You are on page 1of 5

Harmonic Resonance in Power Systems - A

Documented Case
N. Eghtedarpour M.A. Karimi
Technical office, deputy of transmission M. Tavakoli
Fars regional electric co. Technical office, deputy of transmission
Shiraz, Iran Fars regional electric co.
eghtedarpour@frec.co.ir Shiraz, Iran

Abstract— Harmonic resonance occurs in a power system when On August 18, 2013 the Fars power grid experienced an
the power system natural frequency corresponds to the outage of capacitor bank in a sub-transmission 63/20 kV
frequency of a source of harmonic current. This paper studies a substation located in Shiraz suburb. The outage was due to the
real case of power system harmonic resonance that resulted in blow of the capacitor fuse link. However, after the complete
failure of 20-kV capacitor bank fuses. The load current investigation of the capacitors and test performance there was
harmonics are measured and analyzed to investigate the no evidence of failure on capacitor units. The possibility that
individual harmonics of the current and then by using the harmonic resonance had been the cause was considered since
system impedance frequency characteristic, the voltage one of the loads on this substation is a steel rolling factory.
harmonic distortion and the corresponding capacitor current
This paper studies the cause of capacitor fuse blowing in the
are determined. Calculation of the power system natural
above-mentioned substation. The load current harmonics is
frequencies are given for various configurations of system shunt
capacitance and results of the power system harmonic current measured and analyzed to investigate the individual harmonics
and voltage on the capacitor fuse blown is studied. The paper of the current and then by using the system impedance
proposes a criterion for the proper size of capacitor to put in frequency characteristic, the voltage harmonic distortion and
service according to system frequency characteristic and current the corresponding capacitor current are determined. The fuse
harmonics. thermal model is then used to realize the cause of fuse blown.
Measuring and simulation results show that capacitor
Index Terms-- harmonic resonance, system impedance installation has caused a parallel resonance between 5th and
frequency response, harmonc load flow, capacitor fuse. 6th harmonics and due to a relatively high 5th order harmonic
current, the voltage distortion on 5th harmonic has been
I. INTRODUCTION occurred. Since the capacitor impedance is smaller for higher
frequency the voltage harmonics causes large amount of
Shunt capacitors have been utilized for voltage support and harmonic current to the capacitor and finally thermal
power factor correction as a common practice in the electric instability in the fuse.
power grids. Every power system has a natural frequency that
The paper is organized as follows. In Section II the effect
is a function of the system reactance and the amount of power
of capacitor bank on the impedance frequency characteristic of
factor correction capacitors connected to the system [1].
the power system and the corresponding harmonic resonance
Therefore, the installation of shunt capacitors can result in
is described. Section III explains the system configuration and
harmonic resonance and cause an increase in the system
the frequency sweep studies for different capacitor topology is
impedance at the corresponding frequency. In the case that a
illustrated in Section IV. Resonance analysis and harmonic
source of excitation; such as harmonic currents of nonlinear
measurement results are describe in Sections V and VI,
loads exists with a frequency near or equal to the system
respectively. A criterion also proposed in Section VII for
natural frequency, large harmonic voltage distortions can
capacitor installation considering the load current harmonic
result due to the occurrence of resonant conditions. With the
distortion. Finally, Section VIII concludes the paper.
increasing spread of harmonic-producing loads such as motor
drives, power electronic converters, electric arc furnaces, …
the possibility of parallel resonance due to shunt capacitors II. CAPACITOR BANK AND HARMONIC RESONANCE
has become a routine concern for capacitor applications [2]- In a parallel resonant circuit the inductive reactance and
[5]. The problems associated with the parallel resonance are capacitive reactance impedance components are in parallel to
typical of harmonic related heating, including blown fuses, a source of harmonic current. At this frequency where the
circuit breaker heating, and unexplained general equipment inductive and capacitive reactances are equal, harmonic
failures. resonance occurs and the total effective impedance can be

The authors are with Fars regional electric company, Shiraz, Iran
(e-mail: eghtedarpour@frec.co.ir)

