This document contains technical specifications for a transformer including its secondary voltage, frequency, core dimensions, flux densities, number of turns, and other electrical parameters. The rated flux density in the yoke is 1.25 Tesla. A formula is given to calculate peak flux density based on transformer voltage, frequency, core length and height, and number of turns.
This document contains technical specifications for a transformer including its secondary voltage, frequency, core dimensions, flux densities, number of turns, and other electrical parameters. The rated flux density in the yoke is 1.25 Tesla. A formula is given to calculate peak flux density based on transformer voltage, frequency, core length and height, and number of turns.
This document contains technical specifications for a transformer including its secondary voltage, frequency, core dimensions, flux densities, number of turns, and other electrical parameters. The rated flux density in the yoke is 1.25 Tesla. A formula is given to calculate peak flux density based on transformer voltage, frequency, core length and height, and number of turns.
Frequency f 50 Hz Flux Density During Test T 1.25 T External Diameter of the core OD 4.64 m Core bore Diameter Da 3.69 m Stator core net length Lu 1.1468 m Stator core length L 1.36 m Tooth height hd 0.1309 m yoke height hc 0.3095 m Height of the magnetic core ht 0.475 m Rated flux density at no-load in yoke (T) B 1.25 T Number of Turns NS 4
𝑈𝑙𝑖𝑛𝑒−𝑙𝑖𝑛𝑒 𝑡𝑟𝑎𝑛𝑓𝑜𝑟𝑚𝑒 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 × 2
𝐵𝑝𝑒𝑎𝑘 = B 1.316314 Tesla 2 × 𝜋 × 𝑓 × 𝑙𝑢 × ℎ𝑐 × 𝑁𝑆
Voltage on the terminals turns US 394 V
Magnetic Field H 180 A/m Total Ampere Turns ATT 2420 AT Total Current I 610 A