INSULATION RESISTANCE TESTING: HOW LOW CAN


MEGOHMS GO?
By Tom Bishop
EASA Technical Support Specialist
Electrical Apparatus Service Association
St. Louis, MO

All of us in the electrical apparatus service industry test


the winding ground insulation resistance of machines such Table 1-Insulation resistance test voltages
as motors and generators. A frequent question is: What is versus machine rated voltages.
the minimum acceptable megohm (MΩ) value for this wind-
ing? The good news is that there is a standard that identifies Winding rated Insulation resistance
minimum values for insulation resistance of rotating ma- voltage test DC voltage
chines. (AC or DC)
That standard is the “IEEE Recommended Practice for
Testing Insulation Resistance of Rotating Machinery,” IEEE
<1000 500
Std 43-2000. The EASA “Recommended Practice For The
Repair Of Rotating Electrical Apparatus,” ANSI/EASA AR 1000-2500 500-1000
100-2001, uses IEEE 43 for its insulation resistance test
references. Note that IEEE 43 only applies to rotating 2501-5000 1000-2500
machinery. There is no equivalent standard for non-rotating
electrical machinery such as transformers. In this article we 5001-12000 2500-5000
will delve into determining minimum insulation resistance >12000 5000-10000
for rotating electrical machinery.

displays the value of voltage divided by current–i.e., resis-


PURPOSE OF TESTING tance, in megohms. The megohmmeter voltage should be
Before going into the main topic of minimum insulation applied and held for 1 minute, and the reading at 1 minute
resistance, let’s go through a brief refresher on the insula- is recorded as the IR value for the test. The recommended
tion resistance (IR) test. The primary purposes of an insulation test voltage to apply with the megohmmeter increases with
resistance test are to determine if a machine can be placed machine voltage rating as illustrated in Table 1.
back into service, or if high potential winding tests such as Winding temperature affects the megohm value result.
hipot or surge can prudently be performed. Another impor- As temperature increases, insulation resistance decreases.
tant reason for the IR test is to establish a baseline value for The cause is not insulation degradation with temperature,
the winding insulation condition of an installed machine. If but is a physical property of the insulation materials. The IR
the winding IR value is below the acceptable minimum, the reading must therefore be corrected for temperature. The
machine should not be energized, and high potential tests temperature correction per IEEE 43 should be to 40° C; and
should not be performed until the IR value meets or exceeds the correction factor for temperature is such that the mini-
the prescribed minimum. Good winding ground insulation mum insulation resistance value is doubled for every 10° C
behaves like a capacitor, becoming charged when voltage decrease in winding temperature.
is applied across it.
Note: Windings that are very hot (e.g., over 100° C due
The IR value per IEEE 43 should be taken after applying to oven baking) may result in relatively low megohm values.
and holding test voltage on the winding for 1 minute. That Allow the winding to cool to 60° C or lower and then perform
allows some of the capacitive effect to stabilize, making the a temperature-corrected IR test.
readings more consistent. (The theory of insulation capaci-
Expressed as a formula the temperature correction fac-
tance and other components is very complex and beyond
tor is:
our scope in this article.)
Kt = (0.5) (40-T)/10
The most common instrument used for the test is the
battery-powered 500 volt (DC) megohmmeter. One lead is Kt Factor to multiply T by to obtain insulation resis-
applied to the winding leads (typically all tied to the instru- tance corrected to 40° C
ment lead) and the other instrument lead to the frame T Temperature in ° C at which insulation resistance
(ground) of the machine. The meter, which may be digital or was measured
analog, will display the winding megohm value. The meter Here is an example for a winding being tested is at 35° C:
actually applies a voltage and measures the current, then Kt = (0.5) (40-35)/10 = (0.5) 5/10 = (0.5) 1/2 = 0.707

(9/05)
1
Insulation Resistance Testing: How Low Can Megohms Go?

If the measured IR was 100 MΩ at 35° C, the corrected line voltage be used for three phase windings, line-to-
megohms would be: ground voltage for single phase windings, and (nameplate)
100 x 0.707 = 70.7 or about 71 MΩ at 40° C. rated voltage for DC machines or field windings. If the IR is
below the minimums as described above, the machine
should not be started or high potential tested. Corrective
measures, such as cleaning and baking, should be taken to
increase the IR value to an acceptable level.

