet temperature on the water
est capacity stage. When the timer START DE- side of plants that are regulated on brine temper-
LAY has counted down, the compressor will start ature or hot water temperature can be dislocated
and follow the signal up/down. Note, however, by the outside temperature. This requires a 4 - 20
that various limiters may reduce the compressor mA temperature transducer, which is connected
capacity. to the current inlet in UNISAB II as shown in the
Stop wiring diagrams positioned at the end of this man-
When the signal is below 5% (4.8 mA) and AUTO ual.
STOP = YES has been configured, the timer Use a standard temperature transducer with a
STOP DELAY will stop counting down (in case of suitable temperature range, eg -30 - +25°C as
screw compressors). For reciprocating compres- shown in Fig. 6.2. Note that the points of disconti-
sors, the timer STOP DELAY will start once the nuity in the diagram will be determined by the
signal is below the lowest capacity stage. For re- transducer measuring range as seen in the follow-
ciprocating compressors with total unloading, the ing examples 1 and 2.
T inlet T inlet
Sp 1 (+65 5
°C)
14
Sp 2 12 Sp 1
(+25 °C) T out
5
10
4 mA 20 mA
8
(30 °C) (+25 °C)
6
No further compensation will be made once the
Sp 2 4
outside temperature is above the top point of dis-
continuity and below the bottom point of disconti-
2
nuity.
T out
The factor by which the outside temperature will
-10 10 20 30 40
influence the inlet temperature positively or nega-
tively must be set in the BRINE, HOTWATER or In the drawing the settings are SP1 = 12°C at To
UNIVERSAL regulator. In the picture CONFIG, = 0°C and SP2 = 4°C at To = 30°C.
select CONTROL ON = BRINE or HOTWATER, Note that SP1 belongs to the lowest and SP2 to
or (UNIVERSAL regulator) EXT.COL/EXT. HEAT highest outside temperature.
as well as CLIMA CONTROL = YES in the menu
The straight line in Fig. 6.3 shows how the inlet
CONFIG.
temperature is going to vary under the influence of
Example 1: the outside temperature.
On a water cooling unit, the inlet temperature is to
Select the menu BRINE I BRINE TEMP I PA-
be corrected by the outside temperature.
RAMETERS and go down to SET POINT 1 and
1) If the outside temperature is +30 °C or more, SET POINT 2 with K.
the inlet temperature should be +4°C.
Give SET POINT 1 the value SP1 = 12°C from
2) If the outside temperature is +0°C or less, Fig. 6.3 by pressing G.
the inlet temperature should be +12°C.
Give SET POINT 2 the value SP2 = 4°C from
In the menu CONFIG, set CONTROL ON on Fig. 6.3 by pressing G.
BRINE and CLIMA CONTROL on YES. Select an
At the same time set NEUTRAL ZONE = 3°C and
outside sensor with a range of 0 - +30 °C.
PROP.BAND = 10°C as starting points.
The system is now adjusted to the desired func-
tion.
If the outside temperature is -10°C, the value must The slide speed is checked with the compressor in
be 65°C. MANUAL mode, at normal oil temperature and by
The outside temperature can be seen in % of the activating E F used for capacity regulation.
measuring range in the picture CAPACITY: With the slide in minimum position (< 5%) and with
CAPACITY XXX A a constant pressure on E (capacity up), it takes
NOT USED XX about 60 sec for the slide to move to 100%, and
OUTSIDE TEMP. XX % with a constant pressure on F (capacity down)
approx. 60 sec to move down to 0%.
Examples 1) and 2) precondition that the flow
temperature is measured with the normal Pt 100 Is this not the case, adjust the throttle valves.
input, but if a temperature transducer of 4-20 mA
is installed in a common reservoir, the outdoor Volume ratio slide
compensation will also be able to work here. The volume ratio slide is moved by adding or re-
See section Universal regulator in which the pro- moving oil for the slide piston cylinder. The move-
cedure will be exactly the same as described in ment is controlled by UNISAB II, which activates
above examples as this regulator can also be the solenoid valves in the oil lines, thus moving
used for both COOLING and HEATING functions. the slide in the desired direction. If this movement
takes place too fast, the system will become very
In both examples the inlet temperature will rise at
unstable and give rise to unnecessary wear and
falling outside temperatures.
tear of the slide.
If the opposite effect is required, ie rising inlet tem-
To prevent the above, adjustable throttle valves
perature at rising outside temperature, SP1 and
have been built into the oil lines and by changing
SP2 must be switched.
the opening degree of the throttle valves, the slide
movement can be adjusted to a suitable speed.
Adjusting slide speed (screw
The speed is checked with the compressor in
compressors with hydraulic slides)
MANUAL mode and at a normal oil temperature.
The capacity slide is moved by adding or remov- Select picture CAPACITY I VI POSITION I SET
ing oil from the slide piston cylinder. The move- POINT 1.
ment is controlled by UNISAB II, which activates SETPOINT 1 0.0%
ment from 0% to 100% in the picture with VI PO- In case the calculated zero point cannot be set
SITION. within a certain time limit, which is dependent on
The movement from 0% to 100% must be adjust- the calculated movement, an alarm will be issued.
ed on the throttle valves to last approx. 120 sec. When the compressor stops, the slide will drop to
This also applies to the movement from 100% to the calculated zero point. The motor will stop, and
0%. hereafter the slide will be pushed down to the
Use SET POINT 1 with either - 10% or 110% to physical zero position by the built-in spring.
move the slide back and forth until the speed is Once the differential pressure across the com-
correct. pressor has been equalized (Π=1), the calculated
zero point and the physical zero position will be
Variable Zero position the same.
Fig. 6.5
0% 100%
Corrected capacity
Pressure cond.
1.5 12 25 Volume cond.: 4.5 3 2
Cap. slide
Measured slide pos.
0% 100%
The capacity slide signal from the position trans- pacity slide is not allowed to drop while the com-
mitter is scaled in such a way that 0% is read pressor is operating.
when the slide position corresponds to the calcu- For SAB 202S and SAB 202L, which have auto-
lated/set zero point, and 100% is read when the matic settings of the zero point, manual setting is
capacity slide meets the Vi slide, regardless of usually not allowed.
whether the setting is carried out automatically or
The manual setting of the zero point is carried out
manually.
in the picture SETUP I CONFIG. in the configu-
ration point:
Automatic setting of new zero point
(SAB 202) MANUAL ZERO 0.0%
The zero point for the various types of SAB 202 is The setting ranges between 0-40% of max. ca-
calculated according to a programmed algorithm. pacity slide travel (at Vi ratio = 2).
The current calculated value of the zero point is With manual Vi regulation the zero point is cor-
displayed in picture: rected automatically by a factor that depends on
an optimum (calculated) setting of the Vi-slide.
SETUP I DIAGNOSIS I ZERO CAPACITY
Consequently, it is very important that the set-
POS.
ting of the Vi slide is correct.
With manual Vi regulation the zero point is correct-
The setting will be stored when the compressor
ed and set automatically, corresponding to an op-
stops and/or UNISAB II is switched off.
timum setting of the Vi slide. Consequently, it is of
great importance that the setting of the Vi slide
is correct. Built-in spacer block
If the compressor has a built-in spacer block and
Manual setting of new zero point (all Vi regulation is automatic, the MECHANICAL
types of screw compressors) ZERO must be set on YES. Thus, the travel of the
capacity slide will be reduced by the % value
For all screw compressor types without automat-
[0-40%] which is entered in MANUAL ZERO so
ic zero point setting, it is possible to set a "zero
that the corrected capacity may be calculated and
point" manually, below which the compressor ca-
shown correctly.
The value [0-40%] that must be entered in MAN- pressor run for too long a period with a negative
UAL ZERO must have the following size: capacity.
Fig. 6.6
Configuration
length of spacer block To obtain a correct calculation of the zero point, it
manual zero = 100%
length of total capacity travel is important that the compressor type and swept
volume have been entered correctly.
Setting of MECHANICAL ZERO is carried out in
The swept volume of the compressor is deter-
the picture SETUP I CONFIG. in the configura-
mined on the basis of:
tion point:
Compressor type
MECHANICAL ZERO [NO/YES]
RPM (50/60 Hz)
MANUAL ZERO 0.0%
Male/female rotor
The position transmitter is calibrated with the
In case of SAB 202, UNISAB II will automatically
spacer block mounted and the Vi-slide in minimum
enter a swept volume value corresponding to the
(0%).
S type with Male rotor and a 2-pole 50 Hz motor,
ie 1229 m3/h. The correct swept volume must be
The alarm based on the number of revolutions of the com-
In case the slide cannot reach the position corre- pressor, ie 50/60 Hz supply, and on whether the
sponding to a calculated or set zero point (ie a compressor has male or female rotor drive:
positive read capacity) before the expiry of the
SAB 202 SM/ 50 Hz, swept volume = 1229 m3/h
timer Tcap.neg., the compressor will be stopped with
SAB 202 SM/ 60 Hz, swept volume = 1475 m3/h
the following alarm: SAB 202 SF/ 50 Hz, swept volume = 1843 m3/h
CAPACITY ERROR SAB 202 SF/ 60 Hz, swept volume = 2212 m3/h
Each second the timer Tcap.neg. is counting down by SAB 202 LM/ 50 Hz, swept volume = 1590 m3/h
a factor somewhere between 1 and 180 depend- SAB 202 LM/ 60 Hz, swept volume = 1908 m3/h
SAB 202 LF/ 50 Hz, swept volume = 2385 m3/h
ing upon the read negative capacity. Each time
SAB 202 LF/ 60 Hz, swept volume = 2862 m3/h
the slide moves above 0% read capacity, the timer
will be stopped. The timer is reset (set to the reset The nominal swept volume at 50 Hz can be read
value) and is restarted once the slide moves be- on the compressor name plate.
low -2% capacity. As mentioned earlier, two new configuration
The timer is set in the picture SETUP I TIMERS points have been introduced in the picture SETUP
I TIMER RESET in the timer I CONFIG.:
CAP.NEG. MECHANICAL ZERO NO [/YES]
The reset value can be set in the interval of MANUAL ZERO 0.0%
60-20000. The factory value is 10000. Only if the compressor has a built-in spacer block
It is very important that the timer has been set cor- as well as automatic Vi regulation, the ME-
rectly. Too low a value will result in the alarm Ca- CHANICAL ZERO must be set on YES. In all oth-
pacity error. Too high a value will make the com-
charge pressure ratio, compressor type, refriger- However, stop movement if/when reaching
ant and whether there is an economizer. Further- the limit for reasonable power consumption.
more, the corresponding capacity slide position is 2. Deactivate solenoid valve of Vi slide to re-
calculated:
lease Vi slide and move it to minimum posi-
xcap [%] xVi =100 [%] -xVi [%] * tion.
(Vi-slide [mm] /Cap-slide [mm])
3. If still necessary, move capacity slide to the
While in full load mode, the xcap[%] xVi is the set limit VI MODE.
point of the capacity slide position regulator. 4. Change to normal capacity control.
7. Limiting functions
UNISAB II includes a number of limiting functions There is a standard limiter for each of the follow-
(in the following called limiters). ing:
The purpose of a limiter is to prevent shutdowns • Low suction pressure
by limiting or even changing the compressor ca- • High discharge pressure
pacity when the measured value exceeds the se-
lected limits. In most cases, "changing the capac- • High motor current
ity" means decreasing it. However, this is not the • Low brine temperature
case with all limiters. • High water temperature
In general, a limiter can be watching, passive or • High differential pressure
active. While all limiters are watching, the com- Pdiff =Pdisch - Psuct (HPO and
pressor start/stop and the capacity regulation will HPC reciprocating compressors)
work normally.
Furthermore, the following special limiters exist:
While a limiter is passive or active, the compres-
sor cannot be started and will be in staus DELAY. • High suction pressure
If the compressor is in operation, the capacity reg- • Suction ramp
ulation will be partly disabled. Further, if a limiter • High discharge temperature
is active, the capacity will be changed actively.
All relevant limiters are permanently in operation. Standard limiters
If necessary, they will intervene in any of the oper-
The standard limiting function is based on the user
ating modes MANUAL, AUTO and REMOTE.
selected high/low alarm limit, high/low warning
In case the compressor is in MANUAL mode and limit and the limiting zone Lz. In the special case
a limiter is active, the capacity slide will automat- of the high motor current limiter, the value of Lz is
ically be returned to its original value as soon as 2% for screw compressors and 5% for reciprocat-
the limiter is watching. ing compressors. In all other cases, Lz is calculat-
When a limiter is passive or active, the red lamp ed as half the difference between the alarm limit
will flash slowly, and the warning relay will be ac- and the warning limit.
tivated. Further, the display will show whether the Fig. 7.1 illustrates how a standard limiter works
limiter is passive or active. with the high discharge pressure limiter as exam-
ple.
Fig. 7.1
SCREW COMPRESSORS (ALL LIMITERS) and RECIPROCATING COMPRESSORS
RECIPR. COMPRESSORS (MOTOR CURRENT (ALL LIMITERS EXCEPT MOTOR CURRENT
LIMITER) LIMITER)
Discharge press. [bar] Discharge press. [bar]
ALARM
WARNING
Limiting zone
Time Time
1 Limiter is watching. Normal control, capacity can increase or decrease. If compressor is not in operation, it can be started.
2 Limiter changes from watching to passive.
4 Limiter becomes active. Capacity is reduced at once, and timer begins to count.
5 Limiter is active. At each timeout, capacity is reduced and timer restarted, until compressor stops at low capacity. If compres-
sor is not running, it cannot be started and will be in status DELAY.
In the example, the alarm (= shutdown) limit for Motor current limiter
high discharge pressure has been set for 16 bar, Even the high motor current limiter is special for
while the warning limit is 14 bar. As indicated, the reciprocating compressors. When one stage is
size of the limiting zone (Lz) is then (16 -14) / 2 = disengaged due to the limiter, the resulting motor
1 bar. The limit of the limiting zone is thus warning current drop will be measured. It is assumed that
limit - Lz = 14 -1 = 13 bar. if the stage is re-engaged, the motor current will
As shown in Fig. 7.1, most reciprocating compres- increase by the size of the drop. To avoid disen-
sor limiters differ from the corresponding limiters gaging and re-engaging in turn, the limiter will en-
for screw compressor in the way that when the sure that the stage will not be re-engaged until the
measured value is within the limiting zone, the sta- resulting current will be below 95% of the limit for
tus of the limiter will depend on whether the limiter the limiter zone.
has been watching or active. If the limiter has Note that the warning limit for motor current is
been watching, it will remain watching in the limit- SET POINT 1 selected in the picture MOTOR I
ing zone. If the limiter has been active, it will be- MOTOR POWER. If SETPOINT 1 = 1000 kW,
come passive for as long as it is in the limiting the limit for the limiting zone will be 1000 - 2%
zone. = 980 kW for screw compressors, and 1000 -
5% = 950 kW for reciprocating compressors.
High difference pressure limiter High discharge pipe temperature (one-stage re-
Note in particular that this limiter only applies to ciprocating compressors)
HPO and HPC compressors and that it has a fixed From version 1.10 and onwards a capacity limiting
warning limit of 25.2 bar and a fixed alarm limit of function has been entered for all one-stage recip-
26 bar. The limiter is released at 25 bar and it is rocating compressors using refrigerant R717.
passive between 25-25.2 bar. This function is activated at certain operating con-
ditions, especially at excessive differential pres-
Special limiters sure, corresponding to the operating diagram
High suction pressure limitation zone 2 (zone 4, however, for CMO, SMC 100 S/L
and SMC 180).