978-1-4673-6487-4/14/$31.00 ©2014 IEEE

857
very high (parallel resonance) depending on the system III. SYSTEM CONFIGURATION
configuration and loading [1], [5]. Shunt capacitors which are
commonly installed on the low voltage bus of the sub- A single line diagram of the studied power substation is
transmission substations, are widely used for voltage support shown in Fig. 2. The system has 63 kV and 20 kV Bus. The
as well as power factor correction. Installation of capacitor utility supplies power via two 40 MVA wye-grounded/delta
affect directly to resonance frequency of the system and winding transformer. The transformers are also equipped with
sometimes may contribute to harmonic resonance problem. two 1200 A earthing transformers. Four 2.4 MVAR fixed
shunt capacitors are installed on the 20 kV Bus that are to be
Fig. 1 shows the Thevenin equivalent circuit of a power varied from 2.4 to 9.6 MVAR. A harmonic producing load in
system at the capacitor location. Eth and Z th are the open- this figure is a steel rolling factory which is modeled as
circuit system voltage and the Thevenin equivalent constant current source. The system fault level at 20 kV Bus is
impedance, respectively. Z th is obtained by frequency scan 305 MVA.
study [6]. Parallel resonance occurs when the reactance of X C
IV. RESONANCE ANALYSIS
and Z th cancel each other out. That can be expressed as
follows [1]: A well-known and commonly used method to verify if a
capacitor resonates with its supply system is to determine the
2
ratio of the system fault level to the capacitor size [6] and the
1 1 Rth 1 1
f p ,res. = − ≈ (1) resonance frequency can be estimated from this ratio as
2π Lth C 4 L2th 2π Lth C follows,

S s.c.
hres = (5)
Z th = Rth + j hωLth S cap

Where S s.c. is the system short circuit level in MVA and


Eth XC = −j
hω C
Load S cap is the capacitor size in MVA .
Zp

Fig. 1 Power system equivalent circuit at the capacitor location


63 kV
At the resonant frequency, the apparent impedance of the
parallel combination of the equivalent inductance and
capacitance as seen from the harmonic current source becomes
very large, i.e., 20 kV

−j
hωC ( jhωLth + Rth ) (hωLth ) 2
Z p ,res. = ≈ (2) Harmonic
Rth Rth producing
2.4 2.4 loads 2.4 2.4
Since in transmission systems Rth << ω Lth , Z p,res. will MVAR MVAR MVAR MVAR

be very large at the resonance frequency. From (2), it is


realized that during parallel resonance, a small harmonic
current can cause a large voltage distortion at the resonance Inrush limiting
reactor
harmonic,

V bus = Z p , res. I load


h
(3)
res

The current flowing in the capacitor bank would be,

cap bus Lth h


I res = Vres (hres ωC ) = hres ω I (4)
Rth load
It is clear that currents flowing in the capacitor bank will
L
be magnified by the factor th .
Rth
Fig. 2 single line diagram of the studied power substation

858
average RMS value of the feeder current for one typical
200
workday is shown in Fig. 4 The measured current maximum
180 6.3,170.5 Ω
7.7,178 Ω individual harmonic contents are shown in Fig. 5 for
160
5.5,137 Ω 10.7,143 Ω harmonics order up to 9th.
Impedance (Ohm)