MINIMUM IR RULES
We will use some examples to demonstrate the applica-
tion of the minimum IR rules. Our first example is a
form-wound stator winding rated 4000 volts, with an IR of 60
MΩ at 20° C. Recalling that every 10° C decrease results in
a halving of the minimum IR value, the 20° C difference
means we halve the value twice (1/2 x 1/2 = 1/4), i.e., it is
reduced by a factor of 4. That means that the IR value will
be 15 MΩ (60 ÷ 4) at 40° C, a value less than the minimum
IR of 100 MΩ. The insulation resistance of this winding is not
acceptable and corrective measures should be taken.
The second example is a random-wound armature rated
500 volts DC with an IR of 52 MΩ at 30° C. Correcting the
To correct observed insulation resistance (Rt) to 40° C,
multiply by the temperature coefficient Kt. Rc = Rt x Kt megohm value from 30° C to 40° C, a 10° C difference, the
result is 26 MΩ (52 ÷ 2). The 26 MΩ value exceeds the 5 MΩ
minimum value; therefore the armature could be energized
(e.g., put back in service) or high potential tested if desired.
Figure 1. Can be used to graphically convert The field windings of the random-wound armature ma-
temperatures to 40° C. (From Section 8 of EASA’s chine will be used for the third example. The field voltage
Technical Manual.) rating is 150/300 volts and the IR value at 25° C is 12 MΩ.
The 15° C (40° C – 25° C) difference dictates that we use the
Humidity can affect IR readings. However, there are no Kt correction factor formula given above. For the sake of
formulas or “rules of thumb” for the effect of humidity with brevity we will skip displaying the math and use the resulting
respect to rotating electrical machine windings. Nonethe- factor of 0.354. The corrected megohms are 4.25 MΩ (12 x
less, it is a good practice to record the humidity reading as 0.354), and the minimum IR is (kV + 1) 1.30 MΩ. Notice that
well as winding temperature and insulation resistance for we used the higher voltage rating of the winding to deter-
each IR test. Knowing these parameters, insulation resis- mine the minimum acceptable megohm value. Since 4.25
tance readings can be evaluated for the possible effect of MΩ is greater than the 1.30 MΩ minimum, the fields can be
humidity, recognizing that at higher humidity the IR reading energized or high potential tested if desired.
may be lower for a specific temperature.
POLARIZATION INDEX TEST
INTERPRETING THE RESULTS Another test, the polarization index (PI) test, is an expan-
Having considered how to perform the insulation resis- sion of the IR test. The PI test extends the time of the IR test,
tance test, we will now address how to interpret the results. lasting for 10 minutes with constant test voltage applied.
For many years the IEEE 43 standard used the rule of “kV The PI is the ratio of the IR at 10 minutes to the IR at 1
+ 1” (1 kV = 1000 volts) to determine the minimum megohms minute. For example, if the IR at 1 minute was 270 MΩ and
for rotating electrical machinery. After nearly 3 decades of the IR at 10 minutes was 590 MΩ, the PI would be 2.2 (590
being reaffirmed, from 1974 to 2000, the standard was ÷ 270). In general, the PI of a winding should be 2.0 or
significantly revised for the 2000 edition. IEEE 43 now greater. The PI test uses the capacitive behavior of winding
states that “for most DC armature and AC windings built insulation to check its integrity. As the capacitance effect
after about 1970 (form-wound coils)” the minimum IR is 100 stabilizes, leakage current decreases and megohms in-
MΩ. That standard also states that “for most machines with crease.
random wound stator coils and form-wound coils rated If a DC hipot is used to perform the PI test, the leakage
below 1 kV” the minimum IR is 5 MΩ. Capturing the current in microamps is typically measured. Calculating the
remaining windings IEEE 43 states that “for most windings PI from current readings can be done by dividing the 1-
made before about 1970, all field windings, and others not minute microamp value by the 10- minute microamp value.
described” above, the minimum IR is kV+1. For a 240-volt For example, if the 1-minute value was 0.28 microamps and
field winding the minimum, using the “kV+1” rule, would be the 10-minute value was 0.15 microamps, the PI would be
.24 + 1 = 1.24 MΩ. 1.9 (0.28 ÷ 0.15). In this case the PI is less than 2; therefore
Note that all of these minimum values are based on a the insulation system condition does not meet the IEEE 43
winding temperature of 40° C. The winding rated voltage standard minimum requirement. Further baking and/or clean-
can be either AC or DC, and the standard states that line-to- ing would be in order.