It is possible to have a high suction pressure lim-
iting function. The effect of this high suction pres- At such operating conditions compressors of the
sure limiting function is that the compressor ca- CMO/HPO and SMC/HPC type must as minimum
pacity is limited to an adjustable max. value when- load 50% of their capacity when starting up and
ever the suction pressure is above the suction during operation.
pressure warning limit. At present the limit curve (which is a straight line)
Max. capacity at "high suction pressure limitation" is fixed on the basis of a max. permissible dis-
is set in picture: charge pipe/oil temperature (T2max) of 150°C as
SETUP I CALIBRATE I CAP. LIMIT as: LIMIT well as suction superheating of 10°C.
HIGH xxx.x%. Whenever the limiting function is active, the fol-
High limit can be set between 0% and 100% lowing will occur at start-up:
where a setting of 100% disables the function.
– Capacity stages corresponding to a min-
In the WARNING picture the text "SUCT. PRESS imum of 50% will be loaded.
HIGH LIM" will appear.
When the limiting function is active during opera-
Suction ramp tion, with 50% capacity or more, the following will
With the timer SUCTION RAMP it is possible to in- occur:
dicate the speed at which the compressor is al-
– It is impossible, both in MANUAL, AUTO
lowed to lower its suction pressure 1°C. The func-
or REMOTE, to unload capacity stages
tion, which is used for as long as the compressor
so that the capacity drops below 50%, ie
is working down towards its normal operating
50/66% are the lowest capacity stages -
point, is a combination of low suction pressure lim-
also when "total unloading" has been se-
iting function and a ramp function.
lected.
If the suction pressure ramp limiting function pre-
– In AUTO and REMOTE the timer STOP
vents the compressor from increasing its capacity
DELAY will be started at 50/66% if the
above 5%, the timer STOP DELAY will not be ac-
regulator sends out a down regulating
tivated and the compressor will continue operat-
signal. If one of the limiting functions is
ing.
to unload capacity, the timer DELAY
The suction pressure limitation without the ramp DOWN will be started at 50/66%.
function can stop the compressor if capacity
comes below 5% for a longer period.
If the compressor is operating at a capacity below to be stopped on the "total unloading timer" due to
50% when the limiting function is active, the limit- insufficient capacity or if the limiting function pre-
ing function will not actively begin to load stages. vents the capacity from being reduced in MANU-
However, the following will take place: AL, AUTO or REMOTE.
– In MANUAL the compressor will be The limit curve (limiting zones 2/4) corresponds as
stopped on the "total unloading timer" standard to suction superheating of 10°C (factory
provided that the capacity stays below value).
50% for more than approx. 4 mins. Since the limit curve is directly dependent on the
– In AUTO and REMOTE the compressor suction superheating of the plant, the actual su-
will be stopped on the "total unloading perheating of the plant must be entered as set
timer" provided the regulator is neutral point 2 in picture: SUCTION SIDE I SUCTION
and capacity remains below 50% for SUPERHEAT. I SETPOINT 2 if it differs from the
more than approx. 4 mins. above factory value.
– If the regulator sends out a regulating Adjusting range: -10 - +30°C
down signal, the timer STOP DELAY will By adjusting SET POINT 2 parameter for suction
be started. superheating upwards or downwards, the limit
– If one of the other limiting functions is to curve will be dislocated accordingly.
unload capacity, the timer DELAY If SET POINT 2 is set for -10°C, the limit curve will
DOWN will stop at 50/66%. be dislocated so much upward - 20°C compared
– If the regulator sends out a regulating up to normal - that the limiting function will be discon-
signal and the compressor is loading nected.
stages so that capacity rises to 50% or
more, the situation will be the same as Display indications
the one described in the previous sec-
The following tables show the texts appearing in
tion.
the display in connection with the various limiters.
In the WARNING picture the text LIMITING DIS-
CHARGE TEMP. will appear if the compressor is
Standard Limiters:
Low suction pressure PAUSE SUCTION LIM. LIMITING SUCT. PRESS SUCT. PRESS LOW LIM
High discharge pressure PAUSE DISCHARGE LIM. LIMITING DISCH. PRESS DISCH. PRES HIGH LIM
Low brine temperature PAUSE SUCTION LIM. LIMITING BRINE TEMP and BRINE TEMP LOW LIM and
LIMITING SUCT. PRESS LIMITING BRINE TEMP
High water temperature PAUSE DISCHARGE LIM. LIMITING HOT WATER and BRINE TEMP HIGH LIM and
LIMITING DISCH. PRESS LIMITING HOT WATER
Special Limiters:
High suction pressure READY SUCTION LIM. 1) None 2) 3) SUCT. PRESS HIGH LIM 3)
Standard Limiters:
Low suction pressure PAUSE SUCTION LIM. None SUCT. PRESS LOW LIM
High discharge pressure PAUSE DISCHARGE LIM. None DISCH. PRES HIGH LIM
Low brine temperature PAUSE SUCTION LIM. LIMITING BRINE TEMP BRINE TEMP LOW LIM and
LIMITING BRINE TEMP
High water temperature PAUSE DISCHARGE LIM. LIMITING HOT WATER BRINE TEMP HIGH LIM and
LIMITING HOT WATER
High differential pressure Irrelevant DISCHARGE LIM. None HIGH DIFFERENTIAL PRES-
SURE
Special Limiters:
High suction pressure READY SUCTION LIM. 1) None 2) 3) SUCT. PRESS HIGH LIM 3)
Notes:
Only shown while capacity is limited.
If limiter is active (at suction pressure > warning limit), it will remain active until the pressure comes below the warning limit less 2°C/R.
Limiter is not active or passive like standard limiters. It actively limits capacity so that it is less than or equal to the selected LIMIT HIGH.
SET POINT 1 is the pressure at which the pump High filter diff. pressure 300 sec
is to start, and SET POINT 2 is the pressure at Low superheat 300 sec
which the pump is to stop. Consequently, adjust High superheat 300 sec
SET POINT 1 to the lowest pressure level.
Low/high oil temperature 300 sec
Normal setting for SAB 202:
SET POINT 1 = 2.5 Bar
SAB 128HR and 163HR with oil pump
SET POINT 2 = 4 Bar
The compressors SAB 128 and SAB 163 HR are
Move the cursor to SET POINT 1 and press G
frequency regulated screw compressors, ie the
until the cursor moves to the right in the picture.
capacity slide is fixed in maximum position and
With K and J set the value. When the value has cannot be moved.
been set, press G once more.
The electric oil pump is used for prelubrication and
In the same way adjust SET POINT 2.
for maintenance of a minimum oil pressure during
If the compressor differential pressure (discharge operation.
pressure - suction pressure) is below SET POINT
The pump is started and stopped in accordance
1 during operation, the pump will start immediate-
with the compressor differential pressure during
ly. operation.
When the compressor differential pressure has The difference is set in the picture OIL I OIL
been higher than SET POINT 2 for 60 sec, the
PRESSURE I PARAMETER whereupon SET
pump will stop.
POINT 1 and SET POINT 2 will appear.
Normal setting for SAB 128/163 HR: ance with the compressor differential pressure
SET POINT 1 = 2.5 Bar during operation.
SET POINT 2 =4.0 Bar The difference is set in the picture OIL I OIL
Set points are adjusted as described in the previ- PRESSURE I PARAMETER whereupon SET
ous section. POINT 1 and SET POINT 2 will appear.
SET POINT 1 is the pressure at which the pump
Starting sequence
is to start, and SET POINT 2 is the pressure at
Once the compressor has received permission to
which the pump is to stop. Consequently, adjust
start, the oil pump will start and oil will be pumped
SET POINT 1 to the lowest pressure level.
into the compressor lubrication system.
Normal setting for SAB 250/330:
The oil flow switch must be activated within 600
seconds to avoid disconnection. SET POINT 1 = 2.5 Bar
SET POINT 2 = 4.0 Bar
When the oil flow switch is activated, the solenoid
valve (capacity slide down) will be open for 15 Move the cursor to SET POINT 1 and press G
seconds and the electric fan will start. The fre- until the cursor moves to the right of the picture.
quency converter will receive a signal to start. With K and J set the value. When the value has
been set, press G once more.
The speed is increased to 1000 rpm in 10 sec-
onds. In the same way adjust SET POINT 2.
The pump will operate for a minimum of 60 sec- If the compressor differential pressure (discharge
onds and stop if the differential pressure is higher pressure - suction pressure) is below SET POINT
than SET POINT 2 as described above. 1 during operation, the pump will start immediate-
ly.
Alarm surveillance
During start the following alarms are delayed: When the compressor differential pressure has
been higher than SET POINT 2 for 60 sec, the
See also section Timers.
pump will stop.
Starting sequence
Low oil pressure 45 sec When SAB 250/330 compressor stops, UNISAB II
High filter diff. pressure 300 sec will attempt to move the capacity slide below 5%
capacity. If this does not succeed, a CAPACITY
Low superheat 300 sec
ERROR alarm will be issued and the compressor
High superheat 300 sec will not start.
Low/high oil temperature 300 sec When the compressor has received starting per-
mission, the oil full flow pump will start.
SAB 283, SAB 330 and SAB 355 with oil The oil is pumped into the compressor lubrication
pump system, and when the oil flow switch is activated,
The pump is used for prelubrication and for main- the prelubrication period will start.
taining a minimum oil pressure level during oper- When the time has expired, the compressor will
ation. The pump is started and stopped in accord- start and the pump will now run for min. 60 sec.
The pump will stop when the differential pressure GSV/RWF with oil pump
is above SET POINT 2 as described above. The pump is used for prelubrication and for main-
Alarm surveillance taining a minimum oil pressure level during oper-
During start the following alarms are delayed: ation. The pump is started and stopped in accord-
ance with the compressor differential pressure
Low oil pressure 45 sec
during operation.
High filter diff. pressure 300 sec
The difference is set in the picture OIL I OIL
Low superheat 300 sec PRESSURE I PARAMETER whereupon SET
High superheat 300 sec POINT 1 and SET POINT 2 will appear.
Low/high oil temperature 300 sec SET POINT 1 is the pressure at which the pump
is to start whereas SET POINT 2 is the pressure
The delayed alarms are described in section Tim- at which the pump is to stop. Consequently, set
ers. SET POINT 1 for the lowest pressure level.
Normal setting for GSV/RWF:
SAB 80 with fitted (mechanical) oil SET POINT 1 = 2.5 bar.
pump SET POINT 2 = 4.0 bar.
Starting sequence Move the cursor to SET POINT 1 and press G
When the compressor has received starting per- until the cursor has moved to the right side of the
mission, it must be checked if the capacity slide is picture. Set the value by means of K and J .
in minimum position. Before starting the compres- When the value has been set, press G once
sor, the oil level switch in the oil separator must be more.
activated.
SET POINT 2 is set in the same way.
Start the compressor.
If the compressor differential pressure (discharge
After a delay of 60 seconds from compressor pressure - suction pressure) is below SET POINT
start, no signal from the level switch for more than 1 during operation, the pump will start immediate-
10 seconds will result in disconnection. ly.
Alarm surveillance When the compressor differential pressure has
During start the following alarms are delayed: been higher than SET POINT 2 for 60 seconds,
the pump will stop.
Low oil pressure 45 sec
Before start-up the oil level switch in the oil sepa- Normal setting for SV24/26:
rator must be active. If this is not the case, an SET POINT 1 = 2.5 Bar
alarm for oil system error will be issued. SET POINT 2 = 4.0 Bar
No signal from the oil level switch will result in dis- Set points are adjusted as described in the previ-
connection after a delay of 60 seconds from com- ous section.
pressor start or during operation.
Starting sequence
If the oil level switch is active, the prelubrication
Once the compressor has received starting per-
period will begin and the oil will be pumped into
mission, check that the capacity slide is in mini-
the compressor lubrication system. When the time
mum position. The oil pump is started and oil will
period has expired, the compressor will start and
now be pumped into the compressor lubrication
the pump will run for min. 60 seconds. The pump
system. To avoid disconnection, the oil flow switch
will stop if the differential pressure is higher than
must be activated within 45 seconds.
SET POINT 1.
When the oil flow switch is activated, the compres-
Alarm surveillance
sor will start.
During start the following alarms are delayed:
The pump will operate for a minimum of 60 sec-
Low oil pressure 45 sec onds and stop if the differential pressure is higher
High filter diff. pressure 300 sec than SET POINT 2 as described above.
Low superheat 300 sec Alarm surveillance
High superheat 300 sec During start the following alarms are delayed:
The difference is set in the picture OIL I OIL FV 19 with oil pump
PRESSURE I PARAMETER whereupon SET The compressor FV 19 is a small frequency regu-
POINT 1 and SET POINT 2 will appear. lated screw compressor without the stage regulat-
Normal setting for FV 24/26: ed capacity control as featured in the SV 19.
SET POINT 1 = 2.5 Bar The electrical oil pump is used for prelubrication
SET POINT 2 = 4.0 Bar and for maintenance of a minimum oil pressure
Set points are adjusted as described in the previ- during operation.
ous section. The pump is started and stopped in accordance
with the compressor differential pressure during
Starting sequence
operation.
Once the compressor has received permission to
start, the oil pump will start and oil is pumped into The difference is set in the picture OIL I OIL
the compressor lubrication system. PRESSURE I PARAMETER whereupon SET
POINT 1 and SET POINT 2 will appear.
The oil flow switch must be activated within 45
seconds to avoid disconnection. Normal setting for FV 19:
When the oil flow switch is activated, the solenoid SET POINT 1 = 2.5 Bar
valve (capacity slide down) will be open for 15 SET POINT 2 = 4.0 Bar
seconds and the electrical fan will start. The fre- Set points are adjusted as described in the previ-
quency converter will then receive a signal to ous chapter.
start.
Starting sequence
The speed is increased to 1000 rpm in 10 sec- Once the compressor has received starting per-
onds. mission, the oil pump will start and oil will be
The pump will operate for a minimum of 60 sec- pumped into the compressor lubrication system.
onds and will stop if the differential pressure is The oil flow switch must be activated within 45
higher than SET POINT 2 as described above. seconds to avoid disconnection.
Alarm surveillance When the oil flow switch is activated, an oil
During start the following alarms are delayed: by-pass solenoid valve for unloading will open for
Low oil pressure 45 sec 15 seconds and the electrical fan will start.
High filter diff. pressure 300 sec Starting signal is transmitted to the frequency con-
verter.
Low superheat 300 sec
The speed is increased to 1200 rpm in 10 sec-
High superheat 300 sec
onds.
Low/high oil temperature 300 sec
The pump will operate for a minimum of 60 sec-
See also section Timers onds and stop if the differential pressure is higher
than SET POINT 2 as described above.
Alarm surveillance The pump will run for 60 sec and stop.
During start the following alarms are delayed: Alarm surveillance
Low oil pressure 45 sec During start the following alarms are delayed:
High filter diff. pressure 300 sec Low oil pressure 45 sec
Low superheat 300 sec High filter diff. pressure 300 sec
High superheat 300 sec Low superheat 300 sec
High/low oil temperature 300 sec High superheat 300 sec
VMY Mk 2 and 2.5 with built-in oil pump SAB 128/163 Mk 2 Booster with oil
Once the compressor has received starting per- pump
mission, the pump will start. Make sure that the
Once the compressor has received starting per-
capacity slide is in minimum position.
mission, the pump will start. The built-in spring en-
The compressor will start working. sures that the capacity slide is in minimum posi-
tion.
Start the compressor and wait for a signal from the Alarm surveillance
oil flow switch for max. 50+10 sec. During start the following alarms are delayed:
If there is no signal from the oil flow switch for 10 Low oil pressure 300 sec
sec during operation, the compressor will stop.
