DAILY REPORT
1.) Operate the Genertor # 2 while the Generator # 1 stamby and waiting for Preventive Maintenance activity.
2.) Consolidating some circuit diagram
3.) At around 11:46 am the Generator 2 was stop and restore into the operaation immedatley and according to Mr. Lacthman
it is because of frequent some adjustment into the Engine due to fuel feed pump is fluctuating.
ENGINE NO. 2 MAIN BEARING MONITORING GRAPH
TIME 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00
E MAIN BRG. 841 85 85 86 86 85 85 85
E MAIN BRG. 832 84 85 85 85 84 84 84
E MAIN BRG. 863 87 88 88 88 87 88 87
E MAIN BRG. 854 85 87 87 87 86 86 86
E MAIN BRG. 855 86 87 87 87 86 86 86
E MAIN BRG. 866 86 88 88 88 87 87 87
E MAIN BRG. 857 86 87 87 87 86 86 86
E MAIN BRG. 858 86 87 87 87 86 86 86
E MAIN BRG. 859 85 86 87 87 86 86 86
E MAIN BRG. 8410 84 85 85 85 85 85 85
GUIDE BEARING TEMP. 79 79 79 70 80 79 79 78
ALT.BEARING TEMP. 78 80 81 82 83 83 82 82

E MAIN BRG. E MAIN BRG.


1 3
84 85 85 86 86 85 85 85
83 84 85 85 85 84 84 84 86 87 88 88 88 87 88 87

E MAIN BRG.
0
2
09:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00

0 0 0 0
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10

E MAIN BRG. E MAIN BRG. E MAIN BRG.


4 5 6
4 5 6
85 85 87 87 87 86 86 86 85 86 87 87 87 86 86 86 100

50

0 0 0 0
1 2 3 4 5 6 7 8 9 10 0
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10

MAIN ENGINE NO.2 EXHAUST TEMPERATURE IN DEGREES CELCIUS


TIME 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00
ME EXH. OUT 2951 307 319 317 319 310 320 311
ME EXH. OUT 2912 306 318 316 320 314 317 308
ME EXH. OUT 3013 316 329 333 335 328 328 319
ME EXH. OUT 2804 294 307 305 309 302 305 295
ME EXH. OUT 3035 310 320 322 323 313 315 314
ME EXH. OUT 3296 341 346 356 354 340 341 340
ME EXH. OUT 3297 342 348 351 353 341 345 337
ME EXH. OUT 3408 347 348 363 354 341 348 343
ME EXH. OUT 3379 340 356 358 352 344 347 341

Chart Title ME EXH. OUT ME EXH. OUT


ME EXH. OUT 2 3
1

318 316 320 314 317 308 329 333 335 328 328 319
TIME 291 306 301 316

0 0 0 0
500
0 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
OPERATING PARAMETERS IN COOLING ANG LUBRICATION SYSTEM GRAPH
TIME 09:00 10:00 11:00 12:00 13:00 14:00 15:00 16:00 17:00
CONTROLLER. AIR 9.3 9.2 9.2 9.2 9.2 9.5 9.2 9.1
HT-OUT 83 83 85 86 85 84 84 83
HT-WATER PRESS 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4
LT-WATER-INLET TEMP 38 38 39 3.9 39 39 39 39
LT-PRESSURE 3.3 3.4 3.4 3.4 3.4 3.5 3.4 3.4
ME LO.TEMP.IN 70 70 71 71 71 70 70 70
ME LO PRESS 5.1 5.1 5.2 5.1 4.8 5.3 5.1 4.9
LUBE OIL PRESS-INLET ENG4.9 4.9 4.9 4.8 4.8 4.8 4.8 4.8
LUBE OIL PRESS INLET-TC 1.6 1.6 1.6 1.7 1.7 1.6 1.6 1.6
ME FO TEMP 102 118 117 125 118 122 120 120
ME FO PRESS 6.2 5.9 5.9 6.2 5.1 6 5.9 5.8
CHARGE AIR T IN 45 46 47 48 48 47 48 47
CHARGE AIR P IN 0.96 1.1 1.31 1.57 1.51 1.34 1.39 1.29