Partners in Power

Cast Resin Transformers


Technical Information
SGB_GH_engl.qxd 14.11.2001 9:51 Uhr Seite 2

Why Cast Resin Transformers?

The High-Security,
Low-Cost Solution

• Reduced Costs: • Maintenance Free: • Power Reserves:


Low fire risk permits location near No oil, radiator, or tank problems – Short-time overload capacity
the load – shortens expensive LV only needs air for cooling. much greater than liquid-filled
feeders – reduces volt-drop. Completely sealed windings – transformers.
impervious to damp and dust. For longer overloads, forced cooling
Windings are held securely by is a standard option.
• Planning Flexibility and Safety: epoxy-resin insulation along their ‘AN’ transformers can be equipped
No oil sump – no fire barriers – whole length – no re-pressing or for ‘AF’ just by adding fan assembly
no siting restrictions. Thermal adjustments required – even under and relay to uprate to 150 %.
mass less than 15 % of equivalent the most severe load conditions.
oil transformer. • Reliability
No special building work. More than 10.000 units in service.
Statistics show reliability even
better than oil.

3
SGB_GH_engl.qxd 14.11.2001 9:52 Uhr Seite 4

Design Details

The High-Voltage Winding: The Low-Voltage Winding: The Core: Coil clamps:

High-quality, grain-oriented steel, LV-coils are centred against the core


• Spiral layer copper wire winding in Full-height copper sheet is wound and ‘step-lap’ laminated mitred joints by high-temperature synthetic rubber
epoxy/glass fibre insulation, void- in pre-preg insulation and bonded reduce no-load losses and noise spacers.
free cast in steel mould. by a heating process into a strong emission.
cylinder. HV-coils are centred by upper and
• Partial discharge below 10 pc – Binding and two-part coating ensures lower coil clamps with high-
every coil and complete transformer Copper strip connections are pressure cohesion of the core laminations – temperature synthetic rubber pads
routine tested. welded to the sheet winding. protects against corrosion – further which adjust the HV and LV coil
reduces noise. position both radially and axially.
• Cooling ducts not only further Each coil is tested for radial strength
improve cooling, but ensure any in a special press which plots a The Frame: The support clamps are porcelain
stresses fall in air, not inside force-displacement diagram. for optimal insulation and to reduce
the coil. Even the most extreme and rapid Upper and lower steel channel core thermal mass.
temperature fluctuations will not Short-circuit stresses are minimised clamps are joined by steel tie bars The rubber allows thermal expansion,
induce cracking of insulation or because the current distributes freely bound to the core, and the whole and reduces noise.
deformation of the winding, due to across the full-height conductor. transformer assembly is fixed to a Individual adjusters are fitted to the
the balance of strength and elasticity carriage with bi-directional wheels upper coil clamps.
of the epoxy/glass fibre combination. and lifting and towing eyes.

The complete HV and LV insulation Temperature Monitoring:


system exceeds class F – meets USA
ANSI class 150°C/40.000 hrs. Two PTC’s per phase in conjunction
with TS-O1 relay.
‘Alarm’ for temperature exceeding
that set for calculated life
expectancy. ‘Trip’ for temperature at
thermal limit of temperature class.
For forced cooling (up to 150 %
rating normally) PT 100 in
conjunction with TAA-12 relay
controls fans, and monitors all
components of the system – digital
temperature indication is included.
Also fans are tested automatically
every 30 days.

5
SGB_GH_engl.qxd 14.11.2001 9:53 Uhr Seite 6

Environmental Safety Fire performance

Environmental category Climatic category Classifications F0, F1:

• Practically maintenance free. Environmental category as standard Climatic category C2 as standard – Classifications F0 is standard – meets Classification F1 is also available (Note: Classification F2 has been
= E1 (E2 available up to 24 kV) this is the most onerous test, with all flue-gas requirements – no as standard equipment for countries abandoned from standards due to
• Unaffected by the most severe (salt spray exposure or immersion rapid temperature rise from -30°C to restrictions on installation. in which Classification F1 is specified, the fact that suitable test
temperature fluctuations. in salt water). +155°C applied directly to HV coils or for customers requiring such specifications have not been
(not indirectly applied via LV coil specifications. defined.)
• Impervious to damp and dust. heat transfer) only epoxy/glass fibre
makes this possible; particle filled
• No pollution danger – acceptable epoxy is brittle and cracks at low
even in water protection areas. temperatures.