High filter diff. pressure 300 sec
The oil pump runs continually during operation to
Low superheat 300 sec
ensure sufficient pressure to move the capacity
slide. High superheat 300 sec
The oil is pumped into the compressor lubrication Low disch. gas superheat 300 sec
system and when the oil flow switch is activated, Low/high intermediate discharge 300 sec
the prelubrication period will begin. temperature
External starting permission - cursor back to START OIL PUMP. Press G until
immediate stop the cursor moves to the right, then select YES with
The input must be connected in order for the com- J or K .
pressor to run in MANUAL, AUTO or REMOTE. If The pump will now start and run for the time set.
this input is opened during operation, the com- For SAB 202, SAB Mk3 and VMY Mk3 compres-
pressor will stop immediately. sors a warning "Watch the oil pressure" will be is-
When the input is open, STOPPED will appear in sued while the oil pump is in manual operation for
the bottom line of the display. oil charging.
If the pump is to stop before time expiry, select NO
External starting permission - under START OIL PUMP.
normal stop Note: As from 2001 SAB 128/163 Mk3 and SAB
This input and IMMEDIATE STOP must be con- 202 are no longer as standard fitted with a valve
nected before the compressor is going to start in for external connection to the oil pump suction
AUTO or REMOTE. If the input has not been con- side. Thus it is not possible to charge oil with the
nected, the display will read STOPPED in the bot- unit oil pump.
tom line.
If the input is opened during operation, the com- Motor current measuring
pressor capacity will move to its minimum posi- UNISAB II can be supplied with a signal 0-1 Amp
tion, and the compressor will stop on its delay be- AC directly from a current transformer in the com-
fore the actual time to stop. pressor motor starter.
In case the input CAPACITY DOWN BLOCKED is The value for the voltage ratio of the current trans-
connected, the compressor will not reduce capac- former must be entered in the menu CONFIG I
ity once the input EXTERNAL STARTING PER- RANGE M. CURR to get a correct reading of the
MISSION NORMAL STOP is opened. current.
Next, select menu MOTOR I MOTOR CUR-
Oil charging, manual (screw RENT and the following picture will appear:
compressors)
ACTUAL SP XX A
Oil charging cannot take place with UNISAB II in SET POINT 1 XX A
"STOPPED". If the compressor is fitted with an oil SET POINT 2 XX A
pump for oil charging, it can be started in the fol-
lowing way: In SET POINT 1 enter the motor full load current
of the motor as read on the name plate. In SET
Select menu TIMERS I OIL CHARGING and the
POINT 2 a lower value may be entered if the ab-
following picture will appear:
sorbed current is to be limited in certain periods.
START OIL PUMP NO
TIMER 0 sec Set points are set by placing the cursor on SET
POINT 1 or SET POINT 2 respectively. Press G
Place the cursor on TIMER and press G until the until the cursor moves to the right. The correct
cursor moves to the right. Set the number of sec- number can now be set by using J or K.
onds the pump is to run. Press G and move the
It is possible to change between two set points by • Temperature of chilled liquid before evapo-
opening or closing a digital input. See wiring dia- rator.
grams. • Volume flow of cooling gas on pressure side
Open input = SET POINT 1. (m3/h).
See also Current limiters. • Motor power consumption in kW.
• Motor efficiency.
Motor power measuring The measuring of these values are set in the pic-
UNISAB II can be supplied with a 4-20 mA signal ture CONFIG I COP.
from a power transmitter of 0-xxxx KW. COP ACTIVE NO
Enter the power ratio of the power transmitter in FLOW FACTOR 0.20 l/pls
2) AT MIN CAP: If selecting this function, the In case the compressor runs in limited operation,
output will be activated when the compres- it will, however, reduce its capacity. When the
sor is below LOW LIMIT, which is set in the state of operation is back to normal, the compres-
menu CALIB I CAP. LIMIT. The hysteresis sor will return to full load. See also Limitations.
is 1%. If the input is connected while the compressor is
3) AT MAX CAP: Select this function and the READY to start in AUTO or REMOTE, the com-
output is activated when the compressor is pressor will be started by force.
above HIGH LIMIT, which is set in the menu
CALIB I CAP. LIMIT. The hysteresis is Power management system (PMS)
1%.
This function works in MANUAL, AUTO or RE-
Please note that the line CAP.LIMITER is not in- MOTE operation. It is a kind of "an agreement to
cluded in the CALIBRATION menu until the auxil- start" system, consisting of one digital output
iary output has been selected as either AT MIN. "Compressor ready to start", which is set when the
CAP. or AT MAX. CAP. compressor is to start, as well as a digital input
4) RUNNING: If selecting this function, the out- "Permission to start OK". This input must be set
put will be activated whenever the compres- before the timer "PMS confirmation" expires in or-
sor is operating, ie when the start signal to der for the compressor to start.
the compressor has been set. The alarm "Power management system error" is
5) READY-EXT.: This function corresponds to activated if the input "Permission to start OK" has
the above READY function, but here it is not not been set before the timer "PMS confirmation"
required that EXTERNAL START NORMAL expires.
STOP must be set for the output to be acti- The signal can be removed during operation with-
out stopping the compressor.
At compressor start the output(s) for oil return start on two cylinders and the other two are used
is/are not opened until the time set in the timer OIL to connect changes in capacity steps. See draw-
RETURN has expired. ing number 3448-236 on page 128-129.
The time delay function will be disconnected if the Please note that compressors with additional
timer OIL RETURN is set for 0 sec or when the steps do not start totally unloaded but on one
digital inputs for intermediate and high pressure and two cylinders respectively.
oil return are OFF.
The time delay OIL RETURN is set in the timer Oil heating
picture TIMER I TIMER SETUP. Oil heating is NOT a configuration point, but it has
various functions depending on whether the com-
Start unloading system for TCMO 28 pressor in question is configured as a reciprocat-
compressor ing or a screw compressor.
TCMO 28 reciprocating compressors have a Screw compressors
unique unloading system which ensures low start- A heating element will be connected while the
ing torque and a correct balance between high compressor is not in operation and there is no
and low pressure cylinders during part load. When temperature regulation.
the compressor is stopped, during start up and at
Reciprocating compressors
loading stages below or at 50% a hot gas bypass
The heating element outlet is activated by de-
valve “B” is activated to ensure this. See informa-
creasing oil temperature. This function is active
tion sheet for outputs on page 131 - reciprocating
both at compressor stand-still and when the com-
compressors 3448-236.
pressor is in operation.
Additional steps on SMC compressors The set point of this value is set in picture OIL
TEMP I PARAMETER, SET POINT 2. The set
From SMC 104 to SMC 108 the first capacity step
point has a fixed hysteresis of 5K.
is divided in two so that the compressor starts on
one cylinder. The other cylinder is used to connect Ex: Set point 2 = 35°C:
changes in capacity stages. SMC 112 and 116 Heating starts at 35°C and stops at (35+5) = 40°C.
ter the data for the substances (the refrigerant 10 °C/R 00.00 BAR
curve) contained in the refrigerant used.
15 °C/R 00.00 BAR
In the menu SETUP I CALIB I DEF. REFRIG-
ERANT R000, the following picture will appear: 20 °C/R 00.00 BAR
-40 °C/R 00.00 BAR For BAR/°C, enter the pressure as absolute pres-
sure in 1/100 BAR. For temperatures enter values
-35 °C/R 00.00 BAR
between -90°C and +80°C with intervals of 5°C.
-30 °C/R 00.00 BAR Each pressure value in the table must be given a
certain value.
-25 °C/R 00.00 BAR
The pressure can be entered in the range of 00.00
-20 °C/R 00.00 BAR and 99.99 BAR. The table has been initialized to
-15 °C/R 00.00 BAR
00.00 BAR.
9. Calibration
Before initial compressor start-up and after Insufficient or incorrect setting of pressure
service1), adjustments of transducers and position transducers may lead to compressor break-
transmitters must be carried out. Their values down or personal injury.
have usually been preset by the factory, but a re- The temperature sensors must be calibrated as
check must be made before start-up. This is very they are connected electrically with four conduc-
important as failure to adjust may lead to malfunc- tors, which automatically makes up for line resist-
tion during operation. ance.
1) Eg in connection with replacement of CPU
prints, relay prints, pressure transducers or batter- Pressure transducers
ies. See also section Service.
Calibrate the pressure transducers at atmos-
pheric pressure in the compressor.
Use the following pressure transducers:
Table 10
Unit = BAR COMPRESSOR TYPE
Max.
MEAS.POINT SAB/VMY SMC TSMC/ HPC/HPO MAX. permissible
TCMO PRESS. deviation at
ATM.PRESS
Select the menu CALIBRATE, and the following Place the cursor on SUCT. ADJUST and use the
picture will be displayed: G key to change the value.
CALIBRATE Now change the value to the value SUCT. AD-
PRESS.TRANSDUCER
JUST is showing, ie 0.2 Bar with opposite sign.
BRINE TEMP
Note that the adjusting value is in 1/100.
CAPACITY
MOTOR FREQ Change SUCT. ADJUST to the value -.20.
Vi POSITION
Adjust the other pressure levels in the same way.
4 - 20 mA INPUT
However, note that DIFF. PRESS is relevant only
AUX. OUTPUT
for screw compressors and IMED. PRESS only for
CAP. LIMITS
DEF. REFRIGERANT R000
two-stage reciprocating compressors.
The following picture should now appear:
Note that some of the entries in the CALIBRATE
SUCT. PRESS .00 BAR
menu are described in other chapters of this man- SUCT. ADJUST -.20 BAR
ual. DISC. PRESS 0.0 BAR
I and the following picture will appear: OIL PRESS 0.0 BAR
OIL ADJUST -.10 BAR
SUCT. PRESS .20 BAR
DIFF. PRESS 0.0 BAR
SUCT. ADJUST .00 BAR
DIFF. ADJUST ..10 BAR
DISC. PRESS -0.3 BAR
IMED. PRESS 0.0 BAR
DISC. ADJUST .00 BAR
IMED. ADJUST -.10 BAR
OIL PRESS 0.1 BAR
OIL ADJUST .00 BAR
The pressure transducer calibration has now
DIFF. PRESS -0.1 BAR
been carried out correctly.
DIFF. ADJUST .00 BAR
IMED. PRESS 0.1 BAR
IMED. ADJUST .00 BAR Brine temperature
Place the cursor on BRINE TEMP and press the
Note: The pressure values shown are examples
I key once. The following picture will appear:
only. At atmospheric pressure the value of the
BRINE TEMP 18.9°C
pressure transducer must be within the limits for
BRINE ADJUST 0.0°C
"Max. permissible deviation at atm.pressure" as
indicated in the above table. Is this not the case, The BRINE TEMP value is the immediate value
the value will be outside its tolerance and must be measured by the sensor. If a test measuring with
replaced. a precision thermometer shows eg 18.7°C at the
The pressure levels are measured in BAR (rela- sensor, adjustment can be made.
tive pressure) and at atmospheric pressure the Place the cursor on BRINE ADJUST and change
reading must show 0.0 Bar to be correct. the value to -0.2°C. BRINE TEMP will now be
As it appears from the above example, the meas- 18.7°C (18.9-0.2), and adjustment has taken
ured pressure levels are not 0.0 Bar. Consequent- place.
ly calibration must be carried out.
Note that it is only possible to adjust BRINE TEMP CAP. ZERO AD XX.X %
- not the other temperature sensors. CAP. 100 ADJ XX.X %
There are four types of position transmitters: Long-stroke capacity rod transmitter for SAB
Turning transmitter for SAB 110, SAB 128, SAB 283.
163 and SAB 202 (capacity and Vi). Fig. 9.3
Fig. 9.1
ALU-Tube
3
4.5 4. 2 1
3.5
3. 2
100%
2.5 3
SPAN + ZERO 1
2.
No. 3
Short-stroke transmitter for capacity for GST,
0%
ALU-Tube
3
2 1
Slide position
4.5 4.
Volume ratio 3.5
1 = 4 - 20 mA
3. 2
2 = + 24 VDC
Approx. min pos 100%
3 = GND
0% 2.5 3
SPAN + ZERO 1
with distance ring
No. 3
2.
0%
T0177063_0
With the cap/Vi slide in minimum position, adjust Capacity slide adjustment, auto V i
zero until the display shows 0%. With the cap/Vi To adjust the movement of the capacity slide the
slide at maximum position, adjust span until the Vi slide must be in minimum position. The Vi slide
display shows 100%. is brought to minimum the following way: Start the
compressor in MANUAL, select SETUP I and
Capacity slide adjustment
then CAPACITY I.
Start the compressor in MANUAL and make sure
that the capacity slide is in minimum. Adjust the The following picture will appear:
zero screw of the transmitter until the display CAPACITY XX
shows 0%. CAP. POS XX
VI POSITION XX
Now bring the slide to its maximum position (eg
RUNNING XX
when the current consumption is no longer rising),
and adjust the span until the display shows 100%. Select the Vi POSITION and press I to get to the
Return the slide to minimum and check. following picture:
Change SETPOINT 1 to -10% which will change In this picture 0.0% always means that the Vi slide
the Vi adjustment to manual and place the Vi slide will be adjusted automatically by UNISAB II.
in minimum position. Change SETPOINT 1 to -10%, which changes the
Adjust the capacity slide position as described Vi adjustment to manual and places the Vi slide in
above under Capacity slide adjustment. After- minimum position.
wards, remember to reset SET POINT 1 to 0.0%.
Return with H to the picture:
Capacity slide adjustment, auto zero point CAPACITY XX
For SAB 202 compressors with automatic zero CAP. POS XX
Capacity slide adjustment, manual Vi 2) Disconnect the automatic zero point setting
Follow the same procedure as above, but note while setting the transmitter minimum position.
that the capacity transmitter must be adjusted This can be done by setting MANUAL ZERO = 0.1
every time the Vi position is changed. in the picture SETUP I CONFIG.
The following picture will appear: Adjustment of volume ratio slide adjustment,
auto Vi
CAPACITY XX
CAP. POS XX It is assumed that the capacity slide has been set
VI POSITION XX correctly.
RUNNING XX Start the compressor in MANUAL and take the
slide up to 20-30%.
Select the Vi POSITION and press I to get to the
following picture: Select CAPACITY I VI POSITION I and the fol-
lowing picture will appear:
SETPOINT 1 0.0%
SETPOINT 1 0.0%
onds the red LED turns off again which indicates See also Adjusting slide speed in section Com-
that it is ready for 100 % calibration. pressor regulation.
Change SET POINT 1 to 110 % and return to the
above picture where the Vi position is now in- Adjusting long-stroke capacity rod for
creasing. Wait until it stops increasing and then SAB 283
press the calibration button twice. (Note that the For type part no. 1373-038
indicated value may not be correct when the
Note: For long-stroke transmitters with part no.
transmitter is in calibration mode). The red LED
1373-057 calibration and terminal connection are
starts flashing quickly. After approx. 10 seconds
similar to that of SAB 110, SAB 128 etc. Please
the red LED switches to normal flashing which in-
see section above.
dicates that calibration is completed. Vi position
will now indicate 100 %. As shown below, the capacity transmitter is fitted
with a single calibration button surrounded by a
Change SET POINT 1 to -10 % and check mini-
green and red LED.
mum.
During normal operation the red LED is flashing
Change SET POINT 1 to 0.0 % for automatic Vi
rather slowly. The green LED is switched on con-
regulation. Besides, UNISAB II will change to au- stantly when the transmitter is in 100% position
tomatic Vi control itself after the compressor has whereas it flashes quickly when the transmitter is
been stopped. in 0% position.