(9/05)
2
Insulation Resistance Testing: How Low Can Megohms Go?

The megohm value of the insulation on the 1000-megohm scale of a meter


resistance can be obtained from the DC may be indicated more accurately as
In addition to tempera-
hipot readings by dividing the applied 185 MΩ on the 200-megohm scale.
ture and humidity, other The 1000-megohm scale has 2-place
voltage by the microamps of leakage factors that can affect
current. If the PI test voltage in our ex- accuracy in this case when reading
megohmmeter readings below 200 MΩ, and the meter has 3-
ample was 1000 volts, the 1-minute IR
would be 3571 MΩ (1000 ÷ 0.28), and the
are the instruments and place accuracy on the 200-megohm
10-minute value would be 6667 MΩ (1000 the method of applica- scale.
÷ 0.15). Also of note, according to IEEE tion of the test. The
43, if the 1-minute IR is greater than 5000 implied accuracy of an RESULTS WHEN VOLTAGE
megohms, the PI may not be meaningful instrument may change REAPPLIED
and the the PI may be disregarded as a when the megohm scale Another factor is the charging cur-
measure of winding condition. is changed. By “im- rent decay and change in reading as
plied” we mean the voltage is reapplied. The insulation is a
FURTHER TESTING number of significant capacitor and the current across it be-
One other potentially useful test is to digits. comes lower with time. Applying the
apply the IR test at the lower recom- megohmmeter and maintaining the volt-
mended test voltage, then discharge the age causes the capacitive current to
winding, and repeat the IR test at the higher recommended decrease, thus increasing the megohm value (megohms =
test voltage. For example, apply 1000 volts to a winding volts divided by microamps). If the megohm reading at one
rated 4000 volts and obtain the IR, discharge the winding minute is obtained from one lead of a winding and the
and repeat the IR test at 2500 volts. The winding can be megohmmeter reapplied to another set of leads, the second
discharged after the IR test by connecting the winding leads megohm test value will be higher than the first.
together and to ground, e.g., the frame of the electrical The reason is that some of the winding capacitance has
machine. (Caution: See “A Closer Look at High Potential been discharged by the first test, thus the second test
Testing of Rotating Electrical Machine Windings” in the begins at a megohm value greater than that of an uncharged
August 2003 issue of CURRENTS for information on dis- winding. This case applies when the leads of the winding
charging after a hipot test.) being tested are interconnected internally–i.e., there is
If the IR values are about the same for both voltages, and continuity among all the leads. When there are separate
exceed the minimum IR recommendations, the winding windings (e.g., a 6-lead wye-delta motor with separate
ground insulation is probably in satisfactory condition. Con- circuits of leads 1-4, 2-5 and 3-6), each circuit should be
versely, if the IR value decreases with applied voltage there tested individually. The separate circuits should be tested to
is a weakness in the insulation system that may necessitate ground, with all other circuits intentionally connected to
rewinding. ground.
In addition to temperature and humidity, other factors A final note of caution: Make certain that the machine
that can affect megohmmeter readings are the instruments to be tested has been ventilated prior to the IR test, particu-
and the method of application of the test. The implied larly if a winding fault is suspected. Gases from the fault (or
accuracy of an instrument may change when the megohm from a volatile substance such as a solvent or paint) may be
scale is changed. By “implied” we mean the number of ignited by the IR test if an arc occurs during the test.
significant digits. For example, a reading of 190 megohms

L APPA
ICA R
TR
Electrical Apparatus Service Association, Inc.
AT
C
ELE

US

EA SA 1331 Baur Boulevard • St. Louis, MO 63132 U.S.A. • (314) 993-2220 • Fax (314) 993-1269 • www.easa.com
SER

N
IO

IC
V

T
E A
SSOC
IA Reliable Solutions Today! Copyright © 2005

Version 0905-0905
(Update - 9/05)
3

You might also like