7
SGB_GH_engl.qxd 14.11.2001 9:54 Uhr Seite 8

Technical capacity

Silence is a
Inspection guaranteed transformer priority

Transformer ratings, specifications, Type tests and Routine tests Short-circuit strength The reduction of air-transmitted As characteristic noise values for cast
standards noise caused by transformers is resin transformers without enclosures
being taken more and more into in AN operation, the following may
The most important data on the Impulse tests are carried out as type LV foil windings which are bonded to consideration. be utilised in practical applications.
rating plate of the cast resin tests based on customer form a cylinder bloc in combination
transformer are documented by test specifications and as sampling tests with the HV cast-resin windings Therefore, SGB cast resin A-weighted sound pressure level
reports. They are based on order- within the quality assurance system. provide the highest possible transformers are offered not only in MA
related and associated national and Cast resin transformers have been strength levels for generated standard design in accordance with LPA in dB
international standards and successfully tested and supplied for a electrodynamic short-circuit forces. DIN 42 523 but also with reduced
regulations such as IEC 76 and 726, system voltage of Um = 36 kV with a Type tests carried out by recognised losses and noise suppression. A-weighted sound power level
VDE 0532, NF C52-726, BS 7806, lightning impulse voltage of 200 kV. independent international institutes

Core height
ANSI C57-1291, CENELEC HD 464. have substantiated this fact. Based In addition to the choice of induction LWA in dB
Subsequent to impulse tests, partial- on our winding design, the and core material, the overlapping of DWA
discharge measurements are always knowledge derived from testing has core legs and yokes in a „Step-lap“ h and adjunct level of measuring
carried out to check for the proper led to a simplification of centering design has a positive effect on the surface
dielectric state before the unit is and support. emission of noise as well as on the
supplied to the customer. transformer losses.
LS in dB
Additional type tests and routine
LWA and LPA with LS have a specified
tests include:
interrelationship found in
• Heat run test DIN 45 635 / Section 30
• Zero phase-sequence impedance Arrangement of measurement points for noise
• Capacity measurements on dry type transformers LWA = LPA + LS
with enclosure.

Reference surface Measurement path Noise measurements are carried out


as special test at regular intervals.

The following routine tests are


carried out on each transformer:
1m
• Winding resistance
• Ratio and polarity
• Impedance voltage Distance is 1m

• Load losses
• No-load losses and current
• Induced overvoltage test
• Winding test
• Partial discharge test

8
SGB_GH_engl.qxd 14.11.2001 9:56 Uhr Seite 10

Protection enclosures

All-around protection

Standard enclosure For installation in enclosed electrical For further information please refer
operating areas, enclosures are to to our detailed brochure
• Free-standing or installed on be provided with type of protection „Standard enclosures for cast resin
carriage. IP 20 and IP 23 respectively. transformers“.
• For indoor or outdoor installation Enclosure IP 33 is required when
IP 20 to IP 33 outdoors. installing in fabrication halls.
Customer specifications can be met
using modular systems.

10
SGB_GH_engl.qxd 14.11.2001 9:56 Uhr Seite 12

CREATIV CONCEPT REGENSBURG


Partners in Power

Manufacturing range

Manufacture and delivery of:


• Oil immersed transformers up to
and including 1.000 MVA, service
voltage up to 525 kV in compliance
with all relevant standards and for
special designs
• Regulating transformers with on-
load tap changers
• Cast resin transformers up to and
including 24 MVA, rated voltages
up to 36 kV
• System enclosures for cast resin
transformers
• Transformers with line drop or
parallel regulation
• Pole-mounted transformers
• Earthing transformers and
Petersen coils
• Rectifier and furnace transformers
• Resonant-circuit reactances,
coupling transformers and reactors
for AF ripple control systems
• Shunt reactors and current
limiting reactors
• Compact stations

Subject to technical modifications

STARKSTROM-GERÄTEBAU GMBH SÄCHSISCH-BAYERISCHE SMIT TRANSFORMATOREN B.V.


STARKSTROM-GERÄTEBAU GMBH
Ohmstraße 10 • 93055 Regensburg Ohmstraße 1 • 08496 Neumark Groenestraat 336 • NL – 6531 JC Nijmegen
Druckschrift BTt 43/01

Telefon: +49 (0)9 41/78 41-0 Telefon: +49 (0)3 76 00 / 83-0 Telefon: 0031 / 24 - 356 89 11
Telefax: +49 (0)9 41/7 17 21 Telefax: +49 (0)3 76 00 / 34 14 Telefax: 0031 / 24 - 356 87 64
E-Mail: sgb@sgb-trafo.de E-Mail: sgb@sgb-neumark.de E-Mail: sales@smit-trafo.nl
12
www.sgb-trafo.de www.sgb-trafo.de www.smittransformers.com