Fig. 9.7
Dia
7mm
3
2 1
60mm
74mm
will turn OFF to indicate readiness for 100% Capacity slide adjustment, manual Vi
calibration. Follow the same procedure as above, but note
3. Start the compressor and move the slide to that the capacity transmitter must be adjusted
100% position and press the calibration but- every time the Vi position is changed.
ton again. The red LED will start flashing Capacity slide adjustment, auto V i
quickly. After ten seconds the calibration will To adjust the movement of the capacity slide the
be completed and the red LED will flash nor- Vi slide must be in minimum position. The Vi slide
mally. is brought to minimum the following way: Start the
4) To make sure that the slide is in maximum compressor in MANUAL and select CAPACITY
physical position, (UNISAB II does not allow I.
the capacity button to be activated after The following picture will appear:
100% indication in the display has been
CAPACITY XX
reached) it is recommended to set “CAP
CAP. POS XX
100 ADJ” at -10% after 100% calibration of VI POSITION XX
the transmitter has been completed and the RUNNING XX
slide remains in maximum position. See the
Software Calibration section earlier in this Select the Vi POSITION and press I to get to the
section. The slide indication in the display following picture:
must now be 90%. If capacity can be in-
creased further either automatically by UN- SETPOINT 1 0.0%
Note: For short-stroke transmitters with part no. 3. Start the compressor and move the capacity
1373-061 calibration and terminal connection are slide to 100% position and press the calibra-
similar to that of SAB 100, SAB 128 etc. Please tion button again. The red LED will start
see section above. flashing quickly. After ten seconds the cali-
bration will be completed and the red LED
Fig. 9.8
will flash normally.
Short-Stroke Capacity slide adjustment, manual Vi
Follow the same procedure as above, but note
LED-Supply that the capacity transmitter must be adjusted
Calibration push button
every time the Vi position is changed.
LED-Digital output Capacity slide adjustment, auto V i
Adjust the capacity slide position as described Change SET POINT 1 to 0.0% for automatic Vi
above under Adjusting short-stroke capacity control. Besides, UNISAB II will change to auto-
transmitter. Afterwards, remember to reset SET matic Vi control itself after the compressor has
POINT 1 to 0.0%. been stopped.
Volume ratio slide adjustment, auto Vi See also Adjusting slide velocity in section Com-
It is assumed that the capacity slide has been set pressor regulation.
correctly.
Start the compressor in MANUAL and take the Electrical slide systems
slide up to 20-30%. (certain screw compressors)
Select CAPACITY I VI POSITION and the fol- The built-in capacity slide position transmitter
lowing picture will appear: must be adjusted correctly to ensure safe and sta-
ble slide control. This adjustment must always be
SETPOINT 1 0.0% carried out as described in section Transmitter ad-
justment.
Afterwards, the capacity signal must be
In this picture 0.0% will always mean that the Vi
adjusted by software as described in section
slide will be adjusted automatically by UNISAB II. Software adjustment.
Change SETPOINT 1 to -10%, which changes the
Manual slide positioning
Vi adjustment to manual and places the Vi slide in
Contrary to hydraulic slides, the electrical capacity
minimum position.
slide can be positioned manually for test. This is
Return with H to the picture: useful both when performing transmitter adjust-
CAPACITY XX ment and software adjustment.
CAP. POS XX
Select SETUP I CONTROL I COMPRESSOR-
VI POSITION XX
CONTROL = STOPPED and then SETUP I
RUNNING XX
CALIBRATE I CAPACITY. The picture shown in
Wait until Vi does not decrease any further and section Software adjustment will appear. While
push the calibration button once. The red LED is this picture is open (and still STOPPED mode), it
now constantly ON. After 10 sec. the red LED will is possible to move the capacity slide by means of
turn OFF to indicate that it is ready for 100% cali- the E and F buttons.
bration. Note that when reaching the end stop, the alarm
Change SET POINT 1 to 110% and return to the CAPACITY ERROR will be displayed after two
above picture where the Vi position will increase. seconds. Release the button at once and reset the
Wait until it does not increase any further and alarm.
push the calibration button once again. The red Transmitter adjustment
LED will flash quickly and after 10 sec. the calibra- The capacity transmitter is fitted with a single cal-
tion is completed and the red LED will flash nor- ibration button surrounded by a green and a red
mally. LED as shown in Fig. 9.9.
Change SET POINT 1 to -10% and check mini-
mum.
Fig. 9.9
Calibration
push button LED-Working
LED-Position (red)
(green)
Normally
not visible.
For calibration
remove cover
During normal operation the red LED is flashing will start flashing quickly. After ten seconds
rather slowly. The green LED is switched on con- the red LED will change to normal flash rate,
stantly when the transmitter is in 100% position indicating that calibration has been complet-
whereas it flashes quickly when the transmitter is ed.
in 0% position. It is possible to ignore points 3 or 4 or both. Press-
Calibration is carried out as follows: ing the calibration button for five seconds in cali-
1. Apply supply voltage for a minimum of five bration mode will bring the transmitter back to nor-
minutes before calibration. mal operation mode.
2. Press the calibration button for five seconds The 4-20 mA signal from the transmitter is perma-
to get the transmitter in calibration mode. nently available. However, during calibration the
The red LED will change from normal flash signal is based on the default calibration values,
to OFF. so it will not show 0% at minimum capacity nor
100% at maximum capacity!
3. Decrease capacity to its minimum and press
the calibration button once. The red LED Note that it is possible to return to the default cal-
will turn ON. After ten seconds the red LED ibration values by keeping the CAL Switch
will turn OFF again, indicating that the posi- pressed for twenty seconds. However, it is the
tion transmitter is ready for 100% calibra- transmitter manufacturer's default values, which
tion. are reset. These values may differ very much from
the correct values for the compressor in question.
4. Increase capacity to its maximum and press Reset is indicated by the red and green LED flash-
the calibration button twice. The red LED ing briefly a couple of times.
D.OUTPUT 7 0 8 NO OF ALARMS
D.OUTPUT 12 1 13 POWER ON
D.OUTPUT 14 0 15 COP
D.OUTPUT 15 1 16 PROFICOM
D.OUTPUT 17 0
D.OUTPUT 18 0
2) Diagnosis I Misc. functions
Here the state of all digital outputs connected to This picture includes four items:
the selected alarm can be read. SUCT. RAMP L X.X°C/R
SUCT. SUPERH XX.X°C
0 = The output has been open
CAPACITY XXX.X SEC
1 = The output has been activated.
BRAKE DLY X.X SEC
Tables 11 and 12 below show the numbering of
in-/outputs on screw and reciprocating compres- The first item SUCT. RAMP L. shows the state of
sors respectively. the suction ramp function. See section Limiting
functions, Suction ramp.
Return to the previous menu by pressing H:
The value shows the actual suction pressure limit,
which will be equal to the suction pressure set
point if the suction ramp is not active. When the
suction ramp is active, the value will decrease by
1°C every N seconds, where N is the selected val-
ue of the SUCT. RAMP timer.
The second item SUCT. SUPERH is the same as
the suction superheat set point 2, which is used by
the High Discharge Pipe Temperature Limiter.
See section Limiting functions, Special limiters.
The third and the fourth items are explained in 0 = Output open
section Compressor regulation, Electrical slide 1 = Output closed
control.
Table 11 below shows the numbering of the out-
puts.
3) Diagnosis I Software version
Here it can be checked which program version is
6) Diagnosis I Analog inputs
running in UNISAB II:
(Pressures, Temperatures, Current)
Example:
In this picture it is always possible to check the ac-
UNISAB II
tual state of the analog inputs both at compressor
2.00
standstill and during operation.
Sabroe Refrigeration
000119 13 : 46 The picture looks as follows:
PRESS INP 1 XXXX
PRESS INP 2 XXXX
4) Diagnosis I Digital inputs
PRESS INP 3 XXXX
In this picture it is always possible to check the ac- PRESS INP 4 XXXX
tual state of the digital inputs both at compressor PT 100 INP 1 XXXX
standstill and during operation. PT 100 INP 2 XXXX
PT 100 INP 3 XXXX
The inputs are numbered from 1 to 11 and their
PT 100 INP 4 XXXX
particular status is displayed.
CURR. XXXX
0 = Input open EXT. XXXX
CAP. XXXX
1 = Input closed
VI. XXXX
Table 11 below shows the numbering of the in-
puts. It is 12 bit A/D-converted raw values of the input
signal which are displayed.
5) Diagnosis I Digital outputs The displayed raw values are interpreted in the
In this picture it is always possible to check the ac- following way (see tables below):
tual state of the digital outputs both at compressor
standstill and during operation.
Pressure
Reading 7 752 7310 8191
Input from pres.transmit. (VDC) 0 0.5 4.5 5.0
Pt100
Reading -2000 -700 +1850 +2000
Temperature (°C) -200 -70 +185 +200
Ext, Cap, Vi
Reading 7 1606 4818 8030
Input (mA) 0 4 12 20
Curr.
Reading 7 5910
Input (Amp AC) 0 1.0
verter. 0004 00 00 00 00
12) Diagnosis J New password The calculated COP values and a number of inter-
In this picture it is possible to change the pass- mediate calculations are shown in this picture:
word. See section Operating the UNISAB II con- COP XX.X
COP CARNOT X.XX
trol.
COP MECH. X.XX
COOLING OUTPUT XXXX KW
13) Diagnosis I Power on MASS FLOW XXXX kg/h
In this picture it can be checked how many times SHAFT POWER XXXX KW
the power supply for UNISAB II has be reconnect- ABSORBED POWER XXXX KW
MOT. EFFICIENCY XX.X %
ed. This menu is used for trouble shooting.
VOL. FLOW XXXX m3/h
POWER ON OVH.SPC.VOL XXXX l/kg
020606 22:53:31 SAT.SPC.VOL XXXX l/kg
SUPPLY (One red) This diode will flash briefly while voltage is con-
nected to UNISAB II. During normal operation the
CPU PRINT (One green, one red) light is off.
Positioning and identification of these light diodes In case the diode flashes repeatedly when voltage
can be seen from the following drawing. is connected, there may be an error in the voltage
DIGITAL INPUTS, DI1 to DI12 (Green) supply.
The light diodes are marked from DI1 to DI12 and CPU PRINT, ACT1 (green), RST1 (red)
the attached functions appear from the list of in- The green light diode must flash irregularly when-
puts. ever UNISAB II is electrified. A constant light or no
Light in diode = input activated. light is a sign of malfunction.
DIGITAL OUPUTS, DLR1 to DLR18 (Red) The red light diode must usually be off. It is only
The light diodes are marked from DLR1 to DLR18 on for brief moments in case the CPU tries to re-
and the attached functions appear from the list of start the program. This may only happen while
outputs. UNISAB II is switched on.
Transmitter EPROM
YELLOW
GREEN
Receiver
DIGITAL
OUTPUTS CPU PRINT
Battery
1) HLI/BLI cooling
RE1
RE7
2) Capacity stage 7/intermed. press. injection
1) Oil cooling
RE8
2) Oil cooling/thermo pump
DIGITAL
RE9 1) Oil distribution pipe
2) Oil return INPUTS
1) Oil rectifier DI1 Compressor operation
RE10
2) Water cooling
DI2 EXT. start, normal stop
RE11 1) Heating element
2) Heating element DI3 EXT. start, immediate stop
DI4 Starting request (PMS)
RE12 Alarm
DI5 Regulator Sp1/Sp2
RE13 Warning DI6 Motor currentSp1/Sp2
1) Oil pump operation
RE14 DI7
AUX. output 2) Oil return interm.press
DI8 1) Full flow pump operation
RE15 2) Oil return high pressure
Starting request DI9 1) Oil flow switch
2) Oil differential pressostat (mk4)
DI10
RE16 Compressor start Capacity down blocked
DI11 Thermistor (no light function)
RE17 1) Oil pump start
2) Oil rectifier DI12 Not used
MANUAL
operation
Yes
Yes
Display
Yes =
READY
No
Recipr./screw Screw
Prelubrication
No Yes
Contact
Sabroe Ref.
1 2
Yes
Apply jumper, or check connec-
tions from terminals 116-117 to Check connection from terminals 118-
power management system. 119 to motor starter
Is there feed-
back on termi-
nals 41-42 from No Correct wiring
motor guard? connection
Green light di-
ode no 1 on
print.
Yes
No
Error mes- No
sage in oil 3 Check that input STARTING REQUEST
system? FEEDBACK terminals 47-48 are closed.
PMS Light in green diode no. 4 on print. Can
error mes- Yes also be checked in picture DIAGNOSIS
Yes sage re- I DIGITAL INPUT no. 4=1.
ceived?
Check wiring connec-
tion to oil float. When No
float has been activat-
ed, green light diode no No Input Yes Try again
9 will flash on print. closed?
Relay no 17
Yes is activated No Check that CONFIG I
PRELUBRICATION = YES.
on print. Red
Check float
light diode
function
Yes
Yes
Check if feedback is received on termi-
nals 53-54 (green light diode no 7 on
print) from pump motor guard
Yes
Yes
Display
READY?
No
4 5
4 5
Yes Display =
READY?
Is cool-
ing/heat- No Change set point or wait for cool-
ing re- ing/heating requirement.
quired?
Yes
Recipr./screw Screw
Prelubrication
No Yes
7 6
At compressor start-up
green light diode on front
will flash.
PMS
Yes error
message
received?
Check that input STARTING RE-
QUEST FEEDBACK terminals 47-48
is closed. Light in green diode no. 4 No
on print. Can also be checked in pic-
ture DIAGNOSIS I DIGITAL INPUT
no 4=1. Is relay no 16
activated on No
Contact
print when try-
Sabroe Ref.
ing to start (red
No Input Yes light diode)
closed? Try again
Yes
Apply jumper, or check con-
nections from terminals
116-117 to power manage- Check connection from terminals
ment system. 118-119 to motor starter
Is there feedback
on terminals 41-42 No Correct wiring con-
from motor guard? nection
Green light diode
no 1 on print.
Yes
Error mes- No
No
sage in oil
system? No Input Yes
PMS Try again
Yes closed
7 error mes-
Yes sage
received?
shortly Apply jumper, or check connec-
tions from terminal 116-117 to
Check wiring connec- power management system.
tion to oil float. When No
float has been activat-
ed, green light diode
no 9 will flash on print. Relay no
17 is acti- No Check that CONFIG I
vated on PRELUBRICATION = YES
print. Red
light diode.
Yes
Connec- No Correct
tion OK? wiring connect. Check connection from terminals 120-121 to
the pump motor starter.
Yes
Yes
No light/text in display
Is diode on
No Is there light in Yes
CPU print
ACT1 flashing
any diodes on 8
relay card
green
Yes No
Is
voltage No
correct?
9
Contact No Display
Sabroe Ref. Yes
OK?
Check that white code
Yes plug has been fitted.
Problem
solved
= 230 VAC
= 115 VAC
Display reads COPY
EEROM after power =24 VAC
cut
No
Transformer thermally
Is this
activated. May have to
OK
be replaced.
Are terminals
29-32-37 short- Correct error
circuited to
frame?
Are terminals
29-30-33 or 37- Correct error
38 short-
circuited?
Contact
Sabroe Ref.
12. Service
In case some of the main parts of UNISAB II are a. Door in which display and keyboard are fit-
defective, it is possible to replace them. ted.
It is recommended to contact b. Relay print with wiring connections.
Sabroe Refrigeration before changing any of c. CPU print fitted on relay print.
these parts.
d. Transformer.
The main parts comprise:
The parts are shown below in Fig. 12.1.
Fig. 12.1
PAL Battery
U17 EPROM U17 Cooling
plate Trans-
U18 EPROM U18 former
CPU print Fuse
Digital inputs
Empty socket!
NEVER use this
socket together
with sockets pos.
Digital outputs
U17 and U18
Terminals
Mount a new CPU print and door in reverse order Enter the compressor serial no and press the H
as opposed to the dismounting process. key. All three light diodes on the front will flash
When the above has been completed and the shortly, and the display will show the picture CON-
control is switched on, the following picture will ap- FIG.
pear shortly in the display: It is also necessary to enter the original setup, all
COPY EEPROM YES alarm and warning limits as well as set points,
which must be different from the factory setting.