On the other hand, referring to Iran electric industry


140
120
100 standard [9] the current distortion for the customers is limited
80 according to the size of the customer load demand in relation
60
40
No ca pa citor to the short circuit level. The maximum demand of the rolling
20 steel factory is 3 MW. Therefore, considering the short circuit
0 level the current distortion limits are shown in Table I. it can
be seen that during the operation of rolling mills the feeder
Harmonic order contains large 5th harmonic distortion and over the allowable
Capacitor in service range defined by the standard. Considering the current
9.6 MVAR 7.2 MVAR 4.8 MVAR 2.4 MVAR 0 MVAR harmonic distortion and using the frequency response of the
system, harmonic load flow is run to calculate the 20kV Bus
Fig. 3 system impedance versus frequency as viewed from the 20 voltage distortion. The load is modeled in correspondence to
kV bus for different capacitor configuartion the measurement results. The resulted harmonic voltage
distortion due to load current harmonics is shown in Fig. 6.
Rolling mills operation interval
VI. ANALYSIS OF VOLTAGE HARMONIC DISTORTION ON
80 A
CAPACITOR FUSES
60
The behavior of fuse is affected by two effects [10]:
40 electromagnetic and thermal. These two effects together,
result in electro-thermal model of the fuse which is the
20 coupling result of the temperature distribution on fuse
0 resistance and also the current distribution effect on current
fuse losses and temperature distribution.
In recent research, several models of fuses were developed
Fig. 4 1-min average RMS value of the feeder current in a typical workday [12]-[14], most of them are based on a mathematical
representation of the arc physics. These models include
Different studies show that this method is too crude to be transient heating and fusion of notched strip elements in sand,
practically useful. There is no guarantee that this assumption arc ignition, and subsequent burn-back, radial expansion of the
is valid for practical interconnected power systems [2], [7]. arc channels due to fusion of the sand, merging of adjacent
Furthermore, this method only determines the resonance arcs, and many other second-order effects. Other simulations
frequency and does not evaluate the system harmonic have also been done for fuse analysis among them finite
impedance and one cannot determine the severity of the element [11] can be mentioned. Ref.[15] presented thermal
resonance. The formula is based on the assumption that the analysis of a medium voltage fuse by means of the finite
system harmonic reactance is proportional to its fundamental element method. The thermal problem in electric fuses has
reactance determined from the fault level. An alternative to the been studied by different authors. In [11] fuse element is
above method is to conduct harmonic power flow study and/or investigated and its behavior is studied under non-sinusoidal
frequency scan study. The harmonic power flow study is too currents using finite-element method. Different parameters
complicated for this task since the locations of harmonic such as thermal distribution, thermal flux, and electrical
sources and the source characteristics are typically unknown. potential in all fuse parts are obtained for non-sinusoidal
The frequency scan study [6]–[8] is more useful. It can reveal currents and the fuse temperature for various THD values is
the resonance frequencies and the associated magnitudes of determined which results in a factor for the fuse that is called
the combined system-capacitor impedance in the frequency fuse harmonic loss factor (FHLF) in this paper. The FHLF
domain. The system frequency response is calculated using versus frequency is shown in Fig.7. The figure indicates that
DIgSILENT Power Factory software. The total system this function is approximately quadratic and can be written as;
impedance versus frequency plots as viewed from the 20 kV
bus are shown in Fig. 3 for different capacitors configuration. FHLF = 0.0004 f 2 + 0.0002 f − 0.013 (6)
It shows the presence of a high parallel resonance at 275 Hz. Due to the voltage harmonic distortion caused by the
harmonic current of the rolling mills and considering the
V. HARMONIC MEASUREMENT INVESTIGATION capacitor current according to the voltage distortion,
The objective of the harmonic measurement investigation G G
I h = hωV h C (7)
is to determine system harmonic content that would adversely cap
affect a PFC solution. ION-7650 power quality analyzer is n
G G
installed on the suspicious feeder. This device is configured to
calculate and record the maximum individual harmonic
I cap = ¦ I cap
h
(8)
h =1
content of the feeder current every 1 minute. The 1-min

859
90
80
70
60
50
40
FHLF 30
20
10
0
0 50 100 150 200 250 300 350 400 450

Frequency (Hz)