Remember also to calibrate the pressure trans-
Press the H key. UNISAB II will now be reconfig- ducers.
ured and the contents of the EEPROM, corre-
These values are included in the Starting-up Man-
sponding to the compressor setup, will now be
ual. Remember to set time and date. The lan-
copied into the CPU storage.
guage is now English. Select another language if
Important! It is possible to answer NO by means this is required.
of the password. In this case the contents of the
EEPROM and RAM store will be deleted, and
Replacement of relay print
UNISAB II must be reconfigured. See description
under Replacement of CPU print and EEPROM. Dismantle the door completely to provide free ac-
cess to the printed circuit board.
The setting is now the same as before the CPU
print was changed except for the calibration of All connected wires on the relay print must be dis-
the pressure transducers, possibly the brine tem- mounted, but first they must be marked so that
perature as well as the hour counter, which is now correct remounting is possible.
zero. The language is now English. Select anoth- Remove the screws that hold the print and tilt the
er language if this is required. Enter the values print out of the plastic holders at the terminal row
from the table in the Starting-up Manual, which is on the long side of the print.
supplied with the compressor. Remember to set
Pull the print off the guide opposite the terminal
time and date.
row and out of the cabinet.
Move the CPU print with the EPROM and Serial
Replacement of CPU print and
EPROM onto the new relay print.
EEPROM
Mount the new relay print in reverse order as op-
If - as an exception - it proves necessary to insert
posed to the dismounting procedure and connect
a new EEPROM in connection with the replace-
the marked wires in the correct order.
ment of a CPU print, the following procedure must
be observed. When the above has been completed and the
control is switched on, the following picture will ap-
Important!
pear shortly in the display:
See also Replacement of EPROM.
COPY EEPROM YES
Mount the new parts and switch on the control.
The following picture will appears in the display:
SERIAL NO 0 Press the H key. UNISAB II will now be reconfig-
ured and the contents of the EEPROM, corre-
sponding to the compressor setup, will now be When replacing the EPROM or moving it from one
copied into the CPU storage. UNISAB II unit to another, do as follows:
Important! It is possible to answer NO by means • Note the value of the hour counter as well as
of the password. In this case the contents of the the calibration values for pressure transduc-
EEPROM and RAM store will be deleted, and ers and brine temperature.
UNISAB II must be reconfigured. See description • Switch off the power supply to UNISAB II.
under Replacement of CPU print and EEPROM.
• Switch off the compressor motor starter and
The setting is now the same as before the CPU observe all safety measures in accordance
print was changed except for the calibration of with the engineering manual, local rules and
the pressure transducers, possibly the brine tem- regulations.
perature as well as the hour counter, which is now
zero. The language is now English. Select anoth- • Place the door in service position as de-
er language if this is required. Enter the values scribed in Operating UNISAB II
from the table in the Starting-up Manual, which is • The EPROM modules are positioned in the
supplied with the compressor. Remember to set centre of the printed circuit board (see
time and date. Fig. 12.1).
• Each EPROM module is loosened from its
Replacement of EPROM (program) socket by an authorized EPROM puller.
UNISAB II Take care not to damage the pins on the
The EPROMs are programmable modules, EPROM module.
mounted in sockets in the microelectronic part of Fig. 12.2
UNISAB II. Please note that there are two
EPROMs, numbered 0 and 1, identified by white
labels. If replacement is necessary, always re- Notch
place both EPROMs as they belong together.
When the above has been completed and the See section Operating UNISAB II control, Factory
control is switched on, the following picture will ap- settings for information on factory reset.
pear shortly in the display: Once FACTORY RESET has been completed,
COPY EEPROM YES enter all the settings which are included in the ta-
ble UNISAB II settings, and which differ from the
UNISAB II factory values.
Press the H key. UNISAB II will now be reconfig-
ured and the contents of the EEPROM, corre-
sponding to the compressor setup, will now be Replacement of serial EEPROM
copied into the CPU storage. (diagnosis)
The setting is now the same as before EPROM This EEPROM includes information on:
was changed except for timers, which will have e. Compressor serial no.
factory value and the hour counter, which is now
f. Date of initial start-up.
zero. The language is English. Select a different
language if this is required. Enter the values from g. Compressor configuration.
the table in the Starting up manual, which is sup- h. Total number of alarm and warning limits and
plied with the compressor. Remember to set time all other setting values.
and date.
i. Status of up to 30 old alarms.
Important! It is possible to answer NO by means
j. Total number of alarms.
of the password. In this case the contents of the
EEPROM and RAM store will be deleted, and The EEPROM (positioned in a socket) can be re-
UNISAB II must be reconfigured. See description moved from UNISAB II in compliance with the
under Replacement of CPU print and EEPROM. same precautions as described under Replace-
ment of EPROM.
When changing the EPROM in connection with an
upgrade to an updated program version, it is rec- The EEPROM must usually remain in the control
ommended to carry out a FACTORY RESET. as the control cannot function without the EEP-
ROM. However, in case the contents of the EEP-
Before a FACTORY RESET is carried out, write
ROM is to be examined by Sabroe Refrigeration,
down all the UNISAB II settings in the table
Denmark, it can be removed for inspection. When
UNISAB II settings, especially the parameters
removing the EEPROM, switch off the control and
which are changed back to factory setting by a
have an empty EEPROM ready for insertion.
factory reset. This applies to the following param-
eters: Once the new EEPROM has been fitted, switch on
the control again. All information will now be cop-
– Alarm and warning limits, set points,
ied into the new EEPROM.
PID parameters
The control is now ready for operation with the
– Timers, P band factors
same setup as before the EEPROM was re-
– Capacity limits moved.
See the table UNISAB II settings for a complete
review.
UNISAB II/UNISAB II
LED COLOURS
TX DL12 = RED
RX DL13 = GREEN
UNISAB II/PROSAB II
PROSAB II PROSAB II
UNISAB II UNISAB-S/R/RT/RTH UNISAB-S/R/RT/RTH
- TX DL12 S1 S1 S1
COMMUNICATION COMMUNICATION
- RX DL13 MODULE MODULE
S2 S2 S2
63 64 65 66 + - + - + - + -
termination block
LED COLOURS
TX DL12 = RED
RX DL13 = GREEN
The cable is connected in the terminals shown in other controls the resistance is removed and the
Fig. 12.3. The cable must be pulled in parallel terminals are used for passing on the communica-
from control to control. This applies both to the two tion cable.
conductors and the screen. The total length of the cable between the controls
In the first and last control the cable must be fin- must not exceed 1,000 m. Cables of this type are
ished correctly. The resistance of 120 ohm must available from Sabroe Refrigeration.
be fitted as indicated (mounted on delivery). On all
The cable must have the following data:
Impedance: From 135 to 165 Ω at a frequency > 100 kHz
Capacity: Normally < 60 pF per meter
Core: > 0.22 mm2
Type: Twisted pair cable 1x2 or 2x2
Signal attenuation:Max. 9 db over total length of line section/cluster
Shielding: cu shielding braid or shielding braid and shielding foil
Double shielding:Specified as shielding above. The two shields must be isolated from each other with an
isolation voltage of at least 100 VAC.
It is recommended to keep a suitable distance (30 Fig. 12.4
cm) between the communication cables and other
electric cables or motors to prevent electric distur- 1.
bances. Failure to comply with this may cause er-
rors in the running of the multisab sequence. 2.
3.
UNISAB II
4.
UNISAB II
5.
Grounding
UNISAB II must always be grounded to the com- cause a large current surge through the cable
pressor frame. See drawing no. 3448-235/236 screen. The screen may melt, causing the voltage
page 25. equalisation to be broken and the communication
In case of a shut down, there can be large electri- to be hampered by noise.
cal potential on the compressor motor and thereby To avoid this situation, it is strongly recommended
on UNISAB II. to provide an extra equalising wire in parallel with
The data communication cable screen provides a the communication cable between all the units on
voltage equalisation between the UNISAB II units. the network, as indicated in the drawing no.
The above mentioned electrical potential may 3448-235/236 page 25.
1 2 3 14
The MULTISAB system is based on some basic the optimization of the compressors, it may be
rules: necessary to regulate the compressors externally.
1. The system is controlled and optimized ac- The plant itself may also make special demands
cording to suction pressure, brine tempera- as to regulating speed and accuracy, which
ture, discharge pressure or external 4-20 makes a central external regulation necessary.
mA signal, depending on the chosen type of Such an alternative regulation can be carried out
regulation. in several ways:
2. The programmed starting sequence is al- • controlling the digital input External start
ways followed. permission, normal stop
3. Screw compressors in operation are run to • using the digital output Auxiliary output
as high a capacity as possible. • using the 4-20 mA input Auxiliary input
4. It is acceptable that reciprocating compres- • changing capacity set points from PC/PLC
sors operate at part load. via COMSAB II/PCCOMSAB II.
MULTISAB is a regulating system for general ap-
plication. Should special demands be made as to
Fig. 13.2
PC/PLC
possible modem
COMSAB II/PCCOMSAB II
1 2 3 14
In case compressor capacity is controlled through See section Installation of data communication
COMSAB II or PCCOMSAB II from a central com- cable as well as Connecting diagrams to
puter, be aware of the time delay through the com- find information on the physical linking of
munication system. UNISAB II units.
It is possible to make an approximate calculation B: All units must be configured for intercommu-
of this time delay. See COMSAB II instruction no nication. See also section Configuration.
0171-400. In SETUP I CONFIG a compressor number,
If UNISAB II is to be connected to controls of the COMPR. NO, beginning with no 1 and up-
UNISAB S/R or PROSAB II type, see the following wards, corresponding to the number of com-
instructions if the control units are part of the plant pressors must be entered in each unit.
in question: It is recommended to mark the compressors with
1) 0171-761 / UNISAB S-Control this number.
2) 0171-772 / UNISAB R-Control Important!
3) 0178-175 / UNISAB RT-Control If two compressors have the same com-
pressor number entered in UNISAB II, there
4) 0178-181 / UNISAB RTH-Control will be no communication between the units.
5) 0171-729 / PROSAB II In SETUP I CONFIG the communication speed,
6) 0171-743 / the MULTISAB system for BAUD RATE, must be entered. In case the
PROSAB/UNISAB II system only consists of UNISAB II units,
usually choose the highest baud rate. In
System setup case the system consists of both UNISAB II
and PROSAB II or UNISAB II units, choose
To be able to use MULTISAB, a number of points
1200 baud. Note that it must be checked
must be completed. Please find the checklist for
that all units on the network are able to run
MULTISAB setup (see the following pages). The
at the selected rate.
points on the checklist can be explained as fol-
lows: C: All units, especially screw compressors,
must have a swept volume value entered.
A: All units that are to be included in the system
must be connected physically.
In SETUP I CONFIG enter SWEPT VOLUME, er or disconnected from the network, the
which can be read on the compressor name UNISAB II unit with the next START.NO will
plate. See section Configuration. be SYS. REGULATOR.
D: An entry must be made in all units whether The SYS.REGULATOR is master of the co-ordi-
the system contains a common evaporator nated capacity control, which also means
and a common condenser. that the controlled input sensor (point H be-
In SETUP I CONFIG enter the current combina- low) on this particular UNISAB II unit in use.
tion of common evaporator and common If only one compressor is required, it will
condenser in COMMON EVAP/COND. See usually be the compressor of the SYS.REG-
section Configuration. ULATOR which is in operation. However, if
COMPR# is selected, it may very well be
E: All units must be have a system no and a another compressor.
starting no.
Guidelines for selecting COMPR# or START#:
In SETUP I MULTISAB I MULTISAB STATE
enter START NO and a SYSTEM NO. See • COMPR# is easier and more safe if the con-
section MULTISAB. trolled input is not available to all UNISAB II
units.
F: All units in the same system must agree on
the way a regulating master (sys. regulator) • COMPR# must be selected if there are any
is chosen. PROSAB II or UNISAB I units on the sys-
tem.
In SETUP I CONFIG select the same PREF.
MASTER in all UNISAB II units, COMPR# • START# is easier and more safe if equaliz-
or START#. See section Configuration. ing running hours is important, especially if
all (or all but one) compressors must always
If selecting COMPR#, the UNISAB II with the low- be available.
est COMPR. NO (point B above) will always
be SYS.REGULATOR. The only exceptions • Always make sure that COMPR.NO is a
are if the UNISAB II is off power or discon- fixed value, ie never change it to equalize
nected from the network. In such case, the running hours! However, START.NO is
UNISAB II with the next COMPR.NO will be meant to be changed from time to time.
SYS.REGULATOR. Note that a defective G: All units must be adjusted to remote control.
controlled input sensor does not lead to an In SETUP I CONTROL COMPRESSOR.CTRL
automatic change of SYS.REGULATOR in MODE is on REMOTE. See section Com-
this case. pressor regulation.
If selecting START#, the UNISAB II with the low-
est START.NO (point F above) will be Regulation Setup
SYS.REGULATOR for as long as the com-
H: All units must be configured to the desired
pressor belonging to this UNISAB II unit is
regulating method.
running and ready. If the compressor is not
available, UNISAB II is not in REMOTE In SETUP I CONFIG adjust CONTROL ON to
mode, the controlled input sensor (point H the desired regulating method. See section
below) is defective, or UNISAB II is off pow- Configuration.
The following four regulators are available. The 2) Regulator neutral zone, NZ
last two have both a cooling and a warming 3) Regulator proportional band, PB
function:
See section Compressor regulation.
– Suction side
(regulation of suction pressure) Regulation of the entire system will usually take
place on the basis of the regulator in the cur-
– Discharge side rent regulating master (sys. regulator), ie
(regulation of discharge pressure) the compressor with the lowest compressor
– Brine / hot water or starting number.
(regulation of brine/water temperatures) Therefore it is particularly important that the pa-
– Ext. cooling / Ext. heating rameters of the configured regulator has
(regulation of a user defined measuring been set correctly.
value: temp./pressure/level). Always set the same set point on all other units in
– Note that all units that can become mas- the same system (ie with the same SYS-
ter must measure the same value to be TEM NO).
used for the capacity control. If eg Brine K: All units must have their timers adjusted.
/ Hotwater temperature control is select-
ed, a separate temperature sensor must In SETUP I TIMERS I TIMER SETUP the fol-
be available to all the relevant UNISAB II lowing timers are set:
units. Note that point F above describes 1) START DELAY, time delay before start.
how to select the master. 2) STOP DELAY, time delay before stop.
I: All units must (usually) be configured to both See section Timers, Timer setup.
automatic start and automatic stop. If this is
Both timers can be made to work proportionally (ie
not the case, the compressor will not start
depending on the size of Pb).
up automatically in case cooling is required
or stop automatically when cooling is not re- In SETUP I TIMERS I P BAND
quired and the temperature becomes too FACTOR a proportional factor can be set for
low. each of the timers.
In SETUP I CONFIG, choose: This means that if only a small difference exists
between the desired temperature (Sp) and
AUTO START= YES
the current one, the timer in the time delays
AUTO STOP= YES will count very slowly (up to
See section Configuration. 10 times slower than the time set, depend-
J: The chosen regulator must be set in all ing on the factor set).
units. If the difference between the desired temperature
In the picture for the parameter to be regulated, and the current one is considerable (outside
set the following: the P Band), the timer in the time delay will
count in seconds.
1) Regulator set point, SP1 and possibly SP2
See section Timers, P Band factor.
In case of reciprocating compressors, another two Transfer and the Take-over situations are
timers must be set. included.
3) DELAY UP, time delay during loading of As described below, several parameters are
stages. available to adjust the Transfer and the
4) DELAY DOWN, time delay during unloading Take-over function.
of stages. In SETUP ITIMERS I TRANSFER a pro-
Both of these timers can also be made to work portional factor FACTOR DOWN (1-10, de-
proportionally (ie depending on the size of fault 1) can be set for timer DELAY DOWN.
Pb). It is used when MULTISAB wants to let a re-
ciprocating compressor decrease its capac-
In SETUP I TIMERS I P BAND FACTOR a pro- ity in favour of a screw compressor at low
portional factor can be set for each of the capacity. A larger FACTOR DOWN makes
timers. MULTISAB wait longer before reducing the
L: In plants with a combination of screw and reciprocating compressor capacity another
reciprocating compressors a number of fac- stage.
tors may be set to optimize compressor op- In SETUP I TIMERS I TRANSFER the
eration so that the two types of compressors size of a transfer zone ZONE can be set, ie
are used in the best way possible. These the part of the proportional band (0-100%,
factors can only be set on reciprocating default 15%) where transfer may take place.
compressors and will be effective only in
case all reciprocating compressors have In SETUP I TIMERS I TAKE-OVER a
lower starting numbers than the screw com- proportional factor FACTOR UP (1-10, de-
pressors in the same system, and only if fault 1) can be set for timer DELAY UP. It is
TAKE OVER is set to YES in SETUP I used when MULTISAB wants to increase
CONFIG, See section Configuration. the capacity of the reciprocating compres-
sor to force the screw compressor down be-
The optimization is carried out by the Trans- low 5% capacity, making it stop. A larger
fer function and the Take-over function. FACTOR UP makes MULTISAB wait longer
It is not economical to run a screw compres- before increasing the reciprocating com-
sor at low capacity. The Transfer function pressor capacity another stage.
attempts to avoid this by reducing the ca-
pacity of the reciprocating compressor(s), ie In SETUP I TIMERS I TAKE-OVER a
by transferring load to the screw compres- proportional factor FACTOR START (1-10,
sor. The Take-over function increases the default 1) can be set for the START DELAY
capacity of the reciprocating compressor(s) timer. It is used when MULTISAB wants to
to make the screw compressor stop, ie by start a reciprocating compressor to take
taking over load from the screw compres- over the operation from a screw compressor
sor. which is running at low capacity.
default 15%) where take-over may take tivated once TAKE-OVER DELAY
place. expires.
In SETUP I TIMERS I TIMER SETUP the 2) TAKE-OVER MAX, max duration of a
following timers are found. take-over attempt. When TAKE-OVER DE-
1) TAKE-OVER DELAY, time delay at LAY expires, the time delay TAKE-OVER
take-over, fixed at 300 seconds. When a re- MAX will also be activated to ensure that a
ciprocating compressor has calculated that reciprocating compressor will not use more
it is possible to take over a subsequent than the TAKE-OVER MAX time during a
screw compressor, it will pass into a take-over attempt. If the screw compressor
take-over mode and start TAKE-OVER DE- has not stopped before the TAKE-OVER
LAY. If the reciprocating compressor during MAX expires, the reciprocating compressor
the entire count down of take-over delay can will give up and stop. This delay function
continue to take over, thus staying in the can be cancelled by setting the delay for 0
take-over mode, START DELAY will be ac- (default).
14. Checklist
Compressor No.
Checklist for MULTISAB setup
No. Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
A Cabling All co-operating UNISAB
units must be wired to-
gether on common net-
work.
B.1 CONFIG→ Unique ID for each com-
COMPR NO pressor on network
B.2 CONFIG → Identical for all units on
BAUD RATE network
C CONFIG → Must be entered correctly
SWEPT for each compressor, at
VOLUME least for screws
D CONFIG→ Identical for all compres-
COMMON sors within system
EVAP/COND
E.1 MULTISAB Unique priority within sys-
STATE → tem (SYSTEM NO)
START NO
E.2 MULTISAB System ID, identical for all
STATE → compressors on same
SYSTEM NO controlled input
CONFIG → Identical for all compres-
REFRIGERANT sors within system
F CONFIG → Identical for all compres-
PREF. MASTER sors within system
G CONTROL → Must be REMOTE unless
COMPR. the compressor is exclud-
CONTROL ed (temporarily) from
MULTISAB
H.1 CONFIG → Identical for all compres-
CONTROL ON sors within system - see
also item C
H.2 Controlled input The measurement must
sensor be available to all com-
pressors in the system
which can become mas-
ter
I.1 CONFIG → Should usually be YES. If
AUTO START not, the compressor must
be started manually
I.2 CONFIG → Should usually be YES. If
AUTO STOP not, the compressor must
be stopped manually
Compressor No.
Checklist for MULTISAB setup
No. Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
J.1 Set point Identical for all compres-
sors within system
J.2 Neutral zone Matching values for all
and compressors within sys-
tem
P Band
K.1 TIMER SETUP Matching values for all
→ START DE- compressors within sys-
LAY tem
K.1a P BAND FAC- Matching values for all
TOR → compressors within sys-
START DELAY tem
K.2 TIMER SETUP Matching values for all
→ STOP DE- compressors within sys-
LAY tem
K.2a P BAND FAC- Matching values for all
TOR → compressors within sys-
STOP DELAY tem
K.3 TIMER SETUP Matching values for all re-
→ DELAY UP ciprocating compressors
within system
K.3a P BAND FAC- Matching values for all re-
TOR → ciprocating compressors
DELAY UP within system
K.4 TIMER SETUP Matching values for all re-
→ DELAY ciprocating compressors
DOWN within system
K.4a P BAND FAC- Matching values for all re-
TOR → ciprocating compressors
DELAY DOWN within system
L.1 CONFIG → Only recipr. compr. Set
TAKE OVER for YES if compr. is to
take over from screw
L.2 TIMER SETUP Matching values for all re-
→ TK OVER ciprocating compressors
MAX within system (TK = Take)
L.3 TRANSFER → Matching values for all re-
FACTOR ciprocating compressors
DOWN within system
L.4 TRANSFER → Matching values for all re-
ZONE ciprocating compressors
within system
L.5 TAKE-OVER → Matching values for all re-
FACTOR UP ciprocating compressors
within system
Compressor No.
Checklist for MULTISAB setup
No. Item Description 1 2 3 4 5 6 7 8 9 10 11 12 13 14
L.6 TAKE-OVER → Matching values for all re-
FACTOR ciprocating compressors
START within system
L.7 TAKE-OVER → Matching values for all re-
ZONE ciprocating compressors
within system
System no 1 1 1 1 1
Starting no 1 2 3 4 5
Compressor no K1 K2 K3 K4 K5
Example B - plants with one temperature system and five compressors where pref. master = COMPR#.
System no 1 1 1 1 1
Starting no 5 4 3 2 1
Compressor no K1 K2 K3 K4 K5
In examples A and B, K1 will be the regulator (system regulator) of the entire system.
Example C - plants with two temperature systems and five compressors (eg two-stage plants) where
pref. master = COMPR#.
System no 1 1 2 2 2
Starting no 2 1 3 1 2
Compressor no K1 K2 K3 K4 K5
In example C, K1 will be system regulator of system no 1, and K3 will be system regulator of system no 2.
SETUP I MULTISAB I MULTISAB STATE A compressor will not be part of the MULTISAB
shows which unit has been chosen as SYS. REG- system if it is in either MANUAL, AUTO,
ULATOR. STOPPED or SHUTDOWN, or if the digital inputs
In case of two regulating systems or more, it is the EXTERNAL START-NORMAL STOP and EX-
compressor with the lowest number in the individ- TERNAL START-IMMEDIATE STOP have not
ual system that works as system regulator. been connected.
The regulating compressor (SYS. REGULATOR) Moreover, the compressor will not be part of the
will regulate the other compressors in the system MULTISAB system if it is in REMOTE/capacity re-
even if the compressor is in MANUAL, AUTO, mote control with either a 4-20 mA external signal
STOPPED or SHUTDOWN. or communication signal.
Only if the voltage supply or the communication is The way the system operates can be varied de-
disconnected, the system will automatically select pending on whether a reciprocating or a screw
a new system regulator, which will be the unit with compressor comes first in the sequence. Like-
the second lowest number. wise, the way the system operates can be varied
with screw compressors of different sizes, de-
pending on whether a small or large compressor In case of mixed systems, it is recommended that
comes first. all reciprocating compressors in a system is
If compressors of different sizes are mixed, unfor- placed one after the other, followed by the screw
tunate part load conditions may occur, depending compressors, or vice versa. The take-over and
on the sequence. transfer functions will only be effective in case all
of the reciprocating compressors have lower start-
Be aware that if a screw compressor has the low- ing numbers than the screw compressors in the
est starting number, it may go down on low capac- same system.
ity even at small loads.
System no 1 1 1 1 1
Starting no 1 2 3 4 5
Compressor no K1 K2 K3 K4 K5
In example A, K1 will be the regulator (system regulator) of the entire system, but only if it is operating or
able to start.
If K1 is stopped because of an alarm or if one of the digital inputs EXTERNAL START - NORMAL STOP
or EXTERNAL START- IMMEDIATE STOP is disconnected - and a cooling requirement still exists, the
next compressor in the starting sequence will be the regulator of the entire system provided that it is op-
erating or able to start - and that it does start. In the above example K2 will become the regulator.
Example B - plant with one temperature system and five compressors where pref. master = START#.
System no 1 1 1 1 1
Starting no 5 4 3 2 1
Compressor no K1 K2 K3 K4 K5
In example B, K5 will be the regulator (system regulator) of the entire system, but only if it is operating or
able to start.
If K5 is stopped - and a cooling requirement still exists, the next compressor in the starting sequence will
become the regulator of the entire system provided that it is operating or able to start - and that it does
start. In the above example K4 will become the regulator.
Example C - plant with two temperature systems and five compressors (eg two-stage plants)
System no 1 1 2 2 2
Start no 2 1 3 1 2
Compressor no K1 K2 K3 K4 K5
In example C, K2 will be the system regulator of system no 1, and K4 will be the system regulator of sys-
tem no 2 provided that K2 and K4 are operating or able to start.
SETUP I MULTISAB I MULTISAB STATE with screw compressors of different sizes, de-
shows which unit has been chosen as SYS. REG- pending on whether a small or large compressor
ULATOR. comes first.
In case of two regulating systems or more, it is the If compressors of different sizes are mixed, unfor-
compressor with the lowest number in the individ- tunate part load conditions may occur, depending
ual system that works as system regulator. on the sequence.
The regulating compressor (SYS. REGULATOR) Be aware that if a screw compressor has the low-
will regulate the other compressors in the system, est starting number, it may go down on low capac-
but only if the compressor is in REMOTE/MULTI- ity even at small loads.
SAB and at the same time operating or ready to In case of mixed systems it is recommended that
start. all reciprocating compressors in a system be
A compressor will not be part of the MULTISAB placed one after the other, followed by the screw
system if it is in either MANUAL, AUTO, compressors, or vice versa. The take-over and
STOPPED or SHUTDOWN, or if the digital inputs transfer functions will only be effective in case all
EXTERNAL START-NORMAL STOP and EX- of the reciprocating compressors have lower start-
TERNAL START-IMMEDIATE STOP have not ing numbers than the screw compressors in the
been connected. same system.
Moreover, the compressor will not be part of the Note:
MULTISAB system if it is in REMOTE/capacity re- The described example of possible configuration
mote control with either a 4-20 mA external signal where the pref.master = START# can only be
or communication signal. used for plants (systems) which are fitted solely
The way the system operates can be varied de- with UNISAB II units. The function cannot be used
pending on whether a reciprocating or a screw together with a PROSAB II, UNISAB S or UNISAB
compressor is comes first in the sequence. Like- R / RT/ RTH. In such cases set pref.master =
wise, the way the system operates can be varied COMPR# on UNISAB II.
Compressor K1. SAB163 Mk2 K2. SAB163 Mk2 K3. SAB202S K4. SAB202S
System no 1 1 1 1
Starting no 1 2 3 4
Should the temperature rise excessively before When the above has taken place, screw compres-
start of the next compressor, START DELAY must sor K1 {Lead compr.} will run slowly down from
be reduced. 100% while K2 will increase its capacity {Lag com-
In case of too frequent compressor starts/stops, pr.}. When the compressors meet, ie when their
START DELAY must be increased. slide position is the same, they will continue to
regulate in parallel (see Fig. 15.1).
STOP DELAY determines the time the compres-
sor runs at minimum capacity before stop. If quick How much screw compressor K1 decreases in ca-
stop is required, reduce STOP DELAY. If the com- pacity and how fast in order to meet K2 depends
pressor is to run for a longer period, increase completely on the strength of the "UP" regulating
STOP DELAY. signal.
The above is a general description of the various With screw compressors K1 and K2 at 100% and
setting potentials. The final settings will depend with a persistent cooling requirement, START DE-
completely on the plant in question. LAY will be started on screw compressor K3. After
a countdown to zero, K3 will start up. K1 will be
kept at 100% {Runs at max. capacity} and K2 and
Loading sequence K3 will regulate in parallel.
Compressor K1 is assumed to be in operation at
With a persistent cooling requirement and with K1,
eg 70 % {Runs by itself}, K2 {Not my turn}, K3 and
K2 and K3 at 100%, START DELAY will be started
K4 {Not my turn} are stopped.
on screw compressor K4. The timer will count
The MULTISAB status, shown in picture SETUP down to zero, and K4 will start up. K1 and K2 will
I MULTISAB I MULTISAB STATE, is marked be kept at 100% {Runs at max. capacity} and K3
with {--}. and K4 will regulate in parallel.
At increasing cooling requirements and conse- However, the actual capacity requirement must
quent capacity loading, compressor K1 will in- be considered. If there are four reciprocating and
crease capacity until 100% capacity is reached. two screw compressors in the plant, two of the re-
The loading speed depends on how far the imme- ciprocating compressors can be moved to the oth-
diate temperature is above the set point that has er side of the screw compressors during low load
been entered into the regulator. operation. This prevents a screw compressor
from running at too low load in the border area of
If a cooling requirement still exists, ie the immedi-
the take over/transfer function. When load in-
ate temperature is above the set point and the ca-
creases again the reciprocating compressors are
pacity of K1 is above 95%, the time delay (START
moved back in front of the screw compressors as
DELAY) will start up in UNISAB II on compressor
needed. The aim is to keep a constant need for
K2. The timer will count down from its set point to
the capacity of one or more screw compressors
zero, and compressor K2 will start. (Should the
and x number of reciprocating compressors.
temperature reach the set point, ie be within Nz
before START DELAY expires, K2 will not start).
Fig. 15.1
% Lead
100
Lead=lag
75
Increasing capacity 50
Lag
25
Start
5
0 5 10 15 20 25 min.
%
100
Lead
75
Decreasing capacity 50
Lag
25
Stop
5
0 5 10 15 20 25 min.
When two screw compressors regulate in parallel, At decreasing cooling requirement and a conse-
it means that they follow each other up and down quent capacity unloading, compressors K2 and
in capacity and that both units will try to keep the K3 will decrease their capacity until both are be-
same capacity +/- approx. 2%. low the value called parallel capacity. The parallel
If the two compressors that regulate in parallel capacity is automatically calculated by MULTI-
have equal capacities, the capacity change at any SAB. It depends on the size and types of the in-
given relocation of the capacity slide will be dou- volved compressors and the operating conditions.
bled compared to the regulation of a single com- The parallel capacity is the limit at which K2 is
pressor. able to take over for certain. If the two compres-
sors are of equal size, the parallel capacity will
MULTISAB compensates for this by reducing (by usually be about 55%.
half) the up and down regulating speed.
The percentage of PARALLEL CAPACITY can be
read in SETUP I MULTISAB I PARALLEL
Unloading sequence CONTROL.
Three of the four plant compressors are assumed
K3 will now ramp down towards 0% {Stop Ramp
to be in operation, K1 at 100% {Runs at max ca-
Down} with a speed of approx. 12%/min. When K3
pacity}, K2 {Lead compr.} and K3 {Lag compr.}
is below 5% {May stop} the STOP DELAY timer
both in parallel operation at eg 90%.
will start up. When STOP DELAY expires, K3 will
stop {Blocked}. K2 will, until K3 stops, ensure reg-
ulation all alone {Stop Ramp Up}, as K1 remains When K1 and K3 are above 95% the time delay
at 100% {Runs at max capacity}. (START DELAY) will start in UNISAB II
Screw compressor K1 {Lead compr.} and K2 {Lag on compressor K4. The timer will count down from
compr.} will join each other in parallel operation. its set point to zero, and compressor K4 will start
up.