Fig. 7 FHLF versus frequency


(a)

t
Ploss Ih
n
Ploss
= ¦ FHLF ⋅
I1
= 3.2 (9)

n
where, Ploss is the nominal fuse loss power which causes fuse
melting.
Therefore, the total loss power in the fuse according to the
current distortion is 3.2 times the loss power of the
fundamental current. Each 2.4 MVAR of capacitor bank
consists of 12 units of 200 KVAR capacitors that are protected
(b) partially by expulsion fuses with rated current of 50 A. The
time-current characteristic of the fuse is shown in Fig. 8. It can
Fig. 5 measured current maximum individual harmonic contents in
typical workday, (a) even harmonics, (b) odd harmonics be seen that the fuse will blow after 15 sec for the current of
3.2 I n . Therefore, for the time in which the current distortion
is larger it is highly possible for the fuse to start melting.
TABLE I. CURRENT DISTORTION LIMITS
Clearing
Meltingtime
time(Sec.)
(sec)
Maximum current harmonic distortion in percent of
0.01 0.1 1 10 100 1000
maximum demand current (IL)
0
Size of Individual harmonic order n
THD
customer 1 10 100
n<11 11<n<17 17<n<23 23<n<35 n>35 5,000 0

odd even odd even odd even odd even odd even 50
Current (Amps.)

10,000 100
IL/Isc<0.1 15 3.8 7 1.7 6 1.5 2.5 0.6 1.4 0.3 20
150
15,000
200

Voltage Harmonic Distortion in % 250


20,000
7 300
5.8
6
Voltage ha rmonic (%)

25,000
5
4 Fig. 8 Fuse melting characteristic
3
2
1.0
VII. A CRITERION FOR MODIFYING CAPACITOR
1
0.1 0.0 0.2 0.0 0.1 0.0
INSTALLATION
0
2 3 4 5 6 7 8 9 It has been discussed in the previous sections that due to
Ha rmonic order the high current harmonic distortion near the resonance point,
Fig. 6 The resulted harmonic voltage distortion due to load current harmonics the problem of fuse blowing occurred in the substation.
Different methods have been proposed to mitigate this
The capacitor current passes through the fuse, in which the problem by modifying the system impedance frequency
t characteristic. One of the mostly used methods is to change
total loss power ( Ploss ) due to the voltage distortion and the the capacitor size or to move a portion to a different location.
corresponding harmonic currents would be, This section proposes a criterion to study the proper capacitor
size according to current harmonic distortion limits defined by
the standard.

860
Using the FHLF and Eq. (3), loss power of the fuse for
different load current harmonic distortion can be expressed by, 3

Load HDi5
Standard limit
2.5

h
Ploss (Cω h) Z hp Ih 2
= FHLF ⋅ Id Qc=9.6 Mvar
5
1 I fuse
Ploss 1.5
Qc=7.2 Mvar

Ploss 1
Ploss Qc=4.8 Mvar

I1 (10) 1 Qc=2.4 Mvar

HDih Nocapacitor

= FHLF ⋅ (Cω h) Z hp 0.5


I fuse
0
Id
0 2 4 6 8 10 12 14 16 18 20 22 24

Where I h is the load current hth harmonic, I d is the load HD i5

demand current, I fuse is the fuse nominal current and HDih is (a)
th
the h current harmonic distortion. Fig. 9 (a) and (b) show the 8

Load HDi5

Standard limit
fuse loss power relative to the nominal loss power for 5th and 7

7th harmonic distortion of the load current. It can be seen that 6

in the current substation even if HDi5 is on the standard limit, 7


Ploss
5 Qc=9.6 Mvar

Qc=7.2 Mvar
1 4
9.6 MVAR capacitor can result in fuse blown. On the other Ploss
Qc=4.8 Mvar
3
hand, for HDi7 since the resonance occurs for smaller size of
Qc=2.4 Mvar