If a cooling requirements still does not exist, K1
and K2 will decrease their capacity until both are K4 will regulate upwards and the plant will have
below parallel capacity. K2 will ramp down and the following operating mode: K1 at 100 % {Runs
stop as soon as the STOP DELAY timer expires. at max capacity}, K3 {Lead compr.} and K4 {Lag
compr.} both in parallel operation at approx. 65%
K1 will now ensure regulation all alone {Runs by (the parallel operation percentage is lower now
itself}. than during the output state as K4 is larger than
K2).
Operating sequence The alarm on K2 is confirmed (after the oil filter
Three of the four plant compressors are assumed has been replaced), and although K2 enters the
to be in operation, K1 at 100% {Runs at max. ca- READY status {Not my turn}, it will not start until a
pacity}, K2 {Lead compr.} and K3 {Lag compr.} requirement exists, as MULTISAB does not stop
both in parallel operation at eg 80%. K4 to make K2 resume its position in the se-
The cooling requirement is constant. quence.
System no 1 1 1 1
Starting no 1 2 3 4
The following settings have been made in all units: STOP and EXTERNAL START - IMMEDIATE
The digital inputs EXTERNAL START - NORMAL STOP have been connected.
50
25
Time
Capacity for
1 compressor
%
Decreasing requirement for capacity
Compressors 1+2
100
Compressor 2 Compressors 1
75
50
25
0
Time
At increasing cooling requirement and conse- If a cooling requirement still exists, ie the immedi-
quent capacity loading, reciprocating compressor ate suction pressure is higher that the set point,
K1 will load stages at the DELAY UP time lag until the timer START DELAY is started on compressor
100% capacity has been reached. K2. The timer will count down from its set point to
It is possible to make the loading speed depend zero, and K2 will start. (In case the suction pres-
on how far the actual suction pressure is above sure reaches the neutral zone before START DE-
the set point by setting the proportional factor DE- LAY expires, K2 will not start).
LAY UP above 1 in the picture SETUP I TIMERS With compressor K2 at 100% and still capacity re-
I P BAND FACTOR. See section Regulating set- quirement, the timer START DELAY starts on
up.
compressor K3. It will count down before K3 starts K3 will now decrease its capacity to minimum, and
up. after K2 has unloaded one stage, K3 will stop on
When K3 is at 100% and a cooling requirement the timer STOP DELAY.
still exists, the timer START DELAY will start on Reciprocating compressor K2 will now start un-
K4. When timer has expired, K4 will start. loading stages with time delay DELAY DOWN,
until it reaches minimum capacity, ie 25%. One
Unloading sequence stage will be unloaded on compressor K1, and the
timer STOP DELAY will start on K2.
In an operating situation where the entire plant
runs at 100% and with a decreasing cooling re- The system will continue its unloading in stages
quirement, unloading will start on compressor K4 until K1 is stopped.
first. It is also possible that the plant stabilizes at part
K4 will decrease its capacity by unloading stages load, and if the cooling requirement increases, the
with the time delay DELAY DOWN between each situation will be the same as described under
change of stage until it reaches minimum capaci- Loading sequence.
ty, ie 33% (SMC 106S). One stage will now be un- Example of regulation - combination of screw
loaded on compressor K3, which will run at 67%, and reciprocating compressors
and the timer STOP DELAY will start on K4, (dur- The working of MULTISAB will be described on
ing unloading the reciprocating compressors will the basis of the below examples A and B and with
overlap, Fig. 15.2). the indicated compressors.
When time delay STOP DELAY expires on K4, K4
will stop.
A:
Compressor K1. Recip. K2. Recip. K3. Screw K4. Screw K5. Screw
System no 1 1 1 1 1
Starting no 1 2 3 4 5
B:
Compressor K1. Screw K2. Screw K3. Screw K4. Recip. K5. Recip.
System no 1 1 1 1 1
Starting no 1 2 3 4 5
The following settings have been made in all units: STOP and EXTERNAL START - IMMEDIATE
The digital inputs EXTERNAL START - NORMAL STOP have been connected.
In many cases it is advantageous if DELAY UP is With compressor K2 at 100% and a persistent ca-
higher than DELAY DOWN. pacity requirement, the timer START DELAY will
It is recommended to place all reciprocating com- start on K3. The timer will count down before K3
pressors in a system one after the other followed starts up.
by the screw compressors, or vice versa. When K3 is at 100% and a cooling requirement
The take-over and transfer functions described in still exists, the timer START DELAY will start on
the following will only be effective if all reciprocat- K4. When the timer has expired, K4 will start.
ing compressors have lower starting numbers When the above has taken place, screw compres-
than the screw compressors. sor K3 will go down from 100% while K4 will in-
The above is a general description of the various crease its capacity. When they meet, ie when their
settings. The final settings will depend completely slide positions are the same, they will continue to
on the plant in question. regulate in parallel (see Fig. 15.1).
Whether screw compressor K3 decreases its ca-
Loading sequence - sequence A
pacity and how fast to meet K4 depends com-
Compressor K1 is assumed to be in operation at
pletely on the strength of the "UP" regulating sig-
eg 50 % {Runs by itself}, K2 {Not my turn}, K3, K4
nal.
and K5 {Not my turn} have been stopped.
With screw compressors K3 and K4 at 100% and
The MULTISAB status, as shown in picture SET-
with a persistent cooling requirement, START DE-
UP I MULTISAB I MULTISAB STATE, is
LAY will be started on screw compressor K5. After
marked with {--}.
a countdown to zero, K5 will start up. K3 will now
At increasing cooling requirement and conse- be kept at 100% {Runs at max capacity}, and K4
quent capacity loading, reciprocating compressor {Lead compr.} and K5 {Lag compr.} will regulate in
K1 will load stages at the DELAY UP time lag until parallel.
100% capacity has been reached.
It is possible to make the loading speed depend State of transfer
on how far the actual suction pressure is above
In case of a minor cooling requirement, it is as-
the set point by setting the proportional factor DE-
sumed that the plant stabilizes in the following sit-
LAY UP above 1 in the picture SETUP I TIMERS
uation: reciprocating compressors K1 and K2 both
I P BAND FACTOR. See section Regulating set-
at 100% and screw compressor K3 in 40% slide
up.
position.
If a cooling requirement still exists, ie the actual
Reciprocating compressor K2 will now pass into
suction pressure is higher than the set point, the
the "transfer" state, ie it will start decreasing its ca-
timer START DELAY will start on compressor K2.
pacity to force the screw compressor capacity up-
The timer will count down from its set point to ze-
wards.
ro, and reciprocating compressor K2 will start. (In
case the suction pressure reaches the neutral However, this will only take place if the actual suc-
zone before START DELAY expires, K2 will not tion pressure is within the 'transfer zone', consist-
start). ing of the neutral zone (zone 1) plus the transfer
zone (zone 3), which is default 15% of the regula-
tor proportional band, (see Fig. 15.3).
When the reciprocating compressor unloads an- Provided that requirements stay the same, this
other stage, this will happen with a time delay that process will continue until the screw compressor
(in sec) is the setting of DELAY DOWN multiplied is above 85% slide position. Above this fixed limit
by the 'transfer factor' for DELAY DOWN. This it is assumed that the screw compressor is run-
factor, 1-10, has been entered to avoid hunting in ning fairly economically. Further reduction of the
the plant as far as possible as the regulating sys- reciprocating compressor capacity would result in
tem must have time to react to the rise in the suc- a high risk that the screw compressor is no longer
tion pressure when the reciprocating compressor able to take over, causing frequent loading and
is unloading. unloading of stages or start and stop of the recip-
If the suction pressure rises (zone 2), the recipro- rocating compressor.
cating compressor will stop the down regulation The result may be that the reciprocating compres-
while the screw compressor regulates upwards to sor K1 runs at 100%, K2 at 25% and screw com-
get the suction pressure in place. pressor K3 at 85%.
Once the plant has balanced, the reciprocating If the cooling requirement increases, screw com-
compressor will continue the unloading of stages pressor K3 will be loaded at 100%, whereupon re-
and the screw compressor will readjust. ciprocating compressor K2 will be loaded.
Fig. 15.3
6. outside PB
4. 85% PB
2. 15% PB
1. NZ Takeover zone = 1+2
SP
Transfer zone = 1+3
3. 15% PB
5. 85% PB
7. outside PB
ing time DELAY UP multiplied by the 'take-over' are of equal size, the parallel capacity will usually
factor for DELAY UP. This factor, 1-10, has been be approx. 55%.
entered to avoid hunting. The percentage of PARALLEL CAPACITY can be
When reciprocating compressor K2 is loading read in SETUP I MULTISAB I PARALLEL
stages, the suction pressure will drop, but this is CONTROL.
compensated for by unloading on screw compres- K5 will now ramp down towards 0% {Stop Ramp
sor K3, until it reaches minimum and stops on Down} with a speed of approx. 12% /min. When
STOP DELAY. K5 is below 5% {May stop}, the timer STOP DE-
Be aware that during reloading periods it may LAY will start. When STOP DELAY expires, K5
happen that a screw compressor is running at low will stop {Blocked}. K4 will, until K5 stops, ensure
capacity. Furthermore, reloading will take a cer- regulation all alone {Stop Ramp Up} as K1, K2
tain amount of time, which prevents instability in and K3 remain at 100% {Runs at max capacity}.
the plant. Next, the screw compressors K3 {Lead compr.}
In plants with frequent load changes, it may take and K4 {Lag compr.} will work together until K4
longer before the reciprocating compressors take stops.
over/transfer capacity. K3 will now decrease its capacity to a minimum
If the plant is very unstable, the variations may be and stops on its time, STOP DELAY.
absorbed exclusively by the screw compressor. When this has happened reciprocating compres-
Consequently, the screw compressor will in some sor K2 will start unloading stages with the time de-
periods run at low capacity. This can be avoided lay DELAY DOWN until it is down to minimum ca-
by removing the starting permission from either pacity. Next, a stage is unloaded on compressor
the screw compressor or the reciprocating com- K1, and the STOP DELAY time will start on K2 (ie
pressor. during unloading the reciprocating compressors
Reciprocating compressors will only try to take will overlap, (see Fig. 15.2).
over/transfer capacity from/to screw compressors The system will continue unloading in stages until
that come later in the sequence. K1 stops.
Unloading sequence - sequence A The plant may also stabilize at part load, and in
In an operating situation where the entire plant case the cooling requirement is increasing, the sit-
runs at 100% and with a decreasing cooling re- uation will be the same as described under Load-
quirement, unloading will start on the screw com- ing sequence - sequence A.
pressors.
Loading sequence - sequence B
As illustrated in Fig. 15.1, K4 and K5 will reduce Compressor K1 is assumed to have stopped {May
their capacity in parallel until both are below the start}, K2, K3, K4 and K5 {Not my turn} are
value called the parallel capacity. The parallel ca- stopped.
pacity is automatically calculated by MULTISAB.
It depends on the size and types of the involved The MULTISAB status, as shown in picture SET-
compressors and the operating conditions. The UP I MULTISAB I MULTISAB STATE, is
parallel capacity is the limit at which it is certain marked with {--}.
that K4 is able to take over. If the two compressors
In case of a cooling requirement, K1 will start. Be aware that with the above sequence screw
When it has reached 100% capacity, START DE- compressor K1 may start and stabilize at eg 35%
LAY will start on screw compressor K2. The timer capacity corresponding to the actual cooling re-
will count down, and K2 will start up. When this quirement. In this situation a subsequent recipro-
has happened, screw compressor K1 will go down cating compressor will not try to take over be-
from 100%, while the capacity of K2 will go up. cause it comes later in the sequence.
When the compressors meet, ie when their slide
positions are the same, they will regulate in paral- Unloading sequence - sequence B
lel.
With the entire plant running at 100% and a de-
When K1 and K2 are in 100%, the time delay creasing cooling requirement, reciprocating com-
START DELAY will start on screw compressor K3. pressor K5 {Lag compr.} will be the first to unload
When the timer has expired, K3 will start up and stages with time delay DELAY DOWN until it has
K1 will be kept at 100%. reached minimum capacity. Next, one stage is un-
When this has happened, screw compressor K2 loaded on compressor K4, and STOP DELAY will
will go down from 100%, while the capacity of K3 now start on K5 (ie during unloading the recipro-
will go up. When the compressors meet, ie when cating compressors will overlap, (see Fig. 15.2)).
their slide positions are the same, they will regu- When STOP DELAY has expired, compressor K5
late in parallel. will stop, and K4 will now continue the unloading.
Whether K2 reduces its capacity and at which When K4 has unloaded to minimum capacity, it
speed to meet K3 depends completely on the will start up its STOP DELAY time and when this
strength of the "UP" regulating signal. has expired, K4 will stop.
With K2 and K3 at 100% and a persistent cooling Screw compressors K2 and K3 are now going to
requirement, ie the actual suction pressure is decrease their capacity in parallel operation, until
higher than the set point, the time delay START they are below the parallel capacity (usually 55%
DELAY will start on reciprocating compressor K4. if they are of equal size). K3 will be run down to
The timer will count down to zero and reciprocat- minimum capacity and stops on its STOP DELAY
ing compressor K4 will start up. Should the actual time. At the same time K2 will take over.
suction pressure reach the neutral zone before Screw compressors K1 and K2 will adjust in par-
START DELAY expires, K4 will not start. allel to the same slide position and start decreas-
K4 will now load and unload stages according to ing their capacity in parallel operation until they
the cooling requirements, while the screw com- are below the parallel capacity. K2 will be run
pressors K1, K2, K3 are kept at 100% capacity down to minimum capacity and stop on its STOP
{Runs at max capacity}. DELAY time. At the same time K1 will take over.
This will continue until all the compressors are at Depending on the capacity requirement, K1 will
100% capacity. reduce its capacity and possibly stop completely.
Practical example 1
Fig. 15.4
A B C D E F G H I K
0177150_0
Fig. 15.4 shows that the VMY 347 screw com- drops, and K2 will unload and stop. The two recip-
pressor has number 1, the two VMY 325 compres- rocating compressors K4 and K5 will now cover
sors have numbers 2 and 3. Further, SMC 12-100 the cooling requirements.
has number 4 and SMC 8-100 number 5. The se- In interval "E" there is a brief increase in the cool-
quence starting number is seen after "Start #". ing requirement. This increase is covered by K2.
The curve, taken from an existing plant, describes After some time K2 will stop as the cooling re-
a regulating course over a period of approx. 3 quirement has dropped again. However, the plant
hours, divided into intervals from A to K. does not have time to stabilize.
In interval "A" compressors 1 and 2 run at part In interval "F" the cooling requirement rises again
load, until they are both a little below 50% slide and K2 will restart and go up to approx. 60% slide
position, interval "B". Here, the system decides position. Here, the plant stabilizes at a constant
that K1 can be unloaded and K2 will take over. compressor capacity in interval "G".
K2 will now increase its capacity with a simultane- In the period until interval "H" the reciprocating
ous increase in the cooling requirement, which compressor transfers capacity to the screw com-
means that K4 will start up and adjust its capacity, pressor as the screw compressor is below 85%
interval "C". In interval "D" the cooling requirement slide position. K5 stops completely, and K4 will
%
SMC 8-100 Start # 2
100
80
60
40
20
0
SMC 12-100 Start # 1
100
80
60
40
20
0
VMY 325-3 Start # 5
100
80
60
40
20
0
VMY 325-2 Start # 3
100
80
60
40
20
0
VMY 347-1 Start # 4
100
80
60
40
20
0
-4 -3 -2 -1 Immediate
Time
A B C D E F G H I K
0177150_0
Fig. 15.5 shows that the VMY 347 screw com- make K1 start up. At this point K1 and K2 will start
pressor has number 1, the two VMY 325 compres- dividing the capacity. This can be seen in interval
sors have numbers 2 and 3. Furthermore, SMC "D", where K2 has decreased a little, while K1 is
12-100 has number 4 and SMC 8-100 number 5. on its way up.
The sequence starting number is seen after "Start In interval "E" K1 and K2 have the same slide po-
#". sition (approx. 70%) and they regulate in parallel.
The curve, taken from an existing plant, describes In interval "F" K5 may transfer capacity and this
a regulating course over a period of approx. 3 may continue with K4 transferring until interval
hours, divided into intervals from A to K. "G", where the screw compressors have reached
In interval "A" compressors K2 and K4 are running approx. 80%.
at 100% until interval "B". Here, there is a rise in In interval "H" K1 and K2 are above 85% and K4
the cooling requirement, and K5 will start loading. will stay passive until interval "I", where K1 and K2
Until interval "C" these three compressors are run- have regulated down due to decreasing cooling
ning at 100%. A rise in the cooling requirement will requirement. Once they are below 85%, K4 will
transfer its remaining capacity. The screw com- Thus, it can be difficult to achieve an optimum
pressors have now taken over the entire load. compressor operation in every situation. Howev-
Please note that in case the sequence is changed er, it is possible to select compressors by using
during operation, do not expect any immediate re- the signal input external start - normal stop as a
action. If the plant is balanced at this particular supplement to the MULTISAB system facilities as
time, it will continue to operate with the "old" se- described above. By removing the external start -
quence, until a movement has taken place in the normal start signal the compressors can be re-
regulation and it has adapted to the new se- moved from the sequence. MULTISAB will now
quence. The chosen compressor sequence will load compressors with rising sequence numbers -
depend on the operating mode of the plant as well despite the "holes" in the starting sequence.
as the size of the compressors compared to each
other.
Trouble shooting
The plant cannot start
1) Are all UNISAB II units set on REMOTE? – Check communication cable and
2) Have the signals external start - normal stop connection.
and external start - immediate stop been ac- – Do two or more UNISAB II units have
tivated? See UNISAB II drawings Digital in- the same compressor number (COMPR.
puts. NO)? Check the numbers in picture
3) Do the units communicate? - check this by SETUP I CONFIG I COMMUNICA-
means of the picture SETUP I MULTISAB TIONS. They must all be unique.
I ALL COMPRESSORS. Check communi- 2) Do all units that are supposed to run in se-
cation cable. quence have identical SYSTEM NO, which
4) Is the actual suction pressure higher than they must. Check the picture SETUP I
the set point +1/2 neutral zone? MULTISAB I MULTISAB STATE.
5) Are any of the limiting functions active? 3) Check whether all units in the same system
agree upon the same SYS.REGULATOR,
6) Have AUTO START and AUTO STOP been see picture SETUP I MULTISAB I MUL-
configured? TISAB STATE. If this is not the case, do all
7) Has the COLD STORE FUNC. been config- units agree on how to decide the mas-
ured? ter/system regulator? See the PREF.MAS-
TER field in SETUP I CONFIG.
The plant does not run in sequence 4) If PREF. MASTER = START#, has the
1) Do the units communicate? In case of no same START NO been entered in two or
communication, each UNISAB II will run more units? See picture SETUP I MULTI-
with its own regulator. It may be useful to en- SAB I MULTISAB STATE. They must all
ter the picture SETUP I MULTISAB I ALL be unique!
COMPRESSORS and go through the com- 5) Is START NO = 0 in one or more UNISAB II
pressor numbers (use J and K ). There will units? MULTISAB requires that all START
be a question mark (?) in the lower left cor- NO are higher than 0 and that not two are
ner of the display if there is no communica- identical. Note that though it is not possible
tion to the UNISAB II with the selected to select 0 as START NO., the START NO.
number. may still become 0 for several reasons.
2.01 (020221) EEPROM. When switching to the use of two EPROMS at the same time (from version
2.0x) a timing problem occurred which had the effect that writing to and reading from
the EEPROM was not always carried out correctly. This has now been rectified.
Version Description
There was an error in the regulator, which would only occur when a limiter was in passive
mode and when, at the same time, more capacity was required. This error caused the ca-
pacity to decrease very slowly as long as the limiter was in passive mode. This has now
been rectified.
The following compressor type has been added: SAB110SR/LR.
The PID-regulator function has been thoroughly explained in this version of the manual and
it contains practical examples of general usage of this function.
Known errors of this version:
General remarks:
Multisab. Sequential control of several rotatune compressors in the same system as con-
ventional compressors (rotatune master/slave operation) has not yet been implemented. It
is expected to be implemented in version 2.02.2.
The following concerns compressors which control frequency on the frequency converter
by means of a 4-20 mA output signal from the UNISAB II and only in MANUAL OPERA-
TION MODE:
In MANUAL MODE, the compressor capacity will be regulated back to the capacity it had
before the limiter went into active MODE, as soon as the limiter is no longer in function.
Therefore, if capacity is manually regulated up to e.g. 80% and the limiter is activated and
forces capacity down to e.g. 30%, capacity will then automatically be regulated back to 80%
as soon as the limiter is no longer in function. This regulation takes place without activating
the capacity keys.
UNISAB II Evolution: When changing baudrate for port 1 (when using Evolution PLC), a
factory reset must be carried out or UNISAB II must be turned off and on. If this is not car-
ried out, the new communication speed will not be initialized and communication to the PLC
cannot be effected.
Screw compressors:
SAB110SR/LR. During operation for a long period of time in remote or auto control, it might
be quite some time before capacity is decreased even though the regulator requires less
capacity.
Reciprocating compressors:
Motor frequency control in connection with two-stage reciprocating compressors has not
yet been fully implemented.
Version Description
Version Description
Version Description
Known errors:
When using the "copy eeprom" function, all timer values are reset at default values.
When using the 4-20 mA analog output function from UNISAB II to a frequency converter
to control the speed of the compressor motor the following problem is found:
When running in auto or remote control mode, it is still possible to change the speed of the
compressor motor with the operating keys capacity up or capacity down. This should only
be possible in manual control mode.
Version Description
Version Description
Version Description
Version Description
Screw compressors:
Rotatune SAB110SR/LR compressors
The parameters in the oil pressure display have been changed. Consequently, the values
correspond to the values in SAB110L/F (0.0 bar).
Reciprocating compressors:
An error in the code for Rotatune reciprocating compressors has been corrected. Some-
times the alarm: ”Low lube pressure alarm” was activated even though this alarm is intend-
ed for screw compressors only.
2 x Reciptune: The slave compressor does not stop when it reaches minimum capacity.
This error only occurs in version 2.03.2.
An error in the regulator has been corrected. When in AUTO control mode, the compressor
regulation was 5 times slower than in REMOTE control mode.
The SMC/HPC/CMO/HPO reciprocating compressors
Now UNISAB II supports reciprocating compressors with extended capacity unloading.
This applies to operation with as well as without frequency converter. The SMC 180 and
TSMC/TCMO series, however, are NOT supported.
The timer for oil return has been changed from default 0 seconds to default 600 seconds in
order to ensure that the oil from the oil separator does not contain any refrigerant when led
back into the compressor.
The following error has been corrected: Cap. is displayed as 0% at compressor start-up
even though total unloading has not been configured. The error occurs if the compressor
runs in limited operation before UNISAB II receives motor feedback signal from the motor
starter. The timer DELAY UP counts twice before exit 1 becomes active and the correct ca-
pacity is displayed.
When a reciprocating compressor stops because of a limitation, the stop timer now counts
down after reaching the final capacity stage. Earlier, the stop timer was not activated; the
compressor stopped when the DELAY DOWN timer had finished counting down after un-
loading the final capacity stage.
EEPROM (2kB-serial) - To be used in version Eprom 1.10 and earlier versions. 1571-015
EEPROM (4kB-serial) - To be used in version Eprom 1.12 and later versions. 1571-018
Front cover with sheet and display, Sabroe Refrigeration logo 1573-008
Index
B Baud rate
port 1 ................................................................................................................42
port 2 ................................................................................................................42
selecting ...........................................................................................................39
Booster
menu description ..............................................................................................35
Brine
temperature ......................................................................................................33
Brine temperature
Calibration ......................................................................................................128
C Cabinet
open the cabinet ..............................................................................................14
Calculated Vi position ..........................................................................................104
Calibration ...........................................................................................................127
Capacity
corrected capacity ..........................................................................................101
Capacity measuring system
Long-Stroke Capacity-Rod
Calibration ................................................................................................132
Turning Transmitter
Calibration ................................................................................................131
Change to full load ...............................................................................................105
Change to part load .............................................................................................105
Checklist ..............................................................................................................177
Chiller
menu description ..............................................................................................41
Circuit board with light diodes ..............................................................................151
Clima control
menu description ..............................................................................................39
Climate control
description ........................................................................................................97
code plug ...............................................................................................................13
Cold store
funktion ..........................................................................................................123
menu description ..............................................................................................39
Compressor
adjusting slide velocity ...................................................................................100
slide data ....................................................................................... 42, 43, 44, 45
Configuration
menus ..............................................................................................................27
Control and surveillance ......................................................................................113
Aux. output .....................................................................................................121
Capacity down blocked ..................................................................................122
Cold store function .........................................................................................123
COP setting ....................................................................................................121
External start permission- immediate stop .....................................................120
External start permission- normal stop ...........................................................120
D Danbuss
menu description .............................................................................................. 41
Data communication cable
installing the data communication cable ........................................................ 168
Define refrigerant R000 ....................................................................................... 125
Diagnosis
Analog inputs ................................................................................................. 144
COP ............................................................................................................... 146
Digital inputs .................................................................................................. 144
Digital outputs ................................................................................................ 144
Examine memory ........................................................................................... 145
Insp. old alarms .............................................................................................. 142
Misc. functions ............................................................................................... 143
New password ............................................................................................... 146
No. of alarms .................................................................................................. 145
pictures .......................................................................................................... 141
serial number ................................................................................................. 145
Software version ............................................................................................ 144
Zero capacity pos. .......................................................................................... 146
Digital inputs
Diagnosis ....................................................................................................... 144
Digital inputs and outputs
Numbering ..................................................................................................... 147
Digital outputs
Diagnosis .......................................................................................................144
Discharge pressure
menu description ..............................................................................................33
overload ...........................................................................................................56
Display
contrast ............................................................................................................25
description ........................................................................................................14
in Bar or °C/R ...................................................................................................20
Display indications
various limiters ...............................................................................................110
E Economizer
high suction pressure .......................................................................................35
low capacity .....................................................................................................35
menu description ..............................................................................................35
Electrical slide control
SAB 250 and SAB 330 ...................................................................................104
Evolution
no communication to PLC ................................................................................58
warning from PLC ............................................................................................58
Examine memory
Diagnosis .......................................................................................................145
EXT.COOL
menu description ..............................................................................................34
EXT.HEAT
menu description ..............................................................................................34
External input
universal regulators ..........................................................................................94
F Factory setting
restore setting ..................................................................................................41
Factory settings
return to ... ........................................................................................................24
Flow factor
menu description ..............................................................................................41
Front panel
control/recording section ..................................................................................14
green lamp .......................................................................................................14
Red lamp ..........................................................................................................14
Yellow lamp ......................................................................................................14
Function
changing a function ..........................................................................................23
G Green .....................................................................................................................14
Grounding ............................................................................................................170
I Input signal
Auxiliary input signal
screw compressors .................................................................................... 49
auxiliary input signal
HPO-HPC ................................................................................................... 52
recip.compr. ................................................................................................ 51
L Languages
list of languages ............................................................................................... 25
Limiting functions
Standard limiters ............................................................................................ 107
Liquid subcool
menu description .............................................................................................. 41
List of Versions .................................................................................................... 201
Loading sequence ............................................................................................... 185
Long-Stroke Capacity-Rod
Adjusting ........................................................................................................ 135
Multisab
compressor. no. 1 to 14 ...................................................................................35
description ..................................................................................................76, 77
parallel control ..................................................................................................80
preferred master ..............................................................................................35
regulating Setup .............................................................................................173
regulation .......................................................................................................171
special timers
recip.compr. ................................................................................................76
state .................................................................................................................78
system setup ..................................................................................................172
take over ..........................................................................................................41
N New password
Diagnosis .......................................................................................................146
No. of alarms
Diagnosis .......................................................................................................145
Node no
port 1 ................................................................................................................42
port 2 ................................................................................................................42
O Oil cooling
selecting ...........................................................................................................38
setting ..............................................................................................................37
Oil heating ...........................................................................................................124
Oil pump
full flow
screw compr. ..............................................................................................34
Oil rectifier
selecting ...........................................................................................................40
Oil return
reciprocating compressors .............................................................................123
Operating sequence ............................................................................................187
R Regulators ............................................................................................................. 83
Replacing
CPU print and EEPROM ................................................................................ 164
the battery ...................................................................................................... 167
the CPU print ................................................................................................. 163
the door .......................................................................................................... 163
the EPROM (program) UNISAB II .................................................................. 165
the relay print ................................................................................................. 164
the serial EEPROM (diagnosis) ..................................................................... 166
Rotatune
menu description ..................................................................................42, 43, 44
S Sequence
The plant does not run in sequence ............................................................... 199
Serial number
Diagnosis ....................................................................................................... 145
Service ................................................................................................................. 163
Set points
control with current input .................................................................................. 94
on regulators .................................................................................................... 93
Settings
regulating parameters
reciprocating compressors ......................................................................... 90
SAB 330 ..................................................................................................... 93
screw compressors .................................................................................... 91
Short-Stroke Capacity-Rod
Adjusting ........................................................................................................137
Slide brake control ...............................................................................................105
Spacer block
built-in space block ........................................................................................102
Spare parts for UNISAB II ...................................................................................217
Special Limiters ...................................................................................................109
State of take-over ................................................................................................193
State of transfer ...................................................................................................192
Suction Pressure
menu description ..............................................................................................33
Superuser keyword
Diagnosis .......................................................................................................145
Swept volumen
menu description ..............................................................................................39
System numbers ..................................................................................................181
T Temperature
Measured and calculated temperatures
screw compressors .....................................................................................51
measured and calculated temperatures
screw compressors .....................................................................................49
measured/calculated pressures/temperatures
HPO-HPC ...................................................................................................52
Timer description
reciprocating compressors ...............................................................................72
screw compressors ..........................................................................................68
Timers
menu ................................................................................................................63
reciprocating compressor values .....................................................................67
screw compressor values ................................................................................65
Trouble shooting ..................................................................................................141
Trouble-shooting
The plant cannot start ....................................................................................199
Trouble-shooting diagrams
General trouble-shooting, UNISAB II .............................................................160
Start compressor
in AUTO, continued ..........................................................................157, 158
in MANUAL, continued .............................................................................154
Start of compressor
in AUTO mode ..........................................................................................156
in MANUAL mode .....................................................................................153
Start Screw comp,
Prelub. in MANUAL, continued .................................................................155
Start Screw comp.
Prelub. in AUTO mode, continued ............................................................159
U Universal regulator
ext.input ........................................................................................................... 94
Unload
reciprocating compr. ........................................................................................ 39
Unloading sequence ....................................................................................186, 190
V Value
changing a value .............................................................................................. 23
Variable Zero position .......................................................................................... 101
Vi
mode ................................................................................................................ 41
Volume ratio
auto .................................................................................................................. 34
Volume ratio slide ................................................................................................ 100
W Warning
Evolution
warning from PLC ....................................................................................... 58
high oil differential pressure SMC Mk4 ............................................................ 58
identification numbers alarms / warnings ......................................................... 60
watch the oil pressure ...................................................................................... 58
Water
cooling
recip. compr. ............................................................................................... 36
menu description .............................................................................................. 33
Y Yellow .................................................................................................................... 14