2 Nocapacitor

capacitor even small current harmonic can cause fuse blown. 1


The discussion shows that in the installation of capacitors it is 0
required to consider the load harmonic distortion besides the 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
system frequency characteristic. HD i7
(b)
VIII. CONCLUSION Fig. 9 Fuse Loss power for different load current harmonic distortion
A real event in the power system that causes capacitor fuse
blowing in a sub-transmission substation is studied in this [7] De Vasconcellos, A.B., Carvalho, B.C., Lambert, J.A., Anabuki, E.T.,
"Applications of tuned passive harmonic filters in a busbar with non-
paper. The load current harmonics is measured and analyzed linear loads," IEEE 15th International Conference on Harmonics and
to investigate the individual harmonics of the current and then Quality of Power (ICHQP), pp. 238 – 244, Hong Kong, 17-20 Jun.
by using system impedance frequency characteristic, the bus 2012.
voltage harmonic distortion and the corresponding capacitor [8] R. A. Deflandre, T. Gunther, E. Bergeron, “Guide for Assessing the
current are determined. It is shown that due to the high value Network Harmonic Impedances, “CIRED. 14th International
of impedance at the resonance frequency, a considerable Conference and Exhibition on Electricity Distribution. Part 1:
Contributions, Jun. 1997
harmonic voltage distortion could result even for a small value
[9] Iran power industry standards- power quality, partII: Permissible
of harmonic current. This matter causes a relatively large ranges of harmonics, Vol. 13, 1st edition, Apr. 2002.
capacitor current that passes through the fuse and may result
[10] A.H.Gheisari, E.Farjah, H. Abiri, “An Electrothermal Model for
in fuse blown. Investigation of Harmonic Effects Produced by Power Electronic
Devices on Protection Elements,” 2009 Compatibility And Power
REFERENCES Electronics Cpe2009 6th International Conference-Workshop.
[11] H. F. Farahani, M. Sabaghi, “Analysis Of Current Harmonic On Power
[1] R.C. Dugan, M.F. McGranaghan, S. Santoso, H.W. Beaty, Electrical System Fuses Using ANSYS,” Indian Journal of Science and
Power Systems Quality, Second Edition, McGraw-Hill, 2003. Technology Vol. 5 No. 3, Mar 2012, pp.2396-2400.
[2] D. Detjen, J. Jacobs, R.W. De Doncker, and H.-G. Mall, “A new hybrid [12] Hoffmann G, Kaltenborn U, “Thermal Modeling Of High Voltage
filter to dampen resonances and compensate harmonic currents in H.R.C. Fuses And Simulation Of Tripping Characteristic,” 7th Int.
industrial power systems with power factor correction equipment,” Conf. on Electrical Fuses & Their Appl., 2003, pp:174-180.
IEEE Trans. Power Electron., vol. 16, pp. 821–827, Nov. 2001.
[13] Hoffmann G, Kaltenborn U, Thermal modelling of high voltage H.R.C.
[3] E. Bompard, E. Carpaneto, G. Chicco, P. Ribaldone, and C. Vercellino, fuses and simulation of tripping characteristic. Proc. of the 7th ICEFA,
“The impact of public lighting on voltage distortion in low voltage Gdansk (Poland). , 2003, pp:174-180.
distribution systems,” IEEE Trans. Power Delivery, vol. 16, pp. 752–
757, Oct. 2001. [14] Jakubiuk K and W AW, “Heating of fuse-elements in transient and
steady-state,” Proc. of the 7th ICEFA, Gdansk (Poland)., 2003, pp:181-
[4] R. Dugan and B.W. Kennedy, “Predicting harmonic problems resulting 187.
from customer capacitor additions for demand-side management,”
IEEE Trans. Power Syst., vol. 10, pp. 1765–1771, Nov. 1995. [15] John A, Selection, “Selection, Application, And Interchangeability Of
Medium-Voltage Power Fuses In Motor Control Centers,” IEEE
[5] Kolar, V., Palecek, J. ; Kocman, S. ; Trung Vo, T., "Interference Transact. on Industry Appl., Vol. 42, No. 6, Jun. 2006.
between electric traction supply network and distribution power
network - resonance phenomenon," 14th International Conference on
Harmonics and Quality of Power (ICHQP), pp. 1 – 4, Bergamo, 26-29
Sept. 2010.
[6] IEEE Recommended Practice and Requirements for Harmonic Control
in Electric Power Systems, IEEE Std. 519-1992, 1992.

861

You